High-voltage switchgear and controlgear - Part 100: Alternating-current circuit-breakers (IEC 62271-100:2008/A1:2012 (EQV) + corrigendum Dec. 2012)

This part of IEC 62271 is applicable to a.c. circuit-breakers designed for indoor or outdoor installation and for operation at frequencies of 50 Hz and 60 Hz on systems having voltages above 1 000 V. It is only applicable to three-pole circuit-breakers for use in three-phase systems and singlepole circuit-breakers for use in single-phase systems. Two-pole circuit-breakers for use in single-phase systems and application at frequencies lower than 50 Hz are subject to agreement between manufacturer and user. This standard is also applicable to the operating devices of circuit-breakers and to their auxiliary equipment. However, a circuit-breaker with a closing mechanism for dependent manual operation is not covered by this standard, as a rated short-circuit making-current cannot be specified, and such dependent manual operation may be objectionable because of safety considerations. Rules for circuit-breakers with an intentional non-simultaneity between the poles are under consideration; circuit-breakers providing single-pole auto-reclosing are within the scope of this standard.

Hochspannungs-Schaltgeräte und -Schaltanlagen - Teil 100: Wechselstrom-Leistungsschalter IEC 62271-100:2008/A1:2012 (EQV) + corrigendum Dec. 2012)

Appareillage à haute tension - Partie 100: Disjoncteurs à courant alternatif IEC 62271-100:2008/A1:2012 (EQV) + corrigendum Dec. 2012)

Le contenu du corrigendum de décembre 2012 a été pris en considération dans cet exemplaire.

Visokonapetostne stikalne in krmilne naprave - 100. del: Izmenični odklopniki (IEC 62271-100:2008/A1:2012 (EQV) + corrigendum Dec. 2012)

Ta del standarda IEC 62271 se uporablja za izmenične odklopnike za notranjo in zunanjo namestitev, ki delujejo na frekvencah 50 Hz in 60 Hz v sistemih z napetostjo, višjo od 1000 V. Uporablja se samo za tripolne odklopnike v trifaznih sistemih in enopolne odklopnike v enofaznih sistemih. O uporabi dvopolnih odklopnikov v enofaznih sistemih in pri frekvencah, nižjih od 50 Hz, se dogovorita proizvajalec in uporabnik. Ta standard se uporablja tudi za upravljalne naprave za tokovne odklopnike in njihovo pomožno opremo. Vendar ta standard ne zajema odklopnika z zapiralnim mehanizmom za odvisno ročno upravljanje, saj ni mogoče določiti naznačenega toka, ki povzroča kratki stik, pri čemer je lahko odvisno ročno upravljanje vprašljivo zaradi varnosti. Pravila za odklopnike z namerno nesočasnostjo med poli so v obravnavi; odklopniki z enopolnim samodejnim ponovnim vklopom so zajeti v tem standardu.

General Information

Status
Published
Publication Date
07-Jan-2013
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
18-Dec-2012
Due Date
22-Feb-2013
Completion Date
08-Jan-2013

RELATIONS

Buy Standard

Amendment
SIST EN 62271-100:2009/A1:2013 - BARVE na PDF-strani 30,45,46,48,50,51,54,55,56
English language
57 pages
sale 10% off
Preview
sale 10% off
Preview

e-Library read for
1 day

Standards Content (sample)

SLOVENSKI STANDARD
SIST EN 62271-100:2009/A1:2013
01-februar-2013

9LVRNRQDSHWRVWQHVWLNDOQHLQNUPLOQHQDSUDYHGHO,]PHQLþQLRGNORSQLNL ,(&

$ (49 FRUULJHQGXP'HF

High-voltage switchgear and controlgear - Part 100: Alternating-current circuit-breakers

(IEC 62271-100:2008/A1:2012 (EQV) + corrigendum Dec. 2012)
Hochspannungs-Schaltgeräte und -Schaltanlagen - Teil 100: Wechselstrom-
Leistungsschalter IEC 62271-100:2008/A1:2012 (EQV) + corrigendum Dec. 2012)

Appareillage à haute tension - Partie 100: Disjoncteurs à courant alternatif IEC 62271-

100:2008/A1:2012 (EQV) + corrigendum Dec. 2012)
Ta slovenski standard je istoveten z: EN 62271-100:2009/A1:2012
ICS:
29.130.10 Visokonapetostne stikalne in High voltage switchgear and
krmilne naprave controlgear
SIST EN 62271-100:2009/A1:2013 en

