Cleanrooms and associated controlled environments - Part 1: Classification of air cleanliness by particle concentration

ISO 14644-1:2015 specifies the classification of air cleanliness in terms of concentration of airborne particles in cleanrooms and clean zones; and separative devices as defined in ISO 14644‑7. Only particle populations having cumulative distributions based on threshold (lower limit) particle sizes ranging from 0,1 µm to 5 µm are considered for classification purposes. The use of light scattering (discrete) airborne particle counters (LSAPC) is the basis for determination of the concentration of airborne particles, equal to and greater than the specified sizes, at designated sampling locations. ISO 14644-1:2015 does not provide for classification of particle populations that are outside the specified lower threshold particle-size range, 0,1 µm to 5 µm. Concentrations of ultrafine particles (particles smaller than 0,1 µm) will be addressed in a separate standard to specify air cleanliness by nano-scale particles. An M descriptor (see Annex C) may be used to quantify populations of macroparticles (particles larger than 5 µm). ISO 14644-1:2015 cannot be used to characterize the physical, chemical, radiological, viable or other nature of airborne particles.

Salles propres et environnements maîtrisés apparentés — Partie 1: Classification de la propreté particulaire de l'air

ISO 14644-1:2015 spécifie la classification de la propreté de l'air des salles propres, des zones propres et des dispositifs séparatifs tels que définis dans l'ISO 14644‑7 en termes de concentration des particules en suspension dans l'air. Seules sont prises en compte les populations de particules présentant une distribution granulométrique cumulée dont le seuil inférieur se situe dans l'étendue de 0,1 µm à 5 µm. La méthode de référence pour déterminer la concentration de particules dans l'air d'une taille supérieure ou égale aux tailles spécifiées aux points de prélèvement désignés est l'utilisation de compteurs utilisant les propriétés de diffusion de la lumière (light scattering airborne particle counters - LSAPC). La présente partie de l'ISO 14644 ne donne pas de classification pour des populations de particules dont le seuil inférieur se situe en dehors de l'étendue granulométrique de référence de 0,1 µm à 5 µm. Les concentrations de particules ultrafines (plus petites que 0,1 µm) seront traitées dans une norme séparée laquelle spécifiera la propreté particulaire de l'air à l'échelle nanométrique. Un descripteur M (voir l'Annexe C) pouvant être utilisé pour quantifier les populations de macroparticules (particules plus grandes que 5 µm). ISO 14644-1:2015 ne peut pas être utilisée pour caractériser la nature physique, chimique, radiologique ou viable des particules en suspension dans l'air.

General Information

Status
Published
Publication Date
08-Dec-2015
Current Stage
9093 - International Standard confirmed
Start Date
13-Aug-2021
Completion Date
13-Dec-2025
Ref Project

Relations

Overview

ISO 14644-1:2015 - "Cleanrooms and associated controlled environments - Part 1: Classification of air cleanliness by particle concentration" defines how to classify cleanrooms, clean zones and separative devices according to the concentration of airborne particles. The standard covers particle-size thresholds from 0.1 µm to 5 µm, uses light scattering (discrete) airborne particle counters (LSAPC) as the basis for measurement, and retains an M descriptor (Annex C) to quantify macroparticles (>5 µm). ISO 14644-1:2015 specifies the classification method, the reference testing approach (Annex A) and requirements for sampling locations and reporting - but it does not characterize particle chemistry, viability or ultrafine (nano-scale) particles (<0.1 µm).

Key technical topics and requirements

  • Particle size range: Classification applies to cumulative particle thresholds between 0.1 µm and 5 µm. Nano-scale particles are outside this part and handled separately.
  • Measurement method: Use of LSAPC instruments for counting particles ≥ specified sizes (see Annex F for instrument guidance).
  • ISO Classes: Defines integer and intermediate decimal cleanliness classes (tables provide maximum particle concentrations for each class and size).
  • Sampling strategy: Statistical approach based on an adapted hypergeometric sampling model; minimum sampling locations referenced in Table A.1. The model provides at least 95% confidence that 90% of the area will meet class limits.
  • Designation and reporting: Rules for class number, particle sizes, occupancy states and required test reporting (see Clause 5 and Annex A).
  • Macroparticles: Annex C describes counting/sizing of particles >5 µm and use of an M descriptor for regulatory adaptation (e.g., sterile product guidance).

Practical applications

ISO 14644-1:2015 is essential for organizations that design, validate, operate or regulate contamination-controlled environments, including:

  • Pharmaceuticals and sterile manufacturing (cleanroom classification and sterile product annex adaptations)
  • Medical devices and healthcare facilities
  • Microelectronics and semiconductor fabrication
  • Aerospace and precision engineering
  • Food processing where particulate control is required It is used to establish an ISO Class target, select monitoring and test protocols, validate HVAC and filtration performance, and produce compliance test reports for audits and regulatory inspections.

Who should use this standard

  • Cleanroom designers and engineers
  • Validation and quality assurance specialists
  • Facilities and operations managers
  • Test laboratories and auditors
  • Regulatory and compliance personnel

Related standards

  • ISO 14644‑2 (monitoring to provide evidence of performance)
  • ISO 14644‑3 (test methods)
  • ISO 14644‑7 (separative devices: hoods, gloveboxes, isolators)
  • Other parts of ISO 14644 (Parts 4, 5, 8–10) and ISO 14698 (biocontamination control)

Keywords: ISO 14644-1:2015, cleanrooms, air cleanliness, particle concentration, LSAPC, ISO class, sampling locations, macroparticles, clean zones.

Standard
ISO 14644-1:2015 - Cleanrooms and associated controlled environments
English language
37 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
ISO 14644-1:2015 - Cleanrooms and associated controlled environments
English language
37 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ISO 14644-1:2015 - Cleanrooms and associated controlled environments
English language
37 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
ISO 14644-1:2015 - Salles propres et environnements maîtrisés apparentés
French language
39 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
ISO 14644-1:2015 - Salles propres et environnements maîtrisés apparentés
French language
39 pages
sale 15% off
Preview
sale 15% off
Preview

Frequently Asked Questions

ISO 14644-1:2015 is a standard published by the International Organization for Standardization (ISO). Its full title is "Cleanrooms and associated controlled environments - Part 1: Classification of air cleanliness by particle concentration". This standard covers: ISO 14644-1:2015 specifies the classification of air cleanliness in terms of concentration of airborne particles in cleanrooms and clean zones; and separative devices as defined in ISO 14644‑7. Only particle populations having cumulative distributions based on threshold (lower limit) particle sizes ranging from 0,1 µm to 5 µm are considered for classification purposes. The use of light scattering (discrete) airborne particle counters (LSAPC) is the basis for determination of the concentration of airborne particles, equal to and greater than the specified sizes, at designated sampling locations. ISO 14644-1:2015 does not provide for classification of particle populations that are outside the specified lower threshold particle-size range, 0,1 µm to 5 µm. Concentrations of ultrafine particles (particles smaller than 0,1 µm) will be addressed in a separate standard to specify air cleanliness by nano-scale particles. An M descriptor (see Annex C) may be used to quantify populations of macroparticles (particles larger than 5 µm). ISO 14644-1:2015 cannot be used to characterize the physical, chemical, radiological, viable or other nature of airborne particles.

ISO 14644-1:2015 specifies the classification of air cleanliness in terms of concentration of airborne particles in cleanrooms and clean zones; and separative devices as defined in ISO 14644‑7. Only particle populations having cumulative distributions based on threshold (lower limit) particle sizes ranging from 0,1 µm to 5 µm are considered for classification purposes. The use of light scattering (discrete) airborne particle counters (LSAPC) is the basis for determination of the concentration of airborne particles, equal to and greater than the specified sizes, at designated sampling locations. ISO 14644-1:2015 does not provide for classification of particle populations that are outside the specified lower threshold particle-size range, 0,1 µm to 5 µm. Concentrations of ultrafine particles (particles smaller than 0,1 µm) will be addressed in a separate standard to specify air cleanliness by nano-scale particles. An M descriptor (see Annex C) may be used to quantify populations of macroparticles (particles larger than 5 µm). ISO 14644-1:2015 cannot be used to characterize the physical, chemical, radiological, viable or other nature of airborne particles.

ISO 14644-1:2015 is classified under the following ICS (International Classification for Standards) categories: 13.040.35 - Cleanrooms and associated controlled environments. The ICS classification helps identify the subject area and facilitates finding related standards.

ISO 14644-1:2015 has the following relationships with other standards: It is inter standard links to ISO 14644-1:1999. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

You can purchase ISO 14644-1:2015 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of ISO standards.

Standards Content (Sample)


DRAFT INTERNATIONAL STANDARD ISO/DIS 14644-1
ISO/TC 209 Secretariat: ANSI
Voting begins on Voting terminates on

2010-12-02 2011-05-02
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION  •  МЕЖДУНАРОДНАЯ ОРГАНИЗАЦИЯ ПО СТАНДАРТИЗАЦИИ  •  ORGANISATION INTERNATIONALE DE NORMALISATION

Cleanrooms and associated controlled environments —
Part 1:
Classification of air cleanliness by particle concentration
Salles propres et environnements maîtrisés apparentés —
Partie 1: Classification de la propreté particulaire de l'air
[Revision of first edition (ISO 14644-1:1999)]
ICS 13.040.35
ISO/CEN PARALLEL PROCESSING
This draft has been developed within the International Organization for Standardization (ISO), and
processed under the ISO-lead mode of collaboration as defined in the Vienna Agreement.
This draft is hereby submitted to the ISO member bodies and to the CEN member bodies for a parallel
five-month enquiry.
Should this draft be accepted, a final draft, established on the basis of comments received, will be
submitted to a parallel two-month approval vote in ISO and formal vote in CEN.

To expedite distribution, this document is circulated as received from the committee
secretariat. ISO Central Secretariat work of editing and text composition will be undertaken at
publication stage.
Pour accélérer la distribution, le présent document est distribué tel qu'il est parvenu du
secrétariat du comité. Le travail de rédaction et de composition de texte sera effectué au
Secrétariat central de l'ISO au stade de publication.

THIS DOCUMENT IS A DRAFT CIRCULATED FOR COMMENT AND APPROVAL. IT IS THEREFORE SUBJECT TO CHANGE AND MAY NOT BE
REFERRED TO AS AN INTERNATIONAL STANDARD UNTIL PUBLISHED AS SUCH.
IN ADDITION TO THEIR EVALUATION AS BEING ACCEPTABLE FOR INDUSTRIAL, TECHNOLOGICAL, COMMERCIAL AND USER PURPOSES,
DRAFT INTERNATIONAL STANDARDS MAY ON OCCASION HAVE TO BE CONSIDERED IN THE LIGHT OF THEIR POTENTIAL TO BECOME
STANDARDS TO WHICH REFERENCE MAY BE MADE IN NATIONAL REGULATIONS.
RECIPIENTS OF THIS DRAFT ARE INVITED TO SUBMIT, WITH THEIR COMMENTS, NOTIFICATION OF ANY RELEVANT PATENT RIGHTS OF WHICH
THEY ARE AWARE AND TO PROVIDE SUPPORTING DOCUMENTATION.
©  International Organization for Standardization, 2010

ISO/DIS 14644-1
PDF disclaimer
This PDF file may contain embedded typefaces. In accordance with Adobe's licensing policy, this file may be printed or viewed but shall
not be edited unless the typefaces which are embedded are licensed to and installed on the computer performing the editing. In
downloading this file, parties accept therein the responsibility of not infringing Adobe's licensing policy. The ISO Central Secretariat
accepts no liability in this area.
Adobe is a trademark of Adobe Systems Incorporated.
Details of the software products used to create this PDF file can be found in the General Info relative to the file; the PDF-creation
parameters were optimized for printing. Every care has been taken to ensure that the file is suitable for use by ISO member bodies. In
the unlikely event that a problem relating to it is found, please inform the Central Secretariat at the address given below.

Copyright notice
This ISO document is a Draft International Standard and is copyright-protected by ISO. Except as permitted
under the applicable laws of the user’s country, neither this ISO draft nor any extract from it may be
reproduced, stored in a retrieval system or transmitted in any form or by any means, electronic,
photocopying, recording or otherwise, without prior written permission being secured.
Requests for permission to reproduce should be addressed to either ISO at the address below or ISO’s
member body in the country of the requester.
ISO copyright office
Case postale 56 • CH-1211 Geneva 20
Tel. + 41 22 749 01 11
Fax + 41 22 749 09 47
E-mail copyright@iso.org
Web www.iso.org
Reproduction may be subject to royalty payments or a licensing agreement.
Violators may be prosecuted.
ii © ISO 2010 – All rights reserved

ISO/DIS 14644-1
Contents Page
1 Scope.1
2 Normative reference.1
3 Definitions .1
4 Classification .4
5 Demonstration of compliance.5
Annex A (normative) Reference method for determination of air cleanliness classification by
particle concentration.8
Annex B (informative) Worked examples of classification calculations.14
Annex C (informative) Considerations for counting and sizing of particles outside the size range
applicable for classification .23
Annex D (informative) Sequential sampling procedure .26
Annex E (informative) Illustration of the ISO cleanliness classes.35
Bibliography.37

ISO/DIS 14644-1
Foreword
This edition is the result of a systematic review and includes changes in response to user and expert feedback
validated by international enquiry. The title has been revised to “Classification of air cleanliness by particle
concentration” to be consistent with other parts of the standard. The nine ISO cleanliness classes are retained
unchanged, but Table 1 defines the particle concentration at various particle sizes for the nine integer classes.
The use of Table 1 ensures better definition of the appropriate particle-size ranges for the different classes. A
formula is retained to allow definition of intermediate decimal classes. The standard retains the concept of
ultrafine and macroparticle descriptors for particle sizes outside the range appropriate for measurement using
airborne particle counters.
The most significant change is the adoption of a more consistent statistical approach to the selection of
number of sample locations and the evaluation of the data collected. The number of sample locations
compared with the 1999 version of the standard have been changed. The approach allows each location to be
treated independently with a 95 % level of confidence that at least 90 % of the cleanroom or clean zone will
comply with the maximum particle concentration limit for the target class of air cleanliness. A reference table is
provided to define the number of sample locations required. Because a degree of randomness is required, the
cleanroom or clean zone is then divided into equal sectors and the sample location placed randomly within
each sector.
Finally, the annexes have been reordered to improve the logic of the standard.
ISO (the International Organization for Standardization) is a worldwide federation of national standards bodies
(ISO member bodies). The work of preparing International Standards is normally carried out through ISO
technical committees. Each member body interested in a subject for which a technical committee has been
established has the right to be represented on that committee. International organizations, governmental and
non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely with the
International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization.
International Standards are drafted in accordance with the rules given in the ISO/IEC Directives, Part 2.
The main task of technical committees is to prepare International Standards. Draft International Standards
adopted by the technical committees are circulated to the member bodies for voting. Publication as an
International Standard requires approval by at least 75 % of the member bodies casting a vote.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. ISO shall not be held responsible for identifying any or all such patent rights.
ISO 14644-1 was prepared by Technical Committee ISO/TC 209, Cleanrooms and associated controlled
environments.
This second edition cancels and replaces in whole the first edition (ISO 14644-1:1999), which has been
technically revised.
ISO 14644 consists of the following parts, under the general title Cleanrooms and associated controlled
environments:
 Part 1: Classification of air cleanliness by particle concentration
 Part 2: Specifications for monitoring and periodic testing to prove continued compliance with ISO
14644-1:XXXX
 Part 3: Test methods
iv © ISO 2010 – All rights reserved

ISO/DIS 14644-1
 Part 4: Design, construction and start-up
 Part 5: Operations
 Part 6: Vocabulary
 Part 7: Separative devices (clean air hoods, gloveboxes, isolators, and mini-environments)
 Part 8: Classification of airborne molecular contamination
 Part 9: Classification of surface cleanliness by particle concentration
Attention is also drawn to ISO 14698, Cleanrooms and associated controlled environments —
Biocontamination control:
 Part 1: General principles and methods
 Part 2: Evaluation and interpretation of biocontamination data
ISO/DIS 14644-1
Introduction
Cleanrooms and associated controlled environments provide for the control of contamination of air or surfaces
to levels appropriate for accomplishing contamination-sensitive activities. Contamination control can be
beneficial for protection of product or process integrity in applications such as aerospace, microelectronics,
pharmaceuticals, medical devices and healthcare.
This part of ISO 14644 specifies ISO classes of air cleanliness in terms of particle concentration in air volume.
It also specifies the standard method of testing to determine classification, including selection of sampling
locations, and evaluation of class from the data collected.

vi © ISO 2010 – All rights reserved

DRAFT INTERNATIONAL STANDARD ISO/DIS 14644-1

Cleanrooms and associated controlled environments —
Part 1:
Classification of air cleanliness by particle concentration
1 Scope
This part of ISO 14644 covers the classification of air cleanliness in cleanrooms and associated controlled
environments exclusively in terms of concentration of airborne particles. Only particle populations having
cumulative distributions based on threshold (lower limit) particle sizes ranging from 0,1 µm to 5 µm are
considered for classification purposes.
The use of discrete-particle airborne counting and sizing instruments is the basis for determination of the
concentration of airborne particles, equal to and greater than the specified sizes, at designated sampling
locations.
This part of ISO 14644 does not provide for classification of particle populations that are outside of the
specified particle-size range, 0,1 µm to 5 µm. Concentrations of ultrafine particles (particles smaller than
0,1 µm) and macroparticles (particles larger than 5 µm) may be used to quantify these populations in terms of
U descriptors and M descriptors (see 3.3.1 and 3.3.2), respectively.
This part of ISO 14644 cannot be used to characterise the physical, chemical, radiological or viable nature of
airborne particles.
NOTE The actual distribution of particle concentrations within incremental size ranges is normally not predictable and
is typically variable over time.
2 Normative reference
The following normative document contains provisions, which, through reference in this text, constitute
provisions of this part of ISO 14644. Subsequent amendments to or revisions of this publication do not apply.
However, parties to agreements based on this part of ISO 14644 are encouraged to investigate the possibility
of applying the most recent editions of the normative document indicated below.
ISO 21501-4:2007, Determination of particle size distribution — Single particle light interaction methods —
Part 4: Light scattering airborne particle counter for clean spaces
3 Definitions
For the purposes of this part of ISO 14644, the following definitions apply.
3.1 General
3.1.1
cleanroom
room in which the concentration of airborne particles is controlled, and which is constructed and used in a
manner to minimise the introduction, generation, and retention of particles inside the room, and in which other
relevant parameters, e.g. temperature, humidity, and pressure, are controlled as necessary
ISO/DIS 14644-1
3.1.2
clean zone
dedicated space in which the concentration of airborne particles is controlled, and which is constructed and
used in a manner to minimise the introduction, generation, and retention of particles inside the zone and in
which other relevant parameters, e.g. temperature, humidity and pressure, are controlled as necessary
NOTE This zone may be open or enclosed and may or may not be located within a cleanroom.
3.1.3
classification
level of air cleanliness by particle concentration applicable to a cleanroom or clean zone, expressed in terms
of an ISO Class N, which represents maximum allowable concentrations expressed as particles per cubic
metre, for particles equal to and greater than the considered sizes
NOTE 1 The maximum allowable concentrations are defined in Table 1 in 4.2 or determined by Equation (1) in 4.2 if
specifying an intermediate decimal class.
NOTE 2 Classification in accordance with this International Standard is limited to the range extending from ISO Class 1
through ISO Class 9.
NOTE 3 The considered particle sizes applicable for classification in accordance with this International Standard are
limited to the range from ≥ 0,1 µm to  5 µm.
NOTE 4 Air cleanliness may be described and specified (but not classified) in terms of U descriptors or M descriptors
(see 3.3.1 or 3.3.2) for considered threshold particle sizes that are outside of the range covered by classification.
NOTE 5 intermediate decimal ISO classification numbers may be specified, with 0,1 being the smallest permitted
increment; i.e. the range of intermediate decimal ISO classes extends from ISO Class 1,1 through ISO Class 8,9.
NOTE 6 Classification may be specified or accomplished in any of three occupancy states (see 3.4).
3.2 Airborne particles
3.2.1
particle
minute piece of matter with defined physical boundaries
3.2.2
particle size
diameter of a sphere that produces a response, by a given particle-sizing instrument, that is equivalent to the
response produced by the particle being measured
NOTE For discrete-particle light-scattering instruments, the equivalent optical diameter is used.
3.2.3
particle concentration
number of individual particles per unit volume of air
3.2.4
particle size distribution
cumulative distribution of particle concentration as a function of particle size
3.2.5
ultrafine particle
particle with an equivalent diameter less than 0,1 µm
3.2.6
macroparticle
particle with an equivalent diameter greater than 5 µm
2 © ISO 2010 – All rights reserved

ISO/DIS 14644-1
3.2.7
unidirectional airflow
controlled airflow through the entire cross-section of a clean zone with a steady velocity and approximately
parallel airstreams
NOTE This type of airflow results in a directed transport of particles from the clean zone.
3.3 Descriptors
3.3.1
U descriptor
measured or specified concentration, in particles per cubic metre of air, including the ultrafine particles
NOTE The U descriptor may be regarded as an upper limit for the averages at sampling locations (or as an upper
confidence limit, depending upon the number of sampling locations used to characterise the cleanroom or clean zone). U
descriptors cannot be used to define air cleanliness classes by particle concentration, but they may be quoted
independently or in conjunction with air cleanliness classes by particle concentration.
3.3.2
M descriptor
measured or specified concentration of macroparticles per cubic metre of air, expressed in terms of the
equivalent diameter that is characteristic of the measurement method used
NOTE The M descriptor may be regarded as an upper limit for the averages at sampling locations (or as an upper
confidence limit, depending upon the number of sampling locations used to characterise the cleanroom or clean zone). M
descriptors cannot be used to define air cleanliness classes by particle concentration, but they may be quoted
independently or in conjunction with air cleanliness classes by particle concentration.
3.4 Occupancy states
3.4.1
as-built
condition where the cleanroom or clean zone is complete with all services connected and functioning but with
no production equipment, materials or personnel present
3.4.2
at-rest
condition where the cleanroom or clean zone is complete with equipment installed and operating in a manner
agreed upon by the customer and supplier, but with no personnel present
3.4.3
operational
condition where the cleanroom or clean zone is functioning in the specified manner, with the specified number
of personnel present and working in the manner agreed upon
3.5 Roles
3.5.1
customer
organisation, or the agent thereof, responsible for specifying the requirements of a cleanroom or clean zone
3.5.2
supplier
organisation engaged to satisfy the specified requirements of a cleanroom or clean zone
ISO/DIS 14644-1
4 Classification
4.1 Occupancy state(s)
The air cleaniness class by particle concentration of air in a cleanroom or clean zone shall be defined in one
or more of three occupancy states, viz. “as-built,” “at-rest,” or “operational” (see 3.4).
4.2 Classification number
Air cleanliness class by particle concentration shall be designated by a classification number, N. The
maximum permitted concentration of particles, C , for each considered particle size, D, is determined from
n
Table 1.
Table 1 — Air cleanliness classification table by particle concentration
ISO Maximum allowable concentrations (particles/m ) for particles equal to and
a
classification
greater than the considered sizes shown below
number (N)
0,1 µm 0,2 µm 0,3 µm 0,5 µm 1 µm 5 µm
b
d d d d e
ISO Class 1
b b
d d e
ISO Class 2 100
24 10
b
d e
ISO Class 3 1 000 237 102
b
e
ISO Class 4 10 000 2 370 1 020 352
e
ISO Class 5 100 000 23 700 10 200 3 520 832
ISO Class 6 1 000 000 237 000 102 000 35 200 8 320 293

c c c
ISO Class 7 352 000 83 200 2 930

c c c
ISO Class 8 3 520 000 832 000 29 300

c c c
ISO Class 9 35 200 000 8 320 000 293 000
a
All concentrations in the table are cumulative, e.g. for ISO Class 5, the 10 200 particles shown at 0,3 µm include
all particles equal to and greater than this size.
b
These concentrations will lead to large air sample volumes for classification. Sequential sampling procedure
may be applied; see Annex D.
c
Concentration limits are not applicable in this region of the table due to very high particle concentration.
d
Sampling and statistical limitations for particles in low concentrations make classification inappropriate.
e
Sample collection limitations for both particles in low concentrations and sizes greater than 1 μm make
classification inappropriate, due to potential particle losses in the sampling system.

