SIST EN 14308:2010
Thermal insulation products for building equipment and industrial installations - Factory made rigid polyurethane foam (PUR) and polyisocyanurate foam (PIR) products - Specification
Thermal insulation products for building equipment and industrial installations - Factory made rigid polyurethane foam (PUR) and polyisocyanurate foam (PIR) products - Specification
This European Standard specifies the requirements for factory made rigid polyurethane foam (PUR) and polyisocyanurate foam (PIR) products, with a closed cell content not less than 90 %, with or without facings, which are used for the thermal insulation of building equipment and industrial installations, with an operating temperature range of approximately, - 200 °C to + 200 °C. The products are manufactured in the form of blocks, faced or unfaced boards, pipe sections, segments and prefabricated ware. This standard describes product characteristics and includes procedures for testing, evaluation of conformity, marking and labelling. Products covered by this standard are also used in prefabricated thermal insulating systems and composite panels; the performance of systems incorporating these products is not covered. This standard does not specify the required level of a given property that shall be achieved by a product to demonstrate fitness for purpose in a particular application. The levels required for a given application are to be found in regulations and invitations to tender. Products with a declared thermal conductivity greater than 0,100 W/(m • K) at 10 °C are not covered by this standard. This standard does not cover products for in situ-insulation (spraying or dispensing) or products for the insulation of the building structure. This standard does not cover the following acoustical aspects: direct airborne sound insulation and impact noise transmission index. 2 Normative references.
Wärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie - Werkmäßig hergestellte Produkte aus Polyurethan-Hartschaum (PUR) und Polyisocyanurat-Schaum (PIR) - Spezifikation
Dieses Dokument legt die Anforderungen für werkmäßig hergestellte Produkte aus Polyurethan-Hartschaum und Polyisocyanurat-Schaum mit einem Anteil von geschlossenen Zellen von mindestens 90 %, mit oder ohne Kaschierung, fest, die als Wärmedämmstoffe für die Haustechnik und betriebstechnische Anlagen im Temperaturbereich von etwa -200 °C bis + 200 °C benutzt werden.
ANMERKUNG Unterhalb einer Betriebstemperatur von -50 °C sind besondere Prüfungen bezüglich der Eignung der Produkte für den beabsichtigten Anwendungsfall ratsam (z. B. Sauerstoffverflüssigung). In jedem Fall sollten die Empfehlungen des Herstellers beachtet werden.
Die Produkte werden mit oder ohne Kaschierung in der Form von Platten, Rohrschalen, Segmenten und vorgefertigten Produkten hergestellt.
Dieses Dokument beschreibt die Stoffeigenschaften und enthält die Prüfverfahren und Festlegungen für die Konformitätsbewertung, die Kennzeichnung und die Etikettierung.
In diesem Dokument beschriebene Produkte werden auch in vorgefertigten Wärmedämmsystemen und Mehrschicht-Verbundplatten angewendet; die Eigenschaften von Systemen, in die diese Produkte integriert sind, werden nicht behandelt.
Dieses Dokument legt keine Leistungsstufen für eine vorgegebene Eigenschaft fest, die ein Produkt erreichen muss, um für einen bestimmten Anwendungsfall tauglich zu sein. Für bestimmte Anwendungen benötigte Stufen können Regelwerken oder Ausschreibungen entnommen werden.
Dieses Dokument gilt nicht für Produkte, deren Nennwert der Wärmeleitfähigkeit größer ist als 0,100 W/(m×K) bei 10 °C.
Dieses Dokument gilt nicht für Produkte für an der Verwendungsstelle hergestellte Wärmedämmung (eingeblasen oder geschüttet) oder Produkte, die zur Dämmung des Bauwerks bestimmt sind.
Dieses Dokument gilt nicht für die folgenden akustischen Zwecke: Luftschalldämmung und Trittschallübertragung.
Produits isolants thermiques pour l'équipement du bâtiment et les installations industrielles - Produits manufacturés de rigide polyuréthane (PUR) et en mousse polyisocyanurate (PIR) - Spécification
La présente Norme européenne spécifie les exigences relatives aux produits manufacturés en mousse rigide
de polyuréthane (PUR) et en mousse polyisocyanurate (PIR), ayant au moins 90 % de cellules fermées, avec
ou sans parements, utilisés pour l'isolation thermique de l’équipement du bâtiment et des installations
industrielles, dont la température de service se situe environ entre – 200 °C et + 200 °C.