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
SIST EN 62271-100:2009/A1:2013
EUROPEAN STANDARD
EN 62271-100/A1
NORME EUROPÉENNE
December 2012
EUROPÄISCHE NORM
ICS 29.130.10
English version
High-voltage switchgear and controlgear -
Part 100: Alternating-current circuit-breakers
(IEC 62271-100:2008/A1:2012)
Appareillage à haute tension - Hochspannungs-Schaltgeräte und -
Partie 100: Disjoncteurs à courant Schaltanlagen -
alternatif Teil 100: Wechselstrom-Leistungsschalter
(CEI 62271-100:2008/A1:2012) (IEC 62271-100:2008/A1:2012)

This amendment A1 modifies the European Standard EN 62271-100:2009; it was approved by CENELEC on

2012-11-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which

stipulate the conditions for giving this amendment the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on

application to the CEN-CENELEC Management Centre or to any CENELEC member.

This amendment exists in three official versions (English, French, German). A version in any other language

made by translation under the responsibility of a CENELEC member into its own language and notified to the

CEN-CENELEC Management Centre has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,

the Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany,

Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland,

Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Management Centre: Avenue Marnix 17, B - 1000 Brussels

© 2012 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.

Ref. No. EN 62271-100:2009/A1:2012 E
---------------------- Page: 2 ----------------------
SIST EN 62271-100:2009/A1:2013
EN 62271-100:2009/A1:2012 - 2 -
Foreword

The text of document 17A/1009/FDIS, future edition 1 of IEC 62271-100:2008/A1, prepared by SC 17A,

"High-voltage switchgear and controlgear", of IEC TC 17, "Switchgear and controlgear" was submitted to

the IEC-CENELEC parallel vote and approved by CENELEC as EN 62271-100:2009/A1:2012.

The following dates are fixed:
(dop) 2013-08-01
• latest date by which the document has
to be implemented at national level by
publication of an identical national
standard or by endorsement
• latest date by which the national (dow) 2015-11-01
standards conflicting with the
document have to be withdrawn

Attention is drawn to the possibility that some of the elements of this document may be the subject of

patent rights. CENELEC [and/or CEN] shall not be held responsible for identifying any or all such patent

rights.
Endorsement notice

The text of the International Standard IEC 62271-100:2008/A1:2012 was approved by CENELEC as a

European Standard without any modification.
In the Bibliography of EN 62271-100:2009:
- replace reference to EN 62271-203 by the following note:
IEC 62271-203:2011 NOTE Harmonized as EN 62271-203:2012 (not modified).
- add the following note:
IEC 60071-1:2006 NOTE Harmonized as EN 60071-1:2006 + A1:2010 (not modified).
+ A1:2010
---------------------- Page: 3 ----------------------
SIST EN 62271-100:2009/A1:2013
IEC 62271-100
Edition 2.0 2012-09
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
AMENDMENT 1
AMENDEMENT 1
High-voltage switchgear and controlgear –
Part 100: Alternating-current circuit-breakers
Appareillage à haute tension –
Partie 100: Disjoncteurs à courant alternatif
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
CODE PRIX XA
ICS 29.130.10 ISBN 978-2-83220-335-4

Warning! Make sure that you obtained this publication from an authorized distributor.

Attention! Veuillez vous assurer que vous avez obtenu cette publication via un distributeur agréé.

® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale
---------------------- Page: 4 ----------------------
SIST EN 62271-100:2009/A1:2013
– 2 – 62271-100 Amend.1 © IEC:2012
FOREWORD

This amendment has been prepared by subcommittee 17A: High-voltage switchgear and

controlgear, of IEC technical committee 17: Switchgear and controlgear.
The text of this amendment is based on the following documents:
FDIS Report on voting
17A/1009/FDIS 17A/1019/RVD

Full information on the voting for the approval of this amendment can be found in the report

on voting indicated in the above table.

The committee has decided that the contents of this publication will remain unchanged until

the stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data

related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.

The contents of the corrigendum of December 2012 have been included in this copy.

IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates

that it contains colours which are considered to be useful for the correct

understanding of its contents. Users should therefore print this document using a

colour printer.
_____________
---------------------- Page: 5 ----------------------
SIST EN 62271-100:2009/A1:2013
62271-100 Amend.1 © IEC:2012 – 3 –
1.1 Scope
Replace, in the existing Note 1, “non-simu0ltaneity” by “non-simultaneity”.
Replace the existing eighth paragraph by the following new paragraph:

This standard does not cover self-tripping circuit-breakers with tripping devices that cannot be

made inoperative during testing.
3.1.128
effectively earthed neutral system
This correction to definition 3.1.128 applies to the French text only.
3.4.116
circuit-breaker class M1
Replace the existing definition of this term by the following new definition:

circuit-breaker with normal mechanical endurance as demonstrated by specific type tests

3.4.117
circuit-breaker class M2
Delete the existing parentheses in the definition of this term.
Delete the existing note of this term.
3.7.145
pre-insertion time

Replace the existing term, definition and note by the following new term and new definition:

pre-insertion time (of a closing resistor)

interval of time during a closing operation between the instant of contact touch of the resistor

elements in any one pole and the instant of contact touch in the breaking unit of that pole

Add, after the existing note of 3.7.159, the following new term and definition 3.7.160 as

follows:
3.7.160
insertion time (of an opening resistor)

interval of time during an opening operation between the instant of separation of the arcing

contacts in the main interrupters of any one pole and the instant of contact separation in the

resistor interrupters in that pole
3.8 Index of definitions
Add, to the existing alphabetical list, the following new line:
Insertion time (of an opening resistor) 3.7.160

Replace, in the existing alphabetical list, “Pre-insertion time” by “Pre-insertion time (of a

closing resistor)”
---------------------- Page: 6 ----------------------
SIST EN 62271-100:2009/A1:2013
– 4 – 62271-100 Amend.1 © IEC:2012
4.2 Rated insulation level

Add, after the existing text of this subclause, the following new paragraph and new Table 36:

For circuit-breakers with rated voltages 1 100 kV and 1 200 kV, Table 36 applies.

Table 36 – Rated insulation levels for rated voltages of 1 100 kV and 1 200 kV
Rated Rated switching impulse Rated lightning impulse
Rated short-
voltage withstand voltage withstand voltage
duration power-
frequency withstand
voltage
U U
U U s p
r d
kV kV
(kV kV
(peak value) (peak value)
r.m.s. (r.m.s. value)
value)
Phase- Across Phase-to- Between Across Phase-to- Across open switching
to-earth open earth and phases isolating earth and device and/or isolating
and switching across distance between distance
between device open phases
phases and/or switching
isolating device
distance
(Note 3) (Notes 1 (Notes 3 (Notes 2 (Notes 2 and 3)
and 3) and 4) and 3)
(1) (2) (3) (4) (5) (6) (7) (8)
1 100 × 2
1 550 2 635 2 250 2 250 + (630)
1 100
1 550 +
1 100
(900)
1 450
1 100 +
1 800 2 880 2 400 2 400 + (630)
(635)
1 200 × 2
1 800 2 970 2 400 2 400 + (685)
1 200
1 675 +
1 200
1 200 +
(980)
1 600 1 950 3 120 2 550 2 550 + (685)
(695)
1 200 +
1 950 3 120 2 550 2 550 + (685)
(695)
NOTE 1 In column (3) the values in brackets are r.m.s. values.

NOTE 2 In column (6), values in brackets are the peak values of the power-frequency voltage U × 2 3 applied to

the opposite terminal (combined voltage).

In column (8), values in brackets are the peak values of the power-frequency voltage 0,7 U × 2 3 applied to the

opposite terminal (combined voltage).
NOTE 3 Values of column (2) are applicable as follows:

a) the smaller value is for type tests, phase-to-earth, the larger value is for the withstand voltage between phases;

b) the smaller value is for routine tests, phase-to-earth and across the open switching device.

The values of columns (3), (5), (6) and (8) are applicable for type tests only.

NOTE 4 These values are derived using the multiplying factors given in Table 3 of IEC 60071-1:2006.