A representation of the selected classes in graphical form is provided in Figure E.1 (see Annex E).
Equation (1), below, shall be used to determine the maximum particle concentration for intermediate decimal
classes at the considered particle size:
0,1
N 2,08
Cn = 10  ( ) (1)
D
where
C is the maximum permitted concentration (particles per cubic metre) of airborne particles that are
n
equal to and greater than the considered particle size. C is rounded to the nearest whole number, using no
n
more than three significant figures.
4 © ISO 2010 – All rights reserved

ISO/DIS 14644-1
N is the ISO classification number, which shall not exceed a value of 9 or be less than 1. Intermediate
decimal ISO classification numbers may be specified, with 0,1 being the smallest permitted increment of N.
D is the considered particle size, in micrometres.
0,1 is a constant, with a dimension of micrometres.
Table E.1 (see Annex E) provides examples of intermediate decimal classes. The associated notes to Table
E.1 identify restrictions due to sampling and collection limitations.
4.3 Designation
The designation of airborne particle concentration for cleanrooms and clean zones shall include:
a) the classification number, expressed as “ISO Class N”;
b) the occupancy state to which the classification applies;
c) the considered particle size(s), and the related class limit(s), as determined by the classification table
(Table 1) or Equation (1) where each considered lower threshold particle size is in the range from 0,1 µm
through 5 µm.
The considered particle size(s) for which the concentration(s) will be measured shall be agreed upon by the
customer and the supplier.
If measurements are to be made at more than one considered particle size, each larger particle diameter
(e.g. D2) shall be at least 1,5 times the next smaller particle diameter (e.g. D1), i.e. D2 ≥ 1,5  D1.
Example designations:
ISO Class 4; at rest; 0,2 µm 0,5 µm
ISO Class 7,5; in operation; 0.5 µm
5 Demonstration of compliance
5.1 Principle
Compliance with air cleanliness (ISO class) requirements specified by the customer is verified by performing
specified testing procedures and by providing documentation of the results and conditions of testing, as
agreed upon by the customer and the supplier.
5.2 Testing
The reference test method for demonstrating compliance is given in Annex A (normative). Alternative methods
or instrumentation (or both), having at least comparable performance, may be specified. If no alternative is
specified or agreed upon, the reference method shall be used.
Tests performed to demonstrate compliance shall be conducted using calibrated instruments.
5.3 Airborne particle concentration evaluation
Upon completion of testing in accordance with 5.2, the concentration of particles (expressed as number of
particles per cubic metre) in the single sample volume at each sample location shall not exceed the
concentration limit(s) given in Table 1 or derived from Equation (1) for intermediate decimal classes for the
considered size(s). If multiple single sample volumes are taken at a sample location, the concentration shall
ISO/DIS 14644-1
be averaged and the average concentration must not exceed the concentration limits given in Table 1 or
derived from Equation (1) for intermediate decimal classes.
Particle concentrations used for determination of conformance to classification limits shall be measured by the
same method for all considered particle sizes.
5.4 Test report
The results from testing each cleanroom or clean zone shall be recorded and submitted as a comprehensive
report, along with a statement of compliance or non-compliance with the specified designation of air
cleanliness class by particle concentration.
The test report shall include:
a) the name and address of the testing organisation, and the date on which the test was performed;
b) the number and year of publication of this part of ISO 14644, i.e. ISO 14644-1:date of current issue;
c) a clear identification of the physical location of the cleanroom or clean zone tested (including reference to
adjacent areas if necessary), and specific designations for coordinates of all sampling locations;
d) the specified designation criteria for the cleanroom or clean zone, including the ISO classification, the
relevant occupancy state(s), and the considered particle size(s);
e) details of the test method used, with any special conditions relating to the test, or departures from the test
method, and identification of the test instrument and its current calibration certificate;
f) the test results, including particle concentration data for all sampling locations.
NOTE If concentrations of ultrafine particles or macroparticles are quantified, as described in Annex C, the pertinent
information should be included with the test report.
6 © ISO 2010 – All rights reserved

ISO/DIS 14644-1
(Blank page)
ISO/DIS 14644-1
Annex A
(normative)
Reference method for determination of air cleanliness classification
by particle concentration
A.1 Principle
A discrete-particle-counting instrument is used to determine the concentration of airborne particles, equal to
and greater than the specified sizes, at designated sampling locations.
A.2 Apparatus requirements
A.2.1 Particle-counting instrument
The instrument shall have a means of displaying or recording the count and size of discrete particles in air
with a size discrimination capability to detect the total particle concentration in the appropriate particle size
ranges for the class under consideration.
NOTE: Light-scattering discrete airborne particle counters (LSAP) are commonly used for determination of particle
concentration classification.
A.2.2 Instrument calibration
The instrument shall have a valid calibration certificate; the frequency and method of calibration should be
based on current accepted practice.
NOTE: See normative reference to ISO 21501-4.
A.3 Pretest conditions
A.3.1 Preparation for testing
Prior to testing, verify that all aspects of the cleanroom or clean zone that contribute to its integrity are
complete and functioning in accordance with its performance specification.
Such pre-testing may include, for example:
a) airflow tests (e.g. air volume, air velocity, or uniformity of unidirectional airflow);
b) air pressure difference test;
c) containment leak test;
d) installed filter system leakage test.
A.3.2 Pretest equipment setup
Perform equipment setup in accordance with the manufacturer’s instructions.
8 © ISO 2010 – All rights reserved

ISO/DIS 14644-1
A.4 Sampling
A.4.1 Establishment of sampling locations
A.4.1.1
Derive the minimum number of sampling locations, N , from Table A.1. Table A.1 provides the number of
L
sample locations related to the area of each cleanroom or clean zone to be classified and provides at least
95 % confidence that at least 90 % of all locations do not exceed the class limits.
Table A.1 — Sample locations related to cleanroom area
Area of cleanroom (m ) less than Minimum number of sample locations
or equal to to be tested (N )
L
1 1
2 1
4 2
6 3
8 4
10 5
24 6
28 7
32 8
36 9
52 10
56 11
64 12
68 13
72 14
76 15
104 16
108 17
116 18
148 19
156 20
192 21
232 22
276 23
352 24
436 25
500 26
NOTE 1 The number of sample locations in Table A.1 are based on area units of 1, 2,
and 4 m , to achieve 95 % confidence that at least 90 % of the total area does not exceed
the class limit.
ISO/DIS 14644-1
Table A.1 (continued)
NOTE 2 If the zone area falls between two values in the table, the greater of the two
should be selected.
NOTE 3 In the case of unidirectional airflow, the area may be considered as the cross
section of the moving air perpendicular to the direction of the airflow. In all other cases the
area may be considered as the horizontal plan area of the cleanroom or clean zone.
NOTE 4 For practical purposes, it is assumed that each sample location is
representative of its associated area unit.
NOTE 5 Cleanrooms in excess of 500 m in area shall be considered as a series of
smaller zones.
A.4.1.2
In order to position the sample locations, identify the minimum number of sample locations from Table A.1,
use this number to divide the clean zone into equal sectors, and within each sector randomly select a sample
location positioned at the height of the work activity.
If the customer specifies additional sampling locations, their number and positions shall also be specified.
Such additional locations may be those considered critical, based on risk analysis.
A.4.2 Establishment of single sample volume and sampling time per location
A.4.2.1
At each sampling location, sample a sufficient volume of air that a minimum of 20 particles would be detected
if the particle concentration for the largest selected particle size were at the class limit for the designated ISO
class.
The single sample volume, V , per sampling location is determined by using Equation (A.1):
s
V = ( )  1 000 (A.1)
s
C
n,m
where
V is the minimum single sample volume per location, expressed in litres (except see D.4.2.2).
s
C is the class limit (number of particles per cubic metre) for the largest considered particle size
n,m
specified for the relevant class.
20 is the defined number of particles that could be counted if the particle concentration were at the class
limit.
Each single sample volume at each location shall be the same — unless the optional sequential sampling
procedure (see Annex D) is used — and shall be expressed in litres. When V is very large, the time required
s
for sampling can be substantial. By using the optional sequential sampling procedure, both the required
sample volume and the time required to obtain samples may be reduced.
A.4.2.2
The volume sampled at each location shall be at least 2 litres, with a minimum sampling time of 1 minute for
each sample at each location.
10 © ISO 2010 – All rights reserved

ISO/DIS 14644-1
A.4.3 Sampling procedure
A.4.3.1
Set up the particle counter (see A.2) in accordance with the manufacturer’s instructions and in compliance
with the instrument calibration certificate.
A.4.3.2
The sampling probe shall be positioned pointing into the airflow. If the direction of the airflow being sampled is
not controlled or predictable (e.g. non-unidirectional airflow), the inlet of the sampling probe shall be directed
vertically upward.
A.4.3.3
If necessary, allow stable conditions to be established before sampling.
Sample the volume of air determined in A.4.2.1, as a minimum, for each sample at each sampling location.
A.4.3.4
If during testing at multiple locations in any one of the three occupancy states, an unusually high result is
found at a particular location in the single sample volume, further testing may be undertaken at the location to
investigate the problem and determine if the location meets the classification.
A.5 Recording of results
A.5.1 Average concentration of particles at each sampling location
A.5.1.1
Record the result of each sample measurement as the number of particles in each single sample volume at
each of the considered particle size(s) appropriate to the relevant classification of air cleanliness.
A.5.1.2
When two or more single sample volumes are taken at a location, calculate and record the average number of
particles per location at each considered particle size from the individual sample particle concentrations
(A.5.1.1), according to Equation (A.2).
[xxi.1 + i.2 + .xi.n]
xi =  (A.2)
n
where
xi is the average number of particles at location i, representing any location.
x to x are the number of particles in individual samples.
i.1 i.n
n is the number of samples taken at location i.
A.5.1.3
Calculate the concentration per cubic metre.
ISO/DIS 14644-1
xi  1 000
Ci =  (A.3)
Vt
where
xi is the average number of particles at location i, representing each location.
V is the adopted single sample volume in litres.
t
A.6 Interpretation of results
A.6.1 Classification requirements
The cleanroom or clean zone is deemed to have met the specified air cleanliness classification requirements if
the average of the particle concentrations (expressed as number of particles per cubic metre) measured at
each of the sampling locations does not exceed the concentration limits determined in accordance with
Table 1 or intermediate decimal class Equation (1).
12 © ISO 2010 – All rights reserved

ISO/DIS 14644-1
(Blank page)
ISO/DIS 14644-1
Annex B
(informative)
Examples of classification calculations
B.1 Example 1
B.1.1
A cleanroom has a floor area of 18 m and is specified for an air cleanliness by particle concentration of ISO
Class 5 in operation. The classification is to be performed using a discrete-particle counter having a flow rate
of 28,3 litres per minute. Two particle sizes are considered: D ≥ 0,3 µm and D ≥ 0,5 µm.
The number of sample locations, N , is determined to be six, based on Table A.1.
L
B.1.2
The particle concentration limits for ISO Class 5 are taken from Table 1:
C (≥ 0,3 µm) = 10 200 particles/m
n
C (≥ 0,5 µm) = 3 520 particles/m
n
B.1.3
The required single sample volume can be calculated from Equation (A.1) as follows:
V = ()  1 000
s
Cn, m
V = ()  1 000
s
3 520
V = (0,00568)  1 000
s
V = 5,68 litres
s
The single sample volume has been calculated to be 5,68 litres. As the discrete-particle counter being used
for this test had a flow rate of 28,3 litres per minute, a 1-minute single sample count would be required (see
A.4.2.2) and therefore 28,3 litres would be sampled for each single sample volume.
NOTE In A.4.2.2, the minimum sample volume for the procedure is set by calculating the minimum sample volume as
shown above and then determining the sample volume obtained for the operation of the particle counter in the time period
of 1 minute. The sampling at each position must occur for at least 1 minute; if the minimum sample volume as calculated
is satisfied within the 1-minute period, then the sample process can be stopped at the end of 1 minute. If the calculated
minimum volume cannot be obtained within the 1-minute period with the flow rate of the instrument to be used, then the
sampling must continue for a longer time period until at least the minimum sample volume has been obtained. Because
there are several possible flow rates for particle counters, users are cautioned to verify the flow rate of the specific
instrument(s) to be used when determining the sample time needed to satisfy both the 1-minute requirement and the
calculated minimum sample volume.
14 © ISO 2010 – All rights reserved

ISO/DIS 14644-1
B.1.4
At each sampling location only one sample volume is taken. The number of particles per cubic metre, x, is
i
calculated for each location and each particle size as shown in Tables B.1 and B.2:
Table B.1 Sampling data for particles ≥ 0,3 µm
Sample Sample 1 Location Location Limit Pass/fail
location average average for
x ≥ 0,3 µm
i
(counts 0,3 µm
(counts per
per 28,3 counts
cubic metre =
litres) at ISO
location average
Class 5
 35,3)
1 245 245 8 649 10 200 Pass
2 185 185 6 531 10 200 Pass
3 59 59 2 083 10 200 Pass
4 106 106 3 742 10 200 Pass
5 164 164 5 789 10 200 Pass
6 196 196 6 919 10 200 Pass
Table B.2 Sampling data for particles ≥ 0,5 µm
Sample Sample 1 Location Location average Limit for Pass/fail
location average 0,5 µm
x ≥ 0,5 µm (counts per cubic
i
counts at
(counts per metre = location
ISO Class
28,3 litres)
average  35,3)
1 21 21 741 3 520 Pass
2 24 24 847 3 520 Pass
3 0 0 0 3 520 Pass
4 7 7 247 3 520 Pass
5 22 22 777 3 520 Pass
6 25 25 883 3 520 Pass
B.1.5
Each value of the concentration for D ≥ 0,3 µm is less than the limit of 10 200 particles/m and D ≥ 0,5 µm is
less than the limit of 3 520 particles/m as established in B.1.2; therefore, the air cleanliness by particle
concentration of the cleanroom meets the required classification.
B.2 Example 2
B.2.1
A cleanroom has a floor area of 9 m and is specified for an air cleanliness by particle concentration of ISO
Class 3 in operation. The classification is to be performed using a discrete-particle counter having a flow rate
of 50,0 litres per minute. Only one particle size (D ≥ 0,1 µm) is considered.
The number of sample locations, N , is determined to be five, based on Table A.1.
L
ISO/DIS 14644-1
B.2.2
The particle concentration limit for ISO Class 3 at ≥ 0,1 µm is taken from Table 1:
C (≥ 0,1 µm) = 1 000 particles/m
n
B.2.3
The required single sample volume can be calculated from Equation (A.1) as follows:
V = ()  1 000
s
Cn, m
V = ()  1 000
s
1 000
V = (0,02)  1 000
s
V = 20,0 litres
s
The single sample volume has been calculated to be 20,0 litres. As the discrete-particle counter being used
for this test had a flow rate of 50,0 litres per minute, a 1-minute single sample count would be required (see
A.4.2.2) and therefore 50,0 litres would be sampled for each single sample volume.
B.2.4
At each sampling location only one sample volume is taken. The number of particles per cubic metre, x, is
i
calculated for each location and recorded in Table B.3:
Table B.3 — Sampling data for particles ≥ 0.1 m
Sample Sample 1 Location Location average Limit for Pass/fail
location average ≥ 0,1 µm
x ≥ 0,1 µm (counts per cubic
i
counts at
(counts per metre = location
ISO Class 3
50,0 litres)
average  20)
1 46 46 920 1 000 Pass
2 47 47 940 1 000 Pass
3 46 46 920 1 000 Pass
4 44 44 880 1 000 Pass
5 9 9 180 1 000 Pass
B.2.5
Each value of the concentration for D ≥ 0,1 µm is less than the limit of 1 000 particles/m established in
Table 1; therefore, the air cleanliness by particle concentration of the cleanroom meets the required
classification.
16 © ISO 2010 – All rights reserved

ISO/DIS 14644-1
B.3 Example 3
B.3.1
A cleanroom has a floor area of 64 m and is specified for an air cleanliness by particle concentration of ISO
Class 5 in operation. The classification is to be performed using a discrete-particle counter having a flow rate
of 28,3 litres per minute. Only one particle size (D ≥ 0,5 µm) is considered.
The number of sample locations, N , is determined to be twelve, based on Table A.1.
L
B.3.2
The particle concentration limit for ISO Class 5 at ≥ 0,5 µm is taken from Table 1:
C (≥ 0,5 µm) = 3 520 particles/m
n
B.3.3
The required single sample volume can be calculated from Equation (A.1) as follows:
V = ()  1 000
s
Cn, m
V = ()  1 000
s
3 520
V = (0,00568)  1 000
s
V = 5,68 litres
s
The single sample volume has been calculated to be 5,68 litres. As the discrete-particle counter used for this
test had a flow rate of 28,3 litres per minute, a 1-minute single sample count would be required (see A.4.2.2)
and therefore 28,3 litres would be sampled for each single sample volume.
B.3.4
At each sampling location only one sample volume is taken. The number of particles per cubic metre, x, is
i
calculated for each location and recorded in Table B.4:
Table B.4 — Sampling data for particles ≥ 0.5 m
Sample Sample 1 Location Location Limit for Pass/fail
location average average 0,5 µm
x ≥ 0,5 µm
i
concentration concentration counts at
ISO
(counts per (counts per
Class 5
28,3 litres) cubic metre =
location
average  35,3)
1 35 35 1 236 3 520 Pass
2 22 22 777 3 520 Pass
3 89 89 3 142 3 520 Pass
4 49 49 1 730 3 520 Pass
5 10 10 353 3 520 Pass
ISO/DIS 14644-1
Table B.4 (continued)
Sample Sample 1 Location Location Limit for Pass/fail
location average average 0,5 µm
x ≥ 0,5 µm
i
concentration concentration counts
at ISO
(counts per (counts per
Class 5
28,3 litres) cubic metre =
location
average  35,3)
6 60 60 2 118 3 520 Pass
7 18 18 635 3 520 Pass
8 44 44 1 553 3 520 Pass
9 59 59 2 083 3 520 Pass
10 51 51 1 800 3 520 Pass
11 6 6 212 3 520 Pass
12 31 31 1 094 3 520 Pass
B.3.5
Each value of the concentration for D = 0,5 µm is less than the limit of 3 520 particles/m established in
Table 1; therefore, the air cleanliness by particle concentration of the cleanroom meets the required
classification.
B.4 Example 4
B.4.1
A cleanroom has a floor area of 25 m and is specified for an air cleanliness by particle concentration of ISO
Class 5 in operation. The classification is to be performed using a discrete-particle counter having a flow rate
of 28,3 litres per minute. Only one particle size (D ≥ 0,5 µm) is considered.
The number of sample locations is determined to be seven, based on Table A.1.
B.4.2
The particle concentration limit for ISO Class 5 at ≥ 0,5 µm is calculated using Table 1 as follows:
C (≥ 0,5 µm) = C (≥ 0,5 µm) = 3 520 particles/m
n n
B.4.3
The required single sample volume can be calculated from Equation (A.1) as follows:
V = ()  1 000
s
Cn, m
V = ()  1 000
s
3 520
V = (0,00568)  1 000
s
18 © ISO 2010 – All rights reserved

ISO/DIS 14644-1
V = 5,68 litres
s
The single sample volume has been calculated to be 5,68 litres. As the discrete-particle counter being used
for this test had a flow rate of 28,3 litres per minute, a 1-minute single sample count would be required (see
A.4.2.2) and therefore 28,3 litres would be sampled for each single sample volume.
B.4.4
At each sampling location the number of single sample volumes varies from one to three. The number of
particles per cubic metre, x , is calculated for each location and recorded in Table B.5:
i
Table B.5 — Sampling data for particles ≥ 0.5 m
Sample Sample 1 Sample 2 Sample 3 Location Location average Limit for Pass/fail
location average ≥ 0,5 µm
x ≥ x ≥ x ≥ (counts per cubic
i i i
counts at
0,5 µm 0,5 µm 0,5 µm (counts per metre = location
ISO Class
28,3 litres)
average  35,3)
1 47 57 52 1 836 3 520 Pass
2 12  12 424 3 520 Pass
3 162 78 32 91 3 201 3 520 Pass
4 54 159 78 97 3 424 3 520 Pass
5 1 0 0,5 18 3 520 Pass
6 19 22 17 19 682 3 520 Pass
7 5 15 3 7 271 3 520 Pass
8 38 21 30 1 041 3 520 Pass
9 148 74 132 118 4 165 3 520 Fail
10 48 62 53 54 1 918 3 520 Pass

B.4.5
At sample location 9, the average sample volume concentration of 4 165 does not meet ISO Class 5
maximum particle count criteria of 3 520. At location 3 and location 4, one of the individual particle count
concentrations does not meet the limit established in Table 1; however, neither the average particle
concentration for location 3 nor the average particle concentration for location 4 meets the limit established in
Table 1. Because location 9 does not meet the air cleanliness by particle concentration, the cleanroom does
not meet the required classification.
B.5 Example 5
B.5.1
A cleanroom has a floor area of 10,7 m and is specified for an air cleanliness by particle concentr
...


