Test requirements for low voltage aerial bundled cable accessories -- Part 1: Generalities

EN 50483 series applies to overhead line fittings for tensioning, supporting and connecting aerial bundled cables (ABC) of rated voltage U0/U (Um): 0,6/1 (1,2) kV. The objective is to provide a method of testing the suitability of accessories when used under normal operating conditions with low voltage aerial bundled cables (ABC) complying with HD 626. There is variation between the different ABC specifications provided by HD 626, and tests carried out on one of the ABC types may not be completely applicable to ABC of a different specification. Therefore, the purchasers of accessories tested to this European Standard, must ensure that all their requirements are met.

Prüfanforderungen für Bauteile für isolierte Niederspannungsfreileitungen – Teil 1: Allgemeines

EN 50483 (Reihe) gilt für oberirdisch zu verwendende Bauteile zum Abspannen, Aufhängen und Verbinden von iso¬lierten Freileitungen (en.: Aerial Bundled Cables, ABC) für eine Nennspannung von U0/U (Um): 0,6/1 (1,2) kV. Der mit dieser Norm verbundene Zweck besteht darin, ein Verfahren zur Verfügung zu stellen, mit dem die Eignung der Bauteile zur Verwendung mit isolierten Niederspannungsfreileitungen (ABC) nach HD 626 unter normalen Betriebsbedingungen geprüft werden kann. Es gibt Abweichungen zwischen den unterschiedlichen nach HD 626 erstellten ABC-Spezifikationen, und Prü¬fungen, die an einer der unterschiedlichen ABC-Bauarten durchgeführt wurden, sind möglicherweise nicht in vollem Umfang auf ABC einer anderen Spezifikation anwendbar. Daher müssen Auftraggeber von nach dieser Europäischen Norm geprüften Bauteilen sicherstellen, dass alle ihre Anforderungen erfüllt werden. ANMERKUNG   Durch diese Europäische Norm verlieren bestehende Zulassungen nicht ihre Gültigkeit, die auf der Basis nationaler Normen und Spezifikationen und/oder anhand des Nachweises zufriedenstellender  Ergebnisse im Einsatz erfolgte. Jedoch gelten nach früheren Normen oder Spezifikationen zugelassene Produkte nicht als nach dieser Europäischen Norm zugelassen. Es ist möglich, basierend auf einer Vereinbarung zwischen Lieferanten und Auftraggeber und/oder der zuständigen Stelle für Konformitätsbewertungen, nachzuweisen, dass die Konformität mit der früheren Norm für den Anspruch auf Konformität mit dieser Norm verwendet werden kann, vorausgesetzt, eine Bewertung aller zusätzlichen Typprüfungen, deren Durchführung erforderlich sein könnte, ist erfolgt. Alle zusätzlichen Prüfungen, die Teil einer Prüffolge sind, dürfen nicht separat durchgeführt werden. Die klimatischen Bedingungen variieren in Europa in erheblichem Maße, und um diesen unterschiedlichen geografischen Klimabedingungen gerecht werden zu können, ist eine entsprechende Reihe von Prüfungen erforderlich. An dieser Stelle wird eine Reihe zusätzlicher freiwilliger Prüfungen festgelegt, die den verschie-denen klimatischen Anforderungen entsprechen und zwischen Kunden und Lieferanten vereinbart werden sollten (siehe Anhang C in EN 50483-6). Zweck des vorliegenden Teil 1 dieser Norm ist es, die allgemeinen Aspekte der in den obigen Anwendungs-bereich fallenden Produkte festzulegen.

Prescriptions relatives aux essais des accessoires pour réseaux aériens basse tension torsadés -- Partie 1: Généralités

