Flat polyvinyl chloride sheathed flexible cables

This European Standard covers the construction, requirements and particular test methods for flat, flexible PVC insulated and PVC sheathed cables, of rated voltage Uo/U 300/500 V, for use in passenger and goods lifts (elevators), and Uo/U 450/750 V for general purposes and for special applications such as hoists and travelling cranes. Cables of composite construction (for instance, cables with cores of different sizes) are not specified, but conditions are given for the inclusion of telecommunication units into the cables.

Flache PVC-ummantelte Steuerleitungen

Diese Europäische Norm umfasst Aufbau, Anforderungen und besondere Prüfverfahren für flache, PVC-isolierte und -ummantelte flexible Leitungen mit einer Nennspannung von Uo/U 300/500 V für die Verwendung an Personen- und Lastenaufzügen und von Uo/U 450/750 V für allgemeine Verwendung und spezielle Anwendungen wie z. B. Aufzüge und Laufkräne. Leitungen mit gemischtem Aufbau (z. B. Leitungen mit unterschiedlichen Leiternennquerschnitten) sind nicht festgelegt; es sind jedoch die Bedingungen für die Aufnahme von Elementen für Nachrichtenübermittlung in die Leitungen festgelegt. ANMERKUNG 1   Diese Überarbeitung erfolgt Übereinstimmung mit dem Abkommen mit CEN TC 10, um in der gleichen Norm a) flexible Leitungen nach EN 81 und b) flexible Leitungen für Anwendungen wie Aufzüge und Laufkräne festzulegen, die vorher in HD 359 zu finden waren. Nach dieser Übereinkunft sind nur die Leitungen in den Abschnitten 5 und 6 für Anwendungen nach EN 81 geeignet. ANMERKUNG 2   Die Außenmaße der Leitungen sind in Übereinstimmung mit EN 60719 berechnet worden.

Câbles souples méplats gainés en polychlorure de vinyle

La présente Norme Européenne couvre la construction, les prescriptions et les méthodes d’essais particulières pour les câbles méplats souples isolés et gainés en PVC de tension Uo/U 300/500 V, destinés aux ascenseurs et monte-charge et Uo/U 450/750 V pour une utilisation générale et des applications particulières telles que câbles pour festons et grues mobiles. Les câbles de composition mixte (par exemple des câbles comportant des âmes de différentes sections) ne sont pas spécifiés, mais les conditions pour introduire des éléments de câble de télécommunication sont données. NOTE 1   La présente révision, faite est en accord avec le CEN TC 10, spécifie dans la même norme, a) les câbles souples pour ascenseurs  comme prescrit par la EN 81, et b) les câbles souples pour applications telles que festons et grues mobiles, précédemment décrits dans le HD 359. En conformité avec cet accord, uniquement les câbles décrits aux Articles 5 et 6 conviennent pour être utilisés avec la EN 81. NOTE 2   Les diamètres extérieurs des câbles ont été calculés selon la EN 60719.

Ploščati zvijavi kabli, oplaščeni s polvinil kloridom (vsebuje popravek AC:2007)

General Information

Status
Published
Publication Date
31-Jan-2007
Withdrawal Date
31-Jan-2007
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
01-Feb-2007
Due Date
01-Feb-2007
Completion Date
01-Feb-2007

Relations

Effective Date
06-May-2014
Effective Date
28-Jan-2023
Effective Date
24-Sep-2019

Buy Standard

Standard
EN 50214:2007
English language
27 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 50214:2007
01-februar-2007
1DGRPHãþD
SIST EN 50214:1998
SIST HD 359 S2:1998
3ORãþDWL]YLMDYLNDEOLRSODãþHQLVSROYLQLONORULGRP YVHEXMHSRSUDYHN$&
Flat polyvinyl chloride sheathed flexible cables
Flache PVC-ummantelte Steuerleitungen
Câbles souples méplats gainés en polychlorure de vinyle
Ta slovenski standard je istoveten z: EN 50214:2006
ICS:
29.060.20 Kabli Cables
SIST EN 50214:2007 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 50214:2007

