Fire protection — Automatic sprinkler systems — Part 7: Requirements and test methods for early suppression fast response (ESFR) sprinklers

ISO 6182-7:2004 specifies performance requirements, test methods and marking requirements for fusible element and glass-bulb early suppression fast response (ESFR) sprinklers. It is applicable to ESFR sprinklers with flow constants of 202 ± 8.

Protection contre l'incendie — Systèmes d'extinction automatiques du type sprinkler — Partie 7: Prescriptions et méthodes d'essai des sprinklers de type "extinction précoce/réaction rapide"

General Information

Status
Withdrawn
Publication Date
30-Mar-2004
Withdrawal Date
30-Mar-2004
Current Stage
9599 - Withdrawal of International Standard
Completion Date
30-Mar-2020
Ref Project

Relations

Buy Standard

Standard
ISO 6182-7:2004 - Fire protection -- Automatic sprinkler systems
English language
40 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

INTERNATIONAL ISO
STANDARD 6182-7
First edition
2004-04-01


Fire protection — Automatic sprinkler
systems —
Part 7:
Requirements and test methods for early
suppression fast response (ESFR)
sprinklers
Protection contre l'incendie — Systèmes d'extinction automatiques du
type sprinkler —
Partie 7: Prescriptions et méthodes d'essai des sprinklers de type
«extinction précoce/réaction rapide»





Reference number
ISO 6182-7:2004(E)
©
ISO 2004

---------------------- Page: 1 ----------------------
ISO 6182-7:2004(E)
PDF disclaimer
This PDF file may contain embedded typefaces. In accordance with Adobe's licensing policy, this file may be printed or viewed but
shall not be edited unless the typefaces which are embedded are licensed to and installed on the computer performing the editing. In
downloading this file, parties accept therein the responsibility of not infringing Adobe's licensing policy. The ISO Central Secretariat
accepts no liability in this area.
Adobe is a trademark of Adobe Systems Incorporated.
Details of the software products used to create this PDF file can be found in the General Info relative to the file; the PDF-creation
parameters were optimized for printing. Every care has been taken to ensure that the file is suitable for use by ISO member bodies. In
the unlikely event that a problem relating to it is found, please inform the Central Secretariat at the address given below.


©  ISO 2004
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by any means,
electronic or mechanical, including photocopying and microfilm, without permission in writing from either ISO at the address below or
ISO's member body in the country of the requester.
ISO copyright office
Case postale 56 • CH-1211 Geneva 20
Tel. + 41 22 749 01 11
Fax + 41 22 749 09 47
E-mail copyright@iso.org
Web www.iso.org
Published in Switzerland

ii © ISO 2004 – All rights reserved

---------------------- Page: 2 ----------------------
ISO 6182-7:2004(E)
Contents Page
Foreword. iv
Introduction . v
1 Scope. 1
2 Normative reference . 1
3 Terms and definitions. 1
4 Product consistency. 4
5 Product assembly . 4
6 Requirements . 5
7 Test methods. 11
8 Marking of sprinklers. 35
Annex A (informative) Tolerance limit calculation method. 36
Annex B (normative) Tolerances .38
Annex C (informative) Analysis of the strength test for release elements. 39
Bibliography . 40