INTERNATIONAL ISO
STANDARD 14644-1
Second edition
2015-12-15
Cleanrooms and associated controlled
environments —
Part 1:
Classification of air cleanliness by
particle concentration
Salles propres et environnements maîtrisés apparentés —
Partie 1: Classification de la propreté particulaire de l’air
Reference number
©
ISO 2015
© ISO 2015, Published in Switzerland
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized otherwise in any form
or by any means, electronic or mechanical, including photocopying, or posting on the internet or an intranet, without prior
written permission. Permission can be requested from either ISO at the address below or ISO’s member body in the country of
the requester.
ISO copyright office
Ch. de Blandonnet 8 • CP 401
CH-1214 Vernier, Geneva, Switzerland
Tel. +41 22 749 01 11
Fax +41 22 749 09 47
copyright@iso.org
www.iso.org
ii © ISO 2015 – All rights reserved

Contents Page
Foreword .iv
Introduction .v
1 Scope . 1
2 Normative references . 1
3 Terms and definitions . 1
3.1 General . 1
3.2 Airborne particles . 2
3.3 Occupancy states . 3
3.4 Testing instrumentation (see Annex F) . 3
3.5 Instrument specifications . 4
4 Classification . 4
4.1 Occupancy state(s) . 4
4.2 Particle size(s) . 4
4.3 ISO Class number . 4
4.4 Designation . 5
4.5 Intermediate decimal cleanliness classes and particle size thresholds . 5
5 Demonstration of compliance . 6
5.1 Principle . 6
5.2 Testing . 6
5.3 Airborne particle concentration evaluation . 6
5.4 Test report . 6
Annex A (normative) Reference method for classification of air cleanliness by
particle concentration . 8
Annex B (informative) Examples of classification calculations .13
Annex C (informative) Counting and sizing of airborne macroparticles .22
Annex D (informative) Sequential sampling procedure .27
Annex E (informative) Specification of intermediate decimal cleanliness classes and
particle size thresholds .34
Annex F (informative) Test instruments .36
Bibliography .37
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work of preparing International Standards is normally carried out
through ISO technical committees. Each member body interested in a subject for which a technical
committee has been established has the right to be represented on that committee. International
organizations, governmental and non-governmental, in liaison with ISO, also take part in the work.
ISO collaborates closely with the International Electrotechnical Commission (IEC) on all matters of
electrotechnical standardization.
The procedures used to develop this document and those intended for its further maintenance are
described in the ISO/IEC Directives, Part 1. In particular the different approval criteria needed for the
different types of ISO documents should be noted. This document was drafted in accordance with the
editorial rules of the ISO/IEC Directives, Part 2 (see www.iso.org/directives).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. ISO shall not be held responsible for identifying any or all such patent rights. Details of
any patent rights identified during the development of the document will be in the Introduction and/or
on the ISO list of patent declarations received (see www.iso.org/patents).
Any trade name used in this document is information given for the convenience of users and does not
constitute an endorsement.
For an explanation on the meaning of ISO specific terms and expressions related to conformity
assessment, as well as information about ISO’s adherence to the WTO principles in the Technical
Barriers to Trade (TBT) see the following URL: Foreword - Supplementary information
The committee responsible for this document is ISO/TC 209, Cleanrooms and associated controlled
environments.
This second edition cancels and replaces the first edition (ISO 14644-1:1999), which has been
technically revised throughout.
ISO 14644 consists of the following parts, under the general title Cleanrooms and associated controlled
environments:
— Part 1: Classification of air cleanliness by particle concentration
— Part 2: Monitoring to provide evidence of cleanroom performance related to air cleanliness by particle
concentration
— Part 3: Test methods
— Part 4: Design, construction and start-up
— Part 5: Operations
— Part 7: Separative devices (clean air hoods, gloveboxes, isolators and mini-environments)
— Part 8: Classification of air cleanliness by chemical concentration (ACC)
— Part 9: Classification of surface cleanliness by particle concentration
— Part 10: Classification of surface cleanliness by chemical concentration
Attention is also drawn to ISO 14698, Cleanrooms and associated controlled environments —
Biocontamination control:
— Part 1: General principles and methods
— Part 2: Evaluation and interpretation of biocontamination data
iv © ISO 2015 – All rights reserved

Introduction
Cleanrooms and associated controlled environments provide for the control of contamination of air
and, if appropriate, surfaces, to levels appropriate for accomplishing contamination-sensitive activities.
Contamination control can be beneficial for protection of product or process integrity in applications in
industries such as aerospace, microelectronics, pharmaceuticals, medical devices, healthcare and food.
This part of ISO 14644 specifies classes of air cleanliness in terms of the number of particles expressed
as a concentration in air volume. It also specifies the standard method of testing to determine
cleanliness class, including selection of sampling locations.
This edition is the result of a response to an ISO Systematic Review and includes changes in response to
user and expert feedback validated by international enquiry. The title has been revised to “Classification
of air cleanliness by particle concentration” to be consistent with other parts of ISO 14644. The nine
ISO cleanliness classes are retained with minor revisions. Table 1 defines the particle concentration at
various particle sizes for the nine integer classes. Table E.1 defines the maximum particle concentration
at various particle sizes for intermediate classes. The use of these tables ensures better definition
of the appropriate particle-size ranges for the different classes. This part of ISO 14644 retains the
macroparticle descriptor concept; however, consideration of nano-scale particles (formerly defined as
ultrafine particles) will be addressed in a separate standard.
The most significant change is the adoption of a more consistent statistical approach to the selection and
the number of sampling locations; and the evaluation of the data collected. The statistical model is based
on adaptation of the hypergeometric sampling model technique, where samples are drawn randomly
without replacement from a finite population. The new approach allows each location to be treated
independently with at least a 95 % level of confidence that at least 90 % of the cleanroom or clean zone
areas will comply with the maximum particle concentration limit for the target class of air cleanliness.
No assumptions are made regarding the distribution of the actual particle counts over the area of the
cleanroom or clean zone; while in ISO 14644-1:1999 an underlying assumption was that the particle
counts follow the same normal distribution across the room, this assumption has now been discarded
to allow the sampling to be used in rooms where the particle counts vary in a more complex manner. In
the process of revision it has been recognized that the 95 % UCL was neither appropriate nor was applied
consistently in ISO 14644-1:1999. The minimum number of sampling locations required has been changed,
compared with ISO 14644-1:1999. A reference table, Table A.1, is provided to define the minimum number
of sampling locations required based on a practical adaptation of the sampling model technique. An
assumption is made that the area immediately surrounding each sampling location has a homogeneous
particle concentration. The cleanroom or clean zone area is divided up into a grid of sections of near equal
area, whose number is equal to the number of sampling locations derived from Table A.1. A sampling
location is placed within each grid section, so as to be representative of that grid section.
It is assumed for practical purposes that the locations are chosen representatively; a “representative”
location (see A.4.2) means that features such as cleanroom or clean zone layout, equipment disposition
and airflow systems should be considered when selecting sampling locations. Additional sampling
locations may be added to the minimum number of sampling locations.
Finally, the annexes have been reordered to improve the logic of this part of ISO 14644 and portions
of the content of certain annexes concerning testing and test instruments have been included from
ISO 14644-3:2005.
The revised version of this part of ISO 14644 addresses the ≥ 5 µm particle limits for ISO Class
5 in the sterile products annexes of the EU, PIC/S and WHO GMPs by way of an adaptation of the
macroparticle concept.
The revised version of this part of ISO 14644 now includes all matters related to classification of air
cleanliness by particle concentration. The revised version of ISO 14644-2:2015 now deals exclusively
with the monitoring of air cleanliness by particle concentration.
Cleanrooms may also be characterized by attributes in addition to the classification of air cleanliness by
particle concentration. Other attributes, such as air cleanliness in terms of chemical concentration, may
be monitored and the attribute’s grade or level may be designated along with the classification of the ISO
Class of cleanliness. These additional attributes do not suffice alone to classify a cleanroom or clean zone.
vi © ISO 2015 – All rights reserved

INTERNATIONAL STANDARD ISO 14644-1:2015(E)
Cleanrooms and associated controlled environments —
Part 1:
Classification of air cleanliness by particle concentration
1 Scope
This part of ISO 14644 specifies the classification of air cleanliness in terms of concentration of airborne
particles in cleanrooms and clean zones; and separative devices as defined in ISO 14644-7.
Only particle populations having cumulative distributions based on threshold (lower limit) particle
sizes ranging from 0,1 µm to 5 µm are considered for classification purposes.
The use of light scattering (discrete) airborne particle counters (LSAPC) is the basis for determination
of the concentration of airborne particles, equal to and greater than the specified sizes, at designated
sampling locations.
This part of ISO 14644 does not provide for classification of particle populations that are outside the
specified lower threshold particle-size range, 0,1 µm to 5 µm. Concentrations of ultrafine particles
(particles smaller than 0,1 µm) will be addressed in a separate standard to specify air cleanliness
by nano-scale particles. An M descriptor (see Annex C) may be used to quantify populations of
macroparticles (particles larger than 5 µm).
This part of ISO 14644 cannot be used to characterize the physical, chemical, radiological, viable or
other nature of airborne particles.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
ISO 14644-2:2015, Cleanrooms and associated controlled environments — Part 2: Monitoring to provide
evidence of cleanroom performance related to air cleanliness by particle concentration
ISO 14644-7, Cleanrooms and associated controlled environments — Part 7: Separative devices (clean air
hoods, gloveboxes, isolators and mini-environments)
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
3.1 General
3.1.1
cleanroom
room within which the number concentration of airborne particles is controlled and classified, and
which is designed, constructed and operated in a manner to control the introduction, generation and
retention of particles inside the room
Note 1 to entry: The class of airborne particle concentration is specified.
Note 2 to entry: Levels of other cleanliness attributes such as chemical, viable or nanoscale concentrations in the
air, and also surface cleanliness in terms of particle, nanoscale, chemical and viable concentrations might also be
specified and controlled.
Note 3 to entry: Other relevant physical parameters might also be controlled as required, e.g. temperature,
humidity, pressure, vibration and electrostatic.
3.1.2
clean zone
defined space within which the number concentration of airborne particles is controlled and classified,
and which is constructed and operated in a manner to control the introduction, generation and retention
of contaminants inside the space
Note 1 to entry: The class of airborne particle concentration is specified.
Note 2 to entry: Levels of other cleanliness attributes such as chemical, viable or nanoscale concentrations in the
air, and also surface cleanliness in terms of particle, nanoscale, chemical and viable concentrations might also be
specified and controlled.
Note 3 to entry: A clean zone(s) can be a defined space within a cleanroom or might be achieved by a separative
device. Such a device can be located inside or outside a cleanroom.
Note 4 to entry: Other relevant physical parameters might also be controlled as required, e.g. temperature,
humidity, pressure, vibration and electrostatic.
3.1.3
installation
cleanroom or one or more clean zones, together with all associated structures, air-treatment systems,
services and utilities
3.1.4
classification
method of assessing level of cleanliness against a specification for a cleanroom or clean zone
Note 1 to entry: Levels should be expressed in terms of an ISO Class, which represents maximum allowable
concentrations of particles in a unit volume of air.
3.2 Airborne particles
3.2.1
particle
minute piece of matter with defined physical boundaries
3.2.2
particle size
diameter of a sphere that produces a response, by a given particle-sizing instrument, that is equivalent
to the response produced by the particle being measured
Note 1 to entry: For discrete-particle light-scattering instruments, the equivalent optical diameter is used.
3.2.3
particle concentration
number of individual particles per unit volume of air
3.2.4
particle size distribution
cumulative distribution of particle concentration as a function of particle size
3.2.5
macroparticle
particle with an equivalent diameter greater than 5 µm
2 © ISO 2015 – All rights reserved

3.2.6
M descriptor
designation for measured or specified concentration of macroparticles per cubic metre of air, expressed
in terms of the equivalent diameter that is characteristic of the measurement method used
Note 1 to entry: The M descriptor can be regarded as an upper limit for the averages at sampling locations.
M descriptors cannot be used to define ISO Classes, but the M descriptor may be quoted independently or in
conjunction with ISO Classes.
3.2.7
unidirectional airflow
controlled airflow through the entire cross-section of a cleanroom or a clean zone with a steady velocity
and airstreams that are considered to be parallel
3.2.8
non-undirectional airflow
air distribution where the supply air entering the cleanroom or clean zone mixes with the internal air
by means of induction
3.3 Occupancy states
3.3.1
as-built
condition where the cleanroom or clean zone is complete with all services connected and functioning
but with no equipment, furniture, materials or personnel present
3.3.2
at-rest
condition where the cleanroom or clean zone is complete with equipment installed and operating in a
manner agreed upon, but with no personnel present
3.3.3
operational
agreed condition where the cleanroom or clean zone is functioning in the specified manner, with
equipment operating and with the specified number of personnel present
3.4 Testing instrumentation (see Annex F)
3.4.1
resolution
smallest change in a quantity being measured that causes a perceptible change in the corresponding
indication
Note 1 to entry: Resolution can depend on, for example, noise (internal or external) or friction. It may also depend
on the value of a quantity being measured.
[SOURCE: ISO/IEC Guide 99:2007, 4.14]
3.4.2
maximum permissible measurement error
extreme value of measurement error, with respect to a known reference quantity value, permitted by
specifications or regulations for a given measurement, measuring instrument, or measuring system
Note 1 to entry: Usually, the term “maximum permissible errors” or “limits of error” is used where there are two
extreme values.
Note 2 to entry: The term “tolerance” should not be used to designate “maximum permissible error”.
[SOURCE: ISO/IEC Guide 99:2007, 4.26]
3.5 Instrument specifications
3.5.1
LSAPC
light scattering airborne particle counter
light scattering discrete airborne particle counter
instrument capable of counting and sizing single airborne particles and reporting size data in terms of
equivalent optical diameter
Note 1 to entry: The specifications for the LSAPC are given in ISO 21501-4:2007.
3.5.2
discrete-macroparticle counter
instrument capable of counting and sizing single airborne macroparticles
Note 1 to entry: See Table F.1 for specifications.
3.5.3
time-of-flight particle sizing apparatus
discrete-particle counting and sizing apparatus that defines the aerodynamic diameter of particles by
measuring the time for a particle to accommodate to a change in air velocity
Note 1 to entry: This is usually done by measuring the particle transit time optically after a fluid stream
velocity change.
Note 2 to entry: See Table F.2 for specifications.
4 Classification
4.1 Occupancy state(s)
The air cleanliness class by particle concentration of air in a cleanroom or clean zone shall be defined in
one or more of three occupancy states, viz. “as-built,” “at-rest” or “operational” (see 3.3).
4.2 Particle size(s)
One, or more than one, threshold (lower limit) particle sizes situated within the range from ≥0,1 µm to
≥5 µm are to be used to determine air cleanliness particle concentration for classification.
4.3 ISO Class number
Air cleanliness class by particle concentration shall be designated by an ISO Class number, N. The maximum
permitted concentration of particles for each considered particle size is determined from Table 1.
Particle number concentrations for different threshold sizes in Table 1 do not reflect actual particle size
and number distribution in the air and serve as criteria for classification only. Examples of classification
calculations are included in Annex B.
4 © ISO 2015 – All rights reserved

Table 1 — ISO Classes of air cleanliness by particle concentration
ISO Class number Maximum allowable concentrations (particles/m ) for particles equal to and greater
a
(N) than the considered sizes, shown below
0,1 µm 0,2 µm 0,3 µm 0,5 µm 1 µm 5 µm
b d d d d e
1 10
b b d d e
2 100 24 10
b d e
3 1 000 237 102 35
b e
4 10 000 2 370 1 020 352 83
d, e, f
5 100 000 23 700 10 200 3 520 832
6 1 000 000 237 000 102 000 35 200 8 320 293
c c c
7 352 000 83 200 2 930
c c c
8 3 520 000 832 000 29 300
g c c c
9 35 200 000 8 320 000 293 000
a
All concentrations in the table are cumulative, e.g. for ISO Class 5, the 10 200 particles shown at 0,3 µm include all
particles equal to and greater than this size.
b
These concentrations will lead to large air sample volumes for classification. Sequential sampling procedure may be
applied; see Annex D.
c
Concentration limits are not applicable in this region of the table due to very high particle concentration.
d
Sampling and statistical limitations for particles in low concentrations make classification inappropriate.
e
Sample collection limitations for both particles in low concentrations and sizes greater than 1 μm make classification
at this particle size inappropriate, due to potential particle losses in the sampling system.
f
In order to specify this particle size in association with ISO Class 5, the macroparticle descriptor M may be adapted and
used in conjunction with at least one other particle size. (See C.7.)
g
This class is only applicable for the in-operation state.
4.4 Designation
The designation of airborne particle concentration for cleanrooms and clean zones shall include
a) the ISO Class number, expressed as “ISO Class N”,
b) the occupancy state to which the classification applies, and
c) the considered particle size(s).
If measurements are to be made at more than one considered particle size, each larger particle diameter
(e.g. D2) shall be at least 1,5 times the next smaller particle diameter (e.g. D1), i.e. D2 ≥ 1,5 × D1.
EXAMPLE ISO Class number; occupancy state; considered particle size(s)
ISO Class 4; at rest; 0,2 µm, 0,5 µm
4.5 Intermediate decimal cleanliness classes and particle size thresholds
Where intermediate classes, or intermediate particle size thresholds for integer and intermediate
classes are required, refer to informative Annex E.
5 Demonstration of compliance
5.1 Principle
Compliance with air cleanliness (ISO Class) requirements specified by the customer is verified
by performing specified testing procedures and by providing documentation of the results and
conditions of testing.
At-rest or operational classification may be performed periodically based upon risk assessment of the
application, typically on an annual basis.
For monitoring cleanrooms, clean zones and separative devices, ISO 14644-2:2015 shall be used.
NOTE Where the installation is equipped with instrumentation for continuous or frequent monitoring
of air cleanliness by particle concentration and other parameters of performance as applicable, the time
intervals between classification may be extended provided that the results of the monitoring remain within
the specified limits.
5.2 Testing
The reference test method for demonstrating compliance is given in Annex A (normative). Alternative
methods or instrumentation (or both), having at least comparable performance, may be specified. If no
alternative is specified or agreed upon, the reference method shall be used.
Tests performed to demonstrate compliance shall be conducted using instruments which are in
compliance with calibration requirements at the time of testing.
5.3 Airborne particle concentration evaluation
Upon completion of testing in accordance with Annex A, the concentration of particles (expressed as
number of particles per cubic metre) in a single sample volume at each sampling location shall not
exceed the concentration limit(s) given in Table 1 or Table E.1 for intermediate decimal classes for the
considered size(s). If multiple single sample volumes are taken at a sampling location, the concentrations
shall be averaged and the average concentration must not exceed the concentration limits given in
Table 1 or Table E 1. Intermediate particle sizes shall be derived from Formula (E.1).
Particle concentrations used for determination of compliance with ISO Classes shall be measured by
the same method for all considered particle sizes.
5.4 Test report
The results from testing each cleanroom or clean zone shall be recorded and submitted as a
comprehensive report, along with a statement of compliance or non-compliance with the specified
designation of air cleanliness class by particle concentration.
The test report shall include
a) the name and address of the testing organization, and the date on which the test was performed,
b) the number and year of publication of this part of ISO 14644, i.e. ISO 14644-1:2015,
c) a clear identification of the physical location of the cleanroom or clean zone tested (including
reference to adjacent areas if necessary), and specific designations for coordinates of all sampling
locations (a diagrammatic representation can be helpful),
d) the specified designation criteria for the cleanroom or clean zone, including the ISO Class number,
the relevant occupancy state(s), and the considered particle size(s),
e) details of the test method used, with any special conditions relating to the test, or departures from
the test method, and identification of the test instrument and its current calibration certificate, and
6 © ISO 2015 – All rights reserved

f) the test results, including particle concentration data for all sampling locations.
If concentrations of macroparticles are quantified, as described in Annex C, the relevant information
should be included with the test report.
Annex A
(normative)
Reference method for classification of air cleanliness by particle
concentration
A.1 Principle
A discrete-particle-counting instrument is used to determine the concentration of airborne particles,
equal to and greater than the specified sizes, at designated sampling locations.
A.2 Apparatus requirements
A.2.1 Particle-counting instrument
The instrument shall have a means of displaying or recording the count and size of discrete particles
in air with a size discrimination capability to detect the total particle concentration in the appropriate
particle size ranges for the class under consideration.
NOTE Light scattering (discrete) airborne particle counters (LSAPC) are commonly used for undertaking air
cleanliness classification.
A.2.2 Instrument calibration
The particle counter shall have a valid calibration certificate: the frequency and method of calibration
[1]
should be based upon current accepted practice as specified in ISO 21501-4.
NOTE Some particle counters cannot be calibrated to all of the required tests in ISO 21501-4. If this is the
case, record the decision to use the counter in the test report.
A.3 Preparation for particle count testing
Prior to testing, verify that all relevant aspects of the cleanroom or clean zone that contribute to its
integrity are complete and functioning in accordance with its performance specification.
Care should be taken when determining the sequence for performing supporting tests for cleanroom
performance. ISO 14644-3, Annex A provides a checklist.
A.4 Establishment of sampling locations
A.4.1 Deriving the number of sampling locations
Derive the minimum number of sampling locations, N , from Table A.1. Table A.1 provides the number
L
of sampling locations related to the area of each cleanroom or clean zone to be classified and provides
at least 95 % confidence that at least 90 % of the cleanroom or clean zone area does not exceed the
class limits.
8 © ISO 2015 – All rights reserved

Table A.1 — Sampling locations related to cleanroom area
Area of cleanroom (m ) Minimum number of sampling
less than or equal to locations to be tested (N )
L
2 1
4 2
6 3
8 4
10 5
24 6
28 7
32 8
36 9
52 10
56 11
64 12
68 13
72 14
76 15
104 16
108 17
116 18
148 19
156 20
192 21
232 22
276 23
352 24
436 25
636 26
1 000 27
> 1 000 See Formula (A.1)
NOTE 1 If the considered area falls between two values in the table, the greater of the two
should be selected.
NOTE 2 In the case of unidirectional airflow, the area may be considered as the cross
section of the moving air perpendicular to the direction of the airflow. In all other cases the
area may be considered as the horizontal plan area of the cleanroom or clean zone.
A.4.2 Positioning the sampling locations
In order to position the sampling locations
a) use the minimum number of sampling locations N derived from Table A.1,
L
b) then divide the whole cleanroom or clean zone into N sections of equal area,
L
c) select within each section a sampling location considered to be representative of the characteristics
of the section, and
d) at each location, position the particle counter probe in the plane of the work activity or another
specified point.
Additional sampling locations may be selected for locations considered critical. Their number and
positions shall also be agreed and specified.
Additional sections and associated sampling locations may be included to facilitate subdivision into
equal sections.
For non-unidirectional airflow cleanrooms or clean zones, locations may not be representative if they
are located directly beneath non-diffused supply air sources.
A.4.3 Sampling locations for large cleanrooms or clean zones
When the area of the cleanroom or clean zone is greater than 1 000 m , apply Formula (A.1) to determine
the minimum number of sampling locations required.
 
 
A


N =×27  (A.1)


L


1000
 
 
where
N is the minimum number of sampling locations to be evaluated, rounded up to the next whole
L
number;
A is the area of the cleanroom in m .
A.4.4 Establishment of single sample volume and sampling time per location
At each sampling location, sample a volume of air sufficient to detect a minimum of 20 particles
if the particle concentration for the largest selected particle size were at the class limit for the
designated ISO Class.
The single sample volume, V , per sampling location is determined by using Formula (A.2):
s
 
 



V = ×1000 (A.2)

s


C
 

 nm, 
where
Vs is the minimum single sample volume per location, expressed in litres (except see Annex D);
C is the class limit (number of particles per cubic metre) for the largest considered particle
n,m
size specified for the relevant class;
20 is the number of particles that could be counted if the particle concentration were at the
class limit.
The volume sampled at each location shall be at least 2 l, with a minimum sampling time of 1 min for
each sample at each location. Each single sample volume at each sampling location shall be the same.
When V is very large, the time required for sampling can be substantial. By using the optional
s
sequential sampling procedure (see Annex D), both the required sample volume and the time required
to obtain samples may be reduced.
A.5 Sampling procedure
A.5.1 Set up the particle counter (see A.2) in accordance with the manufacturer’s instructions including
performing a zero count check.
10 © ISO 2015 – All rights reserved

A.5.2 The sampling probe shall be positioned pointing into the airflow. If the direction of the airflow
being sampled is not controlled or predictable (e.g. non-unidirectional airflow), the inlet of the sampling
probe shall be directed vertically upward.
A.5.3 Ensure normal conditions for the selected occupancy state are established before sampling.
A.5.4 Sample the volume of air determined in A.4.4, as a minimum, for each sample at each
sampling location.
A.5.5 If an out-of-specification count is found at a location due to an identified abnormal occurrence,
then that count can be discarded and noted as such on the test report and a new sample taken.
A.5.6 If an out-of-specification count found at a location is attributed to a technical failure of the
cleanroom or equipment, then the cause should be identified, remedial action taken and retesting
performed of the failed sampling location, the immediate surrounding locations and any other locations
affected. The choice shall be clearly documented and justified.
A.6 Processing of results
A.6.1 Recording of results
Record the result of each sample measurement as the number of particles in each single sample volume
at each of the considered particle size(s) appropriate to the relevant ISO Class of air cleanliness.
NOTE For particle counters with a concentration calculation mode, the manual evaluation may not be
necessary.
A.6.1.1 Average concentration of particles at each sampling location
When two or more single sample volumes are taken at a location, calculate and record the average
number of particles per location at each considered particle size from the individual sample particle
concentrations, according to Formula (A.3).
 
xx++ .x


ii.12 in.


x = (A.3)


i



 n
 
where
is the average number of particles at location i, representing any location;
x
i
x to x are the number of particles in individual samples;
i.1 i.n
n is the number of samples taken at location i.
A.6.1.2 Calculate the concentration per cubic metre
x ×1000
i
C = (A.4)
i
V
t
where
C is the concentration of particles per cubic metre;
i
is the average number of particles at location i, representing each location;
x
i
V is the selected single sample volume in litres.
t
A.6.2 Interpretation of results
A.6.2.1 Classification requirements
The cleanroom or clean zone is deemed to have met the specified air cleanliness classification
requirements if the average of the particle concentrations (expressed as number of particles per cubic
metre) measured at each of the sampling locations does not exceed the concentration limits determined
from Table 1.
If intermediate classes or particle sizes are used, as defined in Annex E, appropriate limits derived from
Table E.1 or Formula (E.1) should be used.
A.6.2.2 Out-of-specification result
In the event of an out-of-specification count, an investigation shall be undertaken. The result of the
investigation and remedial action shall be noted in the test report (see 5.4).
12 © ISO 2015 – All rights reserved

