Fire fighting - Portable fire extinguishers - Performance and construction

ISO 7165:2009 specifies the principal requirements intended to ensure the safety, reliability and performance of portable fire extinguishers. It is applicable to a fully charged extinguisher having a maximum mass of 20 kg. Subject to local acceptance, application to extinguishers having a total mass of up to 25 kg when fully charged is permitted.

Lutte contre l'incendie — Extincteurs portatifs — Performances et construction

General Information

Status
Withdrawn
Publication Date
02-Mar-2009
Withdrawal Date
02-Mar-2009
Current Stage
9599 - Withdrawal of International Standard
Start Date
17-Jul-2017
Completion Date
13-Dec-2025
Ref Project

Relations

Standard
ISO 7165:2009 - Fire fighting -- Portable fire extinguishers -- Performance and construction
English language
58 pages
sale 15% off
Preview
sale 15% off
Preview

Frequently Asked Questions

ISO 7165:2009 is a standard published by the International Organization for Standardization (ISO). Its full title is "Fire fighting - Portable fire extinguishers - Performance and construction". This standard covers: ISO 7165:2009 specifies the principal requirements intended to ensure the safety, reliability and performance of portable fire extinguishers. It is applicable to a fully charged extinguisher having a maximum mass of 20 kg. Subject to local acceptance, application to extinguishers having a total mass of up to 25 kg when fully charged is permitted.

ISO 7165:2009 specifies the principal requirements intended to ensure the safety, reliability and performance of portable fire extinguishers. It is applicable to a fully charged extinguisher having a maximum mass of 20 kg. Subject to local acceptance, application to extinguishers having a total mass of up to 25 kg when fully charged is permitted.

ISO 7165:2009 is classified under the following ICS (International Classification for Standards) categories: 13.220.10 - Fire-fighting. The ICS classification helps identify the subject area and facilitates finding related standards.

ISO 7165:2009 has the following relationships with other standards: It is inter standard links to ISO 7165:2017, ISO 7165:1999/Amd 1:2004, ISO 7165:1999, ISO 7165:1999/Amd 2:2004. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

You can purchase ISO 7165:2009 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of ISO standards.

Standards Content (Sample)


INTERNATIONAL ISO
STANDARD 7165
Second edition
2009-03-15
Fire fighting — Portable fire
extinguishers — Performance and
construction
Lutte contre l'incendie — Extincteurs portatifs — Performances et
construction
Reference number
©
ISO 2009
PDF disclaimer
This PDF file may contain embedded typefaces. In accordance with Adobe's licensing policy, this file may be printed or viewed but
shall not be edited unless the typefaces which are embedded are licensed to and installed on the computer performing the editing. In
downloading this file, parties accept therein the responsibility of not infringing Adobe's licensing policy. The ISO Central Secretariat
accepts no liability in this area.
Adobe is a trademark of Adobe Systems Incorporated.
Details of the software products used to create this PDF file can be found in the General Info relative to the file; the PDF-creation
parameters were optimized for printing. Every care has been taken to ensure that the file is suitable for use by ISO member bodies. In
the unlikely event that a problem relating to it is found, please inform the Central Secretariat at the address given below.

©  ISO 2009
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by any means,
electronic or mechanical, including photocopying and microfilm, without permission in writing from either ISO at the address below or
ISO's member body in the country of the requester.
ISO copyright office
Case postale 56 • CH-1211 Geneva 20
Tel. + 41 22 749 01 11
Fax + 41 22 749 09 47
E-mail copyright@iso.org
Web www.iso.org
Published in Switzerland
ii © ISO 2009 – All rights reserved