---------------------- Page: 2 ----------------------

SIST EN 50214:2007


EUROPEAN STANDARD
EN 50214

NORME EUROPÉENNE
November 2006
EUROPÄISCHE NORM

ICS 29.060.20 Supersedes HD 359 S2:1990 and EN 50214:1997
Incorporates Corrigendum December 2007

English version


Flat polyvinyl chloride sheathed flexible cables



Câbles souples méplats gainés  Flache PVC-ummantelte
en polychlorure de vinyle Steuerleitungen




This European Standard was approved by CENELEC on 2006-10-01. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, the Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels


© 2006 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 50214:2006 E

---------------------- Page: 3 ----------------------

SIST EN 50214:2007
EN 50214:2006 – 2 –
Foreword
This European Standard was prepared for Technical Committee CENELEC TC 20, Electric
cables, with the agreement of CEN TC 10, Lifts, escalators and moving walks.
The text of the draft was submitted to the formal vote and was approved by CENELEC as
EN 50214 on 2006-10-01.
This European Standard supersedes EN 50214:1997 and HD 359 S2:1990.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2007-10-01
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2008-10-01
The contents of the corrigendum of December 2007 have been included in this copy.
__________

---------------------- Page: 4 ----------------------

SIST EN 50214:2007
– 3 – EN 50214:2006
Contents
Page
1 Scope.5
2 Normative references.5
3 Definitions.6
4 Requirements for the construction of cables . 7
4.1 General.7
4.2 Core identification.7
4.3 Telecommunication Units.7
5 Flat PVC sheathed flexible cables for low rise lifts. 8
5.1 Code designation.8
5.2 Rated voltage.8
5.3 Construction.8
5.4 Tests.10
6 Flat PVC sheathed flexible cables, of rated voltage 300/500 V, for high rise,
high speed lifts .11
6.1 Code designation.11
6.2 Rated voltage.11
6.3 Construction.11
6.4 Tests.13
7 Flat PVC sheathed flexible cable of rated voltage 450/750 V.16
7.1 Code designation.16
7.2 Rated voltage.16
7.3 Construction.16
7.4 Tests.18
8 Test methods.19
9 Marking.19
9.1 General.19
9.2 Common Marking.19
10 Guide to use.19
Annex A (normative) Test methods.20
Annex B (informative) Guide to use .26
Figure 1 – Cable without strain bearing member .10
Figure 2 – Cable with strain bearing member .10
Figure A.1 – Adherence test for strain bearing member (method 1) .23
Figure A.2 – Adherence test for strain bearing member
(method 2, showing two examples of clamping device) .24
Figure A.3 – Adherence between cores and sheath .25
Table 1 – Composition of cables. 8
Table 2 – Grouping of cores. 9
Table 3 – General data.10
Table 4 – Composition of cables.12

---------------------- Page: 5 ----------------------

SIST EN 50214:2007
EN 50214:2006 – 4 –
Table 5 – General data.13
Table 6 – List of applicable tests .14
Table 7 – List of additional applicable tests for cables with strain bearing member(s).15
Table 8 – Composition of cables.16
Table 9 – Grouping of cores.17
Table 10 – General Data .18
Table 11 – List of Applicable Tests .18