Annex B
(informative)
Examples of classification calculations
B.1 Example 1
B.1.1 A cleanroom has a floor area of 18 m and is specified to be ISO Class 5 in operation. The
classification is to be performed using a discrete-particle counter having a flow rate of 28,3 l per minute.
Two particle sizes are considered: D ≥ 0,3 µm and D ≥ 0,5 µm.
The number of sampling locations, N , is determined to be six, based on Table A.1.
L
B.1.2 The particle concentration limits for ISO Class 5 are taken from Table 1:
C (≥ 0,3 µm) = 10 200 particles/m
n
C (≥ 0,5 µm) = 3 520 particles/m
n
B.1.3 The required single sample volume can be calculated from Formula (A.2) as follows:
 
 


V = ×1000


s


C


 nm, 
 





V = ×1000


s



 
 
V = 0,00568 ×1000
()
s
V = 56, 8litres
s
The single sample volume has been calculated to be 5,68 l. As the LSAPC being used for this test had
a flow rate of 28,3 litres per minute, a 1-min single sample count would be required (see A.4.4) and
therefore 28,3 l would be sampled for each single sample volume.
NOTE In A.4.4, the minimum sample volume for the procedure is set by calculating the minimum sample
volume as shown above and then determining the sample volume obtained for the operation of the particle
counter in the time period of 1 min. The sampling at each position must occur for at least 1 min; if the minimum
sample volume as calculated is satisfied within the 1-min period, then the sampling process can be stopped at the
end of 1 min. If the calculated minimum volume cannot be obtained within the 1-min period with the flow rate of
the instrument to be used, then the sampling must continue for a longer time period until at least the minimum
sample volume has been obtained. Because there are several possible flow rates for particle counters, users are
cautioned to verify the flow rate of the specific instrument(s) to be used when determining the sampling time
needed to satisfy both the 1-min requirement and the calculated minimum sample volume.
B.1.4 At each sampling location only one sample volume is taken. The number of particles per cubic
metre, xi, is calculated for each location and each particle size as shown in Tables B.1 and B.2.
Table B.1 — Sampling data for particles ≥ 0,3 µm
Sampling Sample 1 Location sample Location concentration ISO Class 5 limit Pass/fail
location x ≥ 0,3 µm average average for 0,3 µm
i
(counts per (counts per (counts per m = particle size
28,3 l) 28,3 l) location average × 35,3)
1 245 245 8 649 10 200 Pass
2 185 185 6 531 10 200 Pass
3 59 59 2 083 10 200 Pass
4 106 106 3 742 10 200 Pass
5 164 164 5 789 10 200 Pass
6 196 196 6 919 10 200 Pass
Table B.2 — Sampling data for particles ≥ 0,5 µm
Sampling Sample 1 Location sample Location concentration ISO Class 5 limit Pass/fail
location x ≥ 0,5 µm average average for 0,5 µm
i
(counts per (counts per (counts per m = particle size
28,3 l) 28,3 l) location average × 35,3)
1 21 21 741 3 520 Pass
2 24 24 847 3 520 Pass
3 0 0 0 3 520 Pass
4 7 7 247 3 520 Pass
5 22 22 777 3 520 Pass
6 25 25 883 3 520 Pass
B.1.5 Each value of the concentration for D ≥ 0,3 µm is less than the limit of 10 200 particles/m and
D ≥ 0,5 µm is less than the limit of 3 520 particles/m as established in B.1.2; therefore, the air cleanliness
by particle concentration of the cleanroom meets the required ISO Class.
B.2 Example 2
B.2.1 A cleanroom has a floor area of 9 m and is specified to be ISO Class 3 in operation. The
classification is to be performed using a discrete-particle counter having a flow rate of 50,0 l per minute.
Only one particle size (D ≥ 0,1 µm) is considered.
The number of sampling locations, N , is determined to be five, based on Table A.1.
L
B.2.2 The particle concentration limit for ISO Class 3 at ≥ 0,1 µm is taken from Table 1:
C (≥ 0,1 µm) = 1 000 particles/m
n
B.2.3 The required single sample volume can be calculated from Formula (A.2) as follows:
 

 20



V = ×1000


s


C

 
 nm, 
 
 


V = ×1000


s


 

 
14 © ISO 2015 – All rights reserved

V = 00, 21× 000
()
s
V = 20,0litres
s
The single sample volume has been calculated to be 20,0 l. As the discrete-particle counter being used
for this test had a flow rate of 50,0 l per minute, a 1-min single sample count would be required (see
A.4.4) and therefore 50,0 l would be sampled for each single sample volume.
B.2.4 At each sampling location only one sample volume is taken. The number of particles per cubic
metre, x , is calculated for each location and recorded in Table B.3.
i
Table B.3 — Sampling data for particles ≥ 0,1 μm
Sampling Sample 1 Location sample Location concentration ISO Class 3 limit Pass/fail
location x ≥ 0,1 µm average a
...


INTERNATIONAL ISO
STANDARD 14644-1
Redline version
compares Second edition to
First edition
Cleanrooms and associated controlled
environments —
Part 1:
Classification of air cleanliness by
particle concentration
Salles propres et environnements maîtrisés apparentés —
Partie 1: Classification de la propreté particulaire de l’air
Reference number
ISO 14644-1:redline:2015(E)
©
ISO 2015
ISO 14644-1:redline:2015(E)
IMPORTANT — PLEASE NOTE
This is a mark-up copy and uses the following colour coding:
Text example 1 — indicates added text (in green)
— indicates removed text (in red)
Text example 2
— indicates added graphic figure
— indicates removed graphic figure
1.x . — Heading numbers containg modifications are highlighted in yellow in
the Table of Contents
All changes in this document have yet to reach concensus by vote and as such should only
be used internally for review purposes.
DISCLAIMER
This Redline version provides you with a quick and easy way to compare the main changes
between this edition of the standard and its previous edition. It doesn’t capture all single
changes such as punctuation but highlights the modifications providing customers with
the most valuable information. Therefore it is important to note that this Redline version is
not the official ISO standard and that the users must consult with the clean version of the
standard, which is the official standard, for implementation purposes.
© ISO 2015, Published in Switzerland
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized otherwise in any form
or by any means, electronic or mechanical, including photocopying, or posting on the internet or an intranet, without prior
written permission. Permission can be requested from either ISO at the address below or ISO’s member body in the country of
the requester.
ISO copyright office
Ch. de Blandonnet 8 • CP 401
CH-1214 Vernier, Geneva, Switzerland
Tel. +41 22 749 01 11
Fax +41 22 749 09 47
copyright@iso.org
www.iso.org
ii © ISO 2015 – All rights reserved

ISO 14644-1:redline:2015(E)
Contents Page
Foreword .iv
Introduction .vi
1 Scope . 1
2 Normative references . 1
2 3 Definitions Terms and definitions . 1
2.1 3.1 General . 2
2.2 3.2 Airborne particles .3
2.3 Descriptors . 4
2.4 3.3 Occupancy states . 4
3.4 Testing instrumentation (see Annex F) . 5
2.5 3.5 Roles Instrument specifications . 5
3 4 Classification . 6
3.1 4.1 Occupancy state(s) . 6
4.2 Particle size(s) . 6
3.2 4.3 Classification ISO Class number . 6
3.3 4.4 Designation . 8
4.5 Intermediate decimal cleanliness classes and particle size thresholds . 8
4 5 Demonstration of compliance . 8
4.1 5.1 Principle . 8
4.2 5.2 Testing . 8
4.3 5.3 Airborne particle concentration limits evaluation . 9
4.4 5.4 Test report . 9
Annex A (informative) Graphical illustration of the classes of Table 1 .10
Annex B A (normative) Determination of particulate cleanliness classification using a
discrete-particle-counting, light-scattering instrument Reference method for
classification of air cleanliness by particle concentration .11
Annex C (normative) Statistical treatment of particle concentration data .18
Annex D B (informative) Worked examples Examples of classification calculations .20
Annex E C (informative) Considerations for the counting Counting and sizing of particles
outside the size range applicable for classification airborne macroparticles .34
Annex F D (informative) Sequential sampling procedure .40
Annex E (informative) Specification of intermediate decimal cleanliness classes and
particle size thresholds .49
Annex F (informative) Test instruments .51
Bibliography .52
ISO 14644-1:redline:2015(E)
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work of preparing International Standards is normally carried out
through ISO technical committees. Each member body interested in a subject for which a technical
committee has been established has the right to be represented on that committee. International
organizations, governmental and nongovernmentalnon-governmental, in liaison with ISO, also take
part in the work. ISO collaborates closely with the International Electrotechnical Commission (IEC) on
all matters of electrotechnical standardization.
The procedures used to develop this document and those intended for its further maintenance are
described in the ISO/IEC Directives, Part 1. In particular the different approval criteria needed for the
different types of ISO documents should be noted. This document was drafted in accordance with the
editorial rules of the ISO/IEC Directives, Part 2 (see www.iso.org/directives).
Draft International Standards adopted by the technical committees are circulated to the member bodies
for voting. Publication as an International Standard requires approval by at least 75% of the member
bodies casting a voteAttention is drawn to the possibility that some of the elements of this document
may be the subject of patent rights. ISO shall not be held responsible for identifying any or all such patent
rights. Details of any patent rights identified during the development of the document will be in the
Introduction and/or on the ISO list of patent declarations received (see www.iso.org/patents).
Any trade name used in this document is information given for the convenience of users and does not
constitute an endorsement.
For an explanation on the meaning of ISO specific terms and expressions related to conformity
assessment, as well as information about ISO’s adherence to the WTO principles in the Technical Barriers
to Trade (TBT) see the following URL: Foreword - Supplementary information
International Standard ISO 14644-1 was prepared by Technical CommitteeThe committee responsible
for this document is ISO/TC 209, Cleanrooms and associated controlled environments.
This second edition cancels and replaces the first edition (ISO 14644-1:1999), which has been technically
revised throughout.
ISO 14644 consists of the following parts, under the general title Cleanrooms and associated controlled
environments:
— Part 1: Classification of air cleanliness by particle concentration
— Part 2: Specifications for testing and monitoring to prove continued compliance withMonitoring
to provide evidence of cleanroom performance related to  ISO 14644-1 air cleanliness by particle
concentration
— Part 3: Metrology and testTest methods
— Part 4: Design, construction and start-up
— Part 5: Operations
— Part 6: Terms and definitions7: Separative devices (clean air hoods, gloveboxes, isolators and mini-
environments)
— Part 7: Enhanced clean devices8: Classification of air cleanliness by chemical concentration (ACC)
— Part 9: Classification of surface cleanliness by particle concentration
— Part 10: Classification of surface cleanliness by chemical concentration
iv © ISO 2015 – All rights reserved

ISO 14644-1:redline:2015(E)
Users should note that the titles listed for parts 2 to 7 are working titles at the time of the release of part
1. In the event that one or more of these parts are deleted from the work programme, the remaining
parts may be renumbered.
Annexes B and C form an integral part of this part ofAttention is also drawn to ISO 1464414698. Annexes A, D,
E, Cleanrooms and F are for information only.associated controlled environments — Biocontamination control:
— Part 1: General principles and methods
— Part 2: Evaluation and interpretation of biocontamination data
ISO 14644-1:redline:2015(E)
Introduction
Cleanrooms and associated controlled environments provide for the control of airborne particulate
contaminationcontamination of air and, if appropriate, surfaces, to levels appropriate for accomplishing
contamination-sensitive activities. Products and processes that benefit from the control of airborne
contamination include those in such industriesContamination control can be beneficial for protection
of product or process integrity in applications in industries such as aerospace, microelectronics,
pharmaceuticals, medical devices, food, and healthcarehealthcare and food.
This part of ISO 14644 assigns ISO classification levels to be used for the specificationspecifies classes of
air cleanliness in cleanrooms and associated controlled environmentsterms of the number of particles
expressed as a concentration in air volume. It also prescribesspecifies the standard method of testing as
well as the procedure for determining the concentration of airborne particlesto determine cleanliness
class, including selection of sampling locations.
This edition is the result of a response to an ISO Systematic Review and includes changes in response to
user and expert feedback validated by international enquiry. The title has been revised to “Classification
of air cleanliness by particle concentration” to be consistent with other parts of ISO 14644. The nine
ISO cleanliness classes are retained with minor revisions. Table 1 defines the particle concentration at
various particle sizes for the nine integer classes. Table E.1 defines the maximum particle concentration
at various particle sizes for intermediate classes. The use of these tables ensures better definition
of the appropriate particle-size ranges for the different classes. This part of ISO 14644 retains the
macroparticle descriptor concept; however, consideration of nano-scale particles (formerly defined as
ultrafine particles) will be addressed in a separate standard.
The most significant change is the adoption of a more consistent statistical approach to the selection
and the number of sampling locations; and the evaluation of the data collected. The statistical model
is based on adaptation of the hypergeometric sampling model technique, where samples are drawn
randomly without replacement from a finite population. The new approach allows each location to be
treated independently with at least a 95 % level of confidence that at least 90 % of the cleanroom or
clean zone areas will comply with the maximum particle concentration limit for the target class of air
cleanliness. No assumptions are made regarding the distribution of the actual particle counts over the
area of the cleanroom or clean zone; while in ISO 14644-1:1999 an underlying assumption was that the
particle counts follow the same normal distribution across the room, this assumption has now been
discarded to allow the sampling to be used in rooms where the particle counts vary in a more complex
manner. In the process of revision it has been recognized that the 95 % UCL was neither appropriate nor
was applied consistently in ISO 14644-1:1999. The minimum number of sampling locations required has
been changed, compared with ISO 14644-1:1999. A reference table, Table A.1, is provided to define the
minimum number of sampling locations required based on a practical adaptation of the sampling model
technique. An assumption is made that the area immediately surrounding each sampling location has a
homogeneous particle concentration. The cleanroom or clean zone area is divided up into a grid of sections
of near equal area, whose number is equal to the number of sampling locations derived from Table A.1. A
sampling location is placed within each grid section, so as to be representative of that grid section.
It is assumed for practical purposes that the locations are chosen representatively; a “representative”
location (see A.4.2) means that features such as cleanroom or clean zone layout, equipment disposition
and airflow systems should be considered when selecting sampling locations. Additional sampling
locations may be added to the minimum number of sampling locations.
Finally, the annexes have been reordered to improve the logic of this part of ISO 14644 and portions
of the content of certain annexes concerning testing and test instruments have been included from
ISO 14644-3:2005.
For classification purposes,The revised version of this part of ISO 14644 is limited to a designated range
of considered particle sizes for determination of particle concentration limits. This part of addresses the
≥ 5 µm particle limitsISO 14644 also provides standard protocols for the determination and designation
of cleanliness levels that are based on airborne concentrations of particles smaller or larger than the
size range designated for classificationfor ISO Class 5 in the sterile products annexes of the EU, PIC/S
and WHO GMPs by way of an adaptation of the macroparticle concept.
vi © ISO 2015 – All rights reserved

ISO 14644-1:redline:2015(E)
ThisThe revised version of this part of ISO 14644 is one of a series of standards concerned with
cleanrooms and contamination control. Many factors besides airborne particulate cleanliness must
be considered in the design, specification, operation, and control of cleanrooms and other controlled
environments. These are covered in some detail in other parts ofnow includes all matters related to
classification of air cleanliness by particle concentration. The revised version of ISO 14644-2:2015the
International Standards prepared by ISO/TC 209 now deals exclusively with the monitoring of air
cleanliness by particle concentration.
In some circumstances, relevant regulatory agencies may impose supplementary policies or
restrictions. In such situations, appropriate adaptations of the standard testing procedures may be
requiredCleanrooms may also be characterized by attributes in addition to the classification of air
cleanliness by particle concentration. Other attributes, such as air cleanliness in terms of chemical
concentration, may be monitored and the attribute’s grade or level may be designated along with the
classification of the ISO Class of cleanliness. These additional attributes do not suffice alone to classify
a cleanroom or clean zone.
INTERNATIONAL STANDARD ISO 14644-1:redline:2015(E)
Cleanrooms and associated controlled environments —
Part 1:
Classification of air cleanliness by particle concentration
1 Scope
This part of ISO 14644 specifies the classification of air cleanliness in terms of concentration of airborne
particles in cleanrooms and clean zones; and separative devices as defined in ISO 14644-7.
This part of ISO 14644 covers the classification of air cleanliness in cleanrooms and associated controlled
environments exclusively in terms of concentration of airborne particles. Only particle populations
having cumulative distributions based on threshold (lower limit) particle sizes ranging from 0,1 µm to
5 µm are considered for classification purposes.
The use of light scattering (discrete) airborne particle counters (LSAPC) is the basis for determination
of the concentration of airborne particles, equal to and greater than the specified sizes, at designated
sampling locations.
This part of ISO 14644 does not provide for classification of particle populations that are outside of
the specified lower threshold particle -size range, 0,1 µm to 5 µm. Concentrations of ultrafine particles
(particles smaller than 0,1 µm) and macroparticles (particles larger than 5 µm) may be used to quantify
these populations in terms of U descriptors and M descriptors, respectivelywill be addressed in a
separate standard to specify air cleanliness by nano-scale particles. An M descriptor (see Annex C) may
be used to quantify populations of macroparticles (particles larger than 5 µm).
This part of ISO 14644 cannot be used to characterize the physical, chemical, radiological, viable or
viableother nature of airborne particles.
NOTE The actual distribution of particle concentrations within incremental size ranges normally is not
predictable and typically is variable over time.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
ISO 14644-2:2015, Cleanrooms and associated controlled environments — Part 2: Monitoring to provide
evidence of cleanroom performance related to air cleanliness by particle concentration
ISO 14644-7, Cleanrooms and associated controlled environments — Part 7: Separative devices (clean air
hoods, gloveboxes, isolators and mini-environments)
2 3 Definitions Terms and definitions
For the purposes of this part of ISO 14644document, the following terms and definitions apply.
ISO 14644-1:redline:2015(E)
2.1 3.1 General
2.1.1 3.1.1
cleanroom
room in within which the number concentration of airborne particles is controlled and classified, and
which is designed, constructed and used operated in a manner to minimize control the introduction,
generation and retention of particles inside the room, and in which other relevant parameters, e.g.
temperature, humidity, and pressure, are controlled as necessary
Note 1 to entry: The class of airborne particle concentration is specified.
Note 2 to entry: Levels of other cleanliness attributes such as chemical, viable or nanoscale concentrations in the
air, and also surface cleanliness in terms of particle, nanoscale, chemical and viable concentrations might also be
specified and controlled.
Note 3 to entry: Other relevant physical parameters might also be controlled as required, e.g. temperature,
humidity, pressure, vibration and electrostatic.
2.1.2 3.1.2
clean zone
dedicated space in defined space within which the number concentration of airborne particles is
controlled and classified, and which is constructed and used operated in a manner to minimize control the
introduction, generation and retention of particles inside the zone, and in which other relevant parameters,
e.g. temperature, humidity, and pressure, are controlled as necessary contaminants inside the space
Note 1 to entry: The class of airborne particle concentration is specified.
Note 2 to entry: Levels of other cleanliness attributes such as chemical, viable or nanoscale concentrations in the
air, and also surface cleanliness in terms of particle, nanoscale, chemical and viable concentrations might also be
specified and controlled.
Note 3 to entry: This zone may be open or enclosed and may or may not be located within A clean zone(s) can be a
defined space within a cleanroom or might be achieved by a separative device. Such a device can be located inside
or outside a cleanroom.
Note 4 to entry: Other relevant physical parameters might also be controlled as required, e.g. temperature,
humidity, pressure, vibration and electrostatic.
2.1.3 3.1.3
installation
cleanroom or one or more clean zones, together with all associated structures, air-treatment systems,
services and utilities
2.1.4 3.1.4
classification
level (or the process of specifying or determining the level) of airborne particulate cleanliness applicable
to method of assessing level of cleanliness against a specification for a cleanroom or clean zone, expressed
in terms of an ISO Class  N, which represents maximum allowable concentrations (in particles per cubic
metre of air) for considered sizes of particles
Note 1 to entry: The concentrations are determined by using equation (1) in 3.2.
Note 2 to entry: Classification in accordance with this International Standard is limited to the range extending
from ISO Class 1 through ISO Class 9.
Note 1 to entry: The considered particle sizes (lower threshold values) applicable for classification in accordance
with this International Standard are limited to the range from 0,1 µm through 5 µm. Air cleanliness may be
described and specified (but not classified) Levels should be expressed in terms of U descriptors or M descriptors
(see  2.3.1 or  2.3.2) for considered threshold particle sizes that are outside of the range covered by classification an
ISO Class, which represents maximum allowable concentrations of particles in a unit volume of air.
Note 4 to entry: Intermediate ISO classification numbers may be specified, with 0,1 the smallest permitted
increment; i.e., the range of intermediate ISO classes extends from ISO Class 1,1 through ISO Class 8,9.
2 © ISO 2015 – All rights reserved

ISO 14644-1:redline:2015(E)
Note 5 to entry: Classification may be specified or accomplished in any of three occupancy states (see 2.4).
2.2 3.2 Airborne particles
2.2.1 3.2.1
particle
solid or liquid object which, for purposes of classification of air cleanliness, falls within a cumulative
distribution that is based upon a threshold (lower limit) size in the range from 0,1 µm to 5 µm minute
piece of matter with defined physical boundaries
2.2.2 3.2.2
particle size
diameter of a sphere that produces a response, by a given particle-sizing instrument, that is equivalent
to the response produced by the particle being measured
Note 1 to entry: For discrete-particle-counting,  light-scattering instruments, the equivalent optical diameter is used.
2.2.3 3.2.3
particle concentration
number of individual particles per unit volume of air
2.2.4 3.2.4
particle size distribution
cumulative distribution of particle concentration as a function of particle size
2.2.5
ultrafine particle
particle with an equivalent diameter less than 0,1 µm
2.2.6 3.2.5
macroparticle
particle with an equivalent diameter greater than 5 µm
3.2.6
M descriptor
designation for measured or specified concentration of macroparticles per cubic metre of air, expressed
in terms of the equivalent diameter that is characteristic of the measurement method used
Note 1 to entry: The M descriptor can be regarded as an upper limit for the averages at sampling locations.
M descriptors cannot be used to define ISO Classes, but the M descriptor may be quoted independently or in
conjunction with ISO Classes.
2.2.7 3.2.7
fibre unidirectional airflow
particle having an aspect (length-to-width) ratio of 10 or more controlled airflow through the entire
cross-section of a cleanroom or a clean zone with a steady velocity and airstreams that are considered
to be parallel
3.2.8
non-undirectional airflow
air distribution where the supply air entering the cleanroom or clean zone mixes with the internal air
by means of induction
ISO 14644-1:redline:2015(E)
2.3 Descriptors
2.3.1
U descriptor
measured or specified concentration, of particles per cubic metre of air, including the ultrafine particles
Note 1 to entry: The U descriptor may be regarded as an upper limit for the averages at sampling locations (or as
an upper confidence limit, depending upon the number of sampling locations used to characterize the cleanroom
or clean zone). U descriptors cannot be used to define airborne particulate cleanliness classes, but they may be
quoted independently or in conjunction with airborne particulate cleanliness classes.
2.3.2
M descriptor
measured or specified concentration of macroparticles per cubic metre of air, expressed in terms of the
equivalent diameter that is characteristic of the measurement method used
Note 1 to entry: The M descriptor may be regarded as an upper limit for the averages at sampling locations (or as
an upper confidence limit, depending upon the number of sampling locations used to characterize the cleanroom
or clean zone). M descriptors cannot be used to define airborne particulate cleanliness classes, but they may be
quoted independently or in conjunction with airborne particulate cleanliness classes.
2.4 3.3 Occupancy states
2.4.1 3.3.1
as-built
condition where the installation cleanroom or clean zone is complete with all services connected and
functioning but with no production  equipment, materials furniture, materials or personnel present
2.4.2 3.3.2
at-rest
condition where the installation cleanroom or clean zone is complete with equipment installed and
operating in a manner agreed upon by the customer and supplier , but with no personnel present
2.4.3 3.3.3
operational
agreed condition where the installation cleanroom or clean zone is functioning in the specified manner,
with equipment operating and with the specified number of personnel present and working in the
manner agreed upon
4 © ISO 2015 – All rights reserved