La série EN 50483 s’applique aux équipements de lignes aériennes pour ancrage, suspension et raccordement des câbles torsadés aériens de tension assignée U0/U (Um): 0,6/1 (1,2) kV. L’objectif est de fournir une méthode pour tester l’aptitude des accessoires lorsqu’ils sont utilisés dans des conditions normales de service sur les câbles torsadés aériens basse tension définis dans le HD 626. Il y a des écarts entre les différentes spécifications des torsades décrites dans le HD 626 et les essais effectués sur un des types de torsade peuvent ne pas être complètement applicables à une torsade d’une autre spécification. En conséquence, les acheteurs d’accessoires testés selon cette Norme Européenne doivent s’assurer que toutes leurs exigences sont satisfaites. NOTE   La présente Norme Européenne n’annule pas les approbations existantes des produits obtenues sur la base de normes ou spécifications nationales et/ou obtenues par la démonstration de performance satisfaisante en service. Cependant, des produits approuvés selon de telles normes ou spécifications nationales ne peuvent directement réclamer l’approbation à la présente Norme Européenne. Il peut être possible, sous réserve d’un accord entre le fournisseur et l’acheteur et/ou l’organisme compétent d’évaluation de conformité, de démontrer que l’ancienne conformité peut être utilisée pour se réclamer de la conformité à la présente norme, pourvu qu’une évaluation soit faite à partir de tout essai additionnel de type qui pourrait être nécessaire. Un tel essai additionnel faisant partie d’une séquence d’essais ne peut être réalisé séparément. Le climat diffère à travers l’Europe et pour s’adapter aux différentes conditions climatiques, il est nécessaire de proposer une gamme d’essais pour y répondre. Une gamme des essais optionnels et additionnels est fournie pour satisfaire les besoins climatiques variables et ces essais devraient être réalisés selon accord entre client et fournisseur (voir l’Annexe C dans la EN 50483-6). Le but de cette Partie 1 est de définir les aspects communs des produits inclus dans le domaine d’application ci-dessus

Zahteve za preskušanje pribora za nizkonapetostne izolirane nadzemne kable - 1. del: Glavne točke

General Information

Status
Published
Public Enquiry End Date
30-Sep-2007
Publication Date
21-May-2009
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
12-May-2009
Due Date
17-Jul-2009
Completion Date
22-May-2009

Buy Standard

Standard
EN 50483-1:2009
English language
24 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 50483-1:2009
01-julij-2009
=DKWHYH]DSUHVNXãDQMHSULERUD]DQL]NRQDSHWRVWQHL]ROLUDQHQDG]HPQHNDEOH
GHO*ODYQHWRþNH
Test requirements for low voltage aerial bundled cable accessories -- Part 1: Generalities
Prüfanforderungen für Bauteile für isolierte Niederspannungsfreileitungen – Teil 1:
Allgemeines
Prescriptions relatives aux essais des accessoires pour réseaux aériens basse tension
torsadés -- Partie 1: Généralités
Ta slovenski standard je istoveten z: EN 50483-1:2009
ICS:
29.240.20 Daljnovodi Power transmission and
distribution lines
SIST EN 50483-1:2009 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 50483-1:2009

---------------------- Page: 2 ----------------------

SIST EN 50483-1:2009

EUROPEAN STANDARD
EN 50483-1

NORME EUROPÉENNE
January 2009
EUROPÄISCHE NORM

ICS 29.240.20


English version


Test requirements for low voltage aerial bundled cable accessories -
Part 1: Generalities



Prescriptions relatives aux essais  Prüfanforderungen für Bauteile für isolierte
des accessoires pour réseaux aériens Niederspannungsfreileitungen -
basse tension torsadés - Teil 1: Allgemeines
Partie 1: Généralités





This European Standard was approved by CENELEC on 2008-12-01. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: avenue Marnix 17, B - 1000 Brussels


© 2009 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 50483-1:2009 E

---------------------- Page: 3 ----------------------

SIST EN 50483-1:2009
EN 50483-1:2009 – 2 –
Foreword
This European Standard was prepared by a sub-group of WG 11 of the Technical Committee
CENELEC TC 20, Electric cables.
The text of the draft was submitted to the formal vote and was approved by CENELEC as EN 50483-1
on 2008-12-01.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2009-12-01
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2011-12-01
This is Part 1 of CENELEC standard EN 50483 “Test requirements for low voltage aerial bundled
cable accessories”, which has six parts:
– Part 1: Generalities;
– Part 2: Tension and suspension clamps for self supporting system;
– Part 3: Tension and suspension clamps for neutral messenger system;
– Part 4: Connectors;
– Part 5: Electrical ageing test;
– Part 6: Environmental testing.
__________