---------------------- Page: 6 ----------------------

SIST EN 50214:2007
– 5 – EN 50214:2006
1 Scope
This European Standard covers the construction, requirements and particular test methods for
flat, flexible PVC insulated and PVC sheathed cables, of rated voltage U /U 300/500 V, for
o
use in passenger and goods lifts (elevators), and U /U 450/750 V for general purposes and for
o
special applications such as hoists and travelling cranes.
Cables of composite construction (for instance, cables with cores of different sizes) are not
specified, but conditions are given for the inclusion of telecommunication units into the cables.
NOTE 1 This revision is in accordance with an agreement with CEN TC 10 to specify in the same standard a)
flexible cables for lifts as required by EN 81, and b) flexible cable for applications such as hoists and travelling
cranes, previously found in HD 359. In accordance with this agreement only those cables in Clauses 5 and 6 are
suitable for use with EN 81.
NOTE 2 The limits for the overall diameter of the cables have been calculated in accordance with EN 60719.
2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
EN 81 Series Safety rules for the construction and installation of lifts
EN 50334 Marking by inscription for the identification of cores of electric cables
EN 50363 Series Insulating, sheathing and covering materials for low voltage energy
cables
EN 50395 Electrical test methods for low voltage energy cables
EN 50396 Non electrical test methods for low voltage energy cables
EN 60228 Conductors of insulated cables (IEC 60228)
EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions -
Part 1-2: Test for vertical flame propagation for a single insulated wire or
cable - Procedure for 1 kW pre-mixed flame (IEC 60332-1-2)
EN 60719 Calculation of the lower and upper limits for the average outer
dimensions of cables with circular copper conductors and of rated
voltages up to and including 450/750V (IEC 60719)
EN 60811 Series Insulating and sheathing materials of electric and optical cables -
Common test methods (IEC 60811 series)
HD 21 Series Cables of rated voltages up to and including 450/750 V and having
thermoplastic insulation
HD 308 Identification of cores in cables and flexible cords
IEC 60227-6 Polyvinyl chloride insulated cables of rated voltages up to and including
450/750 V - Part 6: Lift cables and cables for flexible connections

---------------------- Page: 7 ----------------------

SIST EN 50214:2007
EN 50214:2006 – 6 –
3 Definitions
3.1 Definitions relating to insulating and sheathing materials
3.1.1
type of compound
the category in which a compound is placed according to its properties, and determined by
specific tests. The type designation is not directly related to the composition of the compound
3.1.2
polyvinyl chloride compound (PVC)
combinations of materials, of which polyvinyl chloride is the characteristic constituent, suitably
selected, proportioned and treated which meet the requirements given in the particular
specification
3.2 Definitions relating to the tests
3.2.1
type tests (Symbol T)
tests required to be made before supplying a type of cable covered by this standard on a
general commercial basis, in order to demonstrate satisfactory performance characteristics to
meet the intended application. These tests are of such a nature that, after they have been
made, they need not be repeated unless changes are made in the cable materials, design or
type of manufacturing process which might change the performance characteristics
3.2.2
sample tests (Symbol S)
tests made on samples of completed cable, or components taken from a completed cable
adequate to verify that the finished product meets the design specifications
3.2.3
routine tests (Symbol R)
tests made on all production cable lengths to demonstrate their integrity
3.3
rated voltage
the rated voltage of a cable is the reference voltage for which the cable is designed, and
which serves to define the electrical tests
The rated voltage is expressed by the combination of two values U /U, expressed in volts:
o
U being the r.m.s. value between any insulated conductor and "earth" (metal covering of the
o
cable or the surrounding medium);
U being the r.m.s. value between any two phase-conductors of a multicore cable or of a
system of single-core cables.
In an alternating current system, the rated voltage of a cable shall be at least equal to the
nominal voltage of the system for which it is intended.
This condition applies both to the value U and to the value U.
o
In a direct current system, the nominal voltage between conductors shall be not higher than
1,5 times the rated voltage (U) of the cable, and the nominal voltage between any conductor
and earth shall not be higher than 1,5 times the rated voltage (U ) of the cable.
o
NOTE The operating voltage of a system may permanently exceed the nominal voltage of such a system by
10 %. A cable can be used at a 10 % higher operating voltage than its rated voltage if the latter is at least equal to
the nominal voltage of the system.