ISO 14644-1:redline:2015(E)
Table 1 — Selected airborne particulate cleanliness classes for cleanrooms and clean zones
ISO classifica- Maximum concentration limits (particles/m of air) for particles equal to and larger
tion number than the considered sizes shown below (concentration limits are calculated in
(N) accordance with equation (1) in 3.2)
0,1 µm 0,2 µm 0,3 µm 0,5 µm 1 µm 5 µm
ISO Class 1 10 2
ISO Class 2 100 24 10 4
ISO Class 3 1 000 237 102 35 8
ISO Class 4 10 000 2 370 1 020 352 83
ISO Class 5 100 000 23 700 10 200 3 520 832 29
ISO Class 6 1 000 000 237 000 102 000 35 200 8 320 293
ISO Class 7 352 000 83 200 2 930
ISO Class 8 3 520 000 832 000 29 300
ISO Class 9 35 200 000 8 320 000 293 000
NOTE Uncertainties related to the measurement process require that concentration data with no more than three
significant figures be used in determining the classification level
3.4 Testing instrumentation (see Annex F)
3.4.1
resolution
smallest change in a quantity being measured that causes a perceptible change in the corresponding
indication
Note 1 to entry: Resolution can depend on, for example, noise (internal or external) or friction. It may also depend
on the value of a quantity being measured.
[SOURCE: ISO/IEC Guide 99:2007, 4.14]
3.4.2
maximum permissible measurement error
extreme value of measurement error, with respect to a known reference quantity value, permitted by
specifications or regulations for a given measurement, measuring instrument, or measuring system
Note 1 to entry: Usually, the term “maximum permissible errors” or “limits of error” is used where there are two
extreme values.
Note 2 to entry: The term “tolerance” should not be used to designate “maximum permissible error”.
[SOURCE: ISO/IEC Guide 99:2007, 4.26]
2.5 3.5 Roles Instrument specifications
2.5.1 3.5.1
customer  LSAPC
light scattering airborne particle counter
light scattering discrete airborne particle counter
organization, or the agent thereof, responsible for specifying the requirements of a cleanroom or clean
zone instrument capable of counting and sizing single airborne particles and reporting size data in terms
of equivalent optical diameter
Note 1 to entry: The specifications for the LSAPC are given in ISO 21501-4:2007.
ISO 14644-1:redline:2015(E)
3.5.2
discrete-macroparticle counter
instrument capable of counting and sizing single airborne macroparticles
Note 1 to entry: See Table F.1 for specifications.
2.5.2 3.5.3
supplier time-of-flight particle sizing apparatus
organization engaged to satisfy the specified requirements of a cleanroom or clean zone discrete-
particle counting and sizing apparatus that defines the aerodynamic diameter of particles by measuring
the time for a particle to accommodate to a change in air velocity
Note 1 to entry: This is usually done by measuring the particle transit time optically after a fluid stream
velocity change.
Note 2 to entry: See Table F.2 for specifications.
3 4 Classification
3.1 4.1 Occupancy state(s)
The particulate cleanlinessair cleanliness class by particle concentration of air in a cleanroom or clean
zone shall be defined in one or more of three occupancy states, viz. “as-built”,” “at-rest” or “operational”
(see 2.43.3).
NOTE It should be recognized that the “as-built” state is applicable to newly completed or newly modified
cleanrooms or clean zones. Once testing in the “as-built” state is completed, further testing for compliance will be
performed in the “at-rest” or the “operational” state, or both.
4.2 Particle size(s)
One, or more than one, threshold (lower limit) particle sizes situated within the range from ≥0,1 µm to
≥5 µm are to be used to determine air cleanliness particle concentration for classification.
3.2 4.3 Classification ISO Class number
Airborne particulate cleanlinessAir cleanliness class by particle concentration shall be designated by
a classificationan ISO Class number, N. The maximum permitted concentration of particles, C for each
n
considered particle size, D is determined from the equation:Table 1.
(1)
Particle number concentrations for different threshold sizes in Table 1 do not reflect actual particle size
and number distribution in the air and serve as criteria for classification only. Examples of classification
calculations are included in Annex B.
6 © ISO 2015 – All rights reserved

ISO 14644-1:redline:2015(E)
where
C is the maximum permitted concentration (in particles per
n
cubic metre of air) of airborne particles that are equal to
or larger than the considered particle size. C is rounded
n
to the nearest whole number, using no more than three
significant figures.
N is the ISO classification number, which shall not exceed a
value of 9. Intermediate ISO classification numbers may be
specified, with 0,1 the smallest permitted increment of N.
D is the considered particle size, in micrometres.
0,1 is a constant, with a dimension of micrometres.
Table 1 — ISO Classes of air cleanliness by particle concentration
ISO Class number Maximum allowable concentrations (particles/m ) for particles equal to and greater
a
(N) than the considered sizes, shown below
0,1 µm 0,2 µm 0,3 µm 0,5 µm 1 µm 5 µm
b d d d d e
1 10
b b d d e
2 100 24 10
b d e
3 1 000 237 102 35
b e
4 10 000 2 370 1 020 352 83
d, e, f
5 100 000 23 700 10 200 3 520 832
6 1 000 000 237 000 102 000 35 200 8 320 293
c c c
7 352 000 83 200 2 930
c c c
8 3 520 000 832 000 29 300
g c c c
9 35 200 000 8 320 000 293 000
a
All concentrations in the table are cumulative, e.g. for ISO Class 5, the 10 200 particles shown at 0,3 µm include all
particles equal to and greater than this size.
b
These concentrations will lead to large air sample volumes for classification. Sequential sampling procedure may be
applied; see Annex D.
c
Concentration limits are not applicable in this region of the table due to very high particle concentration.
d
Sampling and statistical limitations for particles in low concentrations make classification inappropriate.
e
Sample collection limitations for both particles in low concentrations and sizes greater than 1 μm make classification
at this particle size inappropriate, due to potential particle losses in the sampling system.
f
In order to specify this particle size in association with ISO Class 5, the macroparticle descriptor M may be adapted and
used in conjunction with at least one other particle size. (See C.7.)
g
This class is only applicable for the in-operation state.
Table 1 presents selected airborne particulate cleanliness classes and the corresponding particle
concentrations for particles equal to and larger than the considered sizes shown. Figure A.1 (see annex A)
provides a representation of the selected classes in graphical form. In case of dispute, the concentration
C as derived from equation (1) shall serve as the standard value.
n
ISO 14644-1:redline:2015(E)
3.3 4.4 Designation
The designation of airborne particulate cleanliness for clean-roomsparticle concentration for cleanrooms
and clean zones shall include:
a) the classificationISO Class number, expressed as “ISO Class N”;,
b) the occupancy state to which the classification applies;, and
c) the considered particle size(s), and the related concentration(s), as determined by the classification
equation (1) where each considered threshold particle size is in the range from 0,1 µm through 5 µm.
Example designation:
ISO Class 4; operational state; considered sizes:
3 3
0,2 µm (2 370 particles/m), 1 µm (83 particles/m )
The considered particle size(s) for which the concentration(s) will be measured shall be agreed upon by
the customer and the supplier.
If measurements are to be made at more than one considered particle size, each larger particle diameter
(e.g., D2) shall be at least 1,5 times the next smaller particle diameter (e.g. D1), i.e. D2 ≥ 1,5 × D1).
EXAMPLE ISO Class number; occupancy state; considered particle size(s)
ISO Class 4; at rest; 0,2 µm, 0,5 µm
e.g.:
D ≥ 1,5 × D
2 1
4.5 Intermediate decimal cleanliness classes and particle size thresholds
Where intermediate classes, or intermediate particle size thresholds for integer and intermediate
classes are required, refer to informative Annex E.
4 5 Demonstration of compliance
4.1 5.1 Principle
Compliance with air cleanliness (ISO Class) requirements specified by the customer is verified by
performing specified testing procedures and by providing specified documentation of the results and
conditions of testing, as agreed upon by the customer and the supplier.
At-rest or operational classification may be performed periodically based upon risk assessment of the
application, typically on an annual basis.
For monitoring cleanrooms, clean zones and separative devices, ISO 14644-2:2015 shall be used.
NOTE Where the installation is equipped with instrumentation for continuous or frequent monitoring of air
cleanliness by particle concentration and other parameters of performance as applicable, the time intervals between
classification may be extended provided that the results of the monitoring remain within the specified limits.
4.2 5.2 Testing
The reference test method for demonstrating compliance is given in annex BAnnex A. An alternative
method having comparable accuracy (normative). Alternative methods or instrumentation (or both),
having at least comparable performance, may be specified, although if no method. If no alternative is
specified or agreed upon, the reference method shall be used.
Tests performed to demonstrate compliance shall be conducted using calibrated instrumentsinstruments
which are in compliance with calibration requirements at the time of testing.
8 © ISO 2015 – All rights reserved

ISO 14644-1:redline:2015(E)
4.3 5.3 Airborne particle concentration limits evaluation
Upon completion of testing in accordance with 4.2, average particle concentrations and the 95% upper
confidence limit (when applicable) shall be calculated using equations shown in annex C.
Average particle concentration(s), calculatedUpon completion of testing in accordance with equation (C.1)
Annex A, the concentration of particles (expressed as number of particles per cubic metre) in a single
sample volume at each sampling location shall not exceed the concentration limit(s) determined by use of
equation (1)given in 3.2Table 1, as specified [3.3 c)] or Table E.1 for intermediate decimal classes for the
considered size(s). If multiple single sample volumes are taken at a sampling location, the concentrations
shall be averaged and the average concentration must not exceed the concentration limits given in
Table 1 or Table E 1. Intermediate particle sizes shall be derived from Formula (E.1).
In addition, for situations in which the number of sampling locations involved is at least two but not
more than nine, the calculation of 95% upper confidence limits in accordance with C.3 shall not exceed
the concentration limits established above.
NOTE Worked examples of classification calculations are provided in annex D.
Particle concentrations used for determination of conformance to classification limitscompliance with
ISO Classes shall be measured by the same method for all considered particle sizes.
4.4 5.4 Test report
The results from testing each cleanroom or clean zone shall be recorded and submitted as a
comprehensive report, along with a statement of compliance or noncompliancenon-compliance with the
specified designation of airborne particulate cleanliness classificationair cleanliness class by particle
concentration.
The test report shall include the following:
a) the name and address of the testing organization, and the date on which the test was performed;,
b) the number and year of publication of this part of ISO 14644, i.e. ISO 14644-1:2015: date of current issue;,
c) a clear identification of the physical location of the clean-roomcleanroom or clean zone tested
(including reference to adjacent areas if necessary), and specific designations for coordinates of all
sampling locations; (a diagrammatic representation can be helpful),
d) the specified designation criteria for the cleanroom or clean zone, including the ISO classificationClass
number, the relevant occupancy state(s), and the considered particle size(s);,
e) details of the test method used, with any special conditions relating to the test, or departures from
the test method, and identification of the test instrument and its current calibration certificate;, and
f) the test results, including particle concentration data for all sampling location coordinateslocations.
NOTE If concentrations of ultrafine particles or macroparticles are quantified, as described in annex E, the
pertinent information should be included with the test report.
If concentrations of macroparticles are quantified, as described in Annex C, the relevant information
should be included with the test report.
ISO 14644-1:redline:2015(E)
Annex A
(informative)
Graphical illustration of the classes of Table 1
Figure A.1 depicts the air cleanliness classes of Table 1 in graphical form, for illustration purposes
only. The ISO classes of Table 1 are shown as lines representing the class concentration limits for the
considered threshold particle sizes. They are based on calculations using equation (1) of 3.2 As the lines
only approximate the class limits, they are not to be used to define the limits. Such determinations are
made in accordance with equation (1).
The classification lines shown on the graph may not be extrapolated beyond the solid circle symbols, which
indicate the minimum and maximum particle size limits acceptable for each of the ISO classes shown.
The classification lines do not represent actual particle size distributions found in cleanrooms and clean
zones.
Figure A.1 — Graphical representation of ISO-class concentration limits for selected ISO classes
NOTE 1 C represents the maximum permitted concentration (in particles per cubic metre of air) of airborne
n
particles equal to and larger than the considered particle size.
NOTE 2 N represents the specified ISO class number.
10 © ISO 2015 – All rights reserved

ISO 14644-1:redline:2015(E)
Annex B A
(normative)
Determination of particulate cleanliness classification using a
discrete-particle-counting, light-scattering instrument Reference
method for classification of air cleanliness by particle
concentration
B A.1 Principle
A discrete-particle-counting, light-scattering instrument is used to determine the concentration of
airborne particles, equal to and largergreater tha
...


PROJET DE NORME INTERNATIONALE ISO/DIS 14644-1
ISO/TC 209 Secrétariat: ANSI
Début de vote Vote clos le
2010-12-02 2011-05-02
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION  •  МЕЖДУНАРОДНАЯ ОРГАНИЗАЦИЯ ПО СТАНДАРТИЗАЦИИ  •  ORGANISATION INTERNATIONALE DE NORMALISATION

Salles propres et environnements maîtrisés apparentés —
Partie 1:
Classification de la propreté particulaire de l'air
Cleanrooms and associated controlled environments —
Part 1: Classification of air cleanliness by particle concentration
[Révision de la première édition (ISO 14644-1:1999)]
ICS 13.040.35
TRAITEMENT PARALLÈLE ISO/CEN
Le présent projet a été élaboré dans le cadre de l'Organisation internationale de normalisation (ISO) et
soumis selon le mode de collaboration sous la direction de l'ISO, tel que défini dans l'Accord de
Vienne.
Le projet est par conséquent soumis en parallèle aux comités membres de l'ISO et aux comités
membres du CEN pour enquête de cinq mois.
En cas d'acceptation de ce projet, un projet final, établi sur la base des observations reçues, sera
soumis en parallèle à un vote d'approbation de deux mois au sein de l'ISO et à un vote formel au sein
du CEN.
Pour accélérer la distribution, le présent document est distribué tel qu'il est parvenu du
secrétariat du comité. Le travail de rédaction et de composition de texte sera effectué au
Secrétariat central de l'ISO au stade de publication.
To expedite distribution, this document is circulated as received from the committee
secretariat. ISO Central Secretariat work of editing and text composition will be undertaken at
publication stage.
CE DOCUMENT EST UN PROJET DIFFUSÉ POUR OBSERVATIONS ET APPROBATION. IL EST DONC SUSCEPTIBLE DE MODIFICATION ET NE
PEUT ETRE CITE COMME NORME INTERNATIONALE AVANT SA PUBLICATION EN TANT QUE TELLE.
OUTRE LE FAIT D'ETRE EXAMINES POUR ETABLIR S'ILS SONT ACCEPTABLES A DES FINS INDUSTRIELLES, TECHNOLOGIQUES ET
COMMERCIALES, AINSI QUE DU POINT DE VUE DES UTILISATEURS, LES PROJETS DE NORMES INTERNATIONALES DOIVENT PARFOIS ETRE
CONSIDERES DU POINT DE VUE DE LEUR POSSIBILITE DE DEVENIR DES NORMES POUVANT SERVIR DE REFERENCE DANS LA
REGLEMENTATION NATIONALE.
LES DESTINATAIRES DU PRÉSENT PROJET SONT INVITÉS À PRÉSENTER, AVEC LEURS OBSERVATIONS, NOTIFICATION DES DROITS DE PRO-
PRIÉTÉ DONT ILS AURAIENT ÉVENTUELLEMENT CONNAISSANCE ET À FOURNIR UNE DOCUMENTATION EXPLICATIVE.
©  Organisation Internationale de Normalisation, 2010

ISO/DIS 14644-1
PDF – Exonération de responsabilité
Le présent fichier PDF peut contenir des polices de caractères intégrées. Conformément aux conditions de licence d'Adobe, ce
fichier peut être imprimé ou visualisé, mais ne doit pas être modifié à moins que l'ordinateur employé à cet effet ne bénéficie d'une
licence autorisant l'utilisation de ces polices et que celles-ci y soient installées. Lors du téléchargement de ce fichier, les parties
concernées acceptent de fait la responsabilité de ne pas enfreindre les conditions de licence d'Adobe. Le Secrétariat central de l'ISO
décline toute responsabilité en la matière.
Adobe est une marque déposée d'Adobe Systems Incorporated.
Les détails relatifs aux produits logiciels utilisés pour la création du présent fichier PDF sont disponibles dans la rubrique General
Info du fichier; les paramètres de création PDF ont été optimisés pour l'impression. Toutes les mesures ont été prises pour garantir
l'exploitation de ce fichier par les comités membres de l'ISO. Dans le cas peu probable où surviendrait un problème d'utilisation,
veuillez en informer le Secrétariat central à l'adresse donnée ci-dessous.

Notice de droit d'auteur
Ce document de l'ISO est un projet de Norme internationale qui est protégé par les droits d'auteur de l'ISO.
Sauf autorisé par les lois en matière de droits d'auteur du pays utilisateur, aucune partie de ce projet ISO ne
peut être reproduite, enregistrée dans un système d'extraction ou transmise sous quelque forme que ce soit
et par aucun procédé électronique ou mécanique, y compris la photocopie, les enregistrements ou autres,
sans autorisation écrite préalable.
Les demandes d'autorisation de reproduction doivent être envoyées à l'ISO à l'adresse ci-après ou au
comité membre de l'ISO dans le pays du demandeur.
ISO copyright office
Case postale 56 • CH-1211 Geneva 20
Tel. + 41 22 749 01 11
Fax + 41 22 749 09 47
E-mail copyright@iso.org
Web www.iso.org
Toute reproduction est soumise au paiement de droits ou à un contrat de licence.
Les contrevenants pourront être poursuivis.

ii © ISO 2010 – Tous droits réservés

ISO/DIS 14644-1
Sommaire Page
Avant-propos .iv
Introduction.vi
1 Domaine d’application .1
2 Références normatives.1
3 Termes et définitions .1
3.1 Généralités .1
3.2 Particules en suspension dans l'air .2
3.3 Descripteurs.3
3.4 États d’occupation .3
3.5 Intervenants .3
4 Classification .4
4.1 État(s) d'occupation .4
4.2 Numéro de classification.4
4.3 Expression de la classification.5
5 Démonstration de conformité .5
5.1 Principe .5
5.2 Essais .6
5.3 Évaluation de la concentration particulaire dans l’air.6
5.4 Rapport d’essai.6
Annexe A (normative)  Méthode de référence pour déterminer la classe de propreté particulaire
de l’air .7
Annexe B (informative) Exemples d’application de calculs de classes .12
Annexe C (informative)  Indications sur le comptage et le mesurage des tailles particulaires
situées à l'extérieur de l'étendue granulométrique fixée par la classification.19
Annexe D (informative) Procédure de prélèvement séquentiel.21
Annexe E (informative) Illustration des classes de propreté ISO .30

ISO/DIS 14644-1
Avant-propos
Cette version révisée est le résultat d’un examen systématique, et inclut un certain nombre de modifications
suite au retour d’expériences des utilisateurs et des experts, qui sera validée par une enquête internationale.
Le titre a été modifié en « Classification de la propreté particulaire de l’air » afin d’être conforme aux autres
parties de la norme. Les classes ISO au nombre de neuf restent inchangées, mais le Tableau 1 définit
désormais les concentrations particulaires aux différentes tailles pour ces 9 classes au nombre entier (ISO 1,
ISO 2…). L’utilisation du Tableau 1 garantit que la norme définit désormais de façon plus pertinente les tailles
de particules appropriées pour les différentes classes. Une formule est conservée pour permettre l’élaboration
des classes au nombre décimal. La norme conserve le principe des descripteurs des particules ultrafines et
des macroparticules en dehors de l’intervalle adapté au mesurage par les compteurs de particules en
suspension dans l’air.
L’évolution la plus importante est le recours systématique à un même traitement statistique pour déterminer le
nombre de points de prélèvement et analyser les données brutes. Ce qui précède entraine la modification du
nombre de points de prélèvement comparativement à la version de 1999 de la norme. Cette approche prévoit
d’examiner individuellement chaque point de prélèvement ; ceci, afin de vérifier avec un niveau de confiance à
95 %, qu’au moins 90 % de la surface de la salle ou de la zone propre est conforme à la concentration
maximale admissible pour la classe visée. Le nombre de points de prélèvement en fonction de la surface de
la salle ou de la zone considérée est indiqué dans un tableau de référence. Du fait qu’un degré de
randomisation est requis, la salle ou la zone propre est alors divisée en secteurs égaux et l’emplacement du
prélèvement est situé de manière aléatoire à l’intérieur de chaque secteur.
Enfin, l’ordre des annexes a été réorganisé pour améliorer la compréhension de la norme.
L'ISO (Organisation internationale de normalisation) est une fédération mondiale d'organismes nationaux de
normalisation (comités membres de l'ISO). L'élaboration des Normes internationales est en général confiée
aux comités techniques de l'ISO. Chaque comité membre intéressé par une étude a le droit de faire partie du
comité technique créé à cet effet. Les organisations internationales, gouvernementales et non
gouvernementales, en liaison avec l'ISO participent également aux travaux. L'ISO collabore étroitement avec
la Commission électrotechnique internationale (CEI) en ce qui concerne la normalisation électrotechnique.
Les Normes internationales sont rédigées conformément aux règles données dans les Directives ISO/CEI,
Partie 2.
La tâche principale des comités techniques est d'élaborer les Normes internationales. Les projets de Normes
internationales adoptés par les comités techniques sont soumis aux comités membres pour vote. Leur
publication comme Normes internationales requiert l'approbation de 75 % au moins des comités membres
votants.
L'attention est appelée sur le fait que certains des éléments du présent document peuvent faire l'objet de
droits de propriété intellectuelle ou de droits analogues. L'ISO ne saurait être tenue pour responsable de ne
pas avoir identifié de tels droits de propriété et averti de leur existence.
L'ISO 14644-1 a été élaborée par le comité technique ISO/TC 209, Salles propres et environnements
maîtrisés apparentés, en collaboration avec le comité technique CEN/TC 243, Technologies pour la maîtrise
de la contamination.
Cette deuxième édition annule et remplace la première édition (ISO 14644-1:1999), qui a fait l’objet d’une
révision technique.
iv © ISO 2010 – Tous droits réservés

ISO/DIS 14644-1
L'ISO 14644 comprend les parties suivantes, présentées sous le titre général Salles propres et
environnements maîtrisés apparentés :
⎯ Partie 1 : Classification de la propreté particulaire de l’air
⎯ Partie 2 : Exigences pour la surveillance et les contrôles périodiques en vue de démontrer le maintien de
la conformité avec l'ISO 14644-1:XXXX
⎯ Partie 3 : Méthodes d'essai
⎯ Partie 4 : Conception, construction et mise en route
⎯ Partie 5 : Fonctionnement
⎯ Partie 6 : Vocabulaire
⎯ Partie 7 : Dispositifs séparatifs (postes à air propre, boîtes à gants, isolateurs et mini-environnements)
⎯ Partie 8 : Classification de la contamination moléculaire aéroportée
⎯ Partie 9 : Classification de la propreté particulaire des surfaces
L’attention de l’utilisateur est attirée sur l'ISO 14698, Salles propres et environnements maîtrisés apparentés -
Maîtrise de la biocontamination :
⎯ Partie 1 : Principes généraux et méthodes
⎯ Partie 2 : Évaluation et interprétation des données de biocontamination
ISO/DIS 14644-1
Introduction
Les salles propres et les environnements maîtrisés apparentés fournissent des moyens pour maîtriser la
contamination particulaire de l’air ou des surfaces à des niveaux appropriés pour les activités sensibles à la
contamination. La maîtrise de la contamination peut assurer la protection du produit ou l’ensemble du procédé
de fabrication pour des applications telles que l’industrie aérospatiale, la micro-électronique, l’industrie
pharmaceutique, les dispositifs médicaux et la santé.
La présente partie de l’ISO 14644 fixe des classes de propreté particulaire de l’air en termes de nombre de
particules par volume d’air. Elle fixe également la méthode normalisée d’essai afin de déterminer la
classification incluant la sélection des points de prélèvements, et l’obtention de la classe en fonction des
données brutes.
vi © ISO 2010 – Tous droits réservés