Contents Page
Foreword. v
1 Scope . 1
2 Normative references . 1
3 Terms and definitions. 1
4 Classification of extinguishers. 4
5 Extinguishing media, propellants and filling requirements . 4
5.1 Extinguishing media. 4
5.2 Propellants . 5
5.3 Filling requirements. 5
6 Pressure requirements for low-pressure extinguishers. 6
6.1 Test pressure . 6
6.2 Minimum burst pressure. 6
7 General operating performance requirements . 6
7.1 Operating temperatures . 6
7.2 Minimum effective discharge time and bulk range of discharge. 6
7.3 Resistance to temperature changes. 9
7.4 Retention of charge . 10
7.5 Mechanical resistance. 11
7.6 Resistance to corrosion. 13
7.7 Tapping test (powder extinguishers only) . 14
7.8 Intermittent discharge test. 18
8 Performance requirements for test fires . 18
8.1 Rating suitability for the various classes of fire.18
8.2 Test fires — General. 20
8.3 Class A test fire. 21
8.4 Class B test fire. 23
8.5 Class D test fire. 25
8.6 Electrical conductivity of extinguisher discharge. 29
8.7 Class F test fire . 29
8.8 Class F splash test . 31
9 Construction requirements. 35
9.1 High-pressure extinguishers . 35
9.2 Low-pressure extinguishers. 35
9.3 Carrying handle. 38
9.4 Mounting. 38
9.5 Caps, valves and closures. 38
9.6 Safety devices . 39
9.7 Manufacturing tests. 39
9.8 Requirements for plastics components . 40
9.9 Hose assemblies. 42
9.10 Method of operation . 43
9.11 Safety-locking devices . 43
9.12 Requirements for pressure gauges and indicators for low-pressure extinguishers . 44
9.13 Dip-tubes and filters — Water-based extinguishers . 46
9.14 Special requirements for CO extinguishers . 46
9.15 Gasket and O-rings. 47
10 Marking and colour. 47
10.1 Colour. 47
10.2 Marking. 47
10.3 Inspection instructions. 51
11 Manuals. 51
11.1 User manual. 51
11.2 Service manual. 52
Annex A (normative) Alternate test fire for powder extinguishers with a rating exceeding 144B. 53
Bibliography . 58

iv © ISO 2009 – All rights reserved

Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards bodies
(ISO member bodies). The work of preparing International Standards is normally carried out through ISO
technical committees. Each member body interested in a subject for which a technical committee has been
established has the right to be represented on that committee. International organizations, governmental and
non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely with the
International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization.
International Standards are drafted in accordance with the rules given in the ISO/IEC Directives, Part 2.
The main task of technical committees is to prepare International Standards. Draft International Standards
adopted by the technical committees are circulated to the member bodies for voting. Publication as an
International Standard requires approval by at least 75 % of the member bodies casting a vote.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. ISO shall not be held responsible for identifying any or all such patent rights.
ISO 7165 was prepared by Technical Committee ISO/TC 21, Equipment for fire protection and fire fighting,
Subcommittee SC 2, Manually transportable fire extinguishers.
This second edition cancels and replaces the first edition (ISO 7165:1999), which has been technically revised.
It also incorporates the Amendments ISO 7165:1999/Amd 1:2004 and ISO 7165:1999/Amd 2:2004.

INTERNATIONAL STANDARD ISO 7165:2009(E)

Fire fighting — Portable fire extinguishers — Performance and
construction
1 Scope
This International Standard specifies the principal requirements intended to ensure the safety, reliability and
performance of portable fire extinguishers.
It is applicable to a fully charged extinguisher having a maximum mass of 20 kg. Subject to local acceptance,
application to extinguishers having a total mass of up to 25 kg when fully charged is permitted.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
ISO 3130, Wood — Determination of moisture content for physical and mechanical tests
ISO 3941:—, Classification of fires
ISO 4672:1997, Rubber and plastics hoses — Sub-ambient temperature flexibility tests
ISO 4892-2:2006, Plastics — Methods of exposure to laboratory light sources — Part 2: Xenon-arc lamps
ISO 5923, Fire protection — Fire extinguishing media — Carbon dioxide
ISO 7202, Fire protection — Fire extinguishing media — Powder
ISO 7203 (all parts), Fire extinguishing media — Foam concentrates
ISO 9227, Corrosion tests in artificial atmospheres — Salt spray tests
ISO 14520 (all parts), Gaseous fire-extinguishing systems — Physical properties and system design
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
3.1
batch
group of the same products made on the same production line using the same lot of materials during one
production shift
3.2
bulk range
range of the extinguisher when 50 % of its media has been expelled
3.3
charge of extinguisher
mass or volume of the extinguishing medium contained in the extinguisher expressed in volume (litres) for
water-based extinguishers and in mass (kilograms) for other extinguishers
3.4
classification of fires
grouping of fires on the basis of the characteristics as given in 3.4.1 to 3.4.5
See ISO 3941:—.
3.4.1
class A
involving solid materials, usually of an organic nature, in which combustion normally takes place with the
formation of glowing embers
3.4.2
class B
involving liquids or liquefiable solids
3.4.3
class C
involving gases
3.4.4
class D
involving metals
3.4.5
class F
involving cooking media (vegetable or animal oils and fats) in cooking appliances
3.5
clean agent
electrically non-conductive gaseous or vapourizing liquid fire extinguishant that does not leave a residue upon
evaporation
3.6
complete discharge
point in the discharge of an extinguisher when the internal pressure has equalized with the external pressure,
with the valve control being kept fully open
3.7
disposable extinguisher
non-rechargeable extinguisher
extinguisher designed not to be recharged in the field or at the factory, but intended to be discarded after use
3.8
effective discharge time
time from the commencement of discharge of the extinguishing medium at the nozzle to the gas point of the
discharge stream with the control valve fully open
3.9
extinguishing medium
substance contained in the extinguisher that causes extinguishment
2 © ISO 2009 – All rights reserved