© ISO 2004 – All rights reserved iii

---------------------- Page: 3 ----------------------
ISO 6182-7:2004(E)
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards bodies
(ISO member bodies). The work of preparing International Standards is normally carried out through ISO
technical committees. Each member body interested in a subject for which a technical committee has been
established has the right to be represented on that committee. International organizations, governmental and
non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely with the
International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization.
International Standards are drafted in accordance with the rules given in the ISO/IEC Directives, Part 2.
The main task of technical committees is to prepare International Standards. Draft International Standards
adopted by the technical committees are circulated to the member bodies for voting. Publication as an
International Standard requires approval by at least 75 % of the member bodies casting a vote.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. ISO shall not be held responsible for identifying any or all such patent rights.
ISO 6182-7 was prepared by Technical Committee ISO/TC 21, Equipment for fire protection and fire fighting,
Subcommittee SC 5, Fixed firefighting systems using water.
ISO 6182 consists of the following parts, under the general title Fire protection — Automatic sprinkler systems:
 Part 1: Requirements and test methods for sprinklers
 Part 2: Requirements and test methods for wet alarm valves, retard chambers and water motor alarms
 Part 3: Requirements and test methods for dry pipe valves
 Part 4: Requirements and test methods for quick-opening devices
 Part 5: Requirements and test methods for deluge valves
 Part 6: Requirements and test methods for check valves
 Part 7: Requirements and test methods for early suppression fast response (ESFR) sprinklers
 Part 9: Requirements and test methods for water mist nozzles
 Part 10: Requirements and test methods for domestic sprinklers
 Part 11: Requirements and test methods for pipe hangers
The following parts are under preparation:
 Part 8: Requirements and test methods for pre-action dry alarm valves
 Part 12: Requirements and test methods for grooved end pipe couplings
 Part 13: Requirements and test methods for extended coverage sprinklers
iv © ISO 2004 – All rights reserved

---------------------- Page: 4 ----------------------
ISO 6182-7:2004(E)
Introduction
This part of ISO 6182 is one of a number of ISO Standards prepared by ISO/TC 21 covering requirements and
test methods for early suppression fast response (ESFR) sprinklers.
© ISO 2004 – All rights reserved v

---------------------- Page: 5 ----------------------
INTERNATIONAL STANDARD ISO 6182-7:2004(E)

Fire protection — Automatic sprinkler systems —
Part 7:
Requirements and test methods for early suppression fast
response (ESFR) sprinklers
1 Scope
This part of ISO 6182 specifies performance requirements, test methods and marking requirements for fusible
element and glass-bulb early suppression fast response (ESFR) sprinklers. It is applicable to ESFR sprinklers
with flow constants of 202 ± 8.
NOTE 1 Requirements for ESFR sprinklers with flow constants other than 202 ± 8 are in preparation.
NOTE 2 All pressure data in this part of ISO 6182 are also given as gauge pressure in bar. The correct SI unit for
5 2
pressure is the pascal (Pa) (1 bar = 10 N/m = 0,1 MPa).
2 Normative reference
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
ISO 7-1:1994, Pipe threads where pressure-tight joints are made on the threads — Part 1: Dimensions,
tolerances and designation
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
3.1 General
3.1.1
sprinkler
thermosensitive device designed to react at a predetermined temperature by automatically releasing a stream
of water and distributing it in a specified pattern and quantity over a designated area
3.1.2
conductivity factor
C
measure of the conductance between the sprinkler's heat responsive element and the fitting
0,5
NOTE The conductivity factor is expressed in units of (m/s) .
© ISO 2004 – All rights reserved 1

---------------------- Page: 6 ----------------------
ISO 6182-7:2004(E)
3.1.3
response time index
RTI
measure of sprinkler sensitivity
RTI = t u
where
t is equal to the time constant, expressed in seconds, of the heat-responsive element;
u is the gas velocity, expressed in meters per second
0,5
NOTE 1 The response time index is expressed in units of (m◊s) .
NOTE 2 RTI can be used in combination with the conductivity factor (C) to predict the response of a sprinkler in fire
environments defined in terms of gas temperature and velocity versus time.
3.1.4
orientation A
orientation with the airflow perpendicular to both the waterway axis and the plane of the frame arms and with
the heat responsive element upstream of the frame arms
See Figure 1.
3.1.5
orientation B
orientation with the airflow perpendicular to both the waterway axis and the plane of the frame arms and with
the heat responsive element downstream of the frame arms
See Figure 1.
3.1.6
orientation C
·head onÒ orientation with the axis of the sprinkler inlet parallel to the airflow and the deflector perpendicular to
the airflow
See Figure 1.

