Amendment 1 - Round wire concentric lay overhead electrical stranded conductors

Amendement 1 - Conducteurs pour lignes aériennes à brins circulaires, câblés en couches concentriques

General Information

Status
Published
Publication Date
22-May-1997
Drafting Committee
Current Stage
PPUB - Publication issued
Start Date
31-May-1997
Completion Date
23-May-1997
Ref Project

Buy Standard

Standard
IEC 61089:1991/AMD1:1997 - Amendment 1 - Round wire concentric lay overhead electrical stranded conductors
English and French language
16 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NORME
CEI
INTERNATIONALE
IEC
61089
INTERNATIONAL
1991
STANDARD
AMENDEMENT 1
AMENDMENT 1
1997-05
Amendement 1
Conducteurs pour lignes aériennes
à brins circulaires, câblés en couches
concentriques
Amendment 1
Round wire concentric lay overhead
electrical stranded conductors
 IEC 1997 Droits de reproduction réservés  Copyright - all rights reserved
International Electrotechnical Commission 3, rue de Varembé Geneva, Switzerland
Telefax: +41 22 919 0300 e-mail: inmail@iec.ch IEC web site http: //www.iec.ch
CODE PRIX
Commission Electrotechnique Internationale
PRICE CODE H
International Electrotechnical Commission
Pour prix, voir catalogue en vigueur
For price, see current catalogue

---------------------- Page: 1 ----------------------
– 2 – 61089 amend. 1 © CEI:1997
AVANT-PROPOS
Le présent amendement a été établi par le comité d'études 7 de la CEI: Conducteurs pour
lignes électriques aériennes.
Le texte de cet amendement est issu des documents suivants:
FDIS Rapport de vote
7/502/FDIS 7/506/RVD
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l'approbation de cet amendement.
––––––––––
Page 6
1 Domaine d'application
Modifier comme suit:
1.1 La présente Norme internationale prescrit les caractéristiques électriques et mécaniques
des conducteurs pour lignes aériennes à brins circulaires, câblés en couches concentriques et
constitués d'une combinaison des différents fils métalliques suivants:
a) Fils d'aluminium:
*
– aluminium écroui dur selon la CEI 60889 désigné par A1 ;
– alliage d'aluminium type B selon la CEI 60104 désigné par A2*;
– alliage d'aluminium type A selon la CEI 60104 désigné par A3*.
b) Fils en acier zingué (selon la CEI 60888):
– acier normal désigné par S1A ou S1B, pour lesquels A et B sont les classes de
revêtement de zinc, correspondant respectivement aux classes 1 et 2;
– acier à haute résistance désigné par S2A et S2B;
– acier à très haute résistance désigné par S3A.
c) Fils d'acier revêtus d'aluminium (selon la CEI 61232):
– classe 20SA, types A et B, désignés respectivement par SA1A et par SA1B;
– classe 27SA désigné par SA2.
–––––––––
*
 La résistivité de ces métaux est la suivante (en ordre croissant):
A1: 28,264 nΩm (correspondant à 61 % IACS),
A2: 32,530 nΩm (correspondant à 53 % IACS),
A3: 32,840 nΩm (correspondant à 52,5 % IACS).

---------------------- Page: 2 ----------------------
61089 Amend. 1 © IEC:1997 – 3 –
FOREWORD
This amendment has been prepared by IEC technical committee 7: Overhead electrical
conductors.
The text of this amendment is based on the following documents:
FDIS Report on voting
7/502/FDIS 7/506/RVD
Full information on the voting for the approval of this amendment can be found in the report on
voting indicated in the above table.
––––––––
Page 7
1 Scope
Amend as follows:
1.1 This International Standard specifies the electrical and mechanical characteristics of
round wire, concentric lay, overhead, electrical and stranded conductors made of combinations
of any of the following metal wires:
a) Aluminium wires
*
– hard drawn aluminium as per IEC 60889 designated A1 ;
– aluminium alloy type B as per IEC 60104, designated A2*;
– aluminium alloy type A as per IEC 60104, designated A3*.
b) Zinc coated steel wires (as per IEC 60888):
– regular strength steel, designated S1A or S1B, where A and B are zinc coating
classes, corresponding respectively to classes 1 and 2;
– high strength steel, designated S2A or S2B,
– extra high strength steel, designated S3A.
c) Aluminium-clad steel wires (as per IEC 61232):
– class 20SA, types A and B, designated respectively SA1A and SA1B;
– class 27SA, designated as SA2.
–––––––––
*
 The resistivity of these metals is as follows (in increasing order):
A1: 28,264 nΩm (corresponding to 61 % IACS),
A2: 32,530 nΩm (corresponding to 53 % IACS),
A3: 32,840 nΩm (corresponding to 52,5 % IACS).

---------------------- Page: 3 ----------------------
– 4 – 61089 amend. 1 © CEI:1997
1.2 Les désignations des conducteurs inclus dans cette norme sont:
A1, A2, A3,
A1/S1A, A1/S1B, A1/S2A, A1/S2B, A1/S3A,
A2/S1A, A2/S1B, A2/S3A,
A3/S1A, A3/S1B, A3/S3A,
A1/A2, A1/A3,
A1/SA1A, A2/SA1A, A3/SA1A,
S1A, S1B, S2A, S3A,
SA1A, SA1B, SA2.
NOTE – Les conducteurs utilisant un seul type de fils sont appelés conducteurs homogènes (par exemple A1,
A2, S1A, SA2, etc.). Par ailleurs, lorsque les fils ou conducteurs en acier sont cités, ceux-ci peuvent être soit
zingués soit recouverts d'aluminium (Sx ou SAx).
2 Références normatives
Ajouter à la liste le titre de la norme suivante:
CEI 61232: 1993, Fils d'acier revêtus d'aluminium pour usages électriques
Page 8
3 Système de désignation
Ajouter les alinéas suivants à la fin de 3.2:
Les conducteurs homogènes faits de fils d'acier zingué sont désignés par S1A, S1B, S2A, S3A.
Les conducteurs homogènes faits de fils d'acier revêtus d'aluminium sont désignés par SA1A,
SA1B ou SA2.
Ajouter l'alinéa suivant à la fin de 3.4:
Lorsque les fils d'acier rev
...