3.10
fill density
mass in kilograms of extinguishing medium per litre of container volume as fitted for use, complete with valve
and internal fittings
3.11
fire extinguisher
an appliance containing an extinguishing medium that can be discharged and directed onto a fire by the action
of internal pressure; discharge may be achieved by
⎯ stored pressure (constant pressurization of the extinguishing media container);
⎯ cartridge operated [pressurization at the time of use by the release of a pressurizing gas stored in a
separate high-pressure container (cartridge)]
3.12
gas point
point where the medium discharge changes from predominately liquid medium to predominately expellant gas
3.13
lowest observable adverse effect level
LOAEL
lowest concentration at which an adverse physiological or toxicological effect has been observed
3.14
maximum service pressure
p
ms
equilibrium pressure developed in a normally charged and pressurized extinguisher that is conditioned at
60 °C for at least 18 h
3.15
portable fire extinguisher
fire extinguisher that is designed to be carried and operated by hand and that, in working order, has a mass of
not more than 20 kg
NOTE Subject to local acceptance, extinguishers having a total mass of up to 25 kg when fully charged are permitted.
3.16
pressure gauge
device that shows the pressure in the cylinder and the operating range of the extinguisher based on the
operating temperature-pressure relationship.
NOTE The gauge face is marked with the appropriate units.
3.17
pressure indicator
device that shows that the extinguisher is pressurized at its rated expellant gas pressure
3.18
propellant
non-flammable compressed gas used to expel the extinguishing medium
3.19
rechargeable extinguisher
extinguisher designed to be recharged after use
3.20
service pressure
p
s
equilibrium pressure developed in a normally charged and pressurized extinguisher conditioned at 20 °C for at
least 18 h
3.21
wet chemical
chemical agents that include, but are not limited to, aqueous solutions of potassium acetate, potassium
carbonate, potassium citrate, or combinations of these materials
4 Classification of extinguishers
Extinguishers shall be classified by the type of extinguishing medium that they contain. At present, the main
classes of extinguishers are
a) water-based;
b) powder;
c) carbon dioxide;
d) clean agents.
These classes of extinguishers may be further sub-divided; for example, water-based extinguishers may
contain pure water or water with additives, such as wetting agents, viscosity-increasing agents, flame
retardant, foaming agents, wet chemical, etc. Water-based extinguishers, including foam, containing different
types of freezing-point depressants shall be treated as separate and distinct models for the fire rating tests
and for the purpose of testing the range of the operating temperatures, electrical conductivity, etc. All other
requirements relating to the design and construction of water-based extinguishers are applicable to all models,
irrespective of contents.
5 Extinguishing media, propellants and filling requirements
5.1 Extinguishing media
5.1.1 Carbon dioxide
Carbon dioxide used in extinguishers shall comply with ISO 5923.
5.1.2 Clean agents
Clean agents used in extinguishers shall comply with the appropriate part of ISO 14520 or shall be regulated
by the national environmental regulatory body of a country.
NOTE In some countries, the manufacture and use of clean agents is regulated by the Montreal Protocol or by
national regulations.
5.1.3 Powders
Powders used in extinguishers shall comply with ISO 7202, with the exception of powders for use on class D
fires.
5.1.4 Foam concentrates
Foam concentrates used in extinguishers shall comply with the appropriate part of ISO 7203.
NOTE There is no ISO International Standard covering non-foaming additives sometimes added to water to produce
antifreeze, wetting or other special characteristics. However, such extinguishers are included in the category of water-
based extinguishers.
4 © ISO 2009 – All rights reserved