a) Orientation A

Figure 1 — Orientations A, B and C
2 © ISO 2004 – All rights reserved

---------------------- Page: 7 ----------------------
ISO 6182-7:2004(E)

b) Orientation B


c) Orientation C
Key
1 air flow
2 tunnel test section (elevation view)
NOTE If the sprinkler has a symmetrical heat responsive element and frame, Orientation A would be the same as
Orientation B. Testing in both positions is not required.
Figure 1 (continued)
3.1.7
actual delivered density
ADD
rate at which water is deposited from an operating sprinkler onto the top horizontal surface of a simulated
burning combustible array
3.1.8
early suppression
sprinkler system performance whereby the first few sprinklers, which operate, are able to provide sufficient
water to the fire early enough so as to reduce the fire to an acceptable level, if not extinguished
3.1.9
early suppression fast response automatic sprinkler
ESFR
thermosensitive device designed to react at a predetermined temperature by automatically releasing a stream
of water and distributing it in a specified pattern and density over a designated area so as to provide early
suppression of a fire when installed on the appropriate sprinkler piping
3.1.10
assembly load
force exerted on the sprinkler at 0 MPa (0 bar) hydraulic pressure at the inlet
© ISO 2004 – All rights reserved 3

---------------------- Page: 8 ----------------------
ISO 6182-7:2004(E)
3.1.11
design load
force exerted on the sprinkler at the service load of the sprinkler
3.1.12
service load
combined force exerted on the sprinkler body by the assembly load of the sprinkler and the equivalent force of
a 1,2 MPa (12 bar) hydraulic pressure of the inlet
3.1.13
average design strength
·axialÒ glass-bulb suppliers specified and assured lowest average design strength of any batch of 50 bulbs
3.2 Sprinklers classified according to type of heat responsive element
3.2.1
fusible element sprinkler
sprinkler that opens under the influence of heat by the melting of a component
3.2.2
glass-bulb sprinkler
sprinkler that opens under the influence of heat by the bursting of the glass bulb caused by the increased
pressure resulting from expansion of the fluid enclosed therein
3.3 Sprinklers classified according to position
3.3.1
pendent sprinkler
P
sprinkler that is arranged in such a way that the water stream is directed downwards against the distribution
plate
3.3.2
upright sprinkler
U
sprinkler that is arranged in such a way that the water stream is directed upwards against the distribution plate
4 Product consistency
It shall be the responsibility of the manufacturer to implement a quality control programme to ensure that
production continuously meets the requirements of this part of ISO 6182 in the same manner as the originally
tested samples.
Every manufactured sprinkler shall pass a leak resistance test equivalent to a hydrostatic pressure of at least
3,4 MPa (34 bar) for at least 2 s.
5 Product assembly
All sprinklers shall be designed and manufactured in such a way that they cannot be readily adjusted,
dismantled or reassembled.
4 © ISO 2004 – All rights reserved

---------------------- Page: 9 ----------------------
ISO 6182-7:2004(E)
6 Requirements
6.1 Dimensions
6.1.1 Sprinklers shall have a nominal thread size of R 3/4.
6.1.2 Nominal thread sizes shall be suitable for fittings threaded in accordance with ISO 7-1.
The dimensions of all threaded connections should conform to International Standards where applied.
National standards may be used if International Standards are not applicable.
6.1.3 All sprinklers shall be constructed so that a sphere of diameter 8 mm can pass through each water
passage in the sprinkler.
6.2 Nominal operating temperatures (see 7.7)
The nominal operating temperature of ESFR sprinklers shall be as indicated in Table 1.
The nominal operating temperatures of all sprinklers shall be specified in advance by the manufacturer and
verified in accordance with 6.3. They shall be determined as a result of the operating temperature test (see
7.7.1). Nominal operating temperatures shall be within the ranges specified in Table 1.
The nominal operating temperature that is to be marked on the sprinkler shall be that determined when the
sprinkler is tested in accordance with 7.7.1, taking into account the specifications of 6.3.
Table 1 — Nominal operating temperature and colour coding
Values in degrees Celsius
Glass-bulb sprinklers Fusible element sprinklers
Liquid colour code Yoke arm colour code
Nominal operating Nominal operating
temperature temperature
68 to 74 red 68 to 74 uncoloured
93 to 104 green 93 to 104 white

