Fire protection — Foam fire extinguishing systems — Part 6: Vehicle mounted compressed air foam systems

ISO 7076-6:2016 specifies requirements for compressed air foam systems (CAFS) in which foam concentrate and compressed air are continuously added to the water being discharged from the fire-fighting pump. This part of ISO 7076 is applicable to CAFS that can be permanently installed in fire-fighting vehicles, transportable, or mobile. ISO 7076-6:2016 specifies requirements for CAFS which are used at ambient temperatures ranging from ?10 °C to +40 °C. ISO 7076-6:2016 does not apply to stationary CAFS. ISO 7076-6:2016 does not apply to requirements for hazards related to handling foam concentrates, noise generated by CAFS, drives, auxiliary equipment, power sources, or pumps connected to the CAFS. ISO 7076-6:2016 does not specify requirements for special hazards arising from particular conditions under which CAFS are used, for example: - immunity against electromagnetic fields and electrostatic discharge; - operation without supervision; - events specific to the location where the CAFS is set up (e.g. on public roads); - handling of any equipment, devices, etc., which have to be connected to the CAFS or are joined to it (e.g. branch pipes, nozzles and pressure hoses); - decommissioning and disposal.

Protection contre l'incendie — Systèmes d'extinction d'in cendie à mousse — Partie 6: Équipement pour mousse physique à air comprimé monté sur vehicules

General Information

Status
Published
Publication Date
30-May-2016
Current Stage
9093 - International Standard confirmed
Completion Date
09-Dec-2021
Ref Project

Relations

Buy Standard

Standard
ISO 7076-6:2016 - Fire protection -- Foam fire extinguishing systems
English language
21 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

INTERNATIONAL ISO
STANDARD 7076-6
First edition
2016-06-01
Fire protection — Foam fire
extinguishing systems —
Part 6:
Vehicle mounted compressed air
foam systems
Protection contre l’incendie — Systèmes d’extinction d’in cendie à
mousse —
Partie 6: Équipement pour mousse physique à air comprimé monté
sur vehicules
Reference number
ISO 7076-6:2016(E)
©
ISO 2016

---------------------- Page: 1 ----------------------
ISO 7076-6:2016(E)

COPYRIGHT PROTECTED DOCUMENT
© ISO 2016, Published in Switzerland
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized otherwise in any form
or by any means, electronic or mechanical, including photocopying, or posting on the internet or an intranet, without prior
written permission. Permission can be requested from either ISO at the address below or ISO’s member body in the country of
the requester.
ISO copyright office
Ch. de Blandonnet 8 • CP 401
CH-1214 Vernier, Geneva, Switzerland
Tel. +41 22 749 01 11
Fax +41 22 749 09 47
copyright@iso.org
www.iso.org
ii © ISO 2016 – All rights reserved

---------------------- Page: 2 ----------------------
ISO 7076-6:2016(E)

Contents Page
Foreword .v
Introduction .vi
1 Scope . 1
2 Normative references . 1
3 Terms and definitions . 2
4 Requirements . 3
4.1 Compliance . 3
4.1.1 Type assessments . 3
4.1.2 Individual assessments . 3
4.2 Safety and protective measures. 4
4.2.1 General. 4
4.2.2 Mechanical equipment. 4
4.2.3 Components under pressure . 5
4.2.4 Material, parts and components . 5
4.2.5 Hot parts . 5
4.2.6 Electrical equipment . 5
4.2.7 Operator controls and indicators . 5
4.2.8 System failure and continuation of on-going fire-fighting operation . 5
4.2.9 Shutdown control . 6
4.2.10 Maintenance and service . 6
4.2.11 Protection against over-speed . 6
4.2.12 Safety from over-heating . 6
4.3 Performance . 6
4.3.1 Operation . 6
4.3.2 Proportioning ratio and foam solution/air volume ratio . 6
4.3.3 Storage vessels . 7
5 Tests . 7
5.1 General . 7
5.1.1 Atmospheric conditions for tests. 7
5.1.2 Mounting arrangements . 7
5.1.3 Operating conditions for tests . 7
5.1.4 Tolerances . 8
5.1.5 Provision for tests . 8
5.1.6 Test schedule . 8
5.2 Nominal performance . 8
5.2.1 Object . 8
5.2.2 Procedure . 8
5.2.3 Measurements . 8
5.2.4 Requirements . 9
5.3 Endurance . 9
5.3.1 Object . 9
5.3.2 Procedure . 9
5.3.3 Measurements . 9
5.3.4 Requirements . 9
6 Designation .10
7 Marking and data .10
7.1 Marking .10
7.2 Operator instructions .11
7.2.1 General.11
7.2.2 CAFS information .11
7.2.3 Description . . .11
7.2.4 Commissioning, operating and decommissioning .12
© ISO 2016 – All rights reserved iii