PROJET DE NORME INTERNATIONALE ISO/DIS 14644-1

Salles propres et environnements maîtrisés apparentés —
Partie 1:
Classification de la propreté particulaire de l'air
1 Domaine d’application
La présente partie de l'ISO 14644 couvre la classification de la propreté de l'air des salles propres et des
environnements maîtrisés apparentés exclusivement en termes de concentration des particules en
suspension dans l'air. Pour l'application de cette classification, on ne considère que les populations de
particules présentant une distribution cumulée dont le seuil inférieur de sensibilité se situe dans l’étendue
granulométrique de 0,1 µm à 5 µm.
La méthode de référence pour déterminer la concentration de particules dans l’air d’un diamètre supérieur ou
égal à la taille spécifiée aux points de prélèvement indiqués requiert l’utilisation de compteurs, capables de
dénombrer des particules individuelles par taille.
La présente partie de l’ISO 14644 ne donne pas la classification des populations de particules sortant de
l’étendue granulométrique de référence de 0,1 µm à 5 µm. Les concentrations de particules ultrafines (plus
petites que 0,1 µm) et de macroparticules (plus grandes que 5 µm) peuvent être utilisées pour quantifier ces
populations en terme de descripteurs U et M (voir 3.3.1 et 3.3.2), respectivement.
La présente partie de l’ISO 14644 n’est pas applicable pour caractériser la nature physique, chimique,
radiologique ou viable des particules en suspension dans l’air.
NOTE La distribution granulométrique réelle de particules par taille à l’intérieur de l’étendue de référence n'est pas
habituellement prévisible et est typiquement variable avec le temps.
2 Références normatives
Les documents de référence suivants sont indispensables pour l'application du présent document. Pour les
références datées, seule l'édition citée s'applique. Pour les références non datées, la dernière édition du
document de référence (y compris les éventuels amendements) s’applique.
ISO 21501-4 :2007, Détermination de la distribution granulométrique – Méthodes Détermination de la
distribution granulométrique – Méthodes d'interaction lumineuse de particules uniques – Compteur de
particules en suspension dans l'air en lumière dispersée pour espaces propres.
3 Termes et définitions
Pour les besoins de la présente partie de l’ISO 14644, les termes et définitions suivants s’appliquent.
3.1 Généralités
3.1.1
salle propre
salle dans laquelle la concentration des particules en suspension dans l'air est maîtrisée et qui est construite
et utilisée de façon à minimiser l'introduction, la production et la rétention des particules à l'intérieur de la
pièce, et dans laquelle d'autres paramètres pertinents, tels que la température, l'humidité et la pression sont
maîtrisés comme il convient
ISO/DIS 14644-1
3.1.2
zone propre
espace dédié dans lequel la concentration des particules en suspension dans l'air est maîtrisée et qui est
construit et utilisé de façon à minimiser l'introduction, la production et la rétention de particules à l’intérieur de
la pièce, et dans laquelle d'autres paramètres pertinents, tels que la température, l'humidité et la pression sont
maîtrisés comme il convient
NOTE Cet espace peut être clos ou ouvert, et peut ou non être situé à l'intérieur d'une salle propre.
3.1.3
classification
niveau de propreté particulaire de l’air applicable à une salle propre ou une zone propre ; il est exprimé en
termes de Classe ISO N, laquelle représente pour chaque taille de particule considérée, la concentration
maximale admissible par mètre cube d’air en particules de taille égale ou supérieure à celle considérée
NOTE 1 Les concentrations maximales admissibles sont définies dans le Tableau 1 du paragraphe 4.2 ou déterminées
par l’équation (1) en 4.2 si une classe en nombre décimal est requise.
NOTE 2 La classification selon la présente Norme internationale est limitée à l’étendue allant de la classe ISO 1 à la
classe ISO 9.
NOTE 3 Les tailles des particules prises en considération pour les besoins de la classification selon la présente norme
internationale sont limitées à une étendue granulométrique allant de ≥ 0,1 à ≤ 5 µm.
NOTE 4 La propreté de l’air peut être décrite et spécifiée, mais non classée en termes de descripteurs U ou M
(voir 3.3.1 ou 3.3.2) pour les tailles de particules en dehors de l’étendue granulométrique couverte par la classification.
NOTE 5 On peut spécifier des numéros de classification ISO en nombre décimal intermédiaires, pour lesquels
l’incrément le plus petit admissible sera de 0,1. Ainsi, la gamme des classes ISO en nombre décimal intermédiaires
s’étend de la classe ISO 1,1 à la classe ISO 8,9.
NOTE 6 La classification peut s’effectuer dans l’un quelconque des trois états d’occupation (voir 3.4).
3.2 Particules en suspension dans l'air
3.2.1
particule
objet minuscule de matière quelconque qui possède un périmètre physique défini
3.2.2
taille de particule
diamètre d'une sphère qui, dans un instrument donné de mesurage des tailles de particules, donne une
réponse qui est équivalente à la réponse de la particule à mesurer
NOTE Pour les instruments faisant appel aux caractéristiques de la diffusion de la lumière et capables de compter
les particules individuellement, on utilise le terme diamètre optique équivalent.
3.2.3
concentration particulaire
nombre de particules individuelles par unité de volume d’air
3.2.4
distribution granulométrique
distribution cumulée des concentrations de particules en fonction de leur taille
3.2.5
particule ultrafine
particule dont le diamètre équivalent est inférieur à 0,1 µm
2 © ISO 2010 – Tous droits réservés

ISO/DIS 14644-1
3.2.6
macroparticule
particule dont le diamètre équivalent est supérieur à 5 µm
3.2.7
flux d’air unidirectionnel
flux d’air maîtrisé traversant l’ensemble d’un plan de coupe d’une zone propre possédant une vitesse
régulière et des filets à peu près parallèle
NOTE Cette configuration d’écoulement de l’air a pour effet l’évacuation directe des particules de la zone propre.
3.3 Descripteurs
3.3.1
descripteur U
concentration, mesurée ou spécifiée, exprimée en particules par mètre cube d'air et comprenant les particules
ultrafines
NOTE Le descripteur U peut être considéré comme une limite supérieure des moyennes obtenues aux points de
prélèvement ou une limite supérieure de confiance, en fonction du nombre de ces points utilisés pour caractériser la salle
ou la zone propre. Un descripteur U ne peut servir à caractériser une classe de propreté particulaire de l’air, mais peut
être utilisé indépendamment ou conjointement à une classe de propreté particulaire de l'air.
3.3.2
descripteur M
concentration, mesurée ou spécifiée, des macroparticules par mètre cube d'air, exprimée en termes de
diamètre équivalent auquel accède la méthode de mesurage mise en œuvre
NOTE Le descripteur M peut être considéré comme une limite supérieure des moyennes obtenues aux points de
prélèvement ou une limite supérieure de confiance, en fonction du nombre de ces points utilisés pour caractériser la salle
ou la zone propre. Un descripteur M ne peut servir à caractériser une classe de propreté particulaire de l’air, mais peut
être utilisé indépendamment ou conjointement à une classe de propreté particulaire de l'air.
3.4 États d’occupation
3.4.1
après construction
condition dans laquelle la salle propre ou la zone propre est achevée, avec toutes les servitudes connectées
et en fonctionnement, mais hors présence des équipements, des matières de production et des personnes
3.4.2
au repos
condition dans laquelle la salle propre ou la zone propre est achevée, et les équipements sont installés et en
fonctionnement selon un mode convenu entre le client et le fournisseur, mais hors présence des personnes
3.4.3
en activité
condition dans laquelle la salle propre ou la zone propre fonctionne selon le mode prescrit avec l’effectif
spécifié travaillant dans des conditions convenues
3.5 Intervenants
3.5.1
client
organisme ou agent responsable de la rédaction du cahier des charges d’une salle propre ou d’une zone
propre
ISO/DIS 14644-1
3.5.2
fournisseur
organisme chargé de satisfaire les exigences du cahier des charges d’une salle propre ou d’une zone propre
4 Classification
4.1 État(s) d'occupation
La propreté particulaire de l'air d'une salle propre ou d'une zone propre doit être définie pour l'un ou plusieurs
des trois états d'occupation, c'est-à-dire « après construction », « au repos» ou « en activité » (voir 3.4).
4.2 Numéro de classification
La propreté particulaire de l'air doit être désignée par un numéro de classification N. La concentration
maximale admissible C , pour chaque taille D de particule prise en compte est déterminée par le Tableau 1.
n
Tableau 1 – Tableau de classification des classes de propreté particulaire de l’air
Numéro de Concentrations maximales admissibles (particules/m ) en particules de taille égale
a
classification (N)
ou supérieure à celles données ci-dessous
0,1 µm 0,2 µm 0,3 µm 0,5 µm 1 µm 5 µm

b
d d d d e
Classe ISO 1
b b
d d e
Classe ISO 2 100
24 10
b
d e
Classe ISO 3 1 000 237 102
b
e
Classe ISO 4 10 000 2 370 1 020 352
e
Classe ISO 5 100 000 23 700 10 200 3 520 832
Classe ISO 6 1 000 000 237 000 102 000 35 200 8 320 293

c c c
Classe ISO 7 352 000 83 200 2 930

c c c
Classe ISO 8 3 520 000 832 000 29 300

c c c
Classe ISO 9 35 200 000 8 320 000 293 000
a
Toutes les concentrations données dans le tableau sont cumulées. Par exemple, pour la classe ISO 5, les
10 200 particules indiquées à 0,3 µm incluent toutes les particules de tailles égales ou supérieures à cette taille.
b
Ces concentrations conduiront à prélever des volumes importants aux fins de classification. La procédure de
prélèvement séquentiel peut être appliquée, Voir Annexe D.
c
Les concentrations maximales admissibles ne s’appliquent pas dans cette partie du tableau car elles sont très
élevées.
d
Les limites du prélèvement et les limites statistiques sur ces faibles concentrations rendent la classification
inapropriée.
e
Les limites des mécanismes de prélèvement dues à la fois aux faibles concentrations et au prélèvement de
particules de tailles supérieures à 1 µm, rendent la classification inappropriée à cause des particules potentiellement
non mesurées car retenues à l’intérieur du système de prélèvement.
La Figure E.1 donne une représentation graphique des classes retenues (Voir Annexe E).
4 © ISO 2010 – Tous droits réservés

ISO/DIS 14644-1
L’équation (1) ci-dessous doit être utilisée pour déterminer la concentration maximale admissible dans le cas
des classes en nombre décimal intermédiaires à la taille de particule considérée :
2,08
⎛ 0,1⎞
N
C = 10 ×⎜ ⎟ (1)
n
D
⎝ ⎠

C est la concentration maximale admissible (en particules par mètre cube d'air) des particules en
n
suspension dont le diamètre est égal ou supérieur à la taille D. C est arrondi au chiffre entier le plus
n
proche, en se limitant à 3 chiffres significatifs ;
N est le numéro de classification ISO. Il ne doit pas être supérieur à 9 ni inférieur à 1. Les numéros de
classifications en nombre décimal peuvent être spécifiés ; le plus petit incrément de N autorisé étant
0,1 ;
D est la taille considérée en micromètres ;
0,1 est une constante exprimée en micromètres.
Le Tableau E.1 (voir Annexe E) fournit des exemples de classes en nombre décimal intermédiaires. Les notes
du tableau E.1 attirent l’attention sur les limites des mécanismes de prélèvement et de transport des
particules.
4.3 Expression de la classification
L’expression de la propreté particulaire de l’air pour les salles propres et les zones propres doit comporter :
a) le numéro de classification sous la forme « classe ISO N » ;
b) l’état d’occupation pour lequel la classification s’applique ;
c) la ou les tailles particulaires prises en compte et les concentrations maximales admissibles
correspondantes obtenues à partir du tableau de classification (Tableau 1) ou par l’équation (1), les tailles
étant situées dans l’étendue granulométrique allant de 0,1 à 5 µm.
La ou les tailles de particules considérées à mesurer doivent faire l’objet d’un accord entre le client et le
fournisseur.
Si les mesurages sont à faire pour plus d'une taille, chaque taille particulaire plus grande (par exemple, D2)
doit être égale à au moins 1,5 fois celle qui la précède (par exemple, D1), c'est-à-dire D2 ≥ 1,5 × D1.
Exemples d’expression de la classification :
Classe ISO 4 ; au repos ; 0,2 µm 0,5 µm
Classe ISO 7,5 ; en activité ; 0,5 µm
5 Démonstration de conformité
5.1 Principe
La conformité avec les conditions de propreté de l'air (classe ISO) demandées par le client est vérifiée en
mettant en œuvre des procédures d'essais définies, et en remettant un rapport donnant les conditions d'essai
et ses résultats, le tout ayant fait l'objet d'un accord préalable entre le client et son fournisseur.
ISO/DIS 14644-1
5.2 Essais
La méthode d'essai de référence servant à démontrer la conformité est donnée à l'annexe A (normative). On
peut spécifier des méthodes ou des instruments différents proposant des performances au moins
équivalentes à ceux de référence. Si aucune alternative n’est spécifiée ni convenue entre le fournisseur et le
client, il faut utiliser la méthode de référence.
Les essais mis en œuvre pour démontrer la conformité doivent utiliser des instruments étalonnés.
5.3 Évaluation de la concentration particulaire dans l’air
À la fin des essais effectués conformément à 5.2, la concentration particulaire (exprimée en nombre de
particules par mètre cube) mesurée dans le volume élémentaire de l’échantillon prélevé à chaque point, ne
doit pas dépasser la limite maximale admissible donnée dans le Tableau 1 ou déterminée selon l’équation (1)
pour les classes en nombre décimal, pour la ou les tailles considérées. Lorsque plusieurs volumes
élémentaires sont prélevés en un même point, on doit établir la concentration moyenne, et cette concentration
moyenne ne doit pas dépasser les concentrations limites données dans le Tableau 1 ou déterminées selon
l’équation (1) pour les tailles en nombre décimal intermédiaires.
Les concentrations particulaires utilisées pour démontrer la conformité aux limites de classes, doivent être
mesurées avec la même méthode pour toutes les tailles de particules considérées.
5.4 Rapport d’essai
Les résultats des essais, pour chaque salle propre ou zone propre, doivent être consignés par écrit et
présentés dans un rapport contenant une affirmation de conformité ou de non-conformité avec l’expression
spécifiée de la classification particulaire de l’air.
Le rapport d'essai doit mentionner les points suivants :
a) le nom et l'adresse de l'organisme responsable des essais et la date d'exécution de ceux-ci ;
b) le numéro et l’année de publication de la présente partie de l’ISO 14644, c'est-à-dire ISO 14644-1:(année
de publication de l'édition la plus récente) ;
c) une identification claire de l'emplacement de la salle propre ou de la zone propre examinée (avec
référence des locaux adjacents si nécessaire), et les coordonnées précises de tous les points
d'échantillonnage ;
d) les critères de désignation de la salle propre ou de la zone propre considérée, comprenant la
classification ISO, l'état d'occupation pertinent et les tailles particulaires prises en compte ;
e) la description détaillée de la méthode d'essai en y incluant les conditions particulières d'essai ou les
écarts par rapport à la méthode d'essai et l’identification des appareils de mesure et leur certificat
d'étalonnage en cours de validité ;
f) les résultats des essais avec les données de concentration particulaire pour tous les points
échantillonnés.
NOTE Si les concentrations des particules ultrafines ou des macroparticules sont quantifiées, comme décrit à
l'Annexe C, il convient de mentionner l’information appropriée dans le rapport d’essai.
6 © ISO 2010 – Tous droits réservés

ISO/DIS 14644-1
Annexe A
(normative)
Méthode de référence pour déterminer la classe de propreté particulaire
de l’air
A.1 Principe
À chaque point de prélèvement prévu, un compteur de particules est utilisé, de façon à obtenir la
concentration des particules en suspension dans l'air qui ont une taille égale ou supérieure aux tailles
spécifiées.
A.2 Exigences liées à l’appareil
A.2.1 Compteur de particules
L’instrument doit disposer de moyens d’affichage ou d’enregistrement du nombre et de la taille des particules
individuelles en suspension dans l’air et doit présenter une sensibilité granulométrique permettant de détecter
la concentration particulaire totale dans les intervalles granulométriques appropriés pour la classe considérée.
NOTE Les compteurs de particules individuelles utilisant la diffusion de la lumière sont communément utilisés pour
déterminer la classe de propreté particulaire.
A.2.2 Étalonnage de l'appareil
L’appareil doit être accompagné d'un certificat d'étalonnage en cours de validité ; la méthode et la fréquence
d'étalonnage doivent tenir compte de la pratique courante admise.
NOTE Voir la référence normative à l’ISO 21501-4.
A.3 Préalables aux essais
A.3.1 Préparation des essais
Avant les essais, vérifier que tous les aspects de la salle propre ou de la zone propre qui concourent à son
intégrité sont effectifs et fonctionnent conformément au cahier des charges.
Ces vérifications préalables peuvent concernées par exemple :
a) Des essais sur l’écoulement d’air (par exemple débit, vitesse ou uniformité d’un écoulement
unidirectionnel) ;
b) Des essais de pressions différentielles ;
c) Un contrôle des fuites de confinement ;
d) Un essai d’intégrité des filtres installés in situ.
ISO/DIS 14644-1
A.3.2 Réglages préliminaires
Régler l’appareil selon les instructions du fabricant.
A.4 Prélèvement
A.4.1 Détermination des points de prélèvement
A.4.1.1 Prendre le nombre minimal de points de prélèvement N du Tableau A.1. Ce dernier fournit le
L
nombre de points de prélèvement en fonction de la surface de chaque salle propre ou zone propre à classer.
Ce nombre minimal garantit avec au moins 95 % de confiance, qu’au moins 90 % de tous les points ne
dépassent pas les limites de classes.
8 © ISO 2010 – Tous droits réservés

ISO/DIS 14644-1
Tableau A.1 – Points de prélèvement en fonction de la surface de la salle propre
Surface de la salle propre (m ) inférieure Nombre minimal de points de
ou égale à prélèvement (N )
L
1 1
2 1
4 2
6 3
8 4
10 5
24 6
28 7
32 8
36 9
52 10
56 11
64 12
68 13
72 14
76 15
104 16
108 17
116 18
148 19
156 20
192 21
232 22
276 23
352 24
436 25
500 26
NOTE 1 Le nombre de points de prélèvement dans le Tableau A.1 est basé sur des unités (cellules)
de surface de 1, puis 2 puis 4 m , afin d’affirmer avec 95 % de confiance, qu’au moins 90 % de l’aire
totale considérée ne dépasse pas la limite de classe.
NOTE 2 Si la surface de la zone considérée tombe entre deux valeurs dans le tableau, il convient de
retenir la plus grande.
NOTE 3 Dans le cas d’un flux unidirectionnel, la surface à prendre en compte peut être considérée
comme étant le plan de coupe perpendiculaire au sens d’écoulement de l’air. Dans tous les autres cas,
la surface considérée sera le plan horizontal de la salle propre ou de la zone propre.
NOTE 4 D’un point de vue pratique, on suppose que chaque point de prélèvement est représentatif
de l’unité de surface dans laquelle il est mesuré.
NOTE 5 Les salles propres de plus de 500 m doivent être considérées comme constituées d’une
série de zones plus petites.
ISO/DIS 14644-1
A.4.1.2 Afin de déterminer l’emplacement des points de prélèvement, on doit identifier le nombre minimal
de points de prélèvement dans le Tableau A.1, utiliser ce nombre pour diviser la zone propre en unités de
surface égales et dans chaque unité de surface, choisir de manière aléatoire un point de prélèvement
positionné à la hauteur de l’activité.
Si le client demande des points de prélèvement supplémentaires, leur nombre et leur position devront être
également spécifiés. De tels points supplémentaires peuvent être ceux considérés comme critiques en
fonction d’une analyse de risque.
A.4.2 Détermination des volumes élémentaires et des durées de prélèvement à chaque point
de prélèvement
A.4.2.1 À chaque point de prélèvement, prélever un volume d’air suffisant pour qu’un minimum de
20 particules seraient comptées si la concentration pour la taille de particule la plus grosse atteignait la limite
de la classe ISO visée.
Le volume élémentaire V à prélever à chaque point est déterminé au moyen de l’équation (A.1) :
s
⎛ ⎞
⎜ ⎟
V = × 1000 (A.1)
s
⎜ ⎟
C
n,m
⎝ ⎠

V est le volume élémentaire minimal à prélever à chaque point, exprimé en litres (excepté dans le cas
s
de D.4.2.2).
C est la limite de la classe visée (en nombre de particules par mètre cube) pour la plus grosse taille
n,m
de particule considérée.
20 est le nombre de particules qui serait compté si la concentration en particules atteignait la limite de
la classe visée.
Les volumes élémentaires à chaque point doivent être les mêmes – sauf si la procédure de prélèvement
séquentiel facultative (voir Annexe D) est utilisée – et doivent être exprimés en litres. Lorsque V est très
s
grand, la durée de prélèvement requise peut être importante. Le recours à la procédure de prélèvement
séquentiel peut permettre de réduire à la fois la durée de prélèvement et le volume à prélever.
A.4.2.2 Le volume prélevé à chaque point doit être au moins de 2 litres et la durée de prélèvement au
moins d’1 minute.
A.4.3 Procédure de prélèvement
A.4.3.1 Préparer le compteur de particules (voir A.2) suivant les instructions du fabricant et
conformément au certificat d'étalonnage de l'instrument.
A.4.3.2 La sonde de prélèvement doit être disposée face à l'écoulement. Si la direction de l'écoulement à
échantillonner n'est pas maîtrisée ou prévisible (par exemple, un écoulement non unidirectionnel), l'entrée de
la sonde de prélèvement doit être dirigée vers le haut.
A.4.3.3 Si nécessaire, s’assurer que les conditions sont stables avant de débuter les prélèvements.
Prélever au moins le volume d'air calculé suivant A.4.2.1 en chaque point de prélèvement.
10 © ISO 2010 – Tous droits réservés