6.3 Operating temperatures (see 7.7.1)
Sprinklers shall open within a temperature range of
TT±+(0,035 0,62) (1)
where T is the nominal operating temperature, expressed in degrees Celsius.
6.4 Water flow and distribution
6.4.1 Flow constant (see 7.11)
The flow constant, K, for sprinklers is given by the formula
q
V
K = (2)
p
where
p is the pressure, expressed in bars;
q is the flow rate, expressed in litres per minute (l/min).
V
© ISO 2004 – All rights reserved 5

---------------------- Page: 10 ----------------------
ISO 6182-7:2004(E)
The flow constant for ESFR sprinklers shall have values of 202 ± 8 when determined by the test method of
7.11. All values tested shall be within the acceptable range and the standard deviation divided by the average
value of the flow constant shall be less than 2 %.
6.4.2 Water distribution (see 7.12)
6.4.2.1 To demonstrate the required coverage of the protected area allotted to it, the sprinkler shall be
subjected to the tests specified in 7.12.
6.4.2.2 Ten collection pans, as specified in 7.12.1, shall be utilized on a rotating table to measure the
distribution from a single sprinkler. All pan collection rate values shall be recorded. The tenth pan shall have a
collection rate not exceeding 0,80 mm/min.
6.4.2.3 Three samples, or sets of samples, shall be tested to the requirements of Table 2 in accordance
with 7.12.2.
Table 2 — Sprinkler water distribution measurements
a, b
Number Sprinkler Pipe Ceiling Minimum Minimum Minimum Minimum Minimum
Pressure

of spacing spacing clearance 16-pan flue 20-pan non-flue single
sprinklers  to water- average space average 10-pan non-flue
c c

under the  collection density (4 pans) density average pan
c c,d c
water- pans
average density density

collection
system

m m m MPa mm/min mm/min mm/min mm/min mm/min
(bar)
1 0 0 3,04 0,34 21,22 40,80 NR NR NR
(3,4)
1 0 0 4,42 0,34 19,58 36,31 NR NR NR
(3,4)
1 0 0 4,42 0,51 NR 69,36 37,13 20,40 10,61
(5,1)
2 3,04 0 1,27 0,34 24,48 NR NR NR NR
(3,4)
2 3,04 0 3,04 0,34 22,03 NR NR NR NR
(3,4)
2 0 3,04 1,27 0,34 23,66 NR NR NR NR
(3,4)
2 0 3,04 3,04 0,34 23,26 NR NR NR NR
(3,4)
2 3,66 0 1,27 0,34 17,95 NR NR NR NR
(3,4)
2 0 3,66 1,27 0,34 18,36 NR NR NR NR
(3,4)
2 3,04 0 1,27 0,51 NR NR 31,42 24,48 8,16
(5,1)
2 0 3,04 1,27 0,51 NR NR 31,42 24,48 8,16
(5,1)
4 3,04 3,04 1,27 0,34 27,74 NR NR NR NR
(3,4)
4 3,04 3,04 3,04 0,34 35,09 NR NR NR NR
(3,4)
4 2,44 3,6 1,27 0,34 26,93 NR NR NR NR
(3,4)
4 3,04 3,04 1,27 0,51 NR NR 28,97 24,48 15,10
(5,1)

a
All 0,34 MPa (3,4 bar) tests are performed on a system fed from both directions (double feed).
b
All 0,51 MPa (5,1 bar) tests are performed on a system fed from one direction (single feed), except for the two-sprinklers, single-pipe tests which are
performed on a double-feed system.

c
NR = No requirement (see Figures 8 to 13).

d
Average of the ten non-flue pans with the lowest water collection.