4.6 Rated peak withstand current (I )

Add, between the existing first and second paragraphs of this subclause, the following new

paragraph:
---------------------- Page: 7 ----------------------
SIST EN 62271-100:2009/A1:2013
62271-100 Amend.1 © IEC:2012 – 5 –

For circuit-breakers with rated voltages higher than 800 kV, the standard d.c. time constant is

120 ms and the rated peak withstand current equal to 2,7 times the rated short-time withstand

current for 50 Hz and 60 Hz.
4.7 Rated duration of short circuit (t )

Replace the existing text and note of this subclause by the following new sentence:

Subclause 4.7 of IEC 62271-1 is applicable.
4.101.2 DC time constant of the rated short-circuit breaking current
Replace the existing text before Note 1 by the following new text:
a) For circuit-breakers with rated voltages up to and including 800 kV

The standard d.c. time constant is 45 ms. The following are special case d.c. time

constants, related to the rated voltage of the circuit-breaker:
– 120 ms for rated voltages up to and including 52 kV;
– 60 ms for rated voltages from 72,5 kV up to and including 420 kV;
– 75 ms for rated voltages 550 kV and 800 kV.

These special case time constants recognise that the standard value may be inadequate

in some systems. They are provided as unified values for such special system needs,

taking into account the characteristics of the different ranges of rated voltage, for example

their particular system structures, design of lines, etc.
Add, after the existing Note 3, the following new text:
b) For circuit-breakers with rated voltages higher than 800 kV

The standard d.c. time constant is 120 ms. Note 3 is also applicable in this case.

4.102.1 Representation of TRV waves

Replace the existing seventh and eighth paragraphs of this subclause by the following new

paragraphs:

If a circuit-breaker with a rated voltage equal to or less than 800 kV has a short-line fault

rating, the ITRV requirements are covered if the short-line fault tests are carried out using a

line with a time delay less than 100 ns (see 6.104.5.2 and 6.109.3) unless both terminals are

not identical from an electrical point of view (for instance when an additional capacitance is

used as mentioned in Note 4 of 6.109.3). When terminals are not identical from an electrical

point of view, test circuits which produce an equivalent TRV stress across the circuit-breaker

may be used.

For circuit-breakers with a rated voltage higher than 800 kV, the ITRV requirements are

considered to be covered if the short-line fault tests are carried out using a line with a time

delay less than 100 ns and a surge impedance of 450 Ώ unless both terminals are not

identical from an electrical point of view (for instance when an additional capacitance is used

as mentioned in Note 4 of 6.109.3). When terminals are not identical from an electrical point

of view, test circuits which produce an equivalent TRV stress across the circuit-breaker may

be used.

Since the ITRV is proportional to the busbar surge impedance and to the current, the ITRV

requirements can be neglected for all circuit-breakers with a rated short-circuit breaking

current of less than 25 kA and for circuit-breakers with a rated voltage below 100 kV. In

addition the ITRV requirements can be neglected for circuit-breakers installed in metal

enclosed gas insulated switchgear (GIS) because of the low surge impedance. ITRV
---------------------- Page: 8 ----------------------
SIST EN 62271-100:2009/A1:2013
– 6 – 62271-100 Amend.1 © IEC:2012

requirements can also be neglected for circuit-breakers directly connected to a busbar with a

total source side capacitance of more than 800 pF.
4.102.2 Representation of TRV
Replace the existing item a) by the following new item a):
a) Four-parameter reference line (see Figure 10):
u = first reference voltage, in kilovolts;
t = time to reach u , in microseconds;
1 1
u = second reference voltage (TRV peak value), in kilovolts;
t = time to reach u , in microseconds.
2 c

TRV parameters are defined as a function of the rated voltage (U ), the first-pole-to-clear

factor (k ) and the amplitude factor (k ) as follows:
pp af
u = 0,75 × k U
1 pp r

t for terminal fault is derived from u and the specified value of the rate of rise

1 1
u /t = RRRV;
1 1
t for out-of-phase = 2 × t (for terminal fault)
1 1
u = k × k U
c af pp r
1) For rated voltages up to and including 800 kV, k is equal to:
– 1,4 for terminal fault and short-line fault;
– 1,25 for out-of-phase.
t = 4t for terminal fault and short-line fault;
2 1

t for out-of-phase = between t (for terminal fault) and 2t (for terminal fault).

2 2 2
2) For rated voltages higher than 800 kV:
A four-parameter reference line is specified for terminal fault and short-line
fault test-duties and a two-parameter reference line (see b) and Figure 11) for
out-of-phase test-duties. k is equal to:
– 1,5 for terminal fault and short-line fault;
– 1,25 for out-of-phase.

t = 3t for test-duty T100 and for the supply side circuit for short-line fault.