---------------------- Page: 4 ----------------------

SIST EN 50483-1:2009
– 3 – EN 50483-1:2009
Contents
1 Scope .4
2 Normative references .4
3 Terms and definitions .5
4 Symbols .8
5 Products concerned .8
6 Marking .8
7 Quality procedure .8
8 Routine and sample tests .8
8.1 Checking compliance of the supplied products . 9
8.2 Final inspection and testing . 9
8.3 Inspection and test records . 9
9 Type tests . 10
9.1 General test conditions . 10
9.2 Test for permanent marking . 11
9.3 Tests and sample selection . 11
9.4 Test reports . 11
Annex A (normative) List of tests for compliance . 13
Annex B (normative) Test selection – Samples needed for type tests . 15
Annex C (informative) Highest rated temperatures of insulating compounds . 23
Bibliography . 24

Tables
Table A.1 – Selective table for type tests, sample tests and routine tests . 13
Table B.1 – Tension clamps for self supporting system – EN 50483-2 . 15
Table B.2 – Suspension clamps for self supporting system – EN 50483-2 . 16
Table B.3 – Tension clamps for neutral messenger – EN 50483-3 . 17
Table B.4 – Suspension clamps for neutral messenger – EN 50483-3 . 18
Table B.5 – Insulation piercing connectors (IPC) – EN 50483-4 . 19
Table B.6 – Preinsulated sleeves – EN 50483-4 . 21
Table B.7 – Preinsulated lugs – EN 50483-4 . 22

---------------------- Page: 5 ----------------------

SIST EN 50483-1:2009
EN 50483-1:2009 – 4 –
1 Scope
EN 50483 series applies to overhead line fittings for tensioning, supporting and connecting aerial
bundled cables (ABC) of rated voltage U /U (U ): 0,6/1 (1,2) kV.
0 m
The objective is to provide a method of testing the suitability of accessories when used under normal
operating conditions with low voltage aerial bundled cables (ABC) complying with HD 626.
There is variation between the different ABC specifications provided by HD 626, and tests carried out
on one of the ABC types may not be completely applicable to ABC of a different specification.
Therefore, the purchasers of accessories tested to this European Standard, must ensure that all their
requirements are met.
NOTE  This European Standard does not invalidate existing approvals of products achieved on the basis of national standards
and specifications and/or the demonstration of satisfactory service performance. However, products approved according to such
national standards or specifications cannot directly claim approval to this European Standard. It may be possible, subject to
agreement between supplier and purchaser, and/or the relevant conformity assessment body, to demonstrate that conformity to
the earlier standard can be used to claim conformity to this standard, provided an assessment is made of any additional type
testing that may need to be carried out. Any such additional testing that is part of a sequence of testing cannot be done
separately.
Climate differs across Europe and in order to meet the differing geographic climatic conditions it is
necessary to provide a range of tests to meet these variations. A range of optional, additional tests is
provided to meet the varying climatic needs and these should be agreed between the customer and
the supplier (see Annex C in EN 50483-6).
The purpose of this Part 1 is to define the common aspects of the products included in the above
scope.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 50182:2001, Conductors for overhead lines – Round wire concentric lay stranded conductors
EN 50483 series, Test requirements for low voltage aerial bundled cable accessories
EN 60068-1:1994, Environmental testing – Part 1: General and guidance (IEC 60068-1:1988 +
corrigendum Oct. 1988 + A1:1992)
EN 61238-1:2003, Compression and mechanical connectors for power cables for rated voltages up to
36 kV (U = 42 kV) – Part 1: Test methods and requirements (IEC 61238-1:2003, mod.)
m
EN ISO 9001:2008, Quality management systems – Requirements (ISO 9001:2008)
HD 626, Overhead distribution cables of rated voltage U /U(U ): 0,6/1 (1,2) kV
o m
IEC 60050-461, International Electrotechnical Vocabulary (IEV) – Part 461: Electric cables