6 © ISO 2004 – All rights reserved

---------------------- Page: 11 ----------------------
ISO 6182-7:2004(E)
6.5 Ability to function (see 7.6)
6.5.1 When tested in accordance with 7.6.1, all operating parts shall clear the sprinkler within 10 s or shall
comply with the requirements of 6.4.2.
6.5.2 The deflector and its supporting parts shall not sustain significant damage as a result of the deflector
strength test specified in 7.6.2 and shall meet the requirements of 6.4.2.
NOTE In most instances, visual examination of the sprinkler is sufficient to establish conformity with the requirements
of 6.5.1 and 6.5.2.
6.6 Strength of sprinkler body (see 7.4)
The sprinkler body shall not show permanent elongation of more than 0,2 % between the load-bearing points
of the sprinkler body after being subjected to twice the average service load as measured in 7.4.
6.7 Strength of release element (see 7.10)
6.7.1 When tested in accordance with 7.10.1, the elements of glass bulbs shall
a) have an average design strength of at least six times the average service load, and
b) have a design strength lower tolerance limit (L ) on the strength distribution curve of at least two times
TL
the upper tolerance limit (U ) of the service load distribution curve based on calculations with a degree
TL
of confidence (y) of 0,99 for 99 % of samples (n).
Calculations will be based on a normal or Gaussian distribution, except where other distributions can be
shown to be more applicable due to manufacturing of designing factors. See Figure 2 and Annex A.

Key
1 average service load 4 L
TL
2 service load curve
5 average design strength
3 U
6 design strength curve
TL
Figure 2 — Strength curve
© ISO 2004 – All rights reserved 7

---------------------- Page: 12 ----------------------
ISO 6182-7:2004(E)
6.7.2 Fusible heat-responsive elements shall sustain the design load when tested in accordance with
7.10.2.
6.8 Leak resistance and hydrostatic strength (see 7.5)
6.8.1 A sprinkler shall not show any sign of leakage when tested by the method specified in 7.5.1.
6.8.2 A sprinkler shall not rupture, operate, or release any parts when tested by the method specified in
7.5.2.
6.9 Heat exposure (see 7.8)
6.9.1 Glass-bulb type ESFR sprinklers
There shall be no damage to the elements of the glass bulb when the sprinkler is tested by the method
specified in 7.8.1.
6.9.2 All ESFR sprinklers
ESFR sprinklers shall withstand exposure to increased ambient temperature without evidence of weakness or
failure when tested by the method specified in 7.8.2.
6.10 Thermal shock (see 7.9)
Glass-bulb type ESFR sprinklers shall not be damaged when tested by the method specified in 7.9.
6.11 Corrosion
6.11.1 Stress corrosion (see 7.13.1)
When tested in accordance with 7.13.1, each sprinkler shall show no cracks, delaminations, or failures which
can possibly affect its ability to satisfy other requirements. Following exposure, half the sprinkler samples shall
0,5
be tested to requirements of 6.8.1. The remaining samples shall have an RTI of (28 ± 8) (m◊s) when tested
in accordance with 7.7.2.2.
6.11.2 Moist sulfur-dioxide/carbon-dioxide corrosion (see 7.13.2)
ESFR sprinklers shall be resistant to sulfur-dioxide/carbon-dioxide saturated with water vapour when
conditioned in accordance with 7.13.2. Following exposure, the sprinklers shall meet the requirements of 6.8.1
at 1,20 MPa (12,0 bar). Half the samples shall meet the requirements of 6.3 and the remaining samples shall
0,5
have an RTI of (28 ± 8) (m◊s) when tested in accordance with 7.7.2.2.
6.11.3 Moist hydrogen-sulfide corrosion (see 7.13.3)
ESFR sprinklers shall be resistant to hydrogen sulfide saturated with water vapour when conditioned in
accordance with 7.13.3. Following exposure, the sprinklers shall meet the requirements of 6.8.1 at 1,20 MPa
(12,0 bar). Half the samples shall meet the requirements of 6.3 and the remaining samples shall have an RTI
0,5
of (28 ± 8) (m◊s) when tested in accordance with 7.7.2.2.
6.11.4 Salt-spray corrosion (see 7.13.4)
ESFR sprinklers shall be resistant to salt spray when conditioned in accordance with 7.13.4. Following
exposure, the sprinklers shall be tested at 1,20 MPa (12,0 bar) in accordance with 6.8.1 and have an RTI of
0,5
(28 ± 8) (m◊s) when tested in accordance with 7.7.2.2.
8 © ISO 2004 – All rights reserved