NOTE Pour une température de service inférieure à – 50 °C, des essais particuliers sont recommandés pour
s'assurer de l'aptitude à l'emploi du produit dans l'application visée (p.ex. liquéfaction de l'oxygène). Il convient de se
référer systématiquement aux conseils du fabricant.
Les produits sont fabriqués sous la forme de blocs, de panneaux avec ou sans parements, de coquilles, de
segments et de pièces préfabriquées.
La présente norme décrit les caractéristiques des produits et comporte des modes opératoires d’essai,
d'évaluation de conformité, de marquage et d’étiquetage.
Les produits couverts par la présente norme sont également utilisés dans les systèmes d'isolation thermique
préfabriqués et les panneaux composites ; les performances des systèmes incorporant ces produits ne sont
pas traitées.
La présente norme ne spécifie pas le niveau requis pour une propriété donnée que doit posséder un produit
pour démontrer son aptitude à une application particulière. Les niveaux requis pour une application donnée
peuvent être trouvés dans les réglementations et les appels d’offre.
Les produits dont la conductivité thermique déclarée est supérieure à 0,100 W/(m·K) à 10 °C ne sont pas
couverts par la présente norme.
La présente norme ne couvre pas les produits pour isolation in situ (pulvérisation ou dispersion) ni ceux
destinés à l’isolation de la structure du bâtiment.
La présente norme ne couvre pas les aspects acoustiques suivants : isolement direct aux bruits aériens et
indice de transmission des bruits d'impact.
Toplotnoizolacijski proizvodi za opremo stavb in industrijske inštalacije - Proizvodi iz trde poliuretanske pene (PUR) in poliizocianuratne pene (PIR) - Specifikacija
Ta evropski standard določa zahteve za proizvode iz trde poliuretanske pene (PUR) in poliizocianuratne pene (PIR), ki se uporabljajo za toplotno izolacijo za opremo stavb in industrijske inštalacije z delovnim temperaturnim razponom med približno -200°C in +200°C. Proizvodi so narejeni v obliki kock, površinsko obdelanih ali neobdelanih plošč, cevnih izolacij, segmentov in montažnih artiklov. Ta standard opisuje značilnosti proizvodov in vključuje postopke preskušanja, vrednotenja skladnosti, označevanja in uporabe nalepk. Proizvodi, ki jih zajema ta standard, se uporabljajo pri montažnih termoizolacijskih sistemih in vezanih ploščah; zmogljivost sistemov, ki vključujejo te proizvode, ni zajeta. Ta standard ne določa zahtevane ravni določene lastnosti, ki jo mora doseči proizvod, da ustreza zahtevam za uporabnosti pri določenem načinu uporabe. Zahtevane ravni za določen način uporabe so navedene v pravilih in javnih razpisih. Ta standard ne zajema proizvodov z nazivno toplotno prevodnostjo nad 0,100 W/(mK) pri 10°C. Ta standard ne zajema proizvodov za in situ izolacijo (z razprševanjem ali odmerjanjem) ali proizvodov za izolacijo gradbene konstrukcije. Ta standard ne zajema naslednjih zvočnih vidikov: neposredne izolacije zvoka, ki se prenaša po zraku, in indeksa prenosa hrupa udarcev. 2. Normativne reference.
