Fire detection and alarm systems - Part 15: Point type fire detectors using scattered light, transmitted light or ionization sensors in combination with a heat sensor

ISO 7240-15:2004 specifies requirements, test methods and performance criteria for point-type resettable multisensor fire detectors for use in fire detection systems installed in buildings, incorporating in one mechanical enclosure at least one smoke sensor and at least one other sensor which responds to heat, and in which the signal(s) of the smoke sensor(s) is/are combined with the signal(s) of the heat sensor(s). The performance of single components within a multisensor fire detector covered by this standard may not be sufficient for conformity to other standards for the single sensor.

Systèmes de détection et d'alarme d'incendie — Partie 15: Détecteurs d'incendie multicapteurs

General Information

Status
Withdrawn
Publication Date
25-Feb-2004
Withdrawal Date
25-Feb-2004
Current Stage
9599 - Withdrawal of International Standard
Start Date
23-Jun-2014
Completion Date
13-Dec-2025
Ref Project

Relations

Effective Date
28-Feb-2023
Standard
ISO 7240-15:2004 - Fire detection and alarm systems
English language
61 pages
sale 15% off
Preview
sale 15% off
Preview

Frequently Asked Questions

ISO 7240-15:2004 is a standard published by the International Organization for Standardization (ISO). Its full title is "Fire detection and alarm systems - Part 15: Point type fire detectors using scattered light, transmitted light or ionization sensors in combination with a heat sensor". This standard covers: ISO 7240-15:2004 specifies requirements, test methods and performance criteria for point-type resettable multisensor fire detectors for use in fire detection systems installed in buildings, incorporating in one mechanical enclosure at least one smoke sensor and at least one other sensor which responds to heat, and in which the signal(s) of the smoke sensor(s) is/are combined with the signal(s) of the heat sensor(s). The performance of single components within a multisensor fire detector covered by this standard may not be sufficient for conformity to other standards for the single sensor.

ISO 7240-15:2004 specifies requirements, test methods and performance criteria for point-type resettable multisensor fire detectors for use in fire detection systems installed in buildings, incorporating in one mechanical enclosure at least one smoke sensor and at least one other sensor which responds to heat, and in which the signal(s) of the smoke sensor(s) is/are combined with the signal(s) of the heat sensor(s). The performance of single components within a multisensor fire detector covered by this standard may not be sufficient for conformity to other standards for the single sensor.

ISO 7240-15:2004 is classified under the following ICS (International Classification for Standards) categories: 13.220.20 - Fire protection. The ICS classification helps identify the subject area and facilitates finding related standards.

ISO 7240-15:2004 has the following relationships with other standards: It is inter standard links to ISO 1864:1975, ISO 7240-15:2014. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

You can purchase ISO 7240-15:2004 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of ISO standards.

Standards Content (Sample)


INTERNATIONAL ISO
STANDARD 7240-15
First edition
2004-03-01
Fire detection and alarm systems —
Part 15:
Multisensor fire detectors
Systèmes de détection et d'alarme d'incendie —
Partie 15: Détecteurs d'incendie multicapteurs

Reference number
©
ISO 2004
PDF disclaimer
This PDF file may contain embedded typefaces. In accordance with Adobe's licensing policy, this file may be printed or viewed but
shall not be edited unless the typefaces which are embedded are licensed to and installed on the computer performing the editing. In
downloading this file, parties accept therein the responsibility of not infringing Adobe's licensing policy. The ISO Central Secretariat
accepts no liability in this area.
Adobe is a trademark of Adobe Systems Incorporated.
Details of the software products used to create this PDF file can be found in the General Info relative to the file; the PDF-creation
parameters were optimized for printing. Every care has been taken to ensure that the file is suitable for use by ISO member bodies. In
the unlikely event that a problem relating to it is found, please inform the Central Secretariat at the address given below.

