Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCB's) -- Part 1: General rules

This International Standard applies to residual current operated circuit-breakers functionally independent of, or functionally dependent on, line voltage, for household and similar uses, not incorporating overcurrent protection (hereafter referred to as RCCBs), for rated voltages not exceeding 440 V a.c. with rated frequencies of 50 Hz, 60 Hz or 50/60 Hz and rated currents not exceeding 125 A, intended principally for protection against shock hazard. These devices are intended to protect persons against indirect contact, the exposed conductive parts of the installation being connected to an appropriate earth electrode. They may be used to provide protection against fire hazards due to a persistent earth fault current, without the operation of the overcurrent protective device. RCCBs having a rated residual operating current not exceeding 30 mA are also used as a means for additional protection in case of failure of the protective means against electric shock. This standard applies to devices performing simultaneously the functions of detection of the residual current, of comparison of the value of this current with the residual operating value and of opening of the protected circuit when the residual current exceeds this value. They are intended for use in an environment with pollution degree 2. They are suitable for isolation. RCCBs complying with this standard, with the exception of those with an uninterrupted neutral, are suitable for use in IT systems. Special precautions (e.g. lightning arresters) may be necessary when excessive overvoltages are likely to occur on the supply side (for example in the case of supply through overhead lines) (see IEC 60364-4-44). RCCBs of the general type are resistant to unwanted tripping including the case where surge voltages (as a result of switching transients or induced by lightning) cause loading currents in the installation without occurrence of flashover. RCCBs of type S are considered to be sufficient proof against unwanted tripping even if the surge voltage causes a flashover and a follow-on current occurs. Particular requirements are necessary for - residual current operated circuit-breakers with integral overcurrent protection (see IEC 61009-1); - RCCBs incorporated in or intended only for association with plugs and socket-outlets or with appliance couplers for household or similar general purposes; - RCCBs intended to be used at frequencies other than 50 Hz or 60 Hz. The requirements of this standard apply for normal environmental conditions (see 7.1). Additional requirements may be necessary for RCCBs used in locations having severe environmental conditions. RCCBs including batteries are not covered by this standard.

Fehlerstrom-/Differenzstrom-Schutzschalter ohne eingebauten Überstromschutz (RCCBs) für Hausinstallationen und für ähnliche Anwendungen -- Teil 1: Allgemeine Anforderungen

Interrupteurs automatiques à courant différentiel résiduel pour usages domestiques et analogues sans dispositif de protection contre les surintensités incorporées (ID) -- Partie 1: Règles générales

Odklopniki na preostali (residualni) tok brez vgrajene nadtokovne zaščite za gospodinjsko in podobno rabo (RCCB's) – 1. del: Splošna pravila (IEC 61008-1:1996 + A1:2002, spremenjen)