---------------------- Page: 6 ----------------------

SIST EN 50483-1:2009
– 5 – EN 50483-1:2009
3 Terms and definitions
For the purposes of this document, the terms and definitions given in IEC 60050-461 and the following
apply.
3.1
adiabatic
occurring with no addition or loss of heat from the system under consideration
3.2
aerial bundled cable (ABC)
aerial cable consisting of a group of insulated conductors which are twisted together including, or not,
a non insulated conductor
[IEV 461-08-02, modified]
NOTE The terms bundled conductors, bundled cables, bundled cores, conductor bundles and bundle could be used as
equivalent to the term aerial bundled cable (ABC).
3.3
aerial-insulated-cable
insulated cable designed to be suspended overhead and outdoors
[IEV 461-08-01]
3.4
angle of deviation
complementary angle to the angle defined by the two parts of the cable on both sides of the
suspension clamp
3.5
branch connector
metallic device for connecting a branch conductor to a main conductor at an intermediate point on the
latter
[IEV 461-17-05]
3.6
branch conductor
conductor connected to the main conductor by a connector
3.7
clamp bolt
bolt which tightens two parts of a clamp together
3.8
conductor insulation
insulation applied on a conductor
[IEV 461-02-02, modified]
3.9
conductor (of a cable)
part of a cable which has the specific function of carrying current
[IEV 461-01-01]
3.10
connector
metallic device to connect cable conductors together
[IEV 461-17-03]

---------------------- Page: 7 ----------------------

SIST EN 50483-1:2009
EN 50483-1:2009 – 6 –
3.11
core
assembly comprising conductor and its own insulation
[IEV 461-04-04, modified]
3.12
equalizer
arrangement used in the test loop to ensure a point of equipotential in a stranded conductor
[EN 61238-1:2003, 3.8]
3.13
fixture (or fitting)
device for attaching ABC tension or/and suspension clamps to a pole or to a wall
3.14
insulation (of a cable)
insulating materials incorporated in a cable with the specific function of withstanding voltage
[IEV 461-02-01]
3.15
insulation piercing connector (IPC)
connector in which electrical contact with the conductor is made by metallic protrusions which pierce
the insulation of the ABC core
[IEV 461-11-08, modified]
3.16
median connector
connector which during the first heat cycle records the third highest temperature of the six connectors
in the test loop
[EN 61238-1:2003, 3.11]
3.17
messenger
wire or rope, the primary function of which is to support the cable in aerial installations, which may be
separate from or integral with the cable it supports
[IEV 461-08-03]
3.18
minimum breaking load (MBL)
minimum breaking load of the conductor given by HD 626 or the cable manufacturer if not defined in
the standard, or minimum breaking load of the clamp given by the clamp manufacturer
3.19
mobile link
device linking the suspension clamp to the fixture
3.20
neutral messenger system
aerial insulated system where only the neutral messenger supports the ABC
3.21
pre-insulated (terminal) lug
insulated metallic device for connecting an insulated cable conductor to other electrical equipment
3.22
pre-insulated through connector (sleeve)
insulated metallic device for connecting two consecutive lengths of insulated conductors
3.23
rated tensile strength (RTS)
estimate of the conductor breaking load calculated using the specified tensile properties of the
component wires
[EN 50182:2001, 3.7]

---------------------- Page: 8 ----------------------

SIST EN 50483-1:2009
– 7 – EN 50483-1:2009
3.24
recycling code
mark(s), on a product, which identifies(y) the constituent material(s) of the product
3.25
reference conductor
length of conductor(s) without any joints, which is included in the test loop and which enables the
reference temperature and reference resistance(s) to be determined
[EN 61238-1:2003, 3.7, modified]
3.26
reusable connector
connector for connecting ABC to stripped cable or bare conductor where only the branch connection
can be reused
3.27
routine test
test made on all accessories to demonstrate their integrity
3.28
sample test
test made on samples of a product or components taken from a product adequate to verify that the
finished product meets the design specifications
3.29
self supporting system
aerial insulated system where all the cores of the ABC contribute to its support
3.30
sheath
uniform and continuous tubular covering of metallic or non metallic material, generally extruded
[IEV 461-05-03]
3.31
shear head
head of a bolt, or a device fitted over the head of a bolt or a nut, which is designed to break at a
specified torque
3.32
suspension clamp
device which attaches an aerial insulated cable to a fixture in order to carry its weight and any
specified loading
[IEV 461-18-02, modified]
3.33
suspension or tension assembly
clamp with mobile link, or not, and associated fixture
3.34
tension clamp
device which firmly attaches an aerial insulated cable to a fixture and is designed to transmit the
specified mechanical tension in the cable or messenger to the supporting structure
[IEV 461-18-01, modified]
3.35
traceability code
mark(s), on a product, which gives information about its manufacture and year of production
3.36
type test
test required to be made before supplying a type of material covered by this standard on a general
commercial basis, in order to demonstrate satisfactory performance characteristics to meet the
intended application