©  ISO 2004
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by any means,
electronic or mechanical, including photocopying and microfilm, without permission in writing from either ISO at the address below or
ISO's member body in the country of the requester.
ISO copyright office
Case postale 56 • CH-1211 Geneva 20
Tel. + 41 22 749 01 11
Fax + 41 22 749 09 47
E-mail copyright@iso.org
Web www.iso.org
Published in Switzerland
ii © ISO 2004 – All rights reserved

Contents Page
Foreword. v
Introduction . vi
1 Scope. 1
2 References. 1
3 Terms, definitions and abbreviations . 2
3.1 Terms and definitions. 2
3.2 Abbreviations. 3
4 Functions. 3
4.1 General. 3
4.2 Optional functions. 3
5 General requirements. 4
5.1 Design considerations. 4
5.2 Applicability. 4
5.3 Individual alarm indication. 4
5.4 Indication of other conditions. 4
5.5 Calibration. 4
5.6 Sensitivity adjustment. 4
5.7 Sensitivity attenuation and signal disablement. 5
5.8 Monitoring of detachable detectors . 5
5.9 Drift compensation. 5
5.10 Marking. 5
5.11 Technical documentation. 6
5.12 Manufacturer's declaration. 6
5.13 Electrical requirements. 6
5.14 Protection against ingress of foreign bodies. 6
5.15 Requirements for software-controlled multisensor fire detectors . 6
5.16 Storage of programs and data. 8
5.17 Monitoring of memory contents — Optional function . 8
6 Tests. 8
6.1 General. 8
6.2 Repeatability. 13
6.3 Directional dependence. 13
6.4 Reproducibility. 14
6.5 Variation in supply parameters (voltage) . 14
6.6 Air movement. 15
6.7 Dazzling. 15
6.8 Dry heat (operational). 16
6.9 Cold (operational). 16
6.10 Damp heat, steady state (operational) . 17
6.11 Damp heat, steady state (endurance) . 18
6.12 Sulfur dioxide (SO ) corrosion (endurance) . 19
6.13 Shock (operational). 20
6.14 Impact (operational). 21
6.15 Vibration, sinusoidal (operational). 22
6.16 Vibration, sinusoidal (endurance) . 23
6.17 Electromagnetic compatibility (EMC) . 24
6.18 Fire sensitivity. 24
6.19 Special requirements on detector sensitivity — Optional function. 26
7 Test report.26
Annex A (normative) Smoke tunnel .27
Annex B (informative) Construction of the measuring ionization chamber .32
Annex C (normative) Heat tunnel for temperature-response value measurements .36
Annex D (informative) Construction of the heat tunnel .37
Annex E (normative) Apparatus for the dazzling test.39
Annex F (normative) Apparatus for the impact test.40
Annex G (normative) Fire test room .42
Annex H (normative) Open cellulosic (wood) fire (TF1).44
Annex I (normative) Smouldering (pyrolysis) wood fire (TF2).46
Annex J (normative) Glowing smouldering cotton fire (TF3).48
Annex K (normative) Flaming plastics (polyurethane) fire (TF4).50
Annex L (normative) Flaming liquid (n-heptane) fire (TF5) .52
Annex M (normative) Liquid (methylated spirits) fire (TF6).54
Annex N (normative) Low-temperature black-smoke liquid (decalin) fire (TF8) .56
Annex O (informative) Compensation for detector drift .58

iv © ISO 2004 – All rights reserved

Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards bodies
(ISO member bodies). The work of preparing International Standards is normally carried out through ISO
technical committees. Each member body interested in a subject for which a technical committee has been
established has the right to be represented on that committee. International organizations, governmental and
non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely with the
International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization.
International Standards are drafted in accordance with the rules given in the ISO/IEC Directives, Part 2.
The main task of technical committees is to prepare International Standards. Draft International Standards
adopted by the technical committees are circulated to the member bodies for voting. Publication as an
International Standard requires approval by at least 75 % of the member bodies casting a vote.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. ISO shall not be held responsible for identifying any or all such patent rights.
ISO 7240-15 was prepared by Technical Committee ISO/TC 21, Equipment for fire protection and fire fighting,
Subcommittee SC 3, Fire detection and alarm systems.
ISO 7240 consists of the following parts, under the general title Fire detection and alarm systems:
 Part 1: General and definitions
 Part 2: Control and indicating equipment
 Part 4: Power supply equipment
 Part 5: Point-type heat detectors
 Part 6: Carbon monoxide fire detectors
 Part 7: Point-type smoke detectors using scattered light, transmitted light or ionisation
 Part 11: Manual call points
 Part 14: Guidelines for drafting codes of practice for design, installation and use of fire detection and fire
alarm systems in and around buildings
Compatibility assessment of system components will be the subject of the future Part 13.
Introduction
This part of ISO 7240 for multisensor fire detectors describes requirements for different types of multisensor
fire detectors.
This part of ISO 7240 is drafted on the basis of functions which are required to be provided on all multisensor
fire detectors covered by this standard, and optional functions with requirements which may be provided. It is
intended that the options will be used for specific applications, as recommended in application guidelines.
Each optional function is included as a separate entity, with its own set of associated requirements, in order to
permit multisensor fire detectors covered by this standard with different combinations of functions to conform
to this standard.
Other functions associated with fire detection and fire alarm may also be provided, even if not specified in this
part of ISO 7240, if they do not jeopardize any function required by this document.