---------------------- Page: 13 ----------------------
ISO 6182-7:2004(E)
6.11.5 Moist-air exposure (see 7.13.5)
Sprinklers shall be resistant to moist-air exposure when tested in accordance with 7.13.5. Following exposure,
the sprinklers shall operate as intended when tested in accordance with 7.6.2.
6.12 Water hammer (see 7.15)
Sprinklers shall not leak when subjected to pressure surges from 0,4 MPa to 3,4 MPa (4 bar to 34 bar). They
shall show no signs of mechanical damage when tested in accordance with 7.15. Following the water-hammer
test, the samples shall not leak when tested in accordance with 7.5.1 and shall operate as intended when
tested in accordance with 7.6.2.
6.13 Dynamic heating (see 7.7.2)
6.13.1 See also the references in the Bibliography.
0,5
6.13.2 ESFR sprinklers shall meet the RTI limits of (28 ± 8) (m◊s) when tested in orientations A and B as
described in 7.7.2. The RTI value shall not exceed 138 % of the original value when tested in orientation C as
described in 7.7.2. The conductivity factor, C, is not required for this calculation in this part of ISO 6182.
0,5
6.13.3 The conductivity factor (C) shall not exceed 1,0 (m/s) when determined using the prolonged plunge
test (see 7.7.3.2) or the prolonged exposure ramp test (see 7.7.3.3).
6.14 Resistance to heat (see 7.14)
Open sprinklers shall be resistant to high temperatures when tested in accordance with 7.14. After exposure,
the sprinkler shall not show visual deformation or fracture.
6.15 Resistance to vibration (see 7.16)
Sprinklers shall be able to withstand the effects of vibration without deterioration when tested in accordance
with 7.16. After the vibration test of 7.16, sprinklers shall show no visible deterioration and shall meet the
0,5
requirements of 6.8.1 and shall have an RTI of (28 ± 8) (m◊s) when tested in accordance with 7.7.2.2.
6.16 Resistance to impact (see 7.17)
ESFR sprinklers shall have adequate strength to withstand impacts associated with handling, transport and
installation without deterioration of performance or reliability. These sprinklers shall show no fracture or
deformation, shall meet the leak resistance requirement of 6.8.1 and the dynamic heating test requirement of
6.13.3 after the impact test of 7.17.1. If the sprinkler is deformed during testing, water distribution testing
(6.4.2) shall be required.
6.17 Lateral discharge (see 7.18)
When tested in accordance with 7.18, there shall be no direct impingement or dripping of water from the
target.
6.18 Thirty-day leakage resistance (see 7.19)
When tested in accordance with 7.19 sprinklers shall not leak, sustain distortion, or suffer any other
mechanical damage when subjected to 2 MPa (20 bar) water pressure for 30 d.
6.19 Vacuum resistance (see 7.20)
Sprinklers shall not exhibit distortion or mechanical damage and shall meet the leakage requirements of 6.8.1
after being subjected to the test in 7.20.
© ISO 2004 – All rights reserved 9

---------------------- Page: 14 ----------------------
ISO 6182-7:2004(E)
6.20 Resistance to low temperatures (see 7.21)
Sprinklers shall be resistant to low temperatures when tested in accordance with 7.21. After exposure, the
sprinkler shall either be visibly damaged, leak subsequent to thawing, or not be damaged. Sprinklers not
0,5
visibly damaged shall be subjected to the requirements of 6.8 and shall have an RTI of (28 ± 8) (m◊s) when
tested in accordance with 7.7.2.2.
6.21 Actual delivered density (see 7.22)
ESFR sprinklers shall meet the minimum average densities shown in Table 3 when measured in accordance
with 7.22.
Table 3 — ADD measurements
Number of Sprinkler Pipe Ceiling Freeburn Pressure Direction Minimum Minimum
sprinklers spacing spacing clearance convective of feed 16-pan flue space
under the  to water- heat release flow average (4 pans)
a
ADD  collection  ADD
average
apparatus  pans
MPa
m m m kW (bar) mm/min
mm/min
0,34
1 0 0 4,57 1 318 Double 19,18 60,38
(3,4)
0,34
1 0 0 4,57 2 636 Double 9,79 20,40
(3,4)
0,34
2 3,66 0 1,22 2 636 Single 11,83 NR
(3,4)
0,34
2 0 3,66 1,22 2 636 Double 14,28 NR
(3,4)
0,34
4 2,44 3,66 1,22 2 636 Double 26,11 NR
(3,4)
a
NR = No requirement.