General Information
Relations
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Toplotnoizolacijski proizvodi za opremo stavb in industrijske inštalacije - Proizvodi iz trde poliuretanske pene (PUR) in poliizocianuratne pene (PIR) - SpecifikacijaWärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie - Werkmäßig hergestellte Produkte aus Polyurethan-Hartschaum (PUR) und Polyisocyanurat-Schaum (PIR) - SpezifikationProduits isolants thermiques pour l'équipement du bâtiment et les installations industrielles - Produits manufacturés de rigide polyuréthane (PUR) et en mousse polyisocyanurate (PIR) - SpécificationThermal insulation products for building equipment and industrial installations - Factory made rigid polyurethane foam (PUR) and polyisocyanurate foam (PIR) products - Specification91.100.60Thermal and sound insulating materialsICS:Ta slovenski standard je istoveten z:EN 14308:2009SIST EN 14308:2010en,de01-april-2010SIST EN 14308:2010SLOVENSKI
STANDARD
SIST EN 14308:2010
EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 14308
November 2009 ICS 91.100.60 English Version
Thermal insulation products for building equipment and industrial installations - Factory made rigid polyurethane foam (PUR) and polyisocyanurate foam (PIR) products - Specification
Produits isolants thermiques pour l'équipement du bâtiment et les installations industrielles - Produits manufacturés en mousse rigide de polyuréthane (PUR) et en mousse polyisocyanurate (PIR) - Spécification
Wärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie - Werkmäßig hergestellte Produkte aus Polyurethan-Hartschaum (PUR) und Polyisocyanurat-Schaum (PIR) - Spezifikation This European Standard was approved by CEN on 29 September 2009.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2009 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 14308:2009: ESIST EN 14308:2010
EN 14308:2009 (E) 2 Contents Page Foreword .4 1 Scope .6 2 Normative references .6 3 Terms, definitions, symbols, units and abbreviated terms .7 4 Requirements . 11 5 Test methods . 17 6 Designation code . 20 7 Evaluation of conformity . 21 8 Marking and labelling . 22 Annex A (normative)
Factory production control . 23 Annex B (normative)
Determination of minimum service temperature . 27 Annex C (normative)
Determination of the aged value of thermal conductivity and thermal resistance . 33 Annex D (informative)
Additional properties . 41 Annex ZA (informative)
Clauses of this European Standard addressing the provisions of the EU Construction Products Directive . 43 Bibliography . 51
Figures Figure B.1 — Dimensions of test specimens . 32Figure C.1 — Flow chart of the alternative ageing procedures . 34Figure ZA.1 — Example of CE marking information . 50Tables Table 1 — Dimensional tolerances . 12 Table 2 — Levels for dimensional stability . 13 Table 3 — Levels for compressive stress or compressive strength . 15 Table 4 — Test methods, test specimens and conditions. 18 Table A.1 — Minimum product testing frequencies . 23 Table A.2 — Minimum product testing frequencies for the reaction to fire characteristics . 25 Table C.1 — Increments for calculating the aged value of thermal conductivity . 36 Table C.2 — Increments for calculating the aged value of thermal conductivity Tmean = - 120 °C . 36 SIST EN 14308:2010
EN 14308:2009 (E) 3 Table C.3 — Increments for calculating the aged value of thermal conductivity Tmean = + 10 °C . 37 Table C.4 — Increments for calculating the aged value of thermal conductivity Tmean = + 120 °C . 37 Table C.5 — Safety increments to be added to the measured accelerated aged value of thermal conductivity . 39 Table D.1 — Test methods, test specimens, conditions and minimum testing frequencies . 42 Table ZA.1 — Relevant clauses. 44 Table ZA.2 — System(s) of attestation of conformity . 45 Table ZA.3 — Assignment of evaluation of conformity tasks for products under system 1 . 46 Table ZA.4 — Assignment of evaluation of conformity tasks for products under system 3 or system 3 combined with system 4 for reaction to fire . 47
SIST EN 14308:2010
EN 14308:2009 (E) 4 Foreword This document (EN 14308:2009) has been prepared by Technical Committee CEN/TC 88 “Thermal insulating materials and products”, the secretariat of which is held by DIN. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by May 2010, and conflicting national standards shall be withdrawn at the latest by August 2011. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive 89/106/EEC. For relationship with EU Directive 89/106/EEC, see informative Annex ZA, which is an integral part of this document. Locally responsible authorities and contracting entities, who are bound by EU Directives to specify their requirements using European harmonized product standards, are allowed to demand additional properties outside the provisions of this standard if this is technically necessary because of prevailing operational conditions of the building equipment or the industrial installation projected or because of safety regulations. This European Standard contains five annexes: Annex A (normative), Factory production control Annex B (normative), Determination of minimum service temperature Annex C (normative), Determination of the aged value of thermal