vi © ISO 2004 – All rights reserved

INTERNATIONAL STANDARD ISO 7240-15:2004(E)

Fire detection and alarm systems —
Part 15:
Multisensor fire detectors
1 Scope
This part of ISO 7240 specifies requirements, test methods and performance criteria for point-type resettable
multisensor fire detectors for use in fire detection systems installed in buildings, incorporating in one
mechanical enclosure at least one smoke sensor and at least one other sensor which responds to heat, and in
which the signal(s) of the smoke sensor(s) is (are) combined with the signal(s) of the heat sensor(s).
The performance of single components within a multisensor fire detector covered by this standard may not be
sufficient for conformity to other standards for the single sensor.
Certain types of detectors may contain radioactive materials. The national requirements for radiation
protection differ from country to country and they are not therefore specified in this standard. However, such
detectors are expected to conform to the national requirements and be in line with the recommendations of
1)
the Nuclear Energy Agency (NEA) of the Organisation for Economic Co-operation and Development (OECD) .
2 References
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
ISO 209-1, Wrought aluminium and aluminium alloys — Chemical composition and forms of products —
Part 1: Chemical composition
ISO 7240-1, Fire detection and alarm systems — Part 1: General and definitions
ISO 7240-5, Fire detection and alarm systems — Part 5: Point-type heat detectors
ISO 7240-7, Fire detection and alarm systems — Part 7: Point-type smoke detectors using scattered light,
transmitted light or ionization
IEC 60068-1, Environmental testing — Part 1: General and guidance
IEC 60068-2-1, Environmental testing — Part 2: Tests. Tests A: Cold
IEC 60068-2-6, Environmental testing — Part 2: Tests. Test Fc: Vibration (sinusoidal)
IEC 60068-2-27, Environmental testing — Part 2: Tests. Test Ea and guidance: Shock

1) OECD, Recommendations for ionization smoke detectors in implementation of radiation protection standards. Nuclear
Energy Agency, Organisation for economic Co-operation and Development, Paris, France
IEC 60068-2-42, Environmental testing — Part 2-42: Tests. Test Kc: Sulphur dioxide test for contacts and
connections
IEC 60068-2-78, Environmental testing — Part 2-78: Tests — Test Cab: Damp heat, steady state
EN 50130-4, Alarm systems — Part 4: Electromagnetic compatibility — Product family standard: Immunity
requirements for components of fire, intruder and social alarm systems
3 Terms, definitions and abbreviations
3.1 Terms and definitions
For the purposes of this document, the terms and definitions given in ISO 7240-1, ISO 7240-5, ISO 7240-7
and the following apply.
3.1.1
detector response
defined change of the status of a fire detector after actuation of an alarm signal
3.1.2
multisensor fire detector
detector incorporating sensors within one mechanical housing which responds to more than one physical
phenomenon of fire, e.g. smoke and heat, smoke and gas or heat and gas
NOTE The mechanism for actuating alarm signals or for operating automatic fire protection equipment may be
located with the detector or in another part of the system, for example at the control and indicating equipment.
3.1.3
non-volatile memory
memory elements which do not require the presence of an energy source for the retention of their contents
3.1.4
sensor response
defined change of the output signal of a sensing element
NOTE The output signal may be a response to combustion or may result from environmental influences such as
temperature, wind, air pressure, electromagnetic irradiation, etc.
3.1.5
site-specific detector data
alterable data required for the detector to operate in a defined detector configuration
3.1.6
smoke-response value
A
sr
aerosol density in the proximity of a test specimen at the moment that it generates a reference signal in a
smoke tunnel
3.1.7
temperature-response value
temperature in the proximity of a test specimen at the moment that it generates a reference signal
3.1.8
volatile memory
memory elements which require the presence of an energy source for the retention of their contents
2 © ISO 2004 – All rights reserved