Ta mednarodni standard se uporablja za odklopnike na preostali (residualni) tok, ki so funkcionalno neodvisni ali odvisni od linijske napetosti, za gospodinjsko in podobno rabo, brez vgrajene nadtokovne zaščite (v nadaljnjem besedilu: RCCB), za nazivne napetosti do vključno 440 V izmenične napetosti, pri čemer nazivna frekvenca dosega 50 Hz, 60 Hz ali 50/60 Hz in nazivni tok ne presega 125 A in ki so namenjeni predvsem zaščiti pred električnim udarom. Te naprave so namenjene zaščiti oseb pred posrednim stikom, pri čemer so izpostavljeni prevodni deli inštalacije povezani z ustreznim ozemljilom. Uporabljajo se lahko za zaščito pred požarom zaradi stalnega ozemljitvenega okvarnega toka brez naprave za nadtokovno zaščito. Tudi odklopniki na preostali (residualni) tok (RCCB) z nazivnim preostalim obratovalnim tokom do vključno 30 mA se uporabljajo kot dodatna zaščita v primeru odpovedi zaščitnega sredstva pred električnim udarom. Ta standard se uporablja za naprave, ki hkrati izvajajo funkcije zaznavanja preostalega (residualnega) toka, primerjanja vrednosti tega toka s preostalo obratovalno vrednostjo in odprtja zaščitenega tokokroga, kadar preostali tok preseže to vrednost. Odklopniki RCCB so namenjeni uporabi v okolju s stopnjo onesnaženja 2. Primerni so za izolacijo. Odklopniki RCCB, ki so skladni s tem standardom, razen odklopnikov z neprekinjeno nevtralno točko, so primerni za uporabo v sistemih IT. Posebni zaščitni ukrepi (npr. prenapetostni odvodniki) so lahko potrebni, kadar lahko na strani dobave nastane prekomerna prenapetost (na primer v primeru dobave prek nadzemnih vodov) (glejte standard 60364-4-44). Odklopniki RCCB splošnega tipa se ne morejo po nesreči odklopiti, tudi kadar previsoka napetost (zaradi prehodnih preklapljanj ali udara strele) povzroči obremenilne tokove v inštalaciji brez nastanka preboja. Odporniki RCCB tipa S naj bi v zadostni meri ščitili pred neželenim odklopom, celo kadar previsoka napetost povzroči preboj in nastane nadaljnji tok. Posebne zahteve so potrebne za: – odklopnike na preostali (residualni) tok z vgrajeno nadtokovno zaščito (glejte standard IEC 61009-1); – odklopnike RCCB, vgrajene v vtiče ali namenjene le uporabi z vtiči in vtičnicami ali s spojkami naprav za gospodinjsko ali podobno splošno rabo; – odpornike RCCB, namenjene uporabi pri frekvencah, ki niso 50 Hz ali 60 Hz. Zahteve tega standarda se uporabljajo za običajne okoljske pogoje (glejte točko 7.1). Dodatne zahteve so lahko potrebne za odklopnike RCCB, ki se uporabljajo na lokacijah z neugodnimi okoljskimi pogoji. Ta standard ne zajema odklopnikov RCCB z akumulatorji.

General Information

Status
Withdrawn
Publication Date
31-May-2005
Withdrawal Date
16-May-2017
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
16-May-2017
Due Date
08-Jun-2017
Completion Date
17-May-2017

Relations

Buy Standard

Standard
EN 61008-1:2005
English language
160 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI SIST EN 61008-1:2005

STANDARD
junij 2005
2GNORSQLNLQDSUHRVWDOL UHVLGXDOQL WRNEUH]YJUDMHQHQDGWRNRYQH]DãþLWH]D
gospodinjsko in podobno rabo (RCCB's) – 1. del: Splošna pravila (IEC 61008-
1:1996 + A1:2002, spremenjen)
Residual current operated circuit-breakers without integral overcurrent protection for
household and similar uses (RCCB's) - Part 1: General rules (IEC 61008-1:1996 +
A1:2002, modified)
ICS 5HIHUHQþQDãWHYLOND
29.120.50
SIST EN 61008-1:2005(en)
! "#$%!&!%’()*#+’

---------------------- Page: 1 ----------------------

EUROPEAN STANDARD EN 61008-1
NORME EUROPÉENNE
EUROPÄISCHE NORM September 2004

ICS 29.120.50 Supersedes EN 61008-1:1994 + A2:1995 + A11:1995 + A12:1998
+ A13:1998 + A14:1998 + A17:2000


English version


Residual current operated circuit-breakers
without integral overcurrent protection
for household and similar uses (RCCB's)
Part 1: General rules
(IEC 61008-1:1996 + A1:2002, modified)


Interrupteurs automatiques  Fehlerstrom-/Differenzstrom-
à courant différentiel résiduel Schutzschalter ohne eingebauten
pour usages domestiques et analogues Überstromschutz (RCCBs)
sans dispositif de protection contre les für Hausinstallationen und
surintensités incorporées (ID) für ähnliche Anwendungen
Partie 1: Règles générales Teil 1: Allgemeine Anforderungen
(CEI 61008-1:1996 + A1:2002, modifiée) (IEC 61008-1:1996 + A1:2002, modifiziert)




This European Standard was approved by CENELEC on 2004-03-16. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and
notified to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain,
Sweden, Switzerland and United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels


© 2004 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.