---------------------- Page: 8 ----------------------

SIST EN 50214:2007
– 7 – EN 50214:2006
3.4
freely suspended length
the unsupported allowed length of cable between two fixing points
3.5
strain bearing member (sbm)
metallic or non-metallic high tensile strand or bunch included in the cable construction in
order to hold the cable weight
4 Requirements for the construction of cables
4.1 General
Unless otherwise indicated in Clauses 5, 6 or 7 of this EN, the cables shall comply with the
general requirements specified in HD 21.1, Clause 5.
4.2 Core identification
Both cables with or without a green-and-yellow core are harmonised. For cables with five
cores or fewer, the identification of the remaining cores shall be either by colours, in
accordance with a) below, or by numbers in accordance with b) below. For cables with six
cores or more only identification by numbers shall be used, except for any green-and-yellow
core.
a) Identification by colours
The identification system of HD 308 shall be used.
b) Identification by numbers
Identification by numbers shall be in accordance with EN 50334.
The green-and-yellow core, if any, shall not be identified by a number.
4.3 Telecommunication Units
It shall be permitted to introduce telecommunication units into the cable construction
described in Clauses 5 and 6, subject to the following conditions:
1) units shall be chosen from copper pairs or copper coaxial or optical fibres;
NOTE Two pairs may alternatively be included as a quad.
2) units shall have a diameter equal or very close to the diameter of insulated cores;
3) preferably the number of telecommunication units in a cable shall not exceed three;
4) the position of units shall be central and symmetrical;
5) thickness (e ) of the cable sheath, where measured over telecommunication units, shall
2
comply with the requirements for minimum thickness (see 5.3.5 and 6.3.5) but shall not
be taken into account when calculating the mean value;
6) the colour or identification of the outer sheath over units shall not conflict with that of the
cores in 4.2. However, no restriction shall be placed on colours used for insulations under
an outer sheath.

---------------------- Page: 9 ----------------------

SIST EN 50214:2007
EN 50214:2006 – 8 –
5 Flat PVC sheathed flexible cables, of rated voltage 300/500 V, for low rise lifts
5.1 Code designation
Without strain bearing members: H05VVH6-F
With strain bearing members: H05VVD3H6-F
5.2 Rated voltage
300/500 V.
5.3 Construction
5.3.1 Conductor
Material: copper
Number of conductors: 4 up to 24
Nominal cross sections: 0,75 mm² and 1 mm²
The conductors shall be in accordance with the requirements of Class 5 given in EN 60228.
5.3.2 Insulation
The insulation shall be PVC compound of type TI 2 to EN 50363-3 applied around each
conductor.
The mean value of the thickness of insulation shall be not less than the specified value for
each type and size of cable shown in Table 3.
However, the thickness at any place may be less than the specified value provided that the
difference does not exceed 0,1 mm + 10 % of the specified value.
Compliance shall be checked by the test given in EN 50396, 4.1.
The insulation resistance at 70 °C shall be not less than the values given in Table 3.
5.3.3 Assembly of cores
The preferred number of cores for the composition of the cables is given in Table 1, according
to the nominal cross sectional areas of conductors.
Table 1 – Composition of cables
Nominal cross-sectional area Preferred number of cores
2
mm
0,75 6, 9, 12, 16, 18, 20 and 24
1 4, 5, 6, 9, 12, 16, 18, 20 and 24