3.2 Abbreviations
3.2.1
c.i.e.
control and indicating equipment
3.2.2
MSFD
multisensor fire detector
4 Functions
4.1 General
The MSFD shall be capable of detecting the mandatory test fires as specified in 6.18.3.1.
The MSFD shall be capable of processing signals from all incorporated sensing elements intended to respond
to a fire parameter. At least a common signal shall be produced (either in the MSFD itself or in the c.i.e.)
which can be interpreted as a fire alarm signal.
Means shall be provided for the transmission of the fire signal to the c.i.e.
Where the mechanism for actuating alarm signals is located in the c.i.e., means shall be provided for the
transmission of all signals which are necessary for the actuation process.
4.2 Optional functions
4.2.1 Requirements for optional functions
Each optional function is included as a separate entity, with its own set of associated requirements, in order to
permit multisensor fire detectors covered by this part of ISO 7240 with different combinations of functions to
conform to this document.
If an option is taken, all the corresponding requirements shall be met.
The fault of an option shall not jeopardize any function required by this part of ISO 7240.
4.2.2 Types of optional functions
The MSFD may include one or more of the following optional functions:
a) be capable of detecting one or more of the optional fires specified in 6.18.3.1;
b) be provided with means for monitoring the integrity of one or more sensing elements;
c) be provided with means (remote or internal) for changing its response behaviour;
NOTE A change in the response behaviour could be caused by changing a detection algorithm of the MSFD;
d) be capable of visually indicating conditions other than a fire alarm (e.g. fault or stand-by);
e) be provided with a means of calibration;
f) be designed in such a way that the detector head can be detached from its base;
g) provide for connections to ancillary devices, e.g. remote indicators, control relays, etc;
h) provide for special sensitivity settings in order to limit its sensitivity (see 6.19).
5 General requirements
5.1 Design considerations
MSFDs should be designed for installation under the same conditions as other fire detectors specified in the
other parts of ISO 7240. MSFDs shall be designed so that they are reliable and sufficiently durable for their
intended period of use. In particular, MSFDs shall withstand the environmental conditions which may occur in
buildings.
MSFDs shall be so designed that the signal(s) from the smoke sensor(s), combined with the signal(s) from the
heat sensor(s), produce a fire signal.
NOTE In some cases, a fire alarm signal can result from only one element, but the overall fire performance is
dependent on signals from more than one sensor being combined in some form of signal processing.
5.2 Applicability
In order to conform with this standard, the detector shall meet the requirements of Clauses 4 and 5, shall be
tested as described in Clause 6 and shall meet the requirements of the tests.
5.3 Individual alarm indication
Each detector shall be provided with an integral red visual indicator, by which the individual detector which
released an alarm can be identified, until the alarm condition is reset. Where other conditions of the detector
may be visually indicated, they shall be clearly distinguishable from the alarm condition, except when the
detector is switched into a service mode.
For detachable detectors, the indicator may be integral with the base or the detector head.
The visual indicator shall be visible from a distance of 6 m at an angle of up to 5° from the axis of the detector
in any direction, in ambient light intensity up to 500 lx.
5.4 Indication of other conditions
Where other conditions of the status of the detector are indicated visually, they shall be clearly distinguishable
from the alarm indication.
5.5 Calibration
Where means of calibration are provided, they shall not be readily adjustable after manufacture.
5.6 Sensitivity adjustment
Where means for field adjustment of the sensitivity of the detector are provided, then
a) unless the requirements of 5.7 are met, the range of adjustment shall be limited such that the detector
meets the requirements of this standard at the highest and lowest sensitivities possible;
b) the means of adjustment shall not be readily accessible when the detector is installed and ready for
operation.
For the purpose of this clause, adjustment of sensitivity includes any adjustment which leads to a change in
the response to fire.
4 © ISO 2004 – All rights reserved