Ref. No. EN 61008-1:2004 E

---------------------- Page: 2 ----------------------

EN 61008-1:2004 – 2 –
Foreword
The text of the International Standard IEC 61008-1:1996 and its amendment 1:2002, prepared by SC 23E,
Circuit-breakers and similar equipment for household use, of IEC TC 23, Electrical accessories, together with
common modifications prepared by the Technical Committee CENELEC TC 23E, Circuit breakers and
similar devices for household and similar applications, was submitted to the Unique Acceptance Procedure
and was approved by CENELEC as EN 61008-1 on 2004-03-16.

This European Standard supersedes EN 61008-1:1994 + corrigendum Dec. 1997 + A2:1995 +
A2:1995/corrigendum Dec. 1997 + A11:1995 + A11:1995/corrigendum Dec. 1997 + A12:1998 +
A12:1998/corrigendum Apr. 1998 + A13:1998 + A14:1998 + A17:2000.

The following dates were fixed:

– latest date by which the EN has to be implemented
 at national level by publication of an identical
 national standard or by endorsement (dop) 2005-04-01

– latest date by which the national standards conflicting
 with the EN have to be withdrawn (dow) 2009-04-01

This European Standard was prepared under a mandate given to CENELEC by the European Commission
and the European Free Trade Association and covers essential requirements of EC Directives. See
Annex ZZ.

Annexes, clauses, subclauses, figures and tables that are additional to those in IEC 61008-1 are prefixed
with the letter Z.
_________________

---------------------- Page: 3 ----------------------

– 3 – EN 61008-1:2004
Endorsement notice
The text of the International Standard IEC 61000-8-1:1996 + A1:2002 was approved by CENELEC as a
European Standard with agreed common modifications as given below.
Clause Common modification
Contents Add:

Annex ZA (normative) Normative references to international publications with their
corresponding European publications

Annex ZB (normative) Special national conditions

Annex ZC (informative) A-deviations

Annex ZZ (informative) Coverage of Essential Requirements of EC Directives

Table Z1 – Survey of the types of RCCBs according to their method of operation

Table Z2 – Test voltage across the open contacts for verifying the suitability for isolation,
referred to the altitude where the test is carried out
1 In the first paragraph in the last but one line add, after "not exceeding 125 A", the words "for
fixed installations".

Replace note 3 by:
RCCB's within the scope of this standard are intended for used in an environment pollution
degree 2. They are suitable for isolation.
Devices to this standard are suitable for use in IT systems if the requirements of the
installation rules are met.

Renumber the existing notes 4 through 6 to become notes 3 through 5.

Replace the second dashed indent after (the new) note 4 by:
– RCCBs integrated in one unit with a socket-outlet or designed exclusively for being
associated locally with a socket-outlet in the same mounting box.

Replace note 5 by:
NOTE 5 Until a specific EN for SRCDs is prepared and approved, for RCCBs integrated in one unit with a
socket-outlet or designed exclusively for being associated locally with a socket-outlet in the same mounting box the
requirements of this standard in conjunction with those of IEC 60884-1 may be used as far as applicable.

Add at the end of the clause:
This standard contains all requirements necessary to ensure compliance with the operational
characteristics required for these devices by type tests.
It also contains the details relative to test requirements and methods of testing necessary to
ensure reproducibility of test results.
This standard states
a) the characteristics of RCCBs,
b) the conditions with which RCCBs shall comply, with reference to
1) their operation and behaviour in normal service,
2) their operation and behaviour in case of short-circuits,
3) their operation under residual current conditions,
4) their dielectric properties,
5) EMC,