ISO/DIS 14644-1
A.4.3.4 Si au cours d’essais nécessitant plusieurs points de prélèvement, quel que soit l’état d’occupation
de la salle, un résultat anormalement élevé est trouvé sur un prélèvement en un point particulier, des
prélèvements complémentaires peuvent être réalisés en ce point en vue de rechercher les causes du
problème et de déterminer si ce point est conforme ou non.
A.5 Enregistrement des résultats
A.5.1 Concentration particulaire moyenne en chaque point de prélèvement
A.5.1.1 Enregistrer le nombre de particules comptées dans chaque prélèvement pour chaque taille de
particule considérée selon la classe de propreté visée.
A.5.1.2 Si au moins deux prélèvements sont effectués en un point donné, calculer la moyenne du nombre
de particules selon l’équation (A.2) à partir des mesures individuelles effectuées pour chaque taille de
particule considérée (A.5.1.1), et l’enregistrer.
[x + x + .x ]
i.1 i.2 i,n
x = (A.2)
i
n

x est le nombre moyen de particules au point de prélèvement i, qui est représentatif de n’importe
i
quel point ;
x à x sont les nombres de particules de chaque prélèvement ;
i.1 i.n
n est le nombre de prélèvements effectués au point i.
A.5.1.3
Calculer la concentration par mètre cube.
x × 1000
i
C = (A.3)
i
V
t

x est le nombre moyen de particules au point de prélèvement i, qui est représentatif de n’importe
i
quel point ;
V est le volume de prélèvement retenu exprimé en litres.
t
A.6 Interprétation des résultats
A.6.1 Exigences de classification
La salle ou la zone propre sera considérée comme conforme à la classe de propreté de l’air spécifiée si la
moyenne des concentrations en particules exprimée en nombre de particules par mètre cube mesurée à
chaque point de prélèvement ne dépasse pas la limite de concentration spécifiée dans le tableau 1 ou, pour
les classes intermédiaires, déterminée au moyen de l’équation (1).
ISO/DIS 14644-1
Annexe B
(informative)
Exemples d’application de calculs de classes
B.1 Exemple 1
B.1.1 Une salle propre en activité a une surface de plancher de 18 m et est spécifiée pour une propreté
particulaire de l'air de classe ISO 5. Il faut effectuer la classification à l'aide d'un compteur de particules ayant
un débit de prélèvement de 28,3 litres par minute. Deux tailles particulaires sont prises en compte :
D ≥ 0,3 µm et D ≥ 0,5 µm.
D'après le Tableau A.1, le nombre de points de prélèvement N est fixé à six.
L
B.1.2 Les concentrations particulaires limites pour la classe 5 est donnée dans le Tableau 1 :
C (≥ 0,3 µm) = 10 200 particules/m
n
C (≥ 0,5 µm) = 3 520 particules/m
n
B.1.3 Le volume élémentaire de l'échantillon requis peut être calculé à partir de l’équation (A.1) comme
suit :
⎛ ⎞
⎜ ⎟
V = × 1 000
s
⎜ ⎟
C
n,m
⎝ ⎠
⎛ ⎞
V = ⎜ ⎟× 1 000
s
⎜ ⎟
3 520
⎝ ⎠
V = (0,00568) × 1 000
s
V = 5,68 litres
s
Le volume élémentaire de prélèvement calculé est de 5,68 litres. Du fait que le compteur de particules utilisé
pour l’essai a un débit de prélèvement de 28,3 litres par minute, une durée de prélèvement d’une minute par
échantillon s’applique à chaque point (voir A.4.2.2) et, par conséquent, il sera nécessaire de prélever des
échantillons de 28,3 litres pour chaque prélèvement.
NOTE En A.4.2.2, le volume à prélever est déterminé en calculant le volume minimal à prélever tel que ci-dessus
puis en comparant ce volume au volume prélevé par le compteur en une minute. L’échantillonnage à chaque point de
prélèvement doit se faire sur une durée minimale de 1 minute. Si le volume tel que calculé est prélevé par le compteur en
une minute, alors le comptage peut être interrompu au bout d’une minute de prélèvement, si ce volume calculé n’est pas
prélevé par le compteur en une minute, alors le prélèvement doit être poursuivi pour une période plus longue jusqu'à ce
que le volume calculé soit prélevé. L’attention des utilisateurs est attirée sur le fait que les compteurs de particules
peuvent présenter différents débits de prélèvement, les utilisateurs doivent donc vérifier le débit de prélèvement de
l’appareil qu’ils utilisent lorsqu’ils déterminent la durée de prélèvement et le volume à échantillonner de sorte à garantir le
respect des deux conditions.
Un seul échantillon est prélevé à chaque point. Le nombre de particules x , par mètre cube d’air calculé pour chaque point
i
et pour chaque taille de particule, est présenté dans les Tableaux B.1 et B.2 :
12 © ISO 2010 – Tous droits réservés

ISO/DIS 14644-1
Tableau B.1 – Données de prélèvement pour les particules ≥ 0,3 µm
Point Échantillon Moyenne Moyenne Limite Conformité/échec
de 1 du point du point pour des
prélèvement (mesurages mesurages
x ≥ 0,3 µm (mesurages
i
pour de 0,3 µm
par mètre
28,3 litres) à la classe
cube =
ISO 5
moyenne
du point ×
35,3)
1 245 245 8 649 10 200 Conformité
2 185 185 6 531 10 200 Conformité
3 59 59 2 083 10 200 Conformité
4 106 106 3 742 10 200 Conformité
5 164 164 5 789 10 200 Conformité
6 196 196 6 919 10 200 Conformité
Tableau B.2 – Données de prélèvement pour les particules ≥ 0,5 µm
Point Échantillon Moyenne Moyenne Limite Conformité/échec
de 1 du point du point pour des
prélèvement mesurages
x ≥ 0,5 µm (mesurages (mesurages
i
de 0,5 µm
par par mètre
à la classe
28,3 litres) cube =
ISO 5
moyenne
du point ×
35,3)
1 21 21 741 3 520 Conformité
2 24 24 847 3 520 Conformité
3 0 0 0 3 520 Conformité
4 7 7 247 3 520 Conformité
5 22 22 777 3 520 Conformité
6 25 25 883 3 520 Conformité
B.1.4 Chacune des valeurs de concentration pour les particules D ≥ 0,3 µm est inférieure à la limite de
10 200 particules/m et chacune des valeurs de concentration pour les particules D ≥ 0,5 µm est inférieure à la
limite de 3 520 particules/m comme établie en B.1.2 ; par conséquent la propreté particulaire de l’air de la
salle satisfait aux exigences de la classe visée.
B.2 Exemple 2
B.2.1 Une salle propre en activité a une surface de plancher de 9 m et est spécifiée pour une propreté
particulaire de l'air de classe ISO 3. Il faut effectuer la classification à l'aide d'un compteur de particules ayant
un débit de prélèvement de 50,0 litres par minute. Une seule taille de particule (D ≥ 0,1 µm) est prise en
compte.
D'après le Tableau A.1, le nombre de points de prélèvement N est fixé à cinq.
L
B.2.2 La concentration particulaire limite pour une classe ISO 3 à ≥ 0,1 µm est donnée dans le Tableau 1 :
C (≥ 0,1 µm) = 1 000 particules/m
n
ISO/DIS 14644-1
B.2.3 Le volume élémentaire de l'échantillon requis peut être calculé à partir de l’équation (A.1) comme
suit :
⎛ ⎞
⎜ ⎟
V = × 1 000
s
⎜ ⎟
C
n,m
⎝ ⎠
⎛ ⎞
V = ⎜ ⎟× 1 000
s
⎜ ⎟
⎝ ⎠
V = (0,02) × 1 000
s
V = 20,0 litres
s
Le calcul du volume minimal de l’échantillon à prélever à chaque point es
...


NORME ISO
INTERNATIONALE 14644-1
Deuxième édition
2015-12-15
Salles propres et environnements
maîtrisés apparentés —
Partie 1:
Classification de la propreté
particulaire de l’air
Cleanrooms and associated controlled environments —
Part 1: Classification of air cleanliness by particle concentration
Numéro de référence
©
ISO 2015
DOCUMENT PROTÉGÉ PAR COPYRIGHT
© ISO 2015, Publié en Suisse
Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite ni utilisée
sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie, l’affichage sur
l’internet ou sur un Intranet, sans autorisation écrite préalable. Les demandes d’autorisation peuvent être adressées à l’ISO à
l’adresse ci-après ou au comité membre de l’ISO dans le pays du demandeur.
ISO copyright office
Ch. de Blandonnet 8 • CP 401
CH-1214 Vernier, Geneva, Switzerland
Tel. +41 22 749 01 11
Fax +41 22 749 09 47
copyright@iso.org
www.iso.org
ii © ISO 2015 – Tous droits réservés

Sommaire Page
Avant-propos .iv
Introduction .vi
1 Domaine d’application . 1
2 Références normatives . 1
3 Termes et définitions . 1
3.1 Généralités . 2
3.2 Particules en suspension dans l’air . 2
3.3 États d’occupation . 3
3.4 Appareils de mesure (voir l’Annexe F) . 3
3.5 Spécifications de l’instrument . 4
4 Classification . 4
4.1 État(s) d’occupation . 4
4.2 Taille(s) de particule . 4
4.3 Numéro de classe ISO . 4
4.4 Expression de la classification . 5
4.5 Classes décimales intermédiaires de propreté et tailles de particules de référence . 5
5 Démonstration de conformité . 6
5.1 Principe . 6
5.2 Essais . 6
5.3 Évaluation de la concentration particulaire dans l’air . 6
5.4 Rapport d’essai . 6
Annexe A (normative) Méthode de référence pour la classe de propreté particulaire de l’air .8
Annexe B (informative) Exemples d’application de calculs de classes .13
Annexe C (informative) Comptage et mesurage de macroparticules en suspension dans l’air .22
Annexe D (informative) Mode opératoire de prélèvement séquentiel .28
Annexe E (informative) Spécification des classes décimales de propreté et des tailles de
particules intermédiaires .35
Annexe F (informative) Appareils de mesure .37
Bibliographie .39
Avant-propos
L’ISO (Organisation internationale de normalisation) est une fédération mondiale d’organismes
nationaux de normalisation (comités membres de l’ISO). L’élaboration des Normes internationales est
en général confiée aux comités techniques de l’ISO. Chaque comité membre intéressé par une étude
a le droit de faire partie du comité technique créé à cet effet. Les organisations internationales,
gouvernementales et non gouvernementales, en liaison avec l’ISO participent également aux travaux.
L’ISO collabore étroitement avec la Commission électrotechnique internationale (IEC) en ce qui
concerne la normalisation électrotechnique.
Les procédures utilisées pour élaborer le présent document et celles destinées à sa mise à jour sont
décrites dans les Directives ISO/IEC, Partie 1. Il convient, en particulier de prendre note des différents
critères d’approbation requis pour les différents types de documents ISO. Le présent document a été
rédigé conformément aux règles de rédaction données dans les Directives ISO/IEC, Partie 2 (voir www.
iso.org/directives).
L’attention est appelée sur le fait que certains des éléments du présent document peuvent faire l’objet de
droits de propriété intellectuelle ou de droits analogues. L’ISO ne saurait être tenue pour responsable
de ne pas avoir identifié de tels droits de propriété et averti de leur existence. Les détails concernant
les références aux droits de propriété intellectuelle ou autres droits analogues identifiés lors de
l’élaboration du document sont indiqués dans l’Introduction et/ou dans la liste des déclarations de
brevets reçues par l’ISO (voir www.iso.org/brevets).
Les appellations commerciales éventuellement mentionnées dans le présent document sont données
pour information, par souci de commodité, à l’intention des utilisateurs et ne sauraient constituer
un engagement.
Pour une explication de la signification des termes et expressions spécifiques de l’ISO liés à
l’évaluation de la conformité, ou pour toute information au sujet de l’adhésion de l’ISO aux principes
de l’OMC concernant les obstacles techniques au commerce (OTC), voir le lien suivant: Avant-propos —
Informations supplémentaires.
Le comité chargé de l’élaboration du présent document est l’ISO/TC 209, Salles propres et environnements
maîtrisés apparentés.
Cette deuxième édition annule et remplace la première édition (ISO 14644-1:1999) qui a fait l’objet
d’une révision technique dans son ensemble.
L’ISO 14644 comprend les parties suivantes, présentées sous le titre général Salles propres et
environnements maîtrisés apparentés:
— Partie 1: Classification de la propreté particulaire de l’air
— Partie 2: Surveillance du maintien des performances de la salle propre pour la propreté particulaire de l’air
— Partie 3: Méthodes d’essai
— Partie 4: Conception, construction et mise en fonctionnement
— Partie 5: Exploitation
— Partie 7: Dispositifs séparatifs (postes à air propre, boîtes à gants, isolateurs et mini-environnements)
— Partie 8: Classification de la propreté chimique de l’air
— Partie 9: Classification de la propreté des surfaces par la concentration de particules
— Partie 10: Classification de la propreté chimique des surfaces
L’attention est attirée sur l’ISO 14698, Salles propres et environnements maîtrisés apparentés — Maîtrise
de la biocontamination:
iv © ISO 2015 – Tous droits réservés

— Partie 1: Principes généraux et méthodes
— Partie 2: Évaluation et interprétation des données de biocontamination
Introduction
Les salles propres et les environnements maîtrisés apparentés fournissent des moyens pour maîtriser
la contamination de l’air et, le cas échéant, des surfaces à des niveaux appropriés pour les activités
sensibles à la contamination. La maîtrise de la contamination peut être bénéfique pour la protection du
produit ou du procédé pour des applications telles que l’industrie aérospatiale, la micro-électronique,
l’industrie pharmaceutique, les dispositifs médicaux, la santé, l’industrie alimentaire, etc.
La présente partie de l’ISO 14644 spécifie des classes de propreté de l’air en termes de concentration
en nombre de particules par volume d’air. Elle spécifie également la méthode normalisée d’essai afin de
déterminer la classe de propreté, comprenant la sélection des points de prélèvement.
Cette version révisée est le résultat de la réponse à une revue systématique ISO, et inclut des
modifications suite au retour d’expériences des utilisateurs et des experts, validé par une enquête
internationale. Le titre a été révisé en «Classification de la propreté particulaire de l’air» pour être
cohérent avec les autres parties de l’ISO 14644. Les classes de propreté ISO au nombre de neuf sont
conservées avec quelques modifications mineures. Le Tableau 1 définit les concentrations particulaires
pour les différentes tailles pour les 9 classes au nombre entier. Le Tableau E.1 définit les concentrations
particulaires maximales pour les différentes tailles pour les classes intermédiaires. L’utilisation
de ces tableaux assure une meilleure définition des distributions granulométriques appropriées
pour les différentes classes. La présente partie de l’ISO 14644 conserve le principe du descripteur
macroparticules. Toutefois la prise en compte des nanoparticules (anciennement définies comme
particules ultrafines) sera traitée dans une autre norme séparée.
L’évolution la plus importante est le recours à une approche de traitement statistique plus cohérente
pour la sélection et le nombre des points de prélèvement et pour l’évaluation des données recueillies.
Le modèle statistique est basé sur une adaptation de la technique du modèle d’échantillonnage
hypergéométrique selon lequel des échantillons sont prélevés au hasard dans une population finie, sans
remise. Cette nouvelle approche permet d’examiner chaque point de prélèvement individuellement; afin
de vérifier avec un niveau de confiance d’au moins95 %, qu’au moins 90 % de la surface de la salle ou
de la zone propre est conforme à la concentration maximale admissible pour la classe visée. Aucune
condition n’est requise concernant la distribution réelle des comptages particulaires sur l’ensemble
de la salle propre ou zone propre, alors que dans l’ISO 14644-1:1999, une hypothèse admise était que
les comptages particulaires suivent la même distribution normale à travers la salle. Cette hypothèse
a été écartée pour permettre d’utiliser cette méthode d’échantillonnage dans des locaux où les
concentrations particulaires varient de façon plus complexe. Au cours du processus de révision, il a
été reconnu que la limite supérieure de confiance à 95% n’était ni appropriée ni appliquée de façon
constante dans l’ISO 14644-1:1999. Le nombre minimum requis de points de prélèvement a été
modifié par rapport à l’ISO 14644-1:1999. Un tableau de référence, Tableau A.1 est fourni pour définir
le nombre minimum de points de prélèvement requis, en se basant sur une adaptation pratique de la
technique d’échantillonnage. Il est supposé que la surface proche du point de prélèvement présente
une concentration homogène de particules en suspension dans l’air. La salle propre ou zone propre est
partagée dans une grille de sections d’aire à peu près égale, dont le nombre est égal au nombre de points
de prélèvement fourni par le Tableau A.1. Un point de prélèvement est placé au centre de chaque section
de la grille, de façon représentative de cette section.
Il est considéré à des fins pratiques que la localisation des points est faite de façon représentative; un
emplacement «représentatif» (voir A.4.2) signifie que les spécificités telles que la disposition de salle
propre ou zone propre, l’emplacement des équipements et le taux de renouvellement des systèmes non
unidirectionnels doivent être pris en compte lors de la sélection des points de prélèvement. Des points
de prélèvement supplémentaires peuvent être ajoutés au-delà du nombre minimum.
Enfin, l’ordre des annexes a été réorganisé pour améliorer la compréhension de la présente partie de la
norme ISO 14644, et le contenu de certaines annexes de l’ISO 14644-3:2005, concernant les essais et les
instruments d’essais, a été intégré dans cette version de la norme.
La version révisée de la présente partie de l’ISO 14644 traite des limites pour des particules de taille
≥ 5 µm à la classe ISO 5 dans les annexes produits stériles des BPF UE, PIC/S et OMS, en adaptant le
concept des macroparticules.
vi © ISO 2015 – Tous droits réservés

La version révisée de la présente partie de l’ISO 14644 inclut maintenant toutes les questions relatives
à la classification de la propreté particulaire de l’air. La version révisée de l’ISO 14644-2:2015 traite
exclusivement de la surveillance de la propreté particulaire de l’air.
Les salles propres peuvent aussi être caractérisées par des attributs autres que la propreté particulaire
de l’air. D’autres attributs, tels que la propreté chimique de l’air pourront faire l’objet d’une surveillance,
et il sera possible de fixer l’objectif ou le niveau de cet attribut au côté de la classification de la propreté
particulaire de l’air de classe ISO. Ces attributs additionnels ne suffisent pas seuls à classer une salle
propre ou zone propre.
NORME INTERNATIONALE ISO 14644-1:2015(F)
Salles propres et environnements maîtrisés apparentés —
Partie 1:
Classification de la propreté particulaire de l’air
1 Domaine d’application
La présente partie de l’ISO 14644 spécifie la classification de la propreté de l’air des salles propres,
des zones propres et des dispositifs séparatifs tels que définis dans l’ISO 14644-7 en termes de
concentration des particules en suspension dans l’air.
Seules sont prises en compte les populations de particules présentant une distribution granulométrique
cumulée dont le seuil inférieur se situe dans l’étendue de 0,1 µm à 5 µm.
La méthode de référence pour déterminer la concentration de particules dans l’air d’une taille supérieure
ou égale aux tailles spécifiées aux points de prélèvement désignés est l’utilisation de compteurs utilisant
les propriétés de diffusion de la lumière (light scattering airborne particle counters - LSAPC).
La présente partie de l’ISO 14644 ne donne pas de classification pour des populations de particules
dont le seuil inférieur se situe en dehors de l’étendue granulométrique de référence de 0,1 µm à 5 µm.
Les concentrations de particules ultrafines (plus petites que 0,1 µm) seront traitées dans une norme
séparée laquelle spécifiera la propreté particulaire de l’air à l’échelle nanométrique. Un descripteur M
(voir l’Annexe C) pouvant être utilisé pour quantifier les populations de macroparticules (particules
plus grandes que 5 µm).
La présente partie de l’ISO 14644 ne peut pas être utilisée pour caractériser la nature physique,
chimique, radiologique ou viable des particules en suspension dans l’air.
2 Références normatives
Les documents ci-après, dans leur intégralité ou non, sont des références normatives indispensables à
l’application du présent document. Pour les références datées, seule l’édition citée s’applique. Pour les
références non datées, la dernière édition du document de référence s’applique (y compris les éventuels
amendements).
ISO 14644-2:2015, Salles propres et environnements maîtrisés apparentés — Surveillance du maintien des
performances de la salle propre pour la propreté particulaire de l’air.
ISO 14644-7, Salles propres et environnements maîtrisés apparentés — Partie 7: Dispositifs séparatifs
(postes à air propre, boîtes à gants, isolateurs et mini-environnements).
3 Termes et définitions
Pour les besoins du présent document, les termes et définitions suivants s’appliquent.
3.1 Généralités
3.1.1
salle propre
salle dans laquelle la concentration en nombre des particules en suspension dans l’air est maîtrisée et
classée, et qui est construite et utilisée de façon à minimiser l’introduction, la production et la rétention
des particules à l’intérieur de la pièce
Note 1 à l’article: la classe de propreté particulaire de l’air est spécifiée.
Note 2 à l’article: le niveau des autres attributs de propreté de l’air tels que les concentrations chimiques,
viables ou nanométriques, ainsi que le niveau de ceux des surfaces tels que les concentrations particulaires,
nanométriques, chimiques et viables pourrait être aussi spécifié et maîtrisé.
Note 3 à l’article: d’autres paramètres physiques pertinents, par exemple la température, l’humidité, la pression,
les vibrations et les propriétés électrostatiques, pourraient être maîtrisés si requis.
3.1.2
zone propre
espace défini dans lequel la concentration en nombre des particules en suspension dans l’air est
maîtrisée et classée, et qui est construit et utilisé de façon à minimiser l’introduction, la production et la
rétention de particules à l’intérieur de l’espace
Note 1 à l’article: la classe de propreté particulaire de l’air est spécifiée.
Note 2 à l’article: le niveau des autres attributs de propreté de l’air tels que les concentrations chimiques, viables
ou nanométriques, ainsi que le niveau des concentrations particulaires, nanométriques, chimiques et viables des
surfaces pourraient être aussi spécifiés et maîtrisés.
Note 3 à l’article: la zone propre peut être un espace défini à l’intérieur d’une salle propre, ou peut être concrétisée
par un dispositif séparatif. Un tel dispositif peut être situé à l’intérieur d’une salle propre ou non.
Note 4 à l’article: d’autres paramètres physiques pertinents, par exemple la température, l’humidité, la pression,
les vibrations et les propriétés électrostatiques, pourraient être maîtrisés si requis.
3.1.3
installation
une salle propre ou une ou plusieurs zones propres incluant toutes les structures associées, les systèmes
de traitement de l’air et les servitudes
3.1.4
classification
méthode d’évaluation du niveau de propreté d’une salle propre, d’une zone propre
Note 1 à l’article: Il convient que les niveaux soient exprimés en termes d’une classe ISO qui représente la
concentration maximale admissible de particules par unité de volume d’air.
3.2 Particules en suspension dans l’air
3.2.1
particule
objet minuscule de matière quelconque qui possède un périmètre physique défini
3.2.2
taille de particule
diamètre d’une sphère qui, dans un instrument donné de mesure des tailles de particules, donne une
réponse qui est équivalente à la réponse de la particule à mesurer
Note 1 à l’article: Note1 à l’article: Pour les instruments faisant appel aux caractéristiques de la diffusion de la
lumière et capables de compter les particules individuellement, on utilise le terme diamètre optique équivalent.
2 © ISO 2015 – Tous droits réservés