5.7 Sensitivity attenuation and signal disablement
Where means are provided (remotely or internally) to switch off signals from a sensing element or to change
the sensitivity of the detector so that it no longer meets the requirements of this part of ISO 7240, this change
in status shall be made available to the c.i.e.
5.8 Monitoring of detachable detectors
For detachable detectors, a means (e.g. the c.i.e.) shall be provided for a remote monitoring system to detect
the removal of the head from the base, in order to give a fault signal.
5.9 Drift compensation
The provision of “drift compensation” (e.g. to compensate for sensor drift due to the build-up of dirt in the
detector) shall not lead to a significant reduction in the sensitivity of the detector to slowly developing fires.
Since it is not practical to make tests with very slow increases in smoke density, an assessment of the
response of the detector to slow increases in smoke density shall be made by analysis of the circuit/software
and/or physical tests and simulations.
The detector shall be deemed to meet the requirements of this subclause if this assessment shows the
following:
a) for any rate of increase in smoke density, R, which is greater than 25 % of the initial uncompensated
smoke response value of the detector, A , per hour, the time for the detector to give an alarm, does not
sr,u
exceed 1,6 × (A /R) by more than 100 s;
sr,u
b) the range of total compensation C is limited such that C < 0,6 A throughout this range, and that the
t t sr,u
fully compensated smoke response value, A , of the detector does not exceed its initial value by a
sr,c
factor greater than 1,6 (see Annex O).
5.10 Marking
Each detector shall be clearly marked with the following information:
a) a reference to this part of ISO 7240 (e.g. ISO 7240-15:2003);
b) the name or trademark of the manufacturer or supplier;
c) the model designation (type or number);
d) the terminal designations;
e) some mark or code by which the manufacturer can identify, at least, the date or batch of manufacture
(e.g. a serial number or batch code).
For detachable detectors, the marking of the detector head shall include items a), b), c) and e) and the base
shall be marked with at least items c) and d).
Where any marking on the device uses symbols or abbreviations not in common use, these should be
explained in the data supplied with the device.
The marking shall be visible during installation and shall be accessible during maintenance.
The markings shall not be placed on screws or other easily removable parts.
For detectors containing radioactive materials, attention is drawn to the marking provisions of the relevant
national requirements and OECD recommendations.
5.11 Technical documentation
Detectors shall be supplied with sufficient technical, installation and maintenance documentation to ensure
their correct handling, installation and operation. If all of these data are not supplied with each detector,
reference to the appropriate data sheet shall be given on, or with, each detector.
For assessment of the detector performance, the documentation shall include a description of the different
detector functions and of the options taken.
5.12 Manufacturer's declaration
The manufacturer shall declare the following:
 attestation of conformity with this part of ISO 7240;
 attestation that the detector is so designed that under the tested environmental conditions, each material
and each electronic component operates within the limits of its specifications.
5.13 Electrical requirements
5.13.1 Connection of ancillary devices
Where the detector provides for connections to ancillary devices (e.g. remote indicators, control relays),
open- or short-circuit failures of these connections shall not prevent the correct operation of the detector.
5.13.2 Fault signal
Where means are provided to monitor the sensing elements and a fault is detected, either a common signal or
separate signals for each sensing element shall be produced and made available to the c.i.e.
5.14 Protection against ingress of foreign bodies
The detector shall be so designed that a sphere of diameter larger than (1,3 ± 0,05) mm cannot pass into the
smoke measuring chamber.
NOTE This requirement is intended to restrict the access of insects into the smoke measuring chamber of the
detector. It is known that this requirement is not sufficient to prevent the access of all insects, however it is considered that
extreme restrictions on the size of access holes may introduce the danger of clogging by dust, etc. It might therefore be
necessary to take other precautions against false alarms due to the entry of small insects.
5.15 Requirements for software-controlled multisensor fire detectors
5.15.1 General requirements
In the case of multisensor detectors which contain elements that are controlled by software in order to fulfil the
requirements of this part of ISO 7240, the detectors shall conform to the requirements of 5.15.2, and shall
conform to the requirements of 5.15.3 where relevant to the technology used.
6 © ISO 2004 – All rights reserved