---------------------- Page: 4 ----------------------

EN 61008-1:2004 – 4 –
Clause Common modification
c) the tests intended for confirming that these conditions have been met and the methods to
be adopted for the tests,
d) the data to be marked on the devices,
e) the test sequences to be carried out and the number of samples to be submitted for
certification purposes (see Annex A),
f) the routine tests to be carried out on each RCCB to reveal unacceptable variations in
material or manufacture, likely to affect safety (see Annex D).
2 Replace the text of Clause 2 by:
NOTE Normative references to international publications are listed in Annex ZA (normative).
3.3.16 Replace "current paths" by "poles".
3.3.Z1 Add the following new definition:
3.3.Z1
plug-in RCCB
a RCCB having one or more plug-in terminals (see 3.6.Z1) and designed for use with
appropriate means for the plug-in connection
3.6.Z1 Add the following new definition:
3.6.Z1
plug-in terminal
terminal the electrical connection and disconnection of which can be effected without
displacing the conductors of the corresponding circuit.
The connection is effected without the use of a tool and is provided by the resilience of the
fixed and/or moving parts and/or by springs
3.7 Delete 3.7.6 and 3.7.7.
3.Z1 After 3.8, add the following new definitions:
3.Z1 Definitions related to insulation coordination
3.Z1.1
insulation coordination
the mutual correlation of insulation characteristics of electrical equipment taking into account the
expected micro-environment and the influencing stresses
(1.3.1 of IEC 60664-1)
3.Z1.2
working voltage
the highest r.m.s. value of the a.c. or d.c. voltage across any particular insulation which can
occur when the equipment is supplied at rated voltage
(1.3.5 of IEC 60664-1)
NOTE 1 Transients are disregarded.

NOTE 2 Both open circuit conditions and normal operating conditions are taken into account.
3.Z1.3
overvoltage
any voltage having a peak value exceeding the corresponding peak value of maximum
steady-state voltage at normal operating conditions
(1.3.7 of IEC 60664-1)

---------------------- Page: 5 ----------------------

– 5 – EN 61008-1:2004
Clause Common modification
3.Z1.4

impulse withstand voltage
the highest peak value of impulse voltage of prescribed form and polarity, which does not
cause breakdown of the insulation under specific conditions
(1.3.8.1 of IEC 60664-1)
3.Z1.5

overvoltage category
a numeral defining a transient overvoltage condition
(1.3.10 of IEC 60664-1)
3.Z1.6

macro-environment
the environment of the room or other location, in which the equipment is installed or used
(1.3.12.1 of IEC 60664-1)
3.Z1.7

micro-environment
the immediate environment of the insulation which particularly influences the dimensioning of the
creepage distances
(1.3.12.2 of IEC 60664-1)
3.Z1.8

pollution
any addition of foreign matter, solid, liquid or gaseous that can result in a reduction of electric
strength or surface resistivity of the insulation
(1.3.11 of IEC 60664-1)
3.Z1.9

pollution degree
a numeral characterising the expected pollution of the micro-environment
(1.3.13 of IEC 60664-1)
NOTE The pollution degree to which equipment is exposed may be different from that of the macro-environment
where the equipment is located because of protection offered by means such as an enclosure or internal heating to
prevent absorption or condensation of moisture.
3.Z1.10

isolation (isolating function)
function intended to cut off the supply from the whole installation or a discrete section of it by
separating it from every source of electrical energy for reasons of safety
(3.6.10 of IEC 60898-1)
3.Z1.11

isolating distance
the clearance between open contacts, meeting the safety requirements specified for isolation
purposes
(3.6.11 of IEC 60898-1)
3.Z1.12

clearance (see Annex B)
shortest distance in air between two conductive parts along a string stretched the shortest
way between these conductive parts
NOTE For the purpose of determining a clearance to accessible parts, the accessible surface of an insulating
enclosure shall be considered conductive as if it was covered by a metal foil wherever it can be touched by a hand
or a standard test finger according to Figure 3.
3.Z1.13
creepage distance (see Annex B)
shortest distance along the surface of an insulating material between two conductive parts
NOTE For the purpose of determining a creepage distance to accessible parts, the accessible surface of an
insulating enclosure shall be considered conductive as if it was covered by a metal foil wherever it can be touched
by a hand or a standard test finger according to Figure 3.

---------------------- Page: 6 ----------------------

EN 61008-1:2004 – 6 –
Clause Common modification
4.1 Replace the note by the following specification:
The selection of the various types is made according to HD 384 and non conflicting national
wiring rules. Table Z1 lists the types of RCCBs according to the various applications but
does not exclude the use of RCCBs of any classification for protection over and above that
required by the relevant wiring rules.
Add:
Table Z1 – Survey of the types of RCCBs according to their method of operation

Classification 4.1.1 4.1.2.2a) 4.1.2.1 b) 4.1.2.2b)
Marking of use Without E1 E2 E3
a a b
Protection Indirect contact and Indirect contact and Additional protection Additional protection
a a
additional protection additional protection
c
Service continuity Yes Yes No Yes
a
Additional protection, provided only for RCCBs with I ≤ 0,03 A.
Δn
b
Only devices integrated in one unit with a socket-outlet or designed exclusively for being associated locally with a socket outlet in a
same mounting box.
c
This information is given for guidance only.