conductivity Annex D (normative), Additional properties Annex ZA (informative), Clauses of this European Standard addressing the provisions of the EU Construction Products Directive This document includes a bibliography. This European Standard is one of a series of standards for insulation products used in building equipment and industrial installations, but this standard may be used in other areas where appropriate. In pursuance of Resolution BT 20/1993 revised, CEN/TC 88 have proposed defining the standards listed below as a package of European standards, setting 21 months after availability as the date of withdrawal (dow) of national standards which conflict with the European standards of this package. The package of standards comprises the following group of interrelated standards for the specifications of factory made thermal insulation products, all of which come within the scope of CEN/TC 88: EN 14303, Thermal insulation products for building equipment and industrial installations — Factory made mineral wool (MW) products — Specification EN 14304, Thermal insulation products for building equipment and industrial installations — Factory made flexible elastomeric foam (FEF) products — Specification SIST EN 14308:2010
EN 14308:2009 (E) 5 EN 14305, Thermal insulation products for building equipment and industrial installations — Factory made cellular glass (CG) products — Specification EN 14306, Thermal insulation products for building equipment and industrial installations — Factory made calcium silicate (CS) products — Specification EN 14307, Thermal insulation products for building equipment and industrial installations — Factory made extruded polystyrene foam (XPS) products — Specification EN 14308, Thermal insulation products for building equipment and industrial installations — Factory made rigid polyurethane foam (PUR) and polyisocyanurate foam (PIR) products — Specification EN 14309, Thermal insulation products for building equipment and industrial installations — Factory made expanded polystyrene (EPS) products — Specification EN 14313, Thermal insulation products for building equipment and industrial installations — Factory made polyethylene foam (PEF) products — Specification EN 14314, Thermal insulation products for building equipment and industrial installations — Factory made phenolic foam (PF) products — Specification According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. SIST EN 14308:2010
EN 14308:2009 (E) 6 1 Scope This European Standard specifies the requirements for factory made rigid polyurethane foam (PUR) and polyisocyanurate foam (PIR) products, with a closed cell content not less than 90 %, with or without facings, which are used for the thermal insulation of building equipment and industrial installations, with an operating temperature range of approximately, - 200 °C to + 200 °C. NOTE Below an operating temperature of - 50 °C, special tests regarding the suitability of the products in the intended application are advised (e.g. liquefaction of oxygen). Manufacturer's advice should be heeded in all cases. The products are manufactured in the form of blocks, faced or unfaced boards, pipe sections, segments and prefabricated ware. This standard describes product characteristics and includes procedures for testing, evaluation of conformity, marking and labelling. Products covered by this standard are also used in prefabricated thermal insulating systems and composite panels; the performance of systems incorporating these products is not covered. This standard does not specify the required level of a given property that shall be achieved by a product to demonstrate fitness for purpose in a particular application. The levels required for a given application are to be found in regulations and invitations to tender. Products with a declared thermal conductivity greater than 0,100 W/(m · K) at 10 °C are not covered by this standard. This standard does not cover products for in situ-insulation (spraying or dispensing) or products for the insulation of the building structure. This standard does not cover the following acoustical aspects: direct airborne sound insulation and impact noise transmission index. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 822, Thermal insulating products for building applications — Determination of length and width EN 823, Thermal insulating products for building applications — Determination of thickness EN 824, Thermal insulating products for building applications — Determination of squareness EN 825, Thermal insulating products for building applications — Determination of flatness EN 826, Thermal insulating products for building applications — Determination of compression behaviour EN 1604, Thermal insulating products for building applications — Determination of dimensional stability under specified temperature and humidity conditions EN 1606, Thermal insulating products for building applications — Determination of compressive creep EN 1609, Thermal insulating products for building applications — Determination of short term water absorption by partial immersion SIST EN 14308:2010