---------------------- Page: 3 ----------------------
ISO 7076-6:2016(E)

7.2.5 Servicing and maintenance .12
7.2.6 Fault causes and corrections .13
7.2.7 Other technical documents .13
7.2.8 Short-form operating instructions .13
8 Report .13
Annex A (informative) Guidance on the inspection and testing of CAFS .15
Bibliography .21
iv © ISO 2016 – All rights reserved

---------------------- Page: 4 ----------------------
ISO 7076-6:2016(E)

Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work of preparing International Standards is normally carried out
through ISO technical committees. Each member body interested in a subject for which a technical
committee has been established has the right to be represented on that committee. International
organizations, governmental and non-governmental, in liaison with ISO, also take part in the work.
ISO collaborates closely with the International Electrotechnical Commission (IEC) on all matters of
electrotechnical standardization.
The procedures used to develop this document and those intended for its further maintenance are
described in the ISO/IEC Directives, Part 1. In particular the different approval criteria needed for the
different types of ISO documents should be noted. This document was drafted in accordance with the
editorial rules of the ISO/IEC Directives, Part 2 (see www.iso.org/directives).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. ISO shall not be held responsible for identifying any or all such patent rights. Details of
any patent rights identified during the development of the document will be in the Introduction and/or
on the ISO list of patent declarations received (see www.iso.org/patents).
Any trade name used in this document is information given for the convenience of users and does not
constitute an endorsement.
For an explanation on the meaning of ISO specific terms and expressions related to conformity
assessment, as well as information about ISO’s adherence to the WTO principles in the Technical
Barriers to Trade (TBT) see the following URL: Foreword - Supplementary information
The committee responsible for this document is ISO/TC 21, Equipment for fire protection and fire fighting,
Subcommittee SC 6, Foam and powder media and firefighting systems using foam and powder.
ISO 7076 consists of the following parts, under the general title Fire protection — Foam fire extinguishing
systems:
— Part 1: Foam proportioning equipment
— Part 2: Low expansion foam equipment
— Part 3: Medium expansion foam equipment
— Part 4: High expansion foam equipment
— Part 5: Fixed compressed air foam equipment
— Part 6: Vehicle mounted compressed air foam systems
© ISO 2016 – All rights reserved v

---------------------- Page: 5 ----------------------
ISO 7076-6:2016(E)

Introduction
Compressed air foam systems (CAFS) complying with this part of ISO 7076 are installed in or used
in conjunction with fire-fighting vehicles to improve the efficiency of fire-extinguishing processes.
Compressed air foam systems improve the adhesion, penetration and retention time of the fire-
extinguishing agent on the burning material, thereby transferring more energy, and improving the
cooling effect of the applied foam. This is achieved by adding foam concentrates and compressed air, to
be delivered into water under pressure by the fire-fighting pump, to the fire.
Compressed air foam systems generate homogeneous foam that increases the effective contact area
of the foam on the burning material, and improves the adhesion and penetration of the foam to non-
horizontal surfaces of the burning material, thereby increasing the period in which heat is effectively
transferred.
It is assumed that systems defined in this part of ISO 7076 will only be operated by properly trained
personnel.
For CAFS to be used at a temperature outside this temperature range, the particular temperature range
should be specified by the user and the manufacturer should determine by a risk assessment any need
for additional precautions.
vi © ISO 2016 – All rights reserved