4.1.2.1 Replace item a) by "deleted".
Add, after b):
RCCBs of type 4.1.2.1b) shall comply with the relevant requirements of 8.12.
4.1.2.2 Delete the note.
4.1.2.2a) Replace the text in brackets by "(additional requirements are under consideration)".
4.2 Replace the text by "Deleted".
4.3 Delete "single-pole RCCB with two current paths;" and "three-pole RCCB with four current
paths;".
4.4 Replace the text by "Deleted".
4.Z1 Add the following new subclause:
4.Z1 According to the range of ambient air temperature
– RCCBs for use at ambient air temperatures between -5 °C and +40 °C;
– RCCBs for use at ambient air temperatures between -25 °C and +40 °C.
5.1 Delete the first dashed item.
Add the following item to the list:
– ranges of ambient air temperature (see 5.3.Z1)
5.2.1.Z1 Add:
5.2.1.Z1 Rated impulse withstand voltage (U )
imp
The rated impulse withstand voltage of an RCCB shall be equal to or higher than the
standard values of rated impulse withstand voltage given in 5.3.Z2.
5.2.3 Delete the note.
5.3.1 Replace "preferred" by "standard" (twice).

---------------------- Page: 7 ----------------------

– 7 – EN 61008-1:2004
Clause Common modification
Replace the Table by:


RCCBs Circuit supplying the RCCB Rated voltage
Two-pole with two current path Single phase, phase to neutral or phase to 230 V
phase
Single phase, phase to phase 400 V
Three-pole with three current Three phase (3-wire) 400 V
path
Four-pole Three phase (4-wire) 400 V

5.3.3 Delete the value "0,006 A".
5.3.7 Replace the first line by:
The preferred value of rated frequency is 50 Hz.
5.3.12 Replace, in the last but one line "9.22.1.1" by "9.21.1".
5.3.12 Table 1: replace "500 A" by " 500 A**"
Add the following note:
** The verification of the break times at these values is only made for the test of 9.9.2.3.
5.3.Z1 Add the following new subclause:
5.3.Z1 Standard ranges of ambient air temperature
The standard ranges of ambient air temperature are:
– -5 °C to +40 °C;
– -25 °C to +40 °C
5.3.Z2 Add the following new subclause :
5.3.Z2 Standard value of rated impulse withstand voltage (U )
imp
Standard value of the rated impulse voltage (U ) is 4 kV.
imp
NOTE 1 For test voltages to check the insulation see 9.20.
NOTE 2 For test voltages to check the isolation distance across open contacts see Table Z2.
6 The text of Clause 6 becomes 6.Z1 with the following modifications:
6.Z1 Standard marking
c) Add "with the symbol ~"
d) Delete "and/or 60 Hz"
f) Add "(I ) in A or mA"
Δn
g) Replace the text by "Deleted"
h) Add "(I )"
m
l) Add "(I )" between "capacity" and ", if different from." and add "(I )" at the end
Δm m

---------------------- Page: 8 ----------------------

EN 61008-1:2004 – 8 –
Clause Common modification
Replace item n) by:
n) symbol of the method of operation according to Table Z1 of 4.1 if the RCCB is
functionally dependent on the line voltage;
p) Add "unless the correct mode of connection is evident"
Add the following item:
s) RCCBs according to 4.Z1 shall be marked with the symbol (the value -25 included in


the snow flake symbol according to Figure 0027 of ISO 7000), if relevant;

In the second paragraph after s):
Replace "under e), f), and o) " by "under e), f), m), o) and r) (for A type only)".
Replace "under a), b), c) ,k), l) and p)" by "under a), b), c), k), p), r) (for AC type only) and
s)".
Add before the last sentence:
Information under h) (I ) and l) (I ) may be put on the side or on the back or in the
m Δm
documentation, but both shall be indicated together.
Add between the second and third paragraph after s):