5.1.5 Water-based agents
When the extinguishing agent has a pH exceeding 9,5, a warning statement shall be required for the
extinguisher nameplate (see 10.2).
5.2 Propellants
The propellants for stored pressure and cartridge-operated extinguishers shall be air, argon, carbon dioxide,
helium or nitrogen or mixtures of these gases having a maximum dew-point of −55 °C. Non-flammable tracers
may be added to the propellant to facilitate leakage detection. The percentage of the tracer shall be indicated
by the manufacturer and verified by the test laboratory, with the exception that it is not necessary for the
propellant for stored-pressure, water-based extinguishers to meet the above dew-point.
5.3 Filling requirements
5.3.1 Fill density
The maximum fill density for carbon-dioxide extinguishers shall not exceed 0,75 kg/l. The fill density for clean
agent fire extinguishers shall not exceed the values given in the appropriate part of ISO 14520.
NOTE The above fill densities can be subject to national pressure-vessel regulations.
5.3.2 Filling tolerance
The actual charge of an extinguisher shall be the nominal charge within the following limits:
a) water-based extinguisher: 0 % to 5 % by volume;
b) powder extinguishers:
u 1 kg nominal charge, ± 5 % by mass;
> 1 kg but < 3 kg nominal charge, ± 3 % by mass;
W 3 kg nominal charge, ± 2 % by mass;
c) clean agent extinguishers: 0 % to 5 % by mass;
d) carbon dioxide extinguishers: 0 % to 5 % by mass.
5.3.3 Charges
The following are the recommended charges for fire extinguishers:
⎯ water-based: 2 l, 3 l, 6 l, 9 l;
⎯ powder: 1 kg, 2 kg, 3 kg, 4 kg, 6 kg, 9 kg, 12 kg;
⎯ CO: 2,5 kg;
⎯ clean agent: 1 kg, 2 kg, 4 kg, 6 kg.
6 Pressure requirements for low-pressure extinguishers
6.1 Test pressure
1)
The test pressure, p , for low-pressure extinguishers shall be 1,43 × p but in no case less than 2 MPa
t ms
(20 bar).
6.2 Minimum burst pressure
The minimum burst pressure, p , for low-pressure extinguishers shall be 2,7 × p but in no case less than
b ms
5,5 MPa (55 bar).
7 General operating performance requirements
7.1 Operating temperatures
Extinguishers shall be capable of operating reliably within one of the following temperature ranges:
+5 °C to +60 °C;
−5 °C to +60 °C;
−10 °C to +60 °C;
−20 °C to +60 °C;
−30 °C to +60 °C;
−40 °C to +60 °C;
−55 °C to +60 °C;
The temperature range selected from the above ranges shall be marked on the fire extinguisher (see 10.2.1.5).
For water-based extinguishers without any protection against freezing, the minimum operating temperature
shall be 5 °C.
7.2 Minimum effective discharge time and bulk range of discharge
7.2.1 Class A rated extinguishers
The minimum effective discharge time of extinguishers with a 1A rating shall be no less than 8 s.
Extinguishers with ratings of 2A or higher shall have a minimum discharge time of 13 s.
7.2.1.1 Requirements
When three portable fire extinguishers are tested in accordance with 7.2.1.2, the duration of operation of each
extinguisher shall be within ± 3 s of the average value for powder extinguishers and within 15 % of the
average value for other extinguishers, but duration value shall not be less than the minimum specified.