EN 14308:2009 (E) 7 EN 12086, Thermal insulating products for building applications — Determination of water vapour transmission properties EN 12667:2001, Thermal performance of building materials and products — Determination of thermal resistance by means of guarded hot plate and heat flow meter methods — Products of high and medium thermal resistance EN 12939, Thermal performance of building materials and products — Determination of thermal resistance by means of guarded hot plate and heat flow meter methods — Thick products of high and medium thermal resistance EN 13467, Thermal insulating products for building equipment and industrial installations — Determination of dimensions, squareness and linearity of preformed pipe insulation EN 13468, Thermal insulating products for building equipment and industrial installations — Determination of trace quantities of water soluble chloride, fluoride, silicate and sodium ions and pH EN 13471, Thermal insulating products for building equipment and industrial installations — Determination of the coefficient of thermal expansion EN 13501-1:2007, Fire classification of construction products and building elements — Part 1: Classification using data from reaction to fire test EN 13823, Reaction to fire tests for building products — Building products excluding flooring exposed to the thermal attack by a single burning item EN 14706, Thermal insulating products for building equipment and industrial installations — Determination of maximum service temperature EN 14707, Thermal insulating products for building equipment and industrial installations — Determination of maximum service temperature for preformed pipe insulation EN 15715:2009, Thermal insulation products — Instructions for mounting and fixing for reaction to fire testing — Factory made products EN ISO 4590, Rigid cellular plastics — Determination of the volume percentage of open cells and of closed cells (ISO 4590:2002) EN ISO 8497, Thermal insulation — Determination of steady-state thermal transmission properties of thermal insulation for circular pipes (ISO 8497:1994) EN ISO 11925-2, Reaction to fire tests — Ignitability of building products subjected to direct impingement of flame
— Part 2: Single-flame source test (ISO 11925-2:2002) EN ISO 13787, Thermal insulating products for building equipment and industrial installations — Determination of declared thermal conductivity (ISO 13787:2003) 3 Terms, definitions, symbols, units and abbreviated terms 3.1 Terms and definitions For the purposes of this document, the following terms and definitions apply. SIST EN 14308:2010
EN 14308:2009 (E) 8 3.1.1 Terms and definitions as given in EN ISO 9229:2007 3.1.1.1 block
billet (insulation) product generally of rectangular cross-section and with a thickness not significantly smaller than the width NOTE In English, some industries define a large block as a billet. 3.1.1.2 board
slab (insulation) rigid or semi-rigid product of rectangular shape and cross section in which the thickness is uniform and substantially smaller than the other dimensions NOTE Boards are usually thinner than slabs. They may also be supplied in tapered form. 3.1.1.3 pipe section
section (insulation) product in the shape of a cylindrical annulus which may be split to facilitate application 3.1.1.4 lag
segment rigid or semi-rigid insulation product for application to large diameter cylindrical or spherical equipment 3.1.1.5 service temperature range temperature range between the maximum service temperature and the minimum service temperature (see 4.3.2 and 4.3.3) 3.1.2 Additional terms and definitions 3.1.2.1 rigid polyurethane foam (PU) family of rigid cellular plastic insulation products with a substantially closed cell structure including both polymer types based on PIR and PUR 3.1.2.2 PIR rigid cellular plastic insulation product with a substantially closed cell structure based on polymers mainly of polyisocyanurate groups 3.1.2.3 PUR rigid cellular plastic insulation product with a substantially closed cell structure based on polymers mainly of polyurethane groups NOTE Regarding the properties described in this standard PUR and PIR types are not distinguished between. 3.1.2.4 level given value, which is the upper or lower limit of a requirement
NOTE The level is given by the declared value of the characteristic concerned. SIST EN 14308:2010
EN 14308:2009 (E) 9 3.1.2.5 class combination of two levels of the same property between which the performance shall fall 3.1.2.6 prefabricated ware pieces cut, abraded or otherwise formed from a board or block of product, e. g. elbows, T-pieces, etc. 3.1.2.7 production line assemblage of equipment that produces products using a continuous process 3.1.2.8 production unit assemblage of equipment that produces products in a discontinuous process 3.2 Symbols, units and abbreviated terms 3.2.1 Symbols and units used in this standard b is the width mm Di is the inside diameter of pipe sections mm d is the thickness mm dD is the declared thickness of the product mm ∆εb is the relative change in width % ∆εd is the relative change in thickness % ∆εl is the relative change in length % ct is the absolute compressive creep mm t is the total thickness reduction mm 0ct is the relative compressive creep % 0t is the relative deformation % f is the cryogenic thermal stress resistance — L is the deviation from linearity mm l is the length mm λ is the thermal conductivity W/(m · K) λD is the declared thermal conductivity W/(m · K) µ is the water vapour diffusion resistance factor — RD is the declared thermal resistance m² · K/W Sb is the deviation from squareness for boards on length and width mm/m Sd is the deviation from squareness for boards on thickness mm Smax is the deviation from flatness mm SIST EN 14308:2010