If a degree of protection higher than IP20 according to EN 60529 is marked on the device, it
shall comply with it, whichever the method of installation. If the higher degree of protection is
obtained only by a specific method of installation and/or with the use of specific accessories
(e.g. terminal covers, enclosures, etc.), this shall be specified in the manufacturer's literature.
Add at the end:

The suitability for isolation, which is provided by all RCCBs of this standard, may be
indicated by the symbol on the device. When affixed, this marking may be
included in a wiring diagram, where it may be combined with symbols of other functions,
(e.g. other symbols of IEC TC3). When the symbol is used on its own (i.e. not in a wiring
diagram), combination with symbols of other functions is not allowed.
Specifications on appropriate recommendations to the user to regularly operat the test deice
are under consideration.
6.Z2 Add the following new subclause:
6.Z2 Additional marking
Additional marking to other standards (EN or IEC or other) is allowed under the following
conditions:
– the RCCB shall comply with all the requirements of the additional standard;
– the relevant standard to which the additional marking refers shall be indicated adjacent to
this marking and shall be clearly differentiated or separated from the standard marking
according to 6.Z1.
Compliance is checked by inspection and by carrying out all the test sequences required by
the relevant standard. Equivalent or less severe test sequences need not be repeated.
6.Z3 Add the following new subclause:

---------------------- Page: 9 ----------------------

– 9 – EN 61008-1:2004

6.Z3 Guidance table for marking

Marking and other product information Marking may be on the RCCB itself Product information
in the catalogue
If, for small devices the space This information may be Alternatively the Any remaining


available does not allow all
marked on the side or on information may be on the information not
Each RCCB shall be marked in a durable manner with all or, for small
the above data to be marked, the back of the device and inside of any cover which marked shall be given
apparatus, part of the following data:
at least this information shall be visible only before the has to be removed in in the manufacturer's
The minimum requirements are indicated by the symbol "X"
be marked and visible when device is installed. order to connect the catalogues.
the device is installed. supply wires.
X
a)
the manufacturer's name or trademark;
X
b)
type designation, catalogue number or serial number;
X
c)
rated voltage(s) with the symbol ~;
  X
d)
rated frequency, if the RCCB is designed frequencies other than 50Hz (see 5.3.7)
X
e)
rated current
X
f)
rated residual operating current (I )in A or in mA
Δn
  X(*)
h) rated making and breaking capacity (I )
m
  X
j)
the degree of protection (only if different from IP20);
X
k) the position of use (symbol according to IEC 60051), if necessary;
  X(*)
l)
rated residual making and breaking capacity (I ), if different from rated short-circuit
Δm
capacity (I )
m
X
m)
the symbol S (S in a square) for type S devices;
X X
n)
indication that the RCCB is functionally dependent on line voltage, if applicable
X
o)
operating means of the test device, by the letter T;
X X
p)
wiring diagram unless the correct mode of operation is evident,
operating characteristic in presence of residual currents with d.c. components
r)

  - RCCBs of type AC with the symbol
X

  - RCCBs of type A with the symbol
X
X
s)
RCCBs according to 4.Z1 shall be marked with the symbol (snowflake enclosing

-25) if relevant
Indication of the terminal for the neutral with "N"
X

Additional marking of performance to other standards
X

Symbol of rated conditional breaking capacity with a fuse **
X(**)
(*) IΔm and Im ( if different of IΔm) may be anywhere on the device or in the catalogue but shall be together.
(**) Under consideration
NOTE  Specifications on appropriate recommendations to the user to regularly operate the test device are under consideration.

