Heating boilers - Condensing heating boilers for fuel oil

This European Standard applies to oil-fired heating boilers, which are declared by the manufacturer to be condensing boilers up to a nominal heat output of 1 000 kW supplied as a unit with an atomizing oil burner which meets the requirements of EN 267.
NOTE   This European Standard defines three classes of oil fired boilers with efficiency requirements higher than those given for low temperature boilers in the Boiler Efficiency Directive (BED) 94/42/EEC.
This European Standard completes/modifies EN 303-1, EN 303-2 and EN 304 and specifies supplementary requirements for condensing boilers.

Heizkessel - Öl-Brennwertkessel

Diese Europäische Norm gilt für vom Hersteller als Brennwertkessel bezeichnete ölbefeuerte Heizkessel mit einer Nennwärmeleistung von bis zu 1 000 kW, die als Unit (Kessel/Brenner-Einheit) mit einem Ölzerstäubungsbrenner, der die Anforderungen von EN 267 erfüllt, geliefert werden.
ANMERKUNG   Diese Europäische Norm spezifiziert drei Klassen von ölbefeuerten Heizkesseln mit Anforderungen an den Wirkungsgrad, die höher sind als die für Niedertemperatur-Heizkessel in der Richtlinie des Rates über die Wirkungs¬grade von mit flüssigen oder gasförmigen Brennstoffen beschickten neuen Warmwasserheizkesseln 92/42/EWG angege¬benen Anforderungen.
Diese Europäische Norm ergänzt/modifiziert EN 303 1, EN 303 2 und EN 304, und sie legt zusätzliche Anfor¬derungen an Brennwertkessel fest.

Chaudieres de chauffage - Chaudieres de chauffage a condensation au fioul

La présente Norme européenne s'applique aux chaudières de chauffage à fioul, déclarées par le fabricant comme étant des chaudières à condensation pouvant atteindre une puissance calorifique nominale de 1 000 kW et fournies avec un brûleur à pulvérisation conforme aux exigences de l'EN 267.
NOTE   La présente Norme européenne définit trois classes de chaudières à fioul dont les exigences de rendement sont supérieures à celles valables pour les chaudières à basse température données dans la Directive concernant le rendement des chaudières 94/42 CEE.
La présente Norme européenne complète/modifie les normes EN 303-1, EN 303-2 et EN 304 et spécifie des exigences supplémentaires relatives aux chaudières à condensation.

Kotli za gretje – Oljni kondenzacijski kotli za gretje

General Information

Status
Withdrawn
Publication Date
31-Jan-2007
Withdrawal Date
12-Nov-2017
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
07-Nov-2017
Due Date
30-Nov-2017
Completion Date
13-Nov-2017

Relations

Buy Standard

Standard
EN 15034:2007
English language
17 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 15034:2007
01-februar-2007
Kotli za gretje – Oljni kondenzacijski kotli za gretje
Heating boilers - Condensing heating boilers for fuel oil
Heizkessel - Öl-Brennwertkessel
Chaudieres de chauffage - Chaudieres de chauffage a condensation au fioul
Ta slovenski standard je istoveten z: EN 15034:2006
ICS:
97.100.40 *UHOQLNLQDWHNRþHJRULYR Liquid fuel heaters
SIST EN 15034:2007 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 15034:2007

---------------------- Page: 2 ----------------------

SIST EN 15034:2007
EUROPEAN STANDARD
EN 15034
NORME EUROPÉENNE
EUROPÄISCHE NORM
November 2006
ICS 97.100.40

English Version
Heating boilers - Condensing heating boilers for fuel oil
Chaudières de chauffage - Chaudières de chauffage à Heizkessel - Öl-Brennwertkessel
condensation au fioul
This European Standard was approved by CEN on 22 September 2006.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the Central Secretariat or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the official
versions.
CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,
Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania,
Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36  B-1050 Brussels
© 2006 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 15034:2006: E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------

SIST EN 15034:2007
EN 15034:2006 (E)
Contents
Foreword.3
1 Scope .4
2 Normative references .4
3 Terms and definitions .4
4 Requirements.5
5 Test methods.7
6 Marking, labelling and packaging .11
Annex A (normative) Corrections for the determined efficiency for the low water temperature test of
condensing boilers.12
Annex B (informative) Transforming results of efficiency tests to the reference point H .13
S
Annex C (informative) Indirect method (checking purposes only) .14
C.1 General.14
C.2 Indirect method.14
C.2.1 Measurements.14
C.2.2 Calculations.15
Bibliography .17

Table 1 — Level of performance for energy efficiency.7
Table 2 — Calculation of part load efficiency .10
Table C.1 — Symbols and quantities needed to calculate the efficiency at part load. .15