---------------------- Page: 10 ----------------------

SIST EN 50214:2007
– 9 – EN 50214:2006
The cores shall be laid parallel and covered with the sheath.
The cores shall be grouped, lying closely side by side in groups of 2 to 5 cores.
For cables having the preferred number of cores, given in Table 1, the grouping shall comply
with Table 2.
Table 2 – Grouping of cores
Number of cores 6 9 12 16 18 20 24
Number of groups x
number of cores in group 2 x 3 3 x 3 3 x 4 4 x 4 2 x 4 + 2 x 5 5 x 4 6 x 4
NOTE A rip-cord may be added inside each core group.
The green-and-yellow core, if any, shall be placed inside one of the inner core groups, and preferably
next to either core number 7 or 8. For cables with fewer than 8 cores, the green-and-yellow core shall
be placed as centrally as possible
It shall be possible to separate the cores without damage to the insulation.
5.3.4 Strain bearing member (sbm)
A strain bearing member (or members) either of textile material or of metal may be included in
the cable, but shall be separated from the core groups.
NOTE It is permitted to apply a protective surface coating to the sbm.
The sbm shall preferably be located on the edges of the cable in a symmetrical position and
shall be easily separable from the cable, without damage to the cores, when separate
terminations of the sbm are necessary.
5.3.5 Sheath
The sheath shall be PVC compound of type TM 2 to EN 50363-4-1 applied so as to
substantially avoid the formation of cavities. The sheath shall not stick to the cores.
The sheath thickness shall be measured and evaluated generally in accordance with 4.3 of
EN 50396, with the following exceptions.
Measurements for e , e and e shall be taken as follows (see Figures 1 and 2):
1 2 3
e the clearance separating groups of cores shall not at any place be less than the value
1
specified in Table 3;
e the thickness on both flat sides shall be measured in each core group at the place where
2
the sheath is thinnest ; the opposite thickness at the same core shall also be measured.
The mean value of measurements above shall not be less than that specified in Table 3.
The minimum value of e at any place shall not be less than the specified value by more
2
than 0,2 mm + 20 % of the specified value;
e the thickness at the edge and the separation between sbm, if any, and cores shall be
3
measured at both edges of the cable, along the major axis of the cross section. The mean
value of measurements above shall not be less than that specified in Table 3. The
minimum value of e at any place shall not be less than the specified value by more than
3
0,2 mm + 20 % of the specified value.

---------------------- Page: 11 ----------------------

SIST EN 50214:2007
EN 50214:2006 – 10 –

Key
1 Alternative edge shaping
Figure 1 – Cable without strain bearing member


Figure 2 – Cable with strain bearing member

Table 3 – General data
Nominal Maximum Thickness Thickness of sheath and clearance Minimum
of insulation
cross- diameter of insulation
sectional wires in e e e resistance at
1 2 3
area of conductor 70 °C
conductors (min) (mean) (mean)
²
mm mm mm mm mm mm
MΩ.km
0,75 0,21 0,6 0,5 0,8 1,2 0,011
1 0,21 0,6 0,5 0,8 1,2 0,010

5.4 Tests
Compliance with the requirements of 5.3 shall be checked by inspection and by the tests
given in Table 6, for cables without sbm, and in Tables 6 and 7 for cables with sbm.
For the requirement of non-adhesion between sheath and core, this shall be carried out by a
manual test.

---------------------- Page: 12 ----------------------

SIST EN 50214:2007
– 11 – EN 50214:2006
6 Flat PVC sheathed flexible cables, of rated voltage 300/500 V, for high rise,
high speed lifts
6.1 Code designation
Without strain bearing members: H05V3V3H6-F
With strain bearing members: H05V3V3D3H6-F
6.2 Rated voltage
300/500 V.
6.3 Construction
6.3.1 Conductor
Material: copper
Number of conductors: 12 up to 24
Nominal cross sections: 0,75 mm² and 1 mm²
The conductors shall be in accordance with the requirements of Class 5 given in EN 60228.
6.3.2 Insulation
The insulation shall be PVC compound of type TI 5 to EN 50363-3 applied around each
conductor.
The mean value of the thickness of insulation shall be not less than the specified value for
each type and size of cable shown in Table 5.
However, the thickness at any place may be less than the specified value provided that the
difference does not exceed 0,1 mm + 10 % of the specified value.
Compliance shall be checked by the test given in EN 50396, 4.1.
The insulation resistance at 70 °C shall be not less than the values given in Table 5.
6.3.3 Assembly of cores
The cores shall be laid parallel and covered with the sheath.
The cores shall be grouped, lying closely side by side in groups of 4 or 5 cores.
The preferred number of cores and composition of the cables are given in Table 4.