---------------------- Page: 9 ----------------------

SIST EN 50483-1:2009
EN 50483-1:2009 – 8 –
NOTE  These tests are of such a nature that, after they have been made, they need not be repeated unless changes are made
to the accessory materials, design or type of manufacturing process which might change the performance characteristics.
4 Symbols
A list of symbols is available with each part of the standard where applicable.
5 Products concerned
This European Standard applies to the following products:
– tension and suspension clamps for low voltage ABC self supporting system. The type tests are
defined in EN 50483-2;
– tension and suspension clamps for low voltage ABC supporting system with neutral messenger.
The type tests are defined in the EN 50483-3;
– connectors including insulation piercing connectors (IPC), pre-insulated lugs and through
connectors (sleeves) for low voltage ABC systems. The type tests are defined in EN 50483-4.
NOTE  Diagrams show a representation of fittings only and do not indicate any preference of design.
Some type tests are common to several products and have been published under specific standards:
– heat cycling test under EN 50483-5;
– environmental tests under EN 50483-6.
6 Marking
All products mentioned above shall permanently bear:
– manufacturer’s trade mark or logo;
– product code or reference;
– traceability code / batch number;
– the minimum and maximum cross section for which the unit is suitable;
– tightening torque or die reference, if applicable;
– recycling code, if any.
NOTE  Other specific markings should be agreed between customer and manufacturer.
A test for marking is provided in 9.2.
7 Quality procedure
In order to claim compliance with this European Standard, products covered within the series
EN 50483 shall be submitted to all the relevant tests defined in Annexes A and B, and meet the
relevant requirements. The manufacturer shall provide the results of the tests in writing.
8 Routine and sample tests
Compliance of the supplied products shall be established by presenting the results of the tests listed in
Annex A.

---------------------- Page: 10 ----------------------

SIST EN 50483-1:2009
– 9 – EN 50483-1:2009
8.1 Checking compliance of the supplied products
8.1.1 With a quality assurance system
Within this system, the quality plan specific to the product shall specify the procedure of the tests to be
carried out and their frequency.
This plan shall be made by the manufacturer and given to the customer as a part of the contractual
relationship involving the Quality Assurance. The standard model of Quality Management Systems to
be adopted by the manufacturer is described in EN ISO 9001:2008 standard.
8.1.2 Without quality assurance system
These tests shall be carried out on randomly sampled items from each supplied batch according to a
standard or procedure jointly determined by the manufacturer and the purchaser.
It is assumed that these tests are representative of the whole batch.
8.1.2.1 Tests and inspection
The manufacturer or supplier shall, as a minimum, establish and maintain documented procedures for
inspection and testing activities in order to verify that the specified requirements are met. The required
inspection and testing procedures shall be provided in writing.
8.1.2.1.1 Receiving inspection and testing
The manufacturer shall ensure that incoming products are not used or processed until they have been
inspected or otherwise verified as conforming to specified requirements. Verification of conformance to
the specified requirements shall be in accordance with the quality plan and/or documented
procedures.
In determining the amount and nature of receiving inspection, consideration shall be given to the
amount of control at the subcontractor’s premises and the recorded evidence of conformance
provided.
8.1.2.1.2 In-process inspection and testing
The manufacturer shall
a) inspect and test the product as required by the quality plan and/or documented procedure,
b) hold product until the required inspection and tests have been completed or necessary reports
have been received and verified.
8.2 Final inspection and testing
The supplier shall carry out all final inspection and testing in accordance with the quality plan and/or
documented procedures to complete the evidence of conformance of the finished product to the
specified requirements.
The quality plan and/or documented procedures for final inspection and testing shall require that all
specified inspection and tests, including those specified either on receipt of product or in process,
have been carried out and that the results meet the specified requirements.
No product shall be dispatched until all activities specified in the quality plan and/or documented
procedures have been satisfactorily completed and the associated data and documentation are
available and authorized.
8.3 Inspection and test records
The supplier shall establish and maintain records which provide that the products have been inspected
and/or tested. The results shall show clearly whethe
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.