2

---------------------- Page: 4 ----------------------

SIST EN 15034:2007
EN 15034:2006 (E)
Foreword
This document (EN 15034:2006) has been prepared by Technical Committee CEN/TC 57 “Central heating boilers”,
the secretariat of which is held by DIN.
This European Standard shall be given the status of a national standard, either by publication of an identical text or
by endorsement, at the latest by May 2007, and conflicting national standards shall be withdrawn at the latest by
May 2007.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Cyprus, Czech Republic, Denmark,
Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta,
Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United
Kingdom.
3

---------------------- Page: 5 ----------------------

SIST EN 15034:2007
EN 15034:2006 (E)

1 Scope
This European Standard applies to oil-fired heating boilers, which are declared by the manufacturer to be
condensing boilers up to a nominal heat output of 1 000 kW supplied as a unit with an atomizing oil burner which
meets the requirements of EN 267.
NOTE This European Standard defines three classes of oil fired boilers with efficiency requirements higher than those
given for low temperature boilers in the Boiler Efficiency Directive (BED) 94/42/EEC.
This European Standard completes/modifies EN 303-1, EN 303-2 and EN 304 and specifies supplementary
requirements for condensing boilers.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated references,
only the edition cited applies. For undated references, the latest edition of the referenced document (including any
amendments) applies.
EN 303-1:1999, Heating boilers — Part 1: Heating boilers with forced draught burners — Terminology, general
requirements, testing and marking
EN 303-2:1998, Heating boilers — Part 2: Heating boilers with forced draught burners — Special requirements for
boilers with atomizing oil burners
EN 304:1992, Heating boilers — Test code for heating boilers for atomizing oil burners
EN 1443, Chimneys — General requirements
EN 60730-2-9, Automatic electrical controls for household and similar use — Part 2-9: Particular requirements for
temperature sensing controls (IEC 60730-2-9:2000, modified)
3 Terms and definitions
For the purposes of this European Standard, the following terms and definitions apply.
3.1
condensate
liquid formed from combustion products during the condensation process
3.2
nominal condensing output
(P)
value of useful output declared by the manufacturer, in kW and corresponding to the operation of the boiler in a
50 °C/30 °C water temperature regime
3.3
maximum allowable working temperature
temperature that the material can withstand over a long period of time
3.4
condensing boiler
boiler that, under normal operating conditions and at certain operating water temperatures, partially condenses the
water vapour in the combustion products in order to make use of the latent heat of water vapour for heating
purposes and also satisfy the efficiency requirements of this European standard
4

---------------------- Page: 6 ----------------------

SIST EN 15034:2007
EN 15034:2006 (E)
3.5
nominal output
(P )
N
value of the useful output declared by the manufacturer, in kW and corresponding to the operation of the boiler in a
80 °C/60 °C water temperature regime
4 Requirements
4.1 Construction requirements
4.1.1 General
In addition to EN 303-1:1999, clause 4.1, the following requirements shall apply.
4.1.2 Materials in contact with condensate
All parts of the heating boiler likely to come into contact with condensation shall be constructed of sufficiently
corrosion resistant materials or materials protected by a suitable coating, in order to ensure a reasonable life for a
boiler that is installed, used and maintained in accordance with the manufacturer's instructions. Fuel quality
requirements shall be declared by the manufacturer.
4.1.3 Removal of condensation
Condensation produced during boiler operation, including condensation formed in the flue and its connecting pipes,
which shall be removed by means of a discharge pipe (or pipes).
The internal diameter of the outside connection of the condensation discharge system shall be at least 13 mm.
The disposal system, forming part of the boiler or supplied with the boiler, shall be such that:
 it can be easily inspected and cleaned in accordance with the manufacturer's instructions;
 it cannot transmit combustion products into the room where the boiler is installed; this requirement is satisfied if
the disposal system incorporates a water trap;
 water trap has a seal of at least 25 mm at the maximum pressure in the combustion chamber at the maximum
flue length specified by the manufacturer.
Surfaces in contact with condensates (except purpose provided drains, water traps and siphons) shall be designed
to prevent condensation retention.
4.1.4 Control of the combustion products temperature
If the combustion products circuit contains materials that are likely to be affected by heat or is intended to be
connected to a flue (including seals) that is likely to be affected by heat from the combustion products, the boiler
shall incorporate a device to prevent the combustion products temperature exceeding the maximum allowable
working temperature for the material as declared by the manufacturer.
The device for limiting the combustion products temperature shall be a safety temperature cut off. The safety
temperature limiter shall comply with the requirements of EN 60730-2-9 for type 2 devices.
The device for limiting the combustion products temperature may be omitted if the combustion products
temperature in no case is higher than the allowable temperature of the materials used in the combustion products
circuit.
If the flue gas system is not supplied with the appliance, the device for limiting the combustion products
temperature may be supplied as an option to be fitted by the installer. Mounting the device shall be well defined.
5