---------------------- Page: 6 ----------------------
INTERNATIONAL STANDARD ISO 7076-6:2016(E)
Fire protection — Foam fire extinguishing systems —
Part 6:
Vehicle mounted compressed air foam systems
1 Scope
This part of ISO 7076 specifies requirements for compressed air foam systems (CAFS) in which foam
concentrate and compressed air are continuously added to the water being discharged from the fire-
fighting pump. This part of ISO 7076 is applicable to CAFS that can be permanently installed in fire-
fighting vehicles, transportable, or mobile.
This part of ISO 7076 specifies requirements for CAFS which are used at ambient temperatures ranging
from –10 °C to +40 °C.
This part of ISO 7076 does not apply to stationary CAFS.
This part of ISO 7076 does not apply to requirements for hazards related to handling foam concentrates,
noise generated by CAFS, drives, auxiliary equipment, power sources, or pumps connected to the CAFS.
This part of ISO 7076 does not specify requirements for special hazards arising from particular
conditions under which CAFS are used, for example:
— immunity against electromagnetic fields and electrostatic discharge;
— operation without supervision;
— events specific to the location where the CAFS is set up (e.g. on public roads);
— handling of any equipment, devices, etc., which have to be connected to the CAFS or are joined to it
(e.g. branch pipes, nozzles and pressure hoses);
— decommissioning and disposal.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— IEC Electropedia: available at http://www.electropedia.org/
— ISO Online browsing platform: available at http://www.iso.org/obp
ISO 7000, Graphical symbols for use on equipment — Registered symbols
ISO 12100:2010, Safety of machinery — General principles for design — Risk assessment and risk reduction
ISO 13854, Safety of machinery — Minimum gaps to avoid crushing of parts of the human body
ISO 13857, Safety of machinery — Safety distances to prevent hazard zones being reached by upper and
lower limbs
© ISO 2016 – All rights reserved 1

---------------------- Page: 7 ----------------------
ISO 7076-6:2016(E)

ISO 14120, Safety of machinery — Guards — General requirements for the design and construction of fixed
and movable guards
ISO 15383, Protective gloves for firefighters — Laboratory test methods and performance requirements
IEC 60068-1, Environmental testing — Part 1: General and guidance
IEC 60204-1, Safety of machinery — Electrical equipment of machines — Part 1: General requirements
IEC 61310-2, Safety of machinery — Indication, marking and actuation — Part 2: Requirements for marking
3 Terms and definitions
For the purposes of this document, the terms and definitions given in ISO 8421-4, ISO 13943 and the
following apply.
3.1
air delivery rate
volume of air, in ambient conditions, that is fed into the CAFS per unit of time
Note 1 to entry: The measurement units are L/min.
3.2
compressed air foam
mixture of water, foam concentrate and compressed air
3.3
compressed air foam delivery pressure
pressure of compressed air foam at the delivery outlet of the CAFS
Note 1 to entry: The measurement units are MPa.
3.4
compressed air foam delivery rate
volume of compressed air foam at the delivery outlet of the CAFS, converted at atmospheric pressure,
per unit of time
Note 1 to entry: The measurement units are L/min.
3.5
compressed air foam system
CAFS
system in which a foam concentrate and air are continuously added under pressure to the water being
discharged from a fire-fighting pump
3.6
dry foam
operation defined by a nominal foam solution/air volume ratio greater than 1:10, being mixed in the CAFS
3.7
flushing procedure
process to ensure that foam proportioning system associated pipework, to the discharge connection, is
adequately cleaned of foam concentrate and solution to avoid any damage
EXAMPLE Procedure to avoid damage by corrosion.
3.8
foam concentrate delivery rate
volume of foam concentrate fed into CAFS per unit of time
Note 1 to entry: The measurement units are L/min.
2 © ISO 2016 – All rights reserved

---------------------- Page: 8 ----------------------
ISO 7076-6:2016(E)