1) 1 bar = 100 kPa = 0,1 MPa; 1 Pa = 1 N/m .
6 © ISO 2009 – All rights reserved

7.2.1.2 Test method
Carry out the testing of portable extinguishers within 5 min of removal of the extinguisher from the conditioning
temperature. Store portable fire extinguishers for testing in a vertical position for at least 18 h at a temperature
of 20 °C ± 5 °C before the tests are carried out and maintain the temperature within this range until tested as
given below.
a) Weigh the extinguisher.
b) Hold the extinguisher in its normal working position (i.e. hand-held) and keep it immobile for the duration
of the test.
c) For cartridge-operated extinguishers supplied with a final control valve and an independent activation
system, pressurize with the final control valve closed. Open this final control valve 6 s after the
commencement of pressurization of the extinguisher.
d) For cartridge-operated extinguishers where activation is by a simple action, pierce the cartridge and close
the control valve immediately for a period of 6 s, after which reopen the control valve.
e) For extinguishers that are activated by a single operation of the control valve, open the control valve and
leave open for the duration of the test.
f) Measure and record the time between the opening of the final control valve and the commencement of
discharge. Measure and record the effective discharge time.
g) For gaseous extinguishers, reweigh, then calculate and record the residual charge. For all other
extinguishers, reweigh, empty the residual extinguishant, then reweigh or measure and record the
residual change.
All portable fire extinguishers shall operate within 4 s after the final control valve is opened.
7.2.2 Class B rated extinguishers
The minimum effective discharge time of extinguishers with a class B rating shall be no less than the
appropriate value given in Table 1.
7.2.2.1 Requirements
When three portable fire extinguishers are tested in accordance with 7.2.2.2, the duration of operation of each
extinguisher shall be within ± 3 s of the average value for powder extinguishers and within 15 % of the
average value for other extinguishers, but duration value shall not be less than the minimum specified.
7.2.2.2 Test method
Carry out the testing of portable extinguishers within 5 min of the removal of the extinguisher from the
conditioning temperature. Store portable fire extinguishers for testing in a vertical position for at least 18 h at a
temperature of 20 °C ± 5 °C before the tests are carried out and maintain the temperature within this range
until tested as given below.
a) Weigh the extinguisher.
b) Hold the extinguisher in its normal working position (i.e. hand-held) and keep it immobile for the duration
of the test.
c) For cartridge-operated extinguishers supplied with a final control valve and an independent activation
system, pressurize with the final control valve closed. Open this final control valve 6 s after the
commencement of pressurization of the extinguisher.
d) For cartridge-operated extinguishers where activation is by a simple action, pierce the cartridge and close
the control valve immediately for a period of 6 s, after which reopen the control valve.
e) For extinguishers that are activated by a single operation of the control valve, open the control valve and
leave open for the duration of the test.
f) Measure and record the time between the opening of the final control valve and the commencement of
discharge. Measure and record the effective discharge time.
g) For gaseous extinguishers, reweigh, then calculate and record the residual charge. For all other
extinguishers, reweigh, empty the residual extinguishant, then reweigh or measure and record the
residual change.
All portable fire extinguishers shall operate within 4 s after the final control valve is opened.
Table 1 — Minimum effective discharge time of class B rated extinguishers
Minimum discharge time
Classification
s
a
8B —
a
13B —
21B 8
34B 8
55B 9
(70B) 9
89B 9
(113B) 12
144B 15
(183B) 15
233B 15
a
This fire size is for a low-temperature fire test only.

7.2.3 Bulk range
7.2.3.1 Requirements
The minimum bulk range of extinguishers with a class A rating shall be no less than 3 m when determined in
accordance with 7.2.3.2.
7.2.3.2 Test method
Carry out the test indoors using lighting that gives the best possible illumination of the extinguisher medium
during discharge. Use a black background marked to indicate the horizontal distance. Condition the
extinguisher for no less than 18 h at a temperature of 20 °C ± 5 °C and place it in normal operating position
with the discharge nozzle held horizontally 1 m above the floor. Fully discharge the extinguisher with the
control valve fully open within 2 min of conditioning. Record the bulk range of the extinguisher as the range at
the time corresponding to 50 % of the effective discharge time.
NOTE Where the range of effective discharge is difficult to determine visually, supplementary means, such as
collection boxes for powders and condensing plates for liquefied gases, can also be used.
8 © ISO 2009 – All rights reserved