5.15.2 Software documentation
5.15.2.1 General documentation
The manufacturer shall prepare documentation which gives an overview of the software design, which shall be
submitted to the testing authority together with the multisensor fire detectors. This documentation shall
comprise at least a functional description of the main program flow, including the following:
 a brief description of the major modules which are included in the software and the function(s) each
performs;
 the ways in which the modules interact;
 a sample of the documentation for one of the modules described above;
 a date or version reference.
The description shall use graphic representations of the system design and the data flows, or an equivalent
clear method of software documentation.
5.15.2.2 Detailed documentation
The manufacturer shall prepare detailed design documentation and shall make it available for inspection in a
manner which respects the manufacturer's rights of confidentiality.
NOTE This does not necessarily entail submitting such documentation to the testing authority.
This documentation shall comprise at least the following:
a) description of each module of the program, containing
 the name of the module,
 the date or version reference,
 a description of the tasks performed,
 a description of the interfaces, including the type of data transfer, the valid data range and the
checking for valid data;
b) full specification of the implementation phase, e.g.
 source code prior to compiling or assembling,
 CASE tool listings,
 listing of graphic development tools for fuzzy logic.
5.15.3 Program monitoring — Optional function
Means may be provided for monitoring the execution of the program. If the monitoring function detects that the
program has halted or latched, a signal shall be made available to the c.i.e. within a time limit specified by the
manufacturer.
5.16 Storage of programs and data
The program shall be held in non-volatile memory. Each device containing program memory shall be
identifiable such that its contents can be uniquely cross-referenced to the software documentation.
For site-specific detector data stored in volatile memory, the data shall be automatically renewed or protected
against power loss.
5.17 Monitoring of memory contents — Optional function
Means may be provided for detecting the loss of site-specific data. If such a loss occurs, a signal shall be
made available to the c.i.e. within a time limit specified by the manufacturer.
6 Tests
6.1 General
6.1.1 Test classification
6.1.1.1 General
The purpose of the environmental tests is to demonstrate that a detector can operate correctly in its service
environment and that it will continue to do so for a reasonable time. The tests are intended to demonstrate
failures due to realistic service environments, however, some significant failure mechanisms are brought
about by changes which occur slowly under these realistic service conditions. In order to make tests within a
practical and economic time-scale, it is sometimes necessary to accelerate these changes by intensifying the
conditions (e.g. by increasing the level of an environmental parameter or by increasing the frequency of its
application). The tests are divided into two classes: operational and endurance.
6.1.1.2 Operational tests
The test specimen is subjected to test conditions which correspond to the service environment. The object of
these tests is to demonstrate the ability of the equipment to withstand and operate correctly in the normal
service environment and/or to demonstrate the immunity of the equipment to certain aspects of that
environment.
The specimen is, therefore, operational, its condition is monitored and it may be functionally tested during the
tests.
6.1.1.3 Endurance tests
The test specimen may be subjected to conditions more severe than the normal service environment in order
to accelerate the effects of the normal service environment. The object of these tests is to demonstrate the
ability of the equipment to withstand the long-term effects of the service environment. Since the tests are
intended to study the residual rather than the immediate effects, the specimens are normally not supplied with
power or monitored during the conditioning period. However, if by reason of the design of the specimen, it is
necessary for a power supply to be connected, any signal generated during the test shall be ignored.
6.1.2 Assessment of the performance of the sensors
6.1.2.1 General
In order to assess the influence of the environmental tests quantitatively, a suitable detector parameter shall
be measured before and after the tests. For each test, the observable changes of the parameter which define
clear pass/fail criteria are specified.
8 © ISO 2004 – All rights reserved