---------------------- Page: 10 ----------------------

EN 61008-1:2004 – 10 –
Clause Common modification
2)
7.1 In Table 2, second column, add to "–5 °C to +40 °C " in the same box, the range
2)
"-25 °C to +40 °C ".
Modify footnote 7) to read:
7) Extreme limits of –20 °C and 60 °C, for RCCBs for use in the range of  –5 °C to +40 °C and of –35 °C and 60 °C,
for RCCBs for use in the range of –25 °C to +40 °C, are admissible during storage and transportation. These
conditions should be taken into account in the design of the device.
8)
In Table 2, second column, after "2 000 m", add a footnote reference " ".
Add footnote 8) as follows:
8) For installations at higher altitudes, it is necessary to take into account the reduction of the dielectric strength and
of the cooling effect of the air. RCCBs intended to be so used shall be designed specially or used according to an
agreement between manufacturer and user. Information given in the manufacturer's catalogue may take the place of
such an agreement.
7.Z1 Add the following new subclause:
7.Z1 Pollution degree
RCCBs to this standard are intended for environment with pollution degree 2, i.e.: normally,
only non-conductive pollution occurs; occasionally, however, a temporary conductivity caused
by condensation may be expected.
8.1.1 Replace the second paragraph by:
It shall not be possible to alter the operating characteristics of the RCCB by means of external
interventions.
Delete the third paragraph.
8.1.2 Replace the second paragraph by:
The switched neutral pole (see 3.3.15) of four-pole RCCBs shall not close after and shall not
open before the other poles.
Compliance is checked by inspection and by manual test, using any appropriate means (e.g.
indicator lights, oscilloscope, etc.).
Add after the sixth paragraph:
RCCBs shall provide in the open position (see 3.3.13) an isolation distance in accordance with
the requirements necessary to satisfy the isolating function (see 8.3).
Indication of the open and closed position of the main contacts shall be provided by one or
both of the following means:
– the position of the actuator (this being preferred); or
– a separate mechanical indicator.
If a separate mechanical indicator is used to indicate the position of the main contacts, this
shall show the colour red for the closed position (ON) and the colour green for the open
position (OFF).
The means of indication of the contact position shall be reliable.
RCCBs shall be designed so that the actuator, front plate or cover can only be correctly fitted
in a manner which ensures correct contact position indication (see Clause 6).
Compliance is checked by inspection and by the tests of 9.9 and 9.11.2.
When means are provided or specified by the manufacturer to lock the operating means in the
open position, locking in that position shall only be possible when the main contacts are in the
open position.
NOTE Locking of the operating means in the ON position is permitted for particular applications.
Compliance is checked by inspection, taking into account the instructions of the manufacturer.

---------------------- Page: 11 ----------------------

– 11 – EN 61008-1:2004
Clause Common modification
8.1.2 Delete the eigth paragraph and the relevant note.
Delete the note before the last paragraph.
8.1.3 Replace 8.1.3 by:
8.1.3 Clearances and creepage distances
The minimum required clearances and creepage distances are given in Table 3 which is
based on the RCCB being designed for operating in an environment with pollution degree 2.
However, the clearances of item 2, 4 and 5 may be reduced provided that the tests at rated
impulse voltage are withstood.
The insulating materials are classified into Material Groups on the basis of their comparative
tracking index (CTI) according to 2.7.1.1 and 2.7.1.3 of IEC 60664-1 and measured according
to IEC 60112.
Replace Table 3 by the following table:

---------------------- Page: 12 ----------------------

EN 61008-1:2004 – 12 –
Table 3 – Minimum clearances and creepage distances
e, f
Minimum Minimum creepage distances
clearances
mm mm
h
 Group IIIa Group II Group I
d d d
(175V ≤ CTI < 400V) (400V ≤ CTI < 600V) (600V ≤ CTI )
e
Rated voltage Working voltage
V V
Description 230 V/400 V > 25 120 250 400 > 25 120 250 400 > 25 120 250 400
i
230 V
≤ 50 ≤ 50 ≤ 50
i
400 V

1. between live parts which are
separated when the main contacts
4,0 1,2 2,0 4,0 4,0 0,9 2,0 4,0 4,0 0,6 2,0 4,0 4,0
a
are in the open position
2. between live parts of different
3,0 1,2 1,5 3,0 4,0 0,9 1,5 3,0 3,0 0,6 1,5 3,0 3,0
a
polarity
3. between circuits supplied from
different sources, one of which 8,0 3,0 6,0 8,0 3,0 6,0 8,0 3,0 6,0 8,0
g
being PELV or SELV
 Rated voltage
V
230 - 400 230 - 400 230 - 400