2 1
t = 4,5t for T60.
2 1
For out-of-phase test duties OP1 and OP2, time t is derived from u and a rate
3 c
of rise of 1,54 kV/µs.
Replace the existing item c) by the following new item c):
c) Delay line of TRV (see Figures 10 and 11):
t = time delay, in microseconds;
u' = reference voltage, in kilovolts;
t' = time to reach u', in microseconds.
---------------------- Page: 9 ----------------------
SIST EN 62271-100:2009/A1:2013
62271-100 Amend.1 © IEC:2012 – 7 –

The delay line starts on the time axis at the rated time delay and runs parallel to the first

section of the reference line of rated TRV and terminates at the voltage u' (time co-

ordinate t').
For rated voltages lower than 100 kV:

t = 0,15 × t , for terminal fault and out-of-phase in the case of cable systems;

d 3

t = 0,05 × t , for terminal fault and short-line-fault in the case of line systems;

d 3
t = 0,15 × t , for out-of-phase in the case of line systems;
d 3
u' = u /3;
t' is derived from t and t according to Figure 11, t' = t + t /3.
d 3 d 3
For rated voltages from 100 kV up to and including 800 kV:
= 2 µs for terminal fault and for the supply side circuit for short-line fault;
t
t = 2 µs to 0,1 × t for out-of-phase;
d 1
u' = u /2 ;

t' is derived from u', u /t (RRRV) and t according to Figure 10, t' = t + u'/RRRV.

1 1 d d
For rated voltages higher than 800 kV:

t = 2 µs for terminal fault and for the supply side circuit for short-line fault;

u' = u /2;

t' is derived from u', u /t (RRRV) and t according to Figure 10, t' = t + u'/RRRV.

1 1 d d
= 2 µs to 0,05 × t for out-of-phase;
t
d 3
u' = u /3, t' is derived from u and a rate-of-rise of 1,54 kV/µs.
c c

4.102.3 Standard values of TRV related to the rated short-circuit breaking current

Replace the existing second paragraph of this subclause by the following new paragraphs:

Table 3 gives values for rated voltages of 100 kV up to 170 kV for effectively earthed systems.

Table 4 gives values for rated voltages of 100 kV up to 170 kV for non-effectively earthed

systems. Table 5 gives values for rated voltages of 245 kV and above.

The TRV peak values given in Tables 1, 2, 3, 4, 5 and 37 shall be met. The values for the

amplitude factor are given for information only.
---------------------- Page: 10 ----------------------
SIST EN 62271-100:2009/A1:2013
– 8 – 62271-100 Amend.1 © IEC:2012

Table 5 – Standard values of transient recovery voltage – Rated voltages 245 kV and

above for effectively earthed systems – Representation by four parameters
Replace the existing title of Table 5 by the following new title:
Table 5 – Standard values of transient recovery voltage –
Rated voltage 245 kV and above for effectively earthed systems
a b

Add, before the existing table footnotes and , the following new lines to Table 5:

Terminal fault 1,2 1,50 808 404 1 617 1 212 2 404 204 2
1 100 Short-line fault 1 1,50 674 337 1 347 1 011 2 337 170 2
Out-of-phase 2 1,25 - - 2 245 1 458 2-73 748 559 1,54
Terminal fault 1,2 1,50 882 441 1 764 1 323 2 441 222 2
1 200 Short-line fault 1 1,50 735 367 1 470 1 101 2 367 186 2
Out-of-phase 2 1,25 - - 2 449 1 590 2-80 816 610 1,54

Table 6 – Standard multipliers for transient recovery voltage values for second and

third clearing poles for rated voltages above 1 kV

Add, after the existing line "For effectively earthed systems" of this table, the following new

line:
1,2 0,95 0,95 0,83 0,83

Table 7 – Standard values of initial transient recovery voltage – Rated voltages 100 kV

and above
Replace, in the existing header of this table, the symbol "F " by" f ".
Add, before the existing note of this table, the following new lines:
1 100 0,173 0,208 1,5
1 200 0,173 0,208 1,5

Replace, in the existing note of this table, the words "can be roughly represented by a

resulting surge impedance Z of about 260 Ω in the case of a rated voltage lower than 800 kV

and by a resulting surge impedance Z of about 325 Ω in the case of a rated voltage of

800 kV." by " can be roughly represented by a resulting surge impedance Z of about 260 Ω

with the exception of rated voltage 800 kV for which the resulting surge impedance Z is about

325 Ω. "

Replace, in the existing table footnote *, the words "short-circuit breaking current" by " short-

circuit current ".
4.103 Rated short-circuit making current

Replace the existing text of this subclause by the following new text and Table 37:

The rated short-circuit making current (see Figure 8) of a circuit-breaker is related to:

– the a.c. component of the rated short-circuit current;
---------------------- Page: 11 ----------------------
SIST EN 62271-100:2009/A1:2013
62271-100 Amend.1 © IEC:2012 – 9 –
– the d.c. time constant of the rated short-circuit current;
– the rated frequency.