3.2.3
concentration particulaire
nombre de particules individuelles par unité de volume d’air
3.2.4
distribution granulométrique
distribution cumulée des concentrations de particules en fonction de leur taille
3.2.5
macroparticule
particule dont le diamètre équivalent est supérieur à 5 µm
3.2.6
descripteur M
désignation pour la concentration, mesurée ou spécifiée, des macroparticules par mètre cube d’air,
exprimée en termes de diamètre équivalent caractéristique de la méthode de mesure mise en œuvre
Note 1 à l’article: Note1 à l’article: Le descripteur M peut être considéré comme une limite supérieure des
moyennes obtenues aux points de prélèvement. Un descripteur M ne peut servir à caractériser des classes ISO,
mais il peut être utilisé indépendamment ou conjointement aux classes ISO.
3.2.7
flux d’air unidirectionnel
flux d’air maîtrisé traversant l’ensemble d’un plan de coupe d’une salle propre ou zone propre possédant
une vitesse régulière et des filets considérés comme étant parallèles
3.2.8
flux d’air non unidirectionnel
distribution de l’air où l’air soufflé entrant dans la salle propre ou la zone propre se mélange avec l’air
intérieur par phénomène d’induction
3.3 États d’occupation
3.3.1
après construction
condition dans laquelle la salle propre ou la zone propre est achevée, avec toutes les servitudes
connectées et en fonctionnement, mais hors présence des équipements, du mobilier, des matières de
production et des personnes
3.3.2
au repos
condition dans laquelle la salle propre ou la zone propre est achevée, et les équipements sont installés
et en fonctionnement selon un mode convenu, mais hors présence des personnes
3.3.3
en activité
condition convenue dans laquelle la salle propre ou la zone propre fonctionne selon le mode prescrit
avec les équipements en fonctionnement ainsi qu’avec l’effectif spécifié présent
3.4 Appareils de mesure (voir l’Annexe F)
3.4.1
résolution
plus petite variation de la grandeur mesurée qui produit une variation perceptible de l’indication
correspondante
Note 1 à l’article: La résolution peut dépendre, par exemple, du bruit (interne ou externe) ou du frottement. Elle
peut aussi dépendre de la valeur de la grandeur mesurée.
[SOURCE: Guide ISO/IEC 99:2007, 4.14]
3.4.2
erreur maximale de mesurage tolérée
valeur extrême de l’erreur de mesurage, par rapport à une grandeur de référence connue, tolérée par
les spécifications ou les réglementations pour un mesurage, un instrument de mesure ou un système
de mesure donné
Note 1 à l’article: Les termes «erreurs maximales tolérées» ou «limites d’erreur» sont généralement utilisés
lorsqu’il y a deux valeurs extrêmes.
Note 2 à l’article: Il convient de ne pas utiliser le terme «tolérance» pour désigner l’«erreur maximale tolérée».
[SOURCE: Guide ISO/IEC 99:2007, 4.26]
3.5 Spécifications de l’instrument
3.5.1
LSAPC (light scattering airborne particle counter)
compteur de particules en suspension dans l’air utilisant la diffusion de la lumière
compteur de particules individuelles en suspension dans l’air utilisant la diffusion de la lumière
instrument capable de compter et de mesurer individuellement les particules en suspension dans l’air
et de fournir les données de mesure en termes de diamètre optique équivalent
Note 1 à l’article: Les spécifications pour le LSAPC sont données dans l’ISO 21501-4:2007.
3.5.2
compteur de macroparticules individuelles
instrument capable de compter et de mesurer individuellement les macroparticules en suspension dans
l’air
Note 1 à l’article: Voir le Tableau F.1 pour les spécifications.
3.5.3
compteur de particules à temps de vol
appareil de comptage et de mesure de particules qui définit le diamètre aérodynamique des particules
en mesurant la durée nécessaire à une particule pour s’adapter à un changement de vitesse de l’air
Note 1 à l’article: Cela est généralement effectué en mesurant par moyen optique le temps de transition de la
particule après le changement de vitesse d’écoulement d’un fluide.
Note 2 à l’article: Voir le Tableau F.2 pour les spécifications.
4 Classification
4.1 État(s) d’occupation
La propreté particulaire de l’air d’une salle propre ou d’une zone propre doit être définie pour
l’un ou plusieurs des trois états d’occupation, c’est-à-dire «après construction», «au repos» ou «en
activité» (voir 3.3).
4.2 Taille(s) de particule
Pour la détermination de la propreté particulaire de l’air en vue de la classification, une ou plusieurs
tailles de particule dont le seul inférieur se situe dans l’étendue granulométrique de ≥0,1 µm à ≥5 µm
doivent être utilisées.
4.3 Numéro de classe ISO
La propreté particulaire de l’air doit être désignée par un numéro, N, de classe ISO. La concentration
maximale admissible pour chaque taille de particule prise en compte est déterminée par le Tableau 1.
4 © ISO 2015 – Tous droits réservés

Les concentrations en nombre de particules pour les différentes tailles de référence ne reflètent pas la
distribution granulométrique réelle rencontrée dans l’air, et ne servent qu’aux fins de classification. Des
exemples de calculs de classes sont donnés dans l’Annexe B.
Tableau 1 — Classes ISO de la propreté particulaire de l’air
Concentrations maximales admissibles (particules/m ) en particules de taille
Numéro de classe ISO
égale ou supérieure à celles données ci-dessousa
(N)
0,1 µm 0,2 µm 0,3 µm 0,5 µm 1 µm 5 µm
b d d d d e
1 10
b b d d e
2 100 24 10
b d e
3 1 000 237 102 35
b e
4 10 000 2 370 1 020 352 83
d, e, f
5 100 000 23 700 10 200 3 520 832
6 1 000 000 237 000 102 000 35 200 8 320 293
c c c
7 352 000 83 200 2 930
c c c
8 3 520 000 832 000 29 300
g c c c
9 35 200 000 8 320 000 293 000
a
Toutes les concentrations données dans le tableau sont cumulées. Par exemple, pour la classe ISO 5, les 10 200
particules indiquées à 0,3 µm incluent toutes les particules de tailles égales ou supérieures à cette taille.
b
Ces concentrations conduiront à prélever des volumes importants aux fins de classification. La procédure de
prélèvement séquentiel peut être appliquée, voir l’Annexe D.
c
Les concentrations maximales admissibles ne s’appliquent pas dans cette partie du tableau car elles sont très élevées.
d
Les limites du prélèvement et les limites statistiques sur ces faibles concentrations rendent la classification
inappropriée.
e
Les limites des mécanismes de prélèvement, dues à la fois aux faibles concentrations et au prélèvement de particules
de tailles supérieures à 1 µm, rendent la classification inappropriée à cause des particules potentiellement non mesurées
car retenues à l’intérieur du système de prélèvement.
f
Pour réaliser une classification à cette taille de particules, pour la classe ISO 5 on peut adapter le descripteur
macroparticules M en l’associant à au moins une autre taille de particules (voir Annexe C.7).
g  Cette classe est uniquement applicable pour l’état en activité.
4.4 Expression de la classification
L’expression de la propreté particulaire de l’air pour les salles propres et les zones propres doit comporter:
a) le numéro de classe ISO sous la forme «classe ISO N»;
b) l’état d’occupation pour lequel la classification s’applique;
c) la ou les tailles particulaires prises en compte.
Si les mesurages sont à faire pour plus d’une taille, chaque taille particulaire plus grande (par
exemple, D2) doit être égale à au moins 1,5 fois celle qui la précède (par exemple, D1), c’est-à-dire
D2 ≥ 1,5 × D1.
EXEMPLE Numéro de classe ISO, état d’occupation, taille(s) de particule(s) considérée(s) et limite de
classe correspondante
Classe ISO 4; au repos; 0,2 µm; 0,5 µm
4.5 Classes décimales intermédiaires de propreté et tailles de particules de référence
Quand il est besoin de classes intermédiaires, ou de tailles de particules non spécifiées dans le tableau
pour les classes à numéro entier ou intermédiaire, se référer à l’Annexe E (informative).
5 Démonstration de conformité
5.1 Principe
La conformité aux conditions de propreté de l’air (classe ISO) spécifiées par le client est vérifiée par la
réalisation de modes opératoires d’essai spécifiés, et par la fourniture de documentation des résultats
et des conditions de l’essai.
La classification au repos ou en activité peut être réalisée à des intervalles réguliers sur base d’une
analyse des risques de l’application, typiquement une fois par an.
Pour la surveillance des salles propres, des zones propres et des dispositifs séparatifs, l’ISO 14644-2:2015
doit être utilisée.
NOTE Quand l’installation est équipée d’instruments permettant une surveillance continue ou fréquente de
la propreté particulaire de l’air et d’autres paramètres de performances le cas échéant, l’intervalle de temps entre
les opérations de classification peut être étendu à condition que les résultats de surveillance restent à l’intérieur
des limites spécifiées.
5.2 Essais
La méthode d’essai de référence servant à démontrer la conformité est donnée à l’Annexe A (normative).
On peut spécifier des méthodes ou des instruments différents ou les deux donnant au moins des
performances au moins équivalentes à ceux de référence. Si aucune alternative n’est spécifiée ni
convenue il faut utiliser la méthode de référence.
Les essais mis en œuvre pour démontrer la conformité doivent être menés au moyen d’instruments en
conformité avec les exigences d’étalonnage au moment de l’essai.
5.3 Évaluation de la concentration particulaire dans l’air
À la fin des essais effectués conformément à l’Annexe A, la concentration particulaire (exprimée en
nombre de particules par mètre cube) mesurée dans le volume élémentaire de l’échantillon prélevé à
chaque point, ne doit pas dépasser la limite maximale admissible donnée dans le Tableau 1 ou Tableau E.1
pour les classes intermédiaires en nombre décimal, pour la ou les tailles considérées. Lorsque plusieurs
volumes élémentaires sont prélevés en un même point, les concentrations moyennes doivent être
établies, et il est nécessaire que cette concentration moyenne ne dépasse pas les concentrations
limites données dans le Tableau 1 ou Tableau E.1. Les tailles de particules intermédiaires doivent être
déterminées selon la Formule (E.1).
Les concentrations particulaires utilisées pour démontrer la conformité aux limites de classes ISO
doivent être mesurées avec la même méthode pour toutes les tailles de particules considérées.
5.4 Rapport d’essai
Les résultats des essais, pour chaque salle propre ou zone propre, doivent être consignés par écrit
et présentés dans un rapport contenant une affirmation de conformité ou de non-conformité avec
l’expression spécifiée de la classification particulaire de l’air.
Le rapport d’essai doit mentionner les points suivants:
a) le nom et l’adresse de l’organisme responsable des essais et la date d’exécution de ceux-ci;
b) le numéro et l’année de publication de la présente partie de l’ISO 14644, c’est-à-dire
c) une identification claire de l’emplacement de la salle propre ou de la zone propre examinée (avec
référence des locaux adjacents si nécessaire), et les coordonnées précises de tous les points de
prélèvement (une représentation graphique peut être utile);
6 © ISO 2015 – Tous droits réservés

d) les critères de désignation de la salle propre ou de la zone propre considérée, comprenant le numéro
de classe ISO, l’état d’occupation pertinent et les tailles particulaires prises en compte;
e) la description détaillée de la méthode d’essai en y incluant les conditions particulières d’essai ou les
écarts par rapport à la méthode d’essai et l’identification des appareils de mesure et leur certificat
d’étalonnage en cours de validité;
f) les résultats des essais avec les données de concentration particulaire pour tous les points
échantillonnés.
Si les concentrations des macroparticules sont quantifiées, comme décrit à l’Annexe C, il convient de
mentionner l’information appropriée dans le rapport d’essai.
Annexe A
(normative)
Méthode de référence pour la classe de propreté particulaire
de l’air
A.1 Principe
À chaque point de prélèvement prévu, un compteur de particules est utilisé, de façon à obtenir la
concentration des particules en suspension dans l’air qui ont une taille égale ou supérieure aux
tailles spécifiées.
A.2 Exigences liées à l’appareil
A.2.1 Compteur de particules
L’instrument doit disposer de moyens d’affichage ou d’enregistrement du nombre et de la taille des
particules individuelles en suspension dans l’air et doit présenter une sensibilité granulométrique
permettant de détecter la concentration particulaire totale dans les intervalles granulométriques
appropriés pour la classe considérée.
NOTE Les compteurs de particules individuelles utilisant la diffusion de la lumière (LSAPC) sont usuellement
utilisés pour entreprendre la classe de propreté particulaire.
A.2.2 Étalonnage de l’instrument
Le compteur de particules doit être accompagné d’un certificat d’étalonnage en cours de validité;
il convient que la méthode et la fréquence d’étalonnage tiennent compte de la pratique actuellement
[1]
admise et spécifiée dans l’ISO 21501-4 .
NOTE Certains compteurs ne peuvent pas être étalonnés selon toutes les exigences de l’ISO 21501-4. Dans ce
cas la décision d’utiliser un tel compteur doit être consignée dans le rapport d’essai.
A.3 Préparation des essais de comptage particulaire
Avant les essais, vérifier que tous les aspects pertinents de la salle propre ou de la zone propre
qui concourent à son intégrité sont achevés et fonctionnent conformément à la spécification des
performances.
Il convient de prêter attention à la détermination de l’enchaînement des essais préalables
complémentaires à réaliser pour vérifier les performances de la salle propre. L’ISO 14644-3, Annexe A
en fournit une liste.
A.4 Détermination des points de prélèvement
A.4.1 Définir le nombre de points de prélèvement
Prendre le nombre minimal de points de prélèvement N du Tableau A.1 Ce dernier fournit le nombre
L
de points de prélèvement en fonction de la surface de chaque salle propre ou zone propre à classer. Ce
nombre minimal garantit, avec au moins 95 % de confiance, qu’au moins 90 % de la surface de la salle
propre ne dépassent pas les limites de classe.
8 © ISO 2015 – Tous droits réservés

Tableau A.1 — Points de prélèvement en fonction de la surface de la salle propre
Surface de la salle propre (m ) infé- Nombre minimal de points de prélè-
rieure ou égale à vement (N )
L
2 1
4 2
6 3
8 4
10 5
24 6
28 7
32 8
36 9
52 10
56 11
64 12
68 13
72 14
76 15
104 16
108 17
116 18
148 19
156 20
192 21
232 22
276 23
352 24
436 25
636 26
1 000 27
> 1 000 Voir la Formule (A.1)
NOTE 1 à l’article:  Si la surface de la zone considérée tombe entre deux valeurs dans le
tableau, il convient de retenir la plus grande.
NOTE 2 à l’article:  Dans le cas d’un flux unidirectionnel, la surface à prendre en compte peut
être considérée comme étant le plan de coupe perpendiculaire au sens d’écoulement de l’air.
Dans tous les autres cas, la surface considérée sera le plan horizontal de la salle propre ou de
la zone propre.
A.4.2 Localisation des points de prélèvement
Afin de déterminer l’emplacement des points de prélèvement:
a) identifier le nombre minimal N de points de prélèvement dans le Tableau A.1;
L
b) utiliser ce nombre pour diviser la salle propre ou la zone propre en N sections de surface égale;
L
c) choisir un point de prélèvement représentatif des caractéristiques dans chacune de ces sections;
d) positionner la sonde du compteur de particules à hauteur de travail, ou à tout autre point spécifié.
Des points de prélèvement supplémentaires peuvent être sélectionnés pour des emplacements
considérés comme critiques. Leur nombre et emplacement doivent être convenus et spécifiés.
Pour faciliter le découpage de la zone en sections égales, on pourra choisir d’ajouter des sections et
leurs points de prélèvements associés.
Dans le cas de salles propres ou zones propres à écoulement non unidirectionnel, des points de
prélèvement situés directement à l’aplomb de points de soufflage non diffusés sont susceptibles de ne
pas être représentatifs.
A.4.3 Localisation des points de prélèvement dans de grandes salles propres ou
zones propres
Quand la surface de la salle propre ou zone propre est supérieure à 1 000 m , utiliser la Formule (A.1)
qui suit pour déterminer le nombre minimum de points de prélèvement nécessaires.
 


A


N =×27  (A.1)


L


1000
 
 

N représente le nombre minimal de points de prélèvement à évaluer, arrondi au nombre entier
L
supérieur;
A représente la surface de la salle propre en m .
A.4.4 Détermination des volumes élémentaires et des durées de prélèvement à chaque
point de prélèvement
À chaque point de prélèvement, prélever un volume d’air de sorte que si la concentration pour la plus
grosse taille de particule sélectionnée était à la limite supérieure de la classe ISO visée, au moins
20 particules seraient comptées.
Le volume élémentaire V à prélever à chaque point est déterminé au moyen de la Formule (A.2):
s
 

 20



V = ×1000 (A.2)


s


C

 
 nm, 

V représente le volume élémentaire minimal à prélever à chaque point, exprimé en litres (excepté
s
dans le cas de l’Annexe D);
C représente la limite de la classe visée (en nombre de particules par mètre cube) pour la plus
n,m
grosse taille de particule considérée;
20 représente le nombre de particules qui serait compté si la concentration en particules atteignait
la limite de la classe visée.
Le volume prélevé à chaque point doit être d’au moins 2 l, et la durée de prélèvement au moins une
minute pour chaque échantillon à chaque point de prélèvement. Chaque volume prélevé à chaque point
de prélèvement doit être identique.
Lorsque V est très grand, la durée de prélèvement requise peut être importante. Le recours au mode
s
opératoire de prélèvement séquentiel peut permettre de réduire à la fois la durée de prélèvement et le
volume à prélever.
10 © ISO 2015 – Tous droits réservés

A.5 Mode opératoire de prélèvement
A.5.1 Préparer le compteur de particules (voir A.2) suivant les instructions du fabricant et réaliser une
vérification du comptage à zéro.
A.5.2 La sonde de prélèvement doit être disposée face à l’écoulement. Si la direction de l’écoulement
à échantillonner n’est pas maîtrisée ou prévisible (par exemple, un écoulement non unidirectionnel),
l’entrée de la sonde de prélèvement doit être dirigée vers le haut.
A.5.3 S’assurer que les conditions sont stables et appropriées à l’état d’occupation considéré avant de
débuter les prélèvements.
A.5.4 Prélever au moins le volume d’air calculé suivant A.4.4 en chaque point de prélèvement, et pour
chaque échantillon prélevé.
A.5.5 Si un résultat non conforme trouvé sur un point de prélèvement est dû à un incident anormal
identifié, alors cette valeur peut être éliminée et notée comme telle sur le rapport d’essai et un nouveau
prélèvement peut être effectué.
A.5.6 Si un résultat non conforme trouvé sur un point de prélèvement est dû à une défaillance
technique de la salle propre ou d’un équipement, il convient d’en identifier la cause, d’effectuer une
action corrective et de réaliser de nouveaux essais du point de prélèvement non conforme, des points
adjacents et de tout autre point impacté. Le choix des points doit être clairement documenté et justifié.
A.6 Traitement des résultats
A.6.1 Enregistrement des résultats
Enregistrer le résultat de chaque prélèvement sous la forme du nombre de particules comptées
dans chaque volume élémentaire pour chaque taille de particule considérée selon la classe ISO de
propreté visée.
NOTE pour des compteurs de particules affichant automatiquement la concentration au volume de référence
cette opération manuelle pourra ne pas être nécessaire.
A.6.1.1 Concentration particulaire moyenne en chaque point de prélèvement
Si au moins deux prélèvements sont effectués en un point donné, calculer la moyenne du nombre de
particules selon la Formule (A.3) à partir des mesures individuelles effectuées pour chaque taille de
particule considérée et l’enregistrer.
 
xx++ .x


ii.12 in.


x = (A.3)


i 

n 

 

est le nombre moyen de particules au point de prélèvement i, représentant n’importe quel
x
i
point;
x à x représentent les nombres de particules à chaque prélèvement;
i.1 i.n
n représente le nombre de prélèvements effectués au point i.
A.6.1.2 Calculer la concentration par mètre cube
x ×1000
i
C = (A.4)
i
V
t

C est la concentration des particules par mètre cube;
i
est le nombre moyen de particules au point de prélèvement i, représentant chaque point;
x
i
V représente le volume élémentaire de prélèvement spécifié, exprimé en litres.
t
A.6.2 Interprétation des résultats
A.6.2.1 Exigences de classification
La salle ou la zone propre sera considérée comme conforme à la classe de propreté de l’air spécifiée si la
moyenne des concentrations en particules exprimée en nombre de particules par mètre cube mesurée
à chaque point de prélèvement ne dépasse pas la limite de concentration spécifiée dans le Tableau A.1.
Si des classes ou des tailles de particules intermédiaires sont spécifiées selon l’Annexe E, il convient de
fixer des limites de classe appropriées déterminées au moyen du Tableau E.1 ou de la Formule (E.1).
A.6.2.2 Résultat non conforme
En cas de résultat non conforme, une investigation doit être entreprise. Le résultat de cette investigation
et l’action corrective doivent être notés dans le rapport d’essai (voir 5.4).
12 © ISO 2015 – Tous droits réservés

Annexe B
(informative)
Exemples d’application de calculs de classes
B.1 Exemple 1
B.1.1 Une salle propre en activité a une superficie de 18 m et est spécifiée pour une propreté
particulaire de l’air de classe ISO 5. Lla classification sera réalisée à l’aide d’un compteur de particules
ayant un débit de prélèvement de 28,3 l/min. Deux tailles particulai
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...

ISO 14644-1:2015는 클린룸 및 관련 통제된 환경에서 공기 청정도를 입자 농도로 분류하기 위한 표준으로, 공기 중 입자의 농도를 측정하고 분류하는 방법을 명확하게 규정하고 있습니다. 이 표준의 주된 범위는 0.1 µm에서 5 µm 사이의 입자 크기를 기준으로 하는 집합적 분포를 기준으로 하며, 여기에는 특정한 하한 입자 크기를 기준으로 한 입자 농도 분류가 포함됩니다. ISO 14644-1:2015의 강점 중 하나는 공기 중 입자의 농도를 정확하게 측정할 수 있는 광산란식 공기 중 입자 계수기(LSAPC)를 사용하는 점입니다. 이 방법은 지정된 샘플링 위치에서 공기 중 입자의 농도를 정량적으로 확인할 수 있도록 하여, 클린룸의 청정도 관리를 위한 기초 데이터를 제공합니다. 또한 이 표준은 0.1 µm 이하의 초미세입자나 5 µm 이상의 대입자에 대한 분류는 별도의 표준에서 다루어진다는 점에서 명확하게 범위를 제한하여, 관련된 규정의 일관성을 유지하고 있습니다. 이 표준은 공기가 특정 요구 사항을 충족하도록 보장하는 데 필수적인 요소로 작용하고 있으며, 특히 반도체, 제약, 생명 과학 및 기타 고급 제조 산업에서 매우 중요한 역할을 합니다. 따라서 ISO 14644-1:2015는 클린룸의 운영 및 관리를 위한 중요한 기준으로 간주될 수 있으며, 입자 농도에 대한 명확한 분류를 통해 산업 전반의 품질 보증 수준을 향상시키는 데 기여하고 있습니다.

ISO 14644-1:2015は、クリーンルームおよび関連する制御環境における空気の清浄度の分類を定義するための重要な基準です。この標準は、空気中の微粒子の濃度に基づいて清浄度を評価するための枠組みを提供しており、特に0.1µmから5µmの範囲にある粒子の累積分布を考慮しています。 本標準の強みは、空気清浄度の分類が確立された方法に基づいている点です。光散乱(分散)式空気中微粒子カウンター(LSAPC)を利用することで、明確な基準に従った測定が可能であり、第一級の精度で粒子濃度を評価できます。これにより、クリーンルームの環境管理において必要とされる信頼性の高いデータが提供されます。 ISO 14644-1:2015は、特定の状態下での空気清浄度評価という焦点を持っているため、クリーンルームや無菌環境の運営における非常に重要な要素となっています。他の境界線以下の粒子サイズ(0.1µm未満)の分類は別の標準で扱われる予定であり、その専門性がクリーンルームの管理における複雑さを増しつつあることも、関係者にとって知識の深化を促します。 また、ISO 14644-1:2015では、5µmを超えるマクロ粒子の量を評価するためにM記述子が使用できる点も特筆すべきです。これにより、より広範囲な粒子範囲についての洞察が得られ、清浄環境の管理における総合的なアプローチを可能にします。 総じて、ISO 14644-1:2015は、空気の清浄度を分類するための明確かつ体系的な基準を提供し、クリーンルームの運営において不可欠な役割を果たしています。その適用範囲の広さと測定手法の信頼性により、業界内での重要性はますます高まることでしょう。

ISO 14644-1:2015 provides a comprehensive framework for the classification of air cleanliness in cleanrooms and controlled environments, focusing specifically on the concentration of airborne particles. The standard's scope is well-defined, emphasizing particle sizes ranging from 0.1 µm to 5 µm, which are crucial for ensuring that cleanroom environments meet rigorous cleanliness standards necessary for various industries, including pharmaceuticals, biotechnology, and semiconductor manufacturing. One of the key strengths of ISO 14644-1:2015 is its reliance on light scattering airborne particle counters (LSAPC) for measuring particle concentration. This method ensures accuracy and reliability in monitoring air cleanliness, which is essential for maintaining the integrity of sensitive processes and products. The classification system based on cumulative distributions of particle sizes allows for a tailored approach to air cleanliness, enabling organizations to identify specific cleanliness levels that match their operational requirements. Furthermore, the document's clarity in not including ultrafine particles (under 0.1 µm) within its classification scheme highlights a focused approach. It indicates the importance of addressing such particles separately, promoting the development of a future standard that will cater specifically to nano-scale air cleanliness. This forward-thinking aspect of ISO 14644-1:2015 demonstrates its relevance in the context of evolving technologies and industry needs. Additionally, the optional inclusion of an M descriptor, as detailed in Annex C, provides flexibility for quantifying macroparticles over 5 µm. This feature enhances the applicability of the standard across different environments and operational contexts. In conclusion, ISO 14644-1:2015 stands out for its structured methodology and strategic relevance, serving as a cornerstone for establishing air cleanliness standards within cleanrooms and associated controlled environments. The standard effectively addresses the challenges posed by airborne particle concentrations, ensuring that organizations can maintain the necessary levels of cleanliness required for high-stakes applications.