EN 14308:2009 (E) 10 σ10 is the compressive stress at 10 % deformation kPa σc is the compressive stress kPa σm is the compressive strength kPa v is the deviation from squareness for pipe sections mm Wit is the long-term water uptake by total immersion % Wp is the short-term water uptake by partial immersion % ψ0 is the closed cell content (corrected) % Z is the water vapour resistance m2 · h Pa/mg CC(i1/i2/y)σc is the symbol of the declared level for compressive creep CL is the symbol of the declared level for soluble chlorides ions CS(10\Y) is the symbol of the declared level for compressive stress or compressive strength CV is the symbol of the declared value for closed cell content DS(TH) is the symbol of the declared value for dimensional stability
F is the symbol of the declared value for soluble fluoride ions MU is the symbol of the declared value for water vapour diffusion resistance factor NA is the symbol of the declared value for soluble sodium ions pH is the symbol of the declared value for the pH-value SI is the symbol of the declared value for soluble silicate ions ST(+) is the symbol of the declared level for maximum service temperature ST(–) is the symbol of the declared level for minimum service temperature WVT is the symbol of the declared level for water vapour transmission WVP is the symbol of the declared level for water vapour permanence WVPE is the symbol of the declared level for water vapour permeability Z is the symbol of the declared value for water vapour resistance 3.2.2 Abbreviated terms used in this standard PU is rigid PolyUrethane foam including PUR and PIR ITT is Initial Type Test ML is Manufacturer's Literature FPC is Factory Production Control SIST EN 14308:2010
EN 14308:2009 (E) 11 4 Requirements 4.1 General Product properties shall be assessed in accordance with Clause 5. To comply with this standard, products shall meet the requirements of Subclause 4.2, and the requirements of Subclause 4.3 as appropriate. NOTE 1 Information on additional properties is given in Annex
D. One test result for a product property is the average of the measured values on the numbers of test specimens given in Table 4. 4.2 For all applications 4.2.1 Thermal resistance and thermal conductivity For flat specimens, the thermal conductivity shall be based upon measurements carried out in accordance with EN 12667 or EN 12939 for thick products. For cylindrical specimens, EN ISO 8497 shall be used as specified in Subclause 5.3.2. In both cases, the thermal conductivity values shall be determined by the manufacturer and verified in accordance with EN ISO 13787 and Annex C of this product standard. They shall be declared by the manufacturer according to measuring standards mentioned above, covering the product service temperature range. The following conditions apply: the measured values shall be expressed with three significant figures; the declared thermal conductivity curve shall be given as a limit curve, defined in EN ISO 13787; the value of the declared thermal conductivity, λD, shall be rounded upwards to the nearest 0,001 W/(m · K); the lowest reference mean test temperature required is - 170 °C. The declared equation/limit curve is the “declared reference” with three significant figures, that is to
0,000 1 W/(m.K) for λ values below 0,1 W/(m.K) and in 0,001 W/(m.K) for λ values above 0,1 W/(m.K). This shall be used as a reference for the verification of the declaration. When thermal conductivity is declared as a table derived from the equation, rounding upwards to the next 0,001 W/(m.K) has to be done for the full range of the thermal conductivity. NOTE Determinations of the declared thermal conductivity of pipe sections, following EN ISO 8497, having joints in the metering area, include the effects of these joints as defined in EN ISO 23993. 4.2.2 Dimensions and tolerances 4.2.2.1 Linear dimensions The length, l, width, b, and thickness, d, of boards shall be determined in accordance with EN 822 and EN 823. The length, l, thickness, d, and inside diameter, Di, of pipe sections, segments and prefabricated ware shall be determined in accordance with EN 13467. No test result shall deviate from the declared values by more than the tolerances given in Table 1. Products with a surface facing or natural skin shall be tested without removing them. SIST EN 14308:2010
EN 14308:2009 (E) 12 Table 1 — Dimensional tolerances Form of delivery Length Width Thickness Inside diameter Boards l < 1 000 mm l = 1 000 to 2 000 l = 2 001 to 4 000 l > 4 000 ± 5 mm ± 7,5 mm ± 10 mm ± 15 mm ±
5 mm ± 1,5 mm — Pipe section ± 3 mm — ± 2 mm – 0 mm + 2 mma
– 0 mm + 3 mmb Segments + 3 mm ± 2 mm ± 2 mm – 0 mm + 4 mm Prefabricated ware + 3 mm — ± 2 mm — a Applies to inside diameter less than 170 mm. b Applies to inside diameter of 170 mm and greater.