7.3 Resistance to temperature changes
7.3.1 Requirements
Portable extinguishers shall be able to operate at temperatures within one of the temperature ranges given in
7.1 as indicated by the manufacturer and shall comply with the following requirements after being subjected to
the conditions given in 7.3.2.
a) The extinguisher shall operate as intended. The duration of operation shall not be less than 8 s. Carbon
dioxide extinguishers, when tested at 60 °C, shall have duration of not more than the duration established
at 20 °C. When tested at the minimum operating temperature, the discharge duration shall not be greater
than 2,5 times the duration established at 20 °C.
b) The extinguisher shall commence discharge within 5 s of opening the control valve.
c) Powder extinguishers shall not retain more than 15 % of initial charge within the extinguisher following
complete discharge. All other types shall have a maximum residue of 10 %.
7.3.2 Test method
Carry out testing on four extinguishers. Before testing, weigh each extinguisher, then subject two
extinguishers to temperature cycle 1, as given in Table 2, and subject the other two extinguishers to
temperature cycle 2, as given in Table 2. Store at the temperatures given in Table 2 in conditioning chambers;
do not use liquid baths. Maintain extinguishers in an upright position during temperature cycling. The
tolerances given in Table 2 shall be considered as nominal tolerances, with the climatic chamber empty.
Table 2 — Temperature cycles
Duration
a a
Cycle 1 Cycle 2
h
b
Store at minimum
24 ± 1 Store at (60 ± 2) °C
stated temperature (± 2 °C)
24 ± 1 Store at (20 ± 5) °C Store at (20 ± 5) °C
b
Store at minimum
24 ± 1 Store at (60 ± 2) °C
stated temperature (± 2 °C)
a
The storage temperatures refer to the ambient temperature within the conditioning chamber. A liquid bath shall not be used.
b
See 7.1.
Operate the extinguisher within 2 min after its removal from the conditioning chamber. Hold the extinguisher in
its normal working position and keep it immobile for the duration of the test.
Operate the extinguisher in accordance with 7.2.2.2.
Measure and record the time between the opening of the final control valve and the commencement of
discharge. For gaseous extinguishers, reweigh, then calculate and record the residual charge. For all other
extinguishers, reweigh, empty the residual extinguishant, then reweigh or measure and record the residual
change.
7.4 Retention of charge
7.4.1 Routine checks
7.4.1.1 Extinguishers and gas cartridges shall be designed so as to permit their charge to be checked at
regular intervals when they are installed.
7.4.1.2 The charge of the following shall be measured by weighing:
a) all types of gas cartridges for extinguishers;
b) carbon dioxide extinguishers;
c) stored-pressure extinguishers of various types, including some clean agents in which a mass loss of 1 %
of total mass is accompanied by a pressure loss of not more than 10 % of the service pressure at
(20 ± 2) °C.
7.4.1.3 The charge of stored-pressure extinguishers of types not covered in 7.4.1.2 b) and c) shall be
checked by direct measurement of internal pressure at (20 ± 2) °C. For this purpose, the extinguisher shall be
fitted with a built-in pressure-indicating device that can be checked for satisfactory operation.
A connection to which an independent pressure-measuring appliance can be attached may be used as the
means for checking the built-in pressure-indicating device; in this case, a connection of this type shall be
equipped with a pressure-retaining cap.
7.4.2 Retention of charge following partial discharge
7.4.2.1 Requirements
Fire extinguishers shall be fitted with a control valve allowing the discharge of the extinguishing medium to be
interrupted at any time.
The extinguisher shall be adequately resistant to leakage and the second pressure (or mass of contents, as
appropriate) shall be no less than 75 % of the first, after interruption of the discharge as determined in 7.4.2.2.
7.4.2.2 Test method
Carry out this test with three extinguishers conditioned for 18 h at 20 °C ± 5 °C. All three extinguishers shall
pass the test.
Operate the extinguishers and allow the medium to discharge for one half of the measured discharge duration.
For extinguishers with a (propellant) gas cartridge, open the control valve in accordance with a) or b), as
applicable.
a) If the extinguisher is fitted with a pressurization device independent of the device that opens the control
valve, operate the pressurization device and 3 min later open the control valve to initiate discharge.
b) If a single action pressurizes the extinguisher and releases the first emission of gas, pressurize the
extinguisher initially and 3 min later open the control valve again to permit discharge of the extinguishing
medium.
Then close the valve by the action intended to interrupt the emission of the extinguishing medium. Measure
the internal pressure, or, in the case of CO , the mass of the extinguisher, within 10 s of, and again 5 min after,
closure of the control valve, the control valve having remained closed for the duration of this period.
10 © ISO 2009 – All rights reserved