The same parameter shall also be used to assess the repeatability (6.2) and the reproducibility (6.4) of the
specimen.
Since an MSFD consists of more than one sensor responding to more than one phenomenon associated with
combustion, the performance of all incorporated sensors shall be assessed.
6.1.2.2 Performance of the smoke sensor(s)
For the assessment of the performance of a smoke sensor, a smoke tunnel as specified in A.1, the application
of a test aerosol as specified in A.3, and aerosol-measuring equipment as specified in A.4 shall be used.
Since the MSFD has to respond to smoke even though the other sensors may not produce a signal, the alarm
threshold value for the aerosol can be measured and shall be taken as the assessment parameter.
6.1.2.3 Performance of the heat sensor(s)
For the assessment of the performance of the heat sensor, a heat tunnel as specified in Annex C shall be
used.
Since the MSFD need not respond to temperature with an alarm signal, it is the responsibility of the
manufacturer to specify a method by which a signal can be derived from the MSFD which can be used as a
parameter for the assessment of the performance of the heat sensor.
6.1.2.4 Orientation
The orientation for which the maximum smoke response value or the maximum temperature response value is
measured is referred to as the least sensitive orientation for smoke and temperature, respectively. The
orientation for which the minimum smoke response value or the minimum temperature response value is
measured is referred to as the most sensitive orientation for smoke and temperature, respectively.
6.1.3 Atmospheric conditions for tests
Unless otherwise stated in a test procedure, carry out the testing after the test specimen has been allowed to
stabilize in the standard atmospheric conditions for testing as specified in IEC 60068-1 as follows:
 temperature: (15 to 35) °C;
 relative humidity: (25 to 75) %;
 air pressure: (86 to 106) kPa.
If variations in these parameters have a significant effect on a measurement, then such variations should be
kept to a minimum during a series of measurements carried out as part of one test on one specimen.
6.1.4 Operating conditions for tests
If a test method requires a specimen to be operational, connect the specimen to suitable supply and indicating
equipment in accordance with the manufacturer's instructions. Unless otherwise specified in the test method,
set the supply parameters applied to the specimen within the manufacturer's specified range(s) and keep
them substantially constant throughout the tests. The value chosen for each parameter shall normally be the
nominal value, or the mean of the specified range.
The details of the supply and indicating equipment used are noted in the test report (Clause 7).
6.1.5 Mounting arrangements
Mount the specimen by its normal means of attachment in accordance with the manufacturer's instructions. If
these instructions describe more than one method of mounting, choose the method considered to be most
unfavourable for each test.
6.1.6 Tolerances
If a specific tolerance or deviation limit is not specified in a requirement or test procedure, use a tolerance of
± 5 %.
6.1.7 Measurement of the smoke response value
Mount the specimen for which the smoke response value is to be measured in a smoke tunnel, as specified in
A.1, in its normal operating position, by its normal means of attachment. The orientation of the specimen,
relative to the direction of air flow, shall be the least sensitive orientation as determined in the directional
dependence test (6.3), unless otherwise specified in the test procedure.
Before commencing each measurement, purge the smoke tunnel with clean air to ensure that the tunnel and
the specimen are free from the test aerosol.
The air velocity in the proximity of the specimen shall be (0,2 ± 0,04) m/s unless otherwise specified in the test
procedure.
Unless otherwise specified in the test procedure, the air temperature in the tunnel shall be (23 ± 5) °C and
shall not vary by more than 5 K and not faster than 0,2 K/min for all the measurements on a particular detector
type.
Connect the specimen to its supply and indicating equipment as described in 6.1.4, and allow it to stabilize for
at least 15 min.
Introduce the test aerosol into the tunnel as specified in A.3 at such a rate that the increase of aerosol density
is as follows:
∆m
 for detectors using scattered or transmitted light, in decibels per metre per minute: 0,015 uu 0,1 ;
∆t
∆y
 for detectors using ionization, per minute: 0,05 uu 0,3 .
∆t
NOTE These ranges are intended to allow the selection of a convenient rate, depending upon the sensitivity of the
detector, to get a response in a reasonable time.
The initially selected rate of increase in aerosol density shall be similar for all measurements on a particular
detector type.
Make all aerosol density measurements in the proximity of the specimen.
The smoke response value shall be recorded as m, in decibels per metre, or as y, a dimensionless parameter
(see A.4).
6.1.8 Measurement of the temperature response value
Install the specimen for which the temperature response value is to be measured in a heat tunnel, as specified
in Annex C, in its normal operating position, by its normal means of attachment. The orientation of the
specimen, relative to the direction of air flow, shall be the least sensitive one as determined in the directional
dependence test (6.3), unless otherwise specified in the test procedure.
10 © ISO 2004 – All rights reserved