3.9
foam solution/air volume ratio
relationship between parts of liquid (foam solution) and air (at atmospheric pressure) being mixed
together in a CAFS mixing device
Note 1 to entry: The measurement units are L/min.
3.10
foam solution delivery rate
volume of foam solution delivered per unit of time by a system
Note 1 to entry: The measurement units are L/min.
Note 2 to entry: At proportioning ratios of up to 1 %, the difference between water delivery rate and foam
solution delivery rate can be neglected.
3.11
operating range
range (of conditions) specified by the manufacturer of a system and within which the CAFS can be
operated without limitations while achieving the intended performance characteristics
3.12
proportioning ratio
amount of foam concentrate added to water given as a percentage in the foam solution
3.13
water delivery rate
volume of water fed into CAFS per unit of time
Note 1 to entry: The measurement units are L/min.
3.14
wet foam
operation defined by a nominal foam solution/air volume ratio between 1:3 and 1:10, being mixed in
the CAFS
4 Requirements
4.1 Compliance
4.1.1 Type assessments
In order to comply with this part of ISO 7076, the CAFS representative of normal manufacture shall
meet the requirements of Clauses 4, 6 and 7, which shall be verified by visual inspection or engineering
assessment, shall be tested as described in Clause 5 and shall meet the requirements of the tests (see
Annex A for guidance on conducting the assessments).
It is recognized that minor variations occur in the design of CAFS (e.g. to ensure compatibility with
multiple truck types). Where minor variations occur and in the interests of economy, only one variant
of each model need undergo type assessments. The CAFS should undergo new type assessments where
a design change is likely to affect a requirement of this part of ISO 7076. The extent of the re-assessment
can be limited, depending on the type of design change that has been made to the CAFS. In all cases, the
manufacturer should maintain appropriate documentation.
4.1.2 Individual assessments
In addition to the requirements of 4.1.1, each CAFS produced by the manufacturer shall meet the
requirements of Table 1, which shall be verified by visual inspection, engineering assessment or test,
and shall meet the requirements of the tests (see Annex A for guidance on conducting the assessments).
© ISO 2016 – All rights reserved 3

---------------------- Page: 9 ----------------------
ISO 7076-6:2016(E)

Table 1 — Individual assessment schedule
Assessment Subclause
number
Installation of the CAFS on the vehicle 4.2.2.1
Moving parts 4.2.2.2
Over-pressurization prevention 4.2.3.3
Accumulated water removal 4.2.4.1
Hot parts safety 4.2.5.1
Hot parts notice 4.2.5.2
Electrical equipment safety 4.2.6.2
Operator controls and indicators 4.2.7
Shutdown control 4.2.9
Maintenance and service 4.2.10
Protection against over-speed 4.2.11
Safety from over-heating 4.2.12
Drainage 4.3.1.3
Proportioning ratio and foam solution/air volume ratio 4.3.2.1
Maintenance of proportioning ratio 4.3.2.5
Maintenance of foam solution/air volume ratio 4.3.2.7
Storage vessels 4.3.3
Nominal performance 5.2
Marking 7.1
4.2 Safety and protective measures
4.2.1 General
Safety of machinery shall comply with the requirements of ISO 12100.
4.2.2 Mechanical equipment
4.2.2.1 Installation of CAFS on the vehicle
CAFS shall be so designed and constructed as to be installed on the vehicle, in such a way as to prevent
malfunction, disconnection, or damage caused by vibration during operation of the vehicle.
4.2.2.2 Moving parts
4.2.2.2.1 Personnel shall be protected from injury by moving parts during inspection, operation and
service. Where applicable, the following shall be provided:
a) fixed guards as defined in ISO 14120, complying with the safety distances defined in ISO 13857;
b) minimum clearance at the end of a motion sequence according to ISO 13854.
4.2.2.2.2 A cautionary notice shall be fitted to, or adjacent to parts that are accessed during inspection,
operation and service and may cause injury.
4 © ISO 2016 – All rights reserved

---------------------- Page: 10 ----------------------
ISO 7076-6:2016(E)