---------------------- Page: 13 ----------------------

SIST EN 50214:2007
EN 50214:2006 – 12 –
Table 4 – Composition of cables
Number of cores 12 16 18 20 24
Number of groups x
number of cores in group 3 x 4 4 x 4 2 x 4 + 2 x 5 5 x 4 6 x 4
NOTE A rip-cord may be added inside each core group.
The green-and-yellow core, if any, shall be placed inside one of the inner core groups, and preferably
next to either core number 7 or 8.
It shall be possible to separate the cores without damage to the insulation.
6.3.4 Strain bearing member (sbm)
A strain bearing member, or members, either of textile material or metal may be included in
the cable, but shall be separated from the core groups.
NOTE It is permitted to apply a protective surface coating to the sbm.
The use of sbm is compulsory for freely suspended lengths exceeding 45 m. Thus, the value of the
freely suspended length for each particular contract shall be declared. The sbm shall preferably be
located on the edges of the cable in a symmetrical position and shall be easily separable from the
cable, without damage to the cores, when separate terminations of the sbm are necessary.
6.3.5 Sheath
The sheath shall be PVC compound of type TM 4 to EN 50363-4-1, applied so as to
substantially avoid the formation of cavities. The sheath shall not stick to the cores.
The sheath thickness shall be measured and evaluated generally in accordance with 4.3 of
EN 50396, with the following exceptions.
Measurements for e , e and e shall be taken as follows (see Figures 1 and 2):
1 2 3
e the clearance separating groups of cores shall not at any place be less than the value
1
specified in Table 5;
e the thickness on both flat sides shall be measured in each core group at the place where
2
the sheath is thinnest; the opposite thickness at the same core shall also be measured.
The mean value of measurements above shall not be less than that specified in Table 5.
at any place shall not be less than the specified value by more
The minimum value of e
2
than 0,2 mm + 20 % of the specified value;
e the thickness at the edge and the separation between sbm, if any, and cores shall be
3
measured at both edges of the cable, along the major axis of the cross section. The mean
value of measurements above shall not be less than that specified in Table 5. The
minimum value of e at any place shall not be less than the specified value by more than
3
0,2 mm + 20 % of the specified value.

---------------------- Page: 14 ----------------------

SIST EN 50214:2007
– 13 – EN 50214:2006
Table 5 – General data
a
Nominal Minimum
Number of Maximum Nominal Thickness of sheath Cable overall dimensions
cross- insulation
conductors diameter thickness and clearances
section of resistance
of wires of
conductor at 70 °C
insulation
Thickness
e e e Width
1 2 3

(min) (mean) (mean)
min. max. max.
2
mm mm mm mm mm mm mm mm mm
MΩ.km
12 0,75 0,21 0,6 0,5 0,8 1,2 29,4 34,5 4,50 0,011
16 0,75 0,21 0,6 0,5 0,8 1,2 38,8 45,5 4,50 0,011
18 0,75 0,21 0,6 0,5 0,8 1,2 43,3 51,0 4,50 0,011
20 0,75 0,21 0,6 0,5 0,8 1,2 48,3 57,0 4,50 0,011
24 0,75 0,21 0,6 0,5 0,8 1,2 57,7 68,0 4,50 0,011

12 1 0,21 0,6 0,5 0,8 1,2 31,0 36,0 4,65 0,010
16 1 0,21 0,6 0,5 0,8 1,2 41,0 47,0 4,65 0,010
18 1 0,21 0,6 0,5 0,8 1,2 45,8 53,0 4,65 0,010
20 1 0,21 0,6 0,5 0,8 1,2 51,1 59,0 4,65 0,010
24 1 0,21 0,6 0,5 0,8 1,2 61,1 70,0 4,65 0,010
a
Cables with sbm or telecom units may have different overall dimensions.