Connect the specimen to its supply and indicating equipment as specified in 6.1.4, and allow it to stabilize for
at least 15 min.
Before the test, stabilize the temperature of the air stream and the specimen at (25 ± 2) °C. The air flow shall
be maintained at a constant mass flow equivalent to a velocity of (0,8 ± 0,1) m/s at 25 °C.
Raise the air temperature until the heat sensor produces a signal (this might be a fire signal), as specified by
the manufacturer. The rate of rise of the air temperature and the associated tolerances shall correspond to
one of the values, except for 0,2 K/min, 1 K/min and 30 K/min, as specified in ISO 7240-5. Record the
temperature at which this signal is produced as reference data.
The choice of the rate within the range of 3 K/min to 20 K/min shall be specified by the manufacturer.
For this purpose, the manufacturer may supply an MSFD with special outputs. However, it is essential that the
output signal be routed through the amplification path.
6.1.9 Provision for tests
The data specified in 5.10 and 5.11 plus the following numbers of detectors shall be provided for testing in
accordance with this part of ISO 7240:
 for detachable detectors: 20 detector heads and bases;
 for non-detachable detectors: 20 specimens.
The specimens submitted shall be deemed representative of the manufacturer's normal production with
regard to their construction and calibration.
This implies that the mean smoke response value of the 19 specimens as measured in the reproducibility test
(6.4) should also represent the production mean, and that the deviation limits specified for the reproducibility
test should also be applicable to the manufacturer's production.
6.1.10 Test schedule
Test the specimens as specified in Table 1. After the reproducibility test (6.4), number the four specimens with
the least sensitive smoke response (i.e. those with the highest smoke response value) 17 to 20. Number the
others 1 to 16 arbitrarily.
When it is required to determine both the smoke and the temperature response value after an environmental
test, determine the smoke response value first.
Table 1 — Test schedule
Test Subclause Specimen No(s). to be tested
a
Repeatability 6.2 one chosen arbitrarily
a
Directional dependence 6.3 one chosen arbitrarily

a
Reproducibility 6.4 all specimens
Variation of supply parameters 6.5 1
Air movement 6.6 2
b
Dazzling 6.7 3
Dry heat (operational) 6.8 4
Cold (operational) 6.9 5
Damp heat, steady state (operational) 6.10 6

a
Damp heat, steady state (endurance) 6.11 7

a
Sulfur dioxide (SO ) corrosion (endurance) 6.12 8
a
Shock (operational) 6.13 9
a
Impact (operational) 6.14 10
Vibration, sinusoidal (operational) 6.15 11

a
Vibration, sinusoidal (endurance) 6.16 11

c
Electrostatic discharge (operational) 6.17 12
Radiated electromagnetic fields

c
6.17 13
(operational)
Conducted disturbances induced by
c
6.17 14
electromagnetic fields (operational)

c
Fast transient bursts (operational) 6.17 15
Slow high energy voltage surge

c
6.17 16
(operational)
Fire sensitivity
6.18 17, 18, 19, 20
Special requirements on detector sensitivity
6.19 17, 18, 19, 20
(optional)
a
The smoke and temperature response shall be measured.

b
This test applies only to detectors using a scattered or transmitted light principle of operation.

c
In the interests of test economy, it is permitted to use the same specimen for more than one EMC test. In that case, intermediate
functional test(s) on the specimen(s) used for more than one test can be deleted, and the full functional test conducted at the end of the
sequence of tests. However it should be noted that in the event of a failure, it may not be possible to identify which test exposure

caused the failure.
6.1.11 Test report
The test results shall be reported in accordance with Clause 7.
12 © ISO 2004 – All rights reserved

6.2 Repeatability
6.2.1 Object of test
To show that the detector has stable behaviour with respect to its sensitivity even after a number of alarm
conditions.
6.2.2 Test procedure
Measure the smoke response value and the temperature response value of the specimen six times a
...

Questions, Comments and Discussion