6.22 Thrust force measurements (see 7.23)
ESFR sprinklers shall meet the minimum thrust force requirements shown in Table 4 when tested in
accordance with 7.23.
Table 4 — Thrust
Pressure Direction of feed flow Ceiling clearance Minimum required thrust
to thrust plate

MPa m Pa
(bar) (mbar)
0,34 0,71
Double 1,2
(3,4) (0,71)
0,34 0,44
Double 2,1
(3,4) (0,44)
0,51 0,99
Single 2,1
(5,1) (0,99)

10 © ISO 2004 – All rights reserved

---------------------- Page: 15 ----------------------
ISO 6182-7:2004(E)
6.23 Reaction force test (see 7.24)
ESFR sprinklers shall meet the minimum reaction force requirements shown in Table 5 when tested in
accordance with 7.24.
Table 5 — Reaction force
a
Pressure
Minimum required reaction force


MPa
N
(bar)
0,34
57
(3,4)
0,51
85
(5,1)
a
This is 35 % of the maximum force of a K 202 nozzle 476 N/MPa ¥ 0,35 = 167 N/MPa (47,6 N/bar ¥ 0,35 = 16,7 N/bar).
7 Test methods
7.1 General conditions
Carry out the following tests for each type of sprinkler. Before testing, precise drawings of parts and the
assembly shall be submitted together with the appropriate specifications (using SI units). Carry out tests at a
room temperature of (20 ± 5) °C, unless other temperatures are indicated. Test sprinklers with all the
components required by their design and installation. A suggested test programme is illustrated in Figure 3 for
guidance.
7.2 Preliminary examination
Examine the construction to ensure that it complies with the requirements of Clause 4 and Clause 5.
7.3 Visual examination
Before testing, examine the sprinklers visually with respect to the following points:
a) marking,
b) conformity of the sprinklers with the manufacturer's drawings and specifications, and
c) obvious defects.
7.4 Body strength test (see 6.6)
7.4.1 Measure the service load for 15 sprinklers by securely installing each sprinkler, at room temperature,
in a tensile/compression test machine and applying an equivalent of a hydraulic pressure of 1,2 MPa (12 bar)
at the inlet.
Use an indicator capable of reading deflection to an accuracy of 0,01 mm to measure any change in length of
the sprinkler between its load bearing points. Movement of the sprinkler shank thread in the threaded bushing
of the test machine shall be avoided or taken into account.
Release hydraulic pressure, or equivalent force, and remove the heat responsive element of the sprinkler by a
suitable method. When the sprinkler is at room temperature, make a second measurement using the indicator.
Apply an increasing mechanical load to the sprinkler, at a rate not exceeding 500 N/min, until the indicator
reading at the deflector end of the sprinkler returns to the initial value achieved as assembled and under
hydrostatic, or equivalent, load. The mechanical load necessary to achieve this shall be recorded as the
service load. Calculate the average service load. See Annex C.
© ISO 2004 – All rights reserved 11

---------------------- Page: 16 ----------------------
ISO 6182-7:2004(E)
Key
number of sprinklers required

test programme number

Test programme
1 Preliminary examination (7.2)
2 Visual examination (7.3)
3 Body strength (7.4)
4 Leak resistance and hydrostatic strength (7.5)
5 Lodgement (7.6.1)
6 Exposure verification of ability-to-function (7.6.2)
7 Deflector strength (7.6.2)
8 Operating temperature (7.7)
9 Plunge (7.7.2.1)
10 Exposure verification plunge (7.7.2.2)
11 Determination of conductivity factor (7.7.3)
12 Heat expo
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.