The rated short-circuit making current is obtained by multiplying the r.m.s. value of the a.c.

component of the rated short-circuit breaking current (see 4.101) with the peak factor given in

Table 37.
Table 37 – Peak factors for the rated short-circuit making current
Peak factor Frequency Time constant
p.u. Hz ms
2,5 50 45
2,6 60 45
2,7 50 or 60 > 45
4.105 Characteristics for short-line faults

Replace the existing first paragraph of this subclause by the following new paragraph:

Characteristics for short-line faults tests are required for class S2 circuit-breakers designed

for direct connection to overhead lines, irrespective of the type of network on the source side,

having a rated voltage equal or higher than 15 kV and less than 100 kV and a rated short-

circuit breaking current exceeding 12,5 kA. Characteristics for short-line faults are also

required for all circuit-breakers designed for direct connection to overhead lines having a

rated voltage of 100 kV and above and a rated short-circuit breaking current exceeding

12,5 kA.

Delete, in the first indent of the existing item a), the existing words “corresponding to the

rated voltage U ”.

Replace, in the existing note of this subclause, the words "(see Table 8)" by "(see L.3)".

Replace, in the existing item b) of this subclause, the first dashed item by the following new

dashed item:

– standard values of the RRRV factor, based on the line surge impedance Z, the peak

factor k and the line side time delay t that are given in Table 8. For determination of

the line side time delay and the rate-of-rise of the line side voltage, see Figure 16;

---------------------- Page: 12 ----------------------
SIST EN 62271-100:2009/A1:2013
– 10 – 62271-100 Amend.1 © IEC:2012
Table 8 – Standard values of line characteristics for short-line faults
Replace the existing Table 8 by the following new table:
Rated Surge Peak RRRV factor Time
voltage impedance factor delay
50 Hz I 60 Hz
U Z k t
r dL
(kV/µs)/kA
kV µs
450 1,6 0,200 0,240 0,1
15 ≤ U ≤ 38
450 1,6 0,200 0,240 0,2
48,3 ≤ U ≤ 170
450 1,6 0,200 0,240 0,5
245 ≤ U ≤ 800
U > 800 330 1,6 0,147 0,176 0,5

NOTE These values cover the short-line faults dealt with in this standard. For very short lines (t < 5t ) not all

L dL

requirements as given in the table can be met. The procedures for approaching very short lines are given in

IEC 62271-306 [4].

As described in 4.102.1, a value of 450 Ω may be used during testing to cover ITRV requirements.

For the RRRV factor s, see Annex A.
Table 9 – Preferred values of rated capacitive switching currents
Add, before the existing notes of this table, the two following new lines:
1 100 1 200 - - - - -
1 200 1 300 - - - - -
This correction to Note 3 of this table applies to the French text only.
Add, after the existing Note 4 of this table, the following new Note 5:

NOTE 5 Preferred values for rated voltages 1 100 kV and 1 200 kV are based on applications at 50 Hz. Higher

values of current could be possible in the future in systems operated at 60 Hz, however experience shows that

these higher currents would not lead to a higher stress for the circuit-breaker as the recovery voltage is generally

the dominant factor for interruption.
4.109.1 Rated break-time

Replace this existing text and notes of this subclause by the following new text and note:

The rated break time of a circuit-breaker is the maximum interval between the energizing of

the trip circuit and the interruption of the current in the main circuit during test duties T30, T60

and T100s in all poles under the following conditions:
– rated auxiliary supply voltage and frequency;
– rated pressures for operation, insulation and interruption;
– an ambient air temperature of (20 ± 5) °C.