4.2.3 Components under pressure
4.2.3.1 The maximum operation pressure while using CAFS from the designated delivery outlets shall
not exceed 1,0 MPa.
NOTE Higher pressures for specific applications might be agreed between users and a manufacturer.
4.2.3.2 A device shall be provided to relieve the internal pressure of the CAFS after operation.
4.2.3.3 Prevention of over-pressurization shall be ensured.
4.2.4 Material, parts and components
4.2.4.1 If water can accumulate in the air system, a means of removing it shall be provided.
4.2.4.2 Material, parts and components shall be resistant to corrosion by the foam concentrate, foam
solution and compressed air foam.
4.2.5 Hot parts
4.2.5.1 Personnel shall be protected from injury by hot parts during inspection, operation and service
(see ISO 13732-1).
4.2.5.2 A cautionary notice shall be fitted to, or adjacent to parts that are accessed during inspection,
operation and service that may cause injury.
4.2.6 Electrical equipment
4.2.6.1 Electrical equipment shall meet the requirements of IEC 60204-1.
4.2.6.2 Design measures shall be taken to protect electrical equipment from damage by water, foam
concentrate, and foam solution during filling of storage vessels and operation.
4.2.7 Operator controls and indicators
4.2.7.1 Controls and indicators used by the operator during fire-fighting actions shall be adequately
arranged and operated for the purpose of safety, visibility and easier operation [refer to ISO 9335-1,
ISO 9335-2, ISO 9335-3 and IEC 61310 (all parts)].
4.2.7.2 Manual operating equipment and other control elements shall be easy to reach and to operate
when wearing protective gloves for fire-fighters as specified in ISO 15383 and without having to apply
excessive force.
4.2.7.3 The number of switching operations shall be kept to a minimum and the control elements shall
be arranged according to the operating sequence, in such a manner that operating errors are minimized.
4.2.8 System failure and continuation of on-going fire-fighting operation
4.2.8.1 Safety-relevant failures in the CAFS shall be clearly indicated.
EXAMPLE Visual indicators on the fire-fighting pump’s operating panel, supervision of control valves, etc.
© ISO 2016 – All rights reserved 5

---------------------- Page: 11 ----------------------
ISO 7076-6:2016(E)

4.2.8.2 Even in case of failure regarding injection of foam concentrate and/or compressed air, the CAFS
and the associated installation shall then remain in a safe condition to ensure that further extinguishing
operation with water is maintained.
4.2.9 Shutdown control
The operating control station shall be equipped with a control that serves to switch off the system with
a single operating step.
4.2.10 Maintenance and service
4.2.10.1 Each part of CAFS shall be easily maintained and serviced.
4.2.10.2 Each part of CAFS which requires lubrication, such as bearings or moving parts shall be easily
lubricated.
4.2.11 Protection against over-speed
If necessary, the CAFS shall have a means of preventing maximum speed being exceeded. When the
system is switched off, the firefighting pump shall be usable without restrictions and with no user
intervention.
4.2.12 Safety from over-heating
A visual or audible alarm shall activate when the temperature of air compressor oil or temperature of
compressed air rises above a safe level determined by the manufacturer.
4.3 Performance
4.3.1 Operation
4.3.1.1 CAFS shall be capable of 6 h continuous operation at the nominal compressed air foam delivery
rate specified by the manufacturer.
4.3.1.2 Adding foam concentrate while the CAFS is operating shall not cause an interruption in
compressed air foam delivery.
4.3.1.3 It shall be possible to drain, the CAFS of water and foam concentrate.
4.3.1.4 CAFS shall operate at ambient temperature ranging from –10 °C to +40 °C.
4.3.2 Proportioning ratio and foam solution/air volume ratio
4.3.2.1 The proportioning ratio and foam solution/air volume ratio may be continuously or
incrementally adjustable.
4.3.2.2 The method of setting and selecting the proportioning ratio and foam solution/air volume ratio
shall be agreed between user and manufacturer.
4.3.2.3 At nominal foam solution delivery rate, the achievable proportioning ratio shall be not less
than 1 %.
4.3.2.4 Across the range of water delivery rates, the proportioning ratio shall be adjustable at least
within the range 0,5 % to 1,0 %.
6 © ISO 2016 – All rights reserved

---------------------- Page: 12 ----------------------
ISO 7076-6:2016(E)

4.3.2.5 The proportioning ratio shall be automatically maintained within the range −0 % to +30 % of
the designated value, even when pressure or rate of compressed air foam may change.
4.3.2.6 At the nominal proportioning ratio, the CAFS shall produce wet foam within the compressed
air foam delivery rate limits specified by
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.