NOTE Smaller tolerances may be declared by the manufacturer. 4.2.2.2 Squareness Deviation from squareness, Sb, of boards and slabs shall be determined in accordance with EN 824. Deviation from squareness, v, of pipe sections shall be determined in accordance with EN 13467. For boards the deviation from squareness on length and width, Sb, shall not exceed 6 mm/m and the deviation from squareness on thickness, Sd, shall not exceed 2 mm. For pipe sections and segments the deviation from squareness, v, shall not exceed 3 mm. Products with a surface facing or natural skin shall be tested without removing them. 4.2.2.3 Flatness Deviation from flatness, Smax, shall be determined in accordance with EN 825. The deviation from flatness, Smax, shall not exceed 10 mm. Products with a surface facing or natural skin shall be tested without removing them. 4.2.2.4 Pipe section linearity Deviation from linearity, L, shall be determined for pipe sections in accordance with EN 13467. The deviation from linearity, L, shall not exceed 6 mm. Products with a surface facing or natural skin shall be tested without removing them. 4.2.3 Dimensional stability under specified conditions Dimensional stability under specified temperature and humidity conditions shall be determined in accordance with EN 1604; the tests, each on different sets of specimens, shall be carried out under the following test conditions: 1) (48 ± 1) h at (70 ± 2) °C and a relative humidity of (90 ± 5) %; 2) (48 ± 1) h at (- 20 ± 3) °C. SIST EN 14308:2010
EN 14308:2009 (E) 13 The relative changes in length, ∆εl, width, ∆εb, and thickness, ∆εd, shall not exceed the values given in Table 2 for the declared level. Table 2 — Levels for dimensional stability Test conditions Relative Changes Level DS(TH) 1 2 3 1 ∆εl, ∆εb % ≤ 5 ≤ 3 ≤ 2 ∆εd % ≤ 10 ≤ 8 ≤ 6 2 ∆εl, ∆εb % ≤ 1 ≤ 0,5 ≤ 0,5 ∆εd % ≤ 2 ≤ 2 ≤ 2
4.2.4 Reaction to fire of the product as placed on the market Reaction to fire classification of the product, as placed on the market, shall be determined in accordance with EN 13501-1, and the basic Mounting and Fixing rules given in EN 15715:2009.
NOTE This classification is compulsory and always included in the CE Marking label. EN 13501-1:2007, Table 1, is applicable to products applied to flat surfaces or to curved surfaces with a diameter greater than 300 mm. If a flat product which has a classification according to EN 13501-1:2007, Table 1, is used in a linear application, it does not require further classification. EN 13501-1:2007, Table 3, is applicable for products applied on linear objects or with a diameter below or equal 300 mm. Detailed information about the test conditions and the field of application of the classification as stated in the reaction to fire classification report shall be given in the manufacturer’s literature. 4.2.5 Durability characteristics 4.2.5.1 General The appropriate durability characteristics have been considered and are covered in Subclauses 4.2.5.2, 4.2.5.3 and 4.2.5.4. 4.2.5.2 Durability of reaction to fire against ageing/degradation and high temperature The reaction to fire performance of PU products does not change with time or when subjected to the declared maximum service temperature. 4.2.5.3 Durability of thermal resistance against ageing/degradation Any change of the thermal conductivity is covered and considered for declaration by Subclause 4.2.1 and Annex C. SIST EN 14308:2010
EN 14308:2009 (E) 14 4.2.5.4 Durability of thermal resistance against high temperature This is covered by Subclauses 4.2.1, 4.2.3, Annex D, Subclauses 5.3.2, 4.3.2 maximum service temperature (di
...