4. between live parts and

- accessible surfaces of operating
means
-
- screws or other means for fixing
covers which have to be removed
when mounting the RCCB

- surface on which the RCCB is
b
mounted

- screws or other means for fixing
b
the RCCB
b
3,0 4,0 3,0 3,0
- metal covers or boxes
c

- other accessible metal parts

- metal frames supporting flush-
type RCCBs

5. between metal parts of the
mechanism and:
c
-
- accessible metal parts

- screws or other means for fixing
the RCCB

- metal frames supporting flush-
type RCCBs
a
For auxiliary and control contacts the values are given in the relevant standard.
b
The values are doubled if clearances and creepage distances between live parts of the device and the metallic screen or the surface on
which the RCCB is mounted are not dependent on the design of the RCCB only, so that they can be reduced when the RCCB is
mounted in the most unfavourable condition.
c
Including a metal foil in contact with the surfaces of insulating material which are accessible after installation for normal use. The foil is
pushed into corners, grooves, etc., by means of a straight unjointed test finger according to 9.6 (see Figure 3)
d
See IEC 60112.
e
Interpolation is allowed in determining creepage distances corresponding to voltage values intermediate to those listed as working
voltage. For determination of creepage distances see Annex B.
f
Creepage distances cannot be less than the associated clearances.
g
To cover all different voltages including ELV in an auxiliary contact.
h
For material group IIIb (100 V ≤ CTI < 175 V) the values for material group IIIa multiplied by 1,6 apply.
I
For working voltages up to and including 25 V reference may be made to IEC 60664-1.
NOTE 1 The values given for 400 V are also valid for 440 V.
NOTE 2 The parts of the neutral path, if any, are considered to be live parts.
NOTE 3 Care should be taken to provide adequate clearances and creepage distances between live parts of different polarity of RCCBs

e.g. of the plug-in type mounted close to one another.

---------------------- Page: 13 ----------------------

– 13 – EN 61008-1:2004
Clause Common modifications
8.1.5.2 Delete the note after Table 4.
8.1.Z1 Add the following new subclause:
8.1.Z1 Non-interchangeability
For RCCBs intended to be mounted on bases forming a unit therewith (plug-in type or screw-
in type) it shall not be possible, without the aid of a tool, to replace a RCCB when mounted
and wired as for normal use by another of the same make having a higher rated current.
Compliance is checked by inspection.
NOTE The expression "as for normal use" implies that the RCCB is installed according to the manufacturer's
instructions.
8.1.Z2 Add the following new subclause:

8.1.Z2 Mechanical mounting of plug-in type RCCBs
The mechanical mounting of plug-in type RCCBs shall be reliable and have adequate
stability.
8.1.Z2.1 Plug-in type RCCBs, the holding in position of which does not depend solely
on their plug-in connection(s)
Compliance of the mechanical mounting is checked by the relevant tests of 9.12.
8.1.Z2.2 Plug-in type RCCBs, the holding in position of which depends solely on
their plug-in connection(s)
Compliance of the mechanical mounting is checked by the relevant tests of 9.12.
8.3 Replace 8.3 by:

8.3 Dielectric properties and isolating capability
RCCBs shall have adequate dielectric properties and shall ensure isolation.
Compliance is checked by the requirements referred to in 8.3.Z1 to 8.3.Z3.
Control circuits connected to the main circuit shall not be damaged by high d.c. voltage due
to insulating measurements which are carried out after RCCBs are installed.
Compliance is checked by the test of 9.7.6.
8.3.Z1 Dielectric strength at power frequency
RCCBs shall have adequate dielectric properties at power frequency.
Compliance is checked by the tests of 9.7.1, 9.7.2, 9.7.3 and 9.7.4 (if applicable).
After the endurance tests of 9.10 and after the short-circuit tests of 9.11, the RCCBs shall
withstand the test of 9.7.3 but at the reduced test voltage specified in 9.10.3 and 9.11.2.1 i)
respectively and without the previous humidity treatment of 9.7.1.
8.3.Z2 Isolating capability
RCCBs shall be suitable for isolation.
Compliance is checked by the verification of complia
...