7.4.3 Long-term leakage test
7.4.3.1 Requirements for stored-pressure extinguishers
Stored-pressure extinguishers covered by 7.4.1.3 shall not leak at a rate exceeding 5 % per annum of service
pressure.
7.4.3.2 Requirements for gas cartridges and extinguishers checked by mass
Long-term leakage requirements are as follows.
⎯ Stored-pressure extinguishers without a pressure gauge shall not leak at a rate exceeding 5 %/yr or
50 g/yr of its contents, whichever is less [see 7.4.1.2 c)].
⎯ Gas cartridges shall not leak at a rate exceeding 5 %/yr or 7 g/yr of its contents, whichever is less.
⎯ Carbon dioxide extinguishers shall not leak at a rate exceeding 5 %/yr.
7.4.3.3 Test method
Check six samples for leakage after 30 d, 90 d and 120 d. Any loss in pressure or contents at constant
ambient temperature is an indication of a leak.
7.5 Mechanical resistance
7.5.1 Resistance to impact
NOTE This test is intended to prove the resistance of the extinguisher, and particularly that of the head and fittings, to
damage from falling objects or from impact with fixed surfaces.
7.5.1.1 Requirements
The extinguisher shall not release pressure in a potentially dangerous manner when tested in accordance with
7.5.1.2.
The portable extinguishers shall be judged fit and proper if, during the course of the impact tests, there is no
evidence of bursting, breakage or ejection of components that puts the safety of the user at risk.
7.5.1.2 Test method
Carry out the test on two charged, portable fire extinguishers. Test one extinguisher horizontally and the other
vertically. Condition the extinguishers, correctly charged and equipped with all the fittings that are subject to
internal pressure in normal operation, for 18 h to the minimum working temperature ± 2 °C (see 7.1). Within
2 min after the removal of the extinguisher from the conditioning chamber, subject it to the impact test
described below.
For the purpose of this test, an anti-freeze agent is added to prevent freezing of the contents of water-based
extinguishers. Carbon dioxide extinguishers shall be filled to 95 % of volume with water or water plus anti-
freeze agent and pressurized with nitrogen to the working pressure that would exist at the test temperature if
the extinguisher were charged with CO .
If the extinguisher is a gas-cartridge type, fit the charged cartridge and activate the extinguisher with the
control valve shut, so as to keep the extinguisher under pressure.
Conduct the impact test as follows.
a) Mount a steel cylindrical hammer, of 75 mm diameter and total mass of 4,0 kg with flat faces, vertically in
loose guides so that it can drop freely through a height, h, expressed in metres, of not less than 0,3 m
(minimum height 300 mm) as given by Equation (1):
m
h= (1)
where m is the total mass of extinguisher, expressed in kilograms.
b) Place the extinguisher on a rigid flat surface in each of the following two positions in turn:
⎯ in the normal upright position, with the longitudinal axis of the hammer coincident with the
longitudinal axis of the valve;
⎯ lying on its side so that the hammer impacts the valve through the centreline of the extinguisher and
the valve rests on a rigidly fixed steel block; the centreline of the hammer shall not be coincident with
the longitudinal axis of the extinguisher and shall not impact the cylinder.
c) In each of the above positions, submit the valve of the extinguisher to an impact by allowing the steel
hammer to fall vertically onto it from the height, h. The point of impact is determined by the authority
carrying out the test.
7.5.2 Resistance to vibrations
7.5.2.1 Test principle
An extinguisher shall be capable of withstanding exposure to the conditions of a vibration test without
development of physical weakness that would impair its normal operation.
7.5.2.2 Extinguisher mounting requirements
Extinguishers not intended for use in vehicles shall be subjected to the test specified in 7.5.2.5.2.
Extinguishers supplied with a bracket for use in vehicles shall be subjected to the test specified in 7.5.2.5.3.
Extinguishers supplied with a bracket suitable for both general and vehicle use shall be subjected to the test
specified in 7.5.2.5.3.
7.5.2.3 Test criteria
The test criteria are as follows.
a) Following exposure to the vibration test, the extinguisher shall comply with the discharge requirements
specified in 7.2.
b) Physical failure of components that requires repair or replacement of the extinguisher and/or components
before it can be returned to normal service shall be cause for rejection.
7.5.2.4 Mounting of the test specimen
Mount a fully charged extinguisher in an upright position. Mount extinguishers intended for use in vehicles in
their intended bracket. Extinguishers not intended for use in vehicles may be tested without a bracket.
12 © ISO 2009 – All rights reserved