6.4 Tests
Compliance with the requirements of 6.3 shall be checked by inspection and by the tests
given in Table 6, for cables without sbm, and in Tables 6 and 7 for cables with sbm.
Adherence between cores and sheath shall be checked according to A.10 and Table 6.

---------------------- Page: 15 ----------------------

SIST EN 50214:2007
EN 50214:2006 – 14 –
Table 6 – List of applicable tests
1 2 3 4 5 6
Ref. No. Tests Category of test Test Method described in
Cables to Cables to EN Clause
Clause 5 Clause 6
1 Electrical Tests
1.1 Resistance of conductors T, S T, S 50395 5
1.2 Voltage test on completed cable at 2 000 V T, S T, S 50395 6
1.3 Voltage test on cores at 1 500 V T T 50395 7
1.4 Insulation resistance at 70 °C T, S T, S 50395 8.1
1.5 Long term resistance of insulation to direct T T 50395 9
current
1.6 Absence of faults on insulation R R 50395 10
2 Constructional and dimensional
characteristics
2.1 Compliance with constructional provisions T, S - 50214 5.3 Inspection
and manual

test
 - T, S 50214 6.3 Inspection
and manual
test
2.2 Measurement of insulation thickness T, S T, S 50396 4.1
2.3 Measurement of sheath thickness T, S - 50214 5.3.5
- T, S 50214 6.3.5
3 Mechanical properties of insulation
3.1 Tensile test before and after ageing T T 60811-1-1 9.1
3.2 Loss of mass test T T 60811-3-2 8
4 Mechanical properties of sheath
4.1 Tensile test before and after ageing T T 60811-1-1 9.2
4.2 Loss of mass test T T 60811-3-2 8
5 Pressure test at high temperature
5.1 Insulation T T 60811-3-1 8.1
a
5.2 Sheath T T 60811-3-1 8.2

---------------------- Page: 16 ----------------------

SIST EN 50214:2007
– 15 – EN 50214:2006
Table 6 – List of applicable tests (continued)
1 2 3 4 5 6
Ref. No. Tests Category of test Test Method described in
 Cables to Cables to EN Clause
Clause 5 Clause 6
6 Bending and impact test at low
temperature
6.1 Bending test for insulation  60811-1-4 8.1
-15 °C T -
-30 °C - T
b
6.2 Bending test for sheath T 60811-1-4 8.2
b
6.3 Elongation test for insulation T 60811-1-4 8.3
6.4 Elongation test for sheath  60811-1-4 8.4
-15 °C T -
-30 °C - T
6.5 Impact test for insulation  60811-1-4 8.5
-15 °C T -
-30 °C - T
6.6 Impact test for sheath  50214 A.3
-15 °C T -
-30 °C - T
6.7 Unrolling test at low temperature - T 50214 A.4
7 Heat shock test
7.1 Insulation T T 60811-3-1 9
7.2 Sheath T T 50214 A.5
8 Mechanical properties of complete
cables
8.1 Static flexibility test T T 50214 A.6
8.2 Flexing test - T 50214 A.7
8.3 Adherence test between cores and sheath - T 50214 A.10
9 Test under fire conditions T T 60332-1-2 -
a
Hot Pressure test on the sheath of the flat cables should be done on strips of sheath removed from the larger flat
surface. The sample being wrapped around a mandrel having diameter equal to the minor outer dimension minus
twice the sheath thickness (e ).
2
b
Optional for cables passing test 6.7.


Table 7 – List of additional applicable tests for cables with strain bearing member(s)
1 2 3 4 5 6
Ref. No. Tests Category of test Test Method described in
 Cables to Cables to EN Clause
Clause 5 Clause 6
1 Tensile strength for cable with T T 50214 A.8
sbm
2. Adherence test on sbm T T 50214 A.9

---------------------- Page: 17 ----------------------

SIST EN 50214:2007
EN 50214:2006 – 16 –
7 Flat PVC sheathe
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.