---------------------- Page: 7 ----------------------

SIST EN 15034:2007
EN 15034:2006 (E)
4.1.5 Chemical composition of the condensate
If the manufacturer states the chemical composition of the condensate it shall be checked at the end of the test of
5.3.
4.2 Operational requirements
4.2.1 General
In addition to EN 303-2:1998, clause 3, the following requirements shall apply.
4.2.2 Verification of the nominal condensing output
If the manufacturer states the nominal condensing output it is verified under the test conditions of 5.2.
4.2.3 Formation of condensation
When the boiler operates under the conditions of 5.3, condensation shall only form at the points intended for this
purpose and shall be readily drained.
Condensation shall not find its way into parts of the boiler which are not intended to have formation, collection and
discharge of condensation, nor may the condensation cause any nuisance to the operation, the boiler and the
surroundings.
4.2.4 Temperature of combustion products
Under the conditions of 5.4 the temperature of the combustion products shall not exceed the maximum allowable
working temperature for the materials of the combustion circuit and the flue materials, specified by the boiler
manufacturer.
Operation of the safety temperature cut off according to 4.1.4 shall cause a non-volatile lock-out of the boiler.
4.3 Heating requirements
4.3.1 Normal conditions
The combustion requirements are those specified in EN 303-2 and EN 304. The test shall also be carried out when
the boiler is operating in the condensing mode (50 °C/30 °C).
4.3.2 Special conditions
The condensation discharge blockage test, as described in 5.5.2, shall be performed unless the manufacturer fixes
a warning note on the boiler that the condensation discharge has to be checked and cleaned once a year. In the
maintenance manual the inspection and cleaning has to be described in detail.
4.4 Efficiencies requirements
4.4.1 Useful efficiency at full load
Under the test conditions specified in 5.6.1, the useful efficiency at the nominal heat input, shall be at least:
91 + lg P (in %; required for Level I+II) (1)
N
87,5 + 1,5 × lg P (in %; required for Level III) (2)
N
where
6

---------------------- Page: 8 ----------------------

SIST EN 15034:2007
EN 15034:2006 (E)
P is the nominal output.
N
NOTE These formulae are applicable up to 1 000 kW.
4.4.2 Useful efficiency at part load
Under the test conditions specified in 5.6.2, the useful efficiency at 30 % of the nominal heat input, shall be at least:
Table 1 — Level of performance for energy efficiency
a
Level of Energy efficiency mode of Water temperatures
performance operation
I Condensing average return temperature: (30 ± 0,5) °C
99 + lg (P ) < η
N A
II 94 + lg (P ) < η < 99 + lg (P ) Condensing average return temperature: (30 ± 0,5) °C
N B N
III — mean boiler water temperature 40°C
87,5 + 1,5 lg (P ) < η < 94 + lg (P )
N C N
where
η is the efficiency for level I;
A
η is the efficiency for level II;
B
η is the efficiency for level III.
C
NOTE These formulae are applicable up to 1 000 kW.
a
Test methods for level III are necessary to fulfil the requirements of the boiler efficiency directive up to 400 KW, test methods for level I and
level II are optional.

5 Test methods
5.1 General
All the tests are carried out under the conditions laid down in boiler standards EN 303-2 and EN 304, unless
otherwise stated.
If the actual test conditions differ from the reference conditions (20 °C, 70 % relative humidity, 1 013,25 mbar)
and/or the return water temperature differs from the specified value, the correction formulae given in Annex A are
used to correct the determined useful efficiency for the tests outlined in 5.2 and 5.6.2.
5.2 Verification of the nominal condensing output
The water rate is adjusted so as to obtain a return water temperature of (30 ± 0,5) °C and a temperature difference
between flow and return temperature of (20 ± 2) °C.
5.3 Formation of condensation
The boiler shall operate continuously for 4 h under the test conditions of 5.2.
It shall be verified that the requirement of 4.2 3 is fulfilled.
5.4 Temperature of combustion products
The boiler shall be installed as specified in the general test conditions of boiler standards EN 303-2 and EN 304.
The boiler thermostat shall be put out of operation. Where fitted, the control to limit the temperature of combustion
products remains in operation.
7

---------------------- Page: 9 ----------------------

SIST EN 15034:2007
EN 15034:2006 (E)
The temperature of the combustion products shall be progressively raised, either by increasing the fuel rate or by
another means which increases the temperature (e.g. removal of baffles) as specified by the manufacturer. It shall
be verified that the requirement of 4.2.4 is fulfilled.
5.5 Combustion
5.5.1 Normal condit
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.