According to 6.102.3.1, the basic short-circuit test-duties, with the exception of T100a, should

be carried out at the minimum auxiliary supply voltage and/or pressures for operation and/or

interruption. For convenience of testing, the auxiliary supply voltage may be the rated or

maximum value as long as it does not affect the making or breaking capability. (The operating

times of some circuit-breakers may vary with the auxiliary supply voltage). In order to verify

the rated break time during these test-duties, the maximum break time should be amended to

take account of the lower auxiliary supply voltage and pressures as follows:
---------------------- Page: 13 ----------------------
SIST EN 62271-100:2009/A1:2013
62271-100 Amend.1 © IEC:2012 – 11 –
t = t + t - (t - t )
bmax bm w om or
where
t is the maximum determined break time;
bmax

t is the longest of the minimum recorded break times during test-duties T30, T60 and

T100s;

Note that t corresponds to the last pole-to-clear in case of a three-phase test.

t is the necessary arcing window expressed in ms;
– for single-phase tests in substitution for three-phase conditions
• non-effectively earthed neutral systems: t = 150 – dα
• effectively earthed neutral systems: t = 180 – dα
– for three-phase tests
• t = 60 – dα
t is expressed in electrical degrees
t = T× t /360
w we
T period of power frequency (20 ms for 50 Hz, 16,7 ms for 60 Hz)

dα is the tripping impulse step in the search for the minimum arcing time, it is equal

to18 electrical degrees
t is the maximum recorded opening time on no-load, with minimum auxiliary supply
voltage and pressures for operation and/or interruption.

t is the maximum recorded opening time on no-load, with auxiliary supply voltage and

pressures for operation with the rated condition.

If the maximum break time determined according to this procedure exceeds the rated break

time, the test-duty that has given the longest break time may be repeated with auxiliary supply

voltage and pressure for operation and interruption at their rated values.

The rated break time is defined based on the minimum arcing time because the longest

recorded arcing time during the tests can be longer than under the actual field condition.

NOTE The break time during a make-break operation may be longer than that of a single break operation for

some circuit-breaker designs. Such longer break times may impact system protection strategy and stability if the

delay is longer than the relay time. Users should advise the manufacturer of the maximum allowable break time

during make-break operations.
Table 11 – Type tests

Replace, in the existing Table 11, the existing twentieth line on short-line fault tests by the

following new line:
Short-line fault tests *# 6.109
U ≥ 15kV and I > 12,5 kA, in case of
r sc
direct connection to overhead lines
6.2.11 Voltage test as a condition check

Replace the existing text and notes of this subclause by the following new text, new Notes 1

and 2 and new Table 38:

Subclause 6.2.11 of IEC 62271-1 is not applicable; the tests specified there are replaced with

the following:
---------------------- Page: 14 ----------------------
SIST EN 62271-100:2009/A1:2013
– 12 – 62271-100 Amend.1 © IEC:2012

Where after mechanical or environmental tests (see 6.101.1.4) the insulating properties

across open contacts of a circuit-breaker cannot be verified by visual inspection with sufficient

reliability, a power-frequency withstand voltage test in dry condition according to 6.2.11 of

IEC 62271-1 across the open circuit-breaker shall be applied as a condition check. For GIS

and dead tank circuit-breakers test conditions refer to Table 38.

For gas enclosed vacuum circuit-breakers the voltage test as a condition check may not be

sufficient. For such cases the vacuum integrity shall be demonstrated.

Where after making, breaking or switching tests (see 6.102.9) a voltage test is performed as a

condition check, the following conditions shall apply:

For circuit-breakers with an asymmetrical current path, the connections shall be reversed. The

complete tests shall be carried out once for each arrangement of the connections. For dead

tank and GIS circuit-breakers having a symmetrical current path, a test to earth is required

with the circuit-breaker in closed position. When a test to earth is required, the rated

insulation voltages across open contacts and to earth may be different. For such cases, each

of the rated values corresponding to the test condition shall be used as the reference value

for the determination of the test voltage. These requirements are summarised in Table 38.

– Circuit-breakers with U ≤ 72,5 kV

A 1 min power-frequency voltage test shall be performed. The test voltage shall be 80 %

of the value in Tables 1a or 1b, column (2) of IEC 62271-1.
– Circuit-breakers with 72,5 kV < U ≤ 245 kV

An impulse voltage test shall be performed. The crest value of the impulse voltage shall

be 60 % of the highest relevant value in Tables 1a or 1b, column (4) of IEC 6
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.