7.5.2.5 Test orientation
7.5.2.5.1 Axes of orientation
Subject the extinguisher to the vibration test specified in 7.5.2.5.2 or 7.5.2.5.3 in each of the three rectilinear
axes in the following order: horizontal, lateral and vertical.
7.5.2.5.2 General extinguishers
The vibration applied shall have the following characteristics:
⎯ frequency: 40 Hz;
⎯ amplitude: 0,25 mm ± 0,03 mm;
⎯ duration: 2 h (in each orientation specified in 7.5.2.5.1).
7.5.2.5.3 Vehicle extinguishers
Subject the vehicle extinguishers to the following tests.
a) Subject the extinguisher to the variable frequency and amplitude specified below in each orientation
specified in 7.5.2.5.1:
⎯ frequency: 10 Hz to 19 Hz, amplitude: 0,75 mm ± 0,08 mm;
⎯ frequency: 20 Hz to 39 Hz, amplitude: 0,50 mm ± 0,05 mm;
⎯ frequency: 40 Hz to 60 Hz, amplitude: 0,25 mm ± 0,03 mm.
Vibrate the extinguisher for 5 min at each frequency and increase the frequency at discrete intervals of
2 Hz.
b) Vibrate the extinguisher for 2 h at the frequency that produced the maximum resonance as determined in
a) above or, if no resonance is observed, subject the extinguisher to the test specified in 7.5.2.5.2.
Complete the tests specified in a) and b) above in one plane before making tests in the next plane.
7.6 Resistance to corrosion
7.6.1 External corrosion test
Subject complete and fully charged extinguishers, including their mounting bracket and wall hook, to a salt
spray test in accordance with the neutral salt spray test (NSS) as defined in ISO 9227, for a period of 480 h.
Carefully wash the extinguisher to remove any salt deposits and let it dry for 24 h. Test two samples, either
two of the same size or one sample each of two different sizes from the same family.
At the conclusion of the test, the following requirements shall be satisfied.
⎯ The mechanical operation of all working parts shall be unimpaired; the force required to release the safety
device shall be as specified in 9.11.1.
⎯ The minimum effective discharge time and method of operation shall comply with requirements specified
in 7.2 and 9.10.
⎯ The pressure gauge, if one is fitted, shall remain functional and watertight. It shall conform to 9.12.2 and
9.12.7.
⎯ There shall be no corrosion of the metal of the extinguisher body; discoloration or superficial corrosion of
non-ferrous metals is acceptable, but galvanic corrosion between dissimilar metals shall not be permitted.
⎯ When tested in accordance with 9.9.3, the burst pressure of the hose shall be as specified. The test shall
be carried out at 20 ± 5 °C.
7.6.2 Internal corrosion test for extinguishers using water-based media
Subject two extinguishers, charged in accordance with the manufacturer's filling instructions, eight times to the
temperature cycle defined in Table 3.
Table 3 — Temperature cycle
a
Duration
Temperature
Stage
h °C
b
24 ± 1
W 24
2 20 ± 5
24 ± 1 60 ± 2
W 24 20 ± 5
a
The temperature refers to the ambient temperature of the conditioning chamber. A liquid bath shall not be used. The
duration of any one complete cycle shall not exceed 120 h.

b
The lowest temperature marked on the extinguisher ± 2 °C. See 7.1.

On completion of the eight temperature cycles, cut each body into two sections in a manner sufficient to
permit internal examination. Disregard detachment of any protective coating local to the plane of section.
There shall be no visible signs of corrosion of the metal nor detachment, cracking or bubbling of any protective
coating. There shall be no visible change in the colour of the extinguishing media other than that resulting
from the thermal cycling.
Allowance should be made for a change of colour that occurs naturally due to the temperature changes. It is
recommended that two samples of the agent be stored in closed glass containers and one subjected to the
same cycles as the extinguishers in order to establish a reference sample.
7.7 Tapping test (powder extinguishers only)
7.7.1 Requirements
Portable extinguishers shall comply with the following requirements after being subjected to the conditioning
specified in 7.7.3; they shall
a) operate satisfactorily;
b) commence discharge within 5 s of the opening of the control valve;
c) not retain more than 15 % of initial charge within the extinguisher following complete discharge (complete
extinguisher discharge includes the medium and propellant).
7.7.2 Test apparatus
The test apparatus shall consist of a compaction machine, designed to accept only one extinguisher at a time,
which shall be raised by a rod and guided by castors.
The plate supporting the extinguisher shall be steel (300 ± 5) mm square and (60 ± 1) mm thick. Figure 1 is an
example of an acceptable test apparatus.
14 © ISO 2009 – All rights reserved

Observe the following points.
⎯ Ensure that the rod is adjustable so as to adjust to the extinguisher base.
⎯ Ensure that the rod can move freely in the guide castors.
⎯ The extinguisher shall be guided without constraint.
⎯ The impact shall take place on the steel plate and not on the rod.

a)  General diagram
Figure 1 (continued)
b)  View from above
Figure 1 (continued)
16 © ISO 2009 – All rights reserved

Dimensions in millimetres
c)  Details of cam, key item No. 9 in Figure 1 a)
Key
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...