SIST EN 17255-2:2020
(Main)Stationary source emissions - Data acquisition and handling systems - Part 2: Specification of requirements on data acquisition and handling systems
Stationary source emissions - Data acquisition and handling systems - Part 2: Specification of requirements on data acquisition and handling systems
This European Standard specifies the performance requirements on data acquisition and handling systems (DAHS) regarding implementation of the procedures defined in EN 17255-1 including
— data acquisition;
— data processing;
— data storage;
— data output;
— generation of reports;
— system functions;
— data security;
— documentation.
This European Standard supports the requirements of EN 14181 and legislation such as the IED and E-PRTR. It does not preclude the use of additional features and functions provided the minimum requirements of this European Standard are met and that these features do not adversely affect data quality, clarity or access.
This European Standard does not cover additional requirements for multiplexing systems where gases are sampled from multiple sources.
Emissionen aus stationären Quellen - Datenerfassungs- und Auswerteeinrichtungen - Teil 2: Festlegung von Anforderungen an Datenerfassungs- und Auswerteeinrichtungen
Dieses Dokument legt die Leistungsanforderungen an Datenerfassungs- und Auswerteeinrichtungen (DAHS) hinsichtlich der Umsetzung der in EN 17255 1 definierten Verfahren fest, einschließlich
- Datenerfassung;
- Datenverarbeitung;
- Datenspeicherung;
- Datenausgabe;
- Berichterstellung;
- Systemfunktionen;
- Datenintegrität;
- Dokumentation.
Dieses Dokument unterstützt die Anforderungen von EN 14181 sowie Rechtsvorschriften wie IED und E PRTR. Sie schließt die Verwendung zusätzlicher Möglichkeiten und Funktionen unter der Voraussetzung nicht aus, dass die Mindestanforderungen in diesem Dokument erfüllt werden und diese Möglichkeiten die Qualität und Verständlichkeit der Daten sowie den Datenzugriff nicht negativ beeinträchtigen.
Émissions de sources fixes - Systèmes d’acquisition et de traitement de données - Partie 2 : Spécification des exigences relatives aux systèmes d’acquisition et de traitement de données
Le présent document spécifie les exigences de performance relatives aux systèmes d'acquisition et de traitement de données (DAHS) concernant la mise en oeuvre des modes opératoires définis dans l'EN 17255 1 ; ces exigences portent sur :
- l'acquisition des donnés ;
- le traitement des données ;
- le stockage de données ;
- la sortie des données ;
- la production de rapports ;
- les fonctions du système ;
- l'intégrité des données ;
- la documentation.
Le présent document vient à l'appui des exigences de l'EN 14181 et de législations telles que la Directive IED et le règlement relatif au PRTR européen. Il n'interdit pas l'utilisation de caractéristiques et de fonctions supplémentaires, à condition que les exigences minimales du présent document soient remplies et que ces caractéristiques n'aient pas d'influence négative sur la qualité et la clarté des données ou sur l'accès à ces dernières.
Emisije nepremičnih virov - Sistemi za zajem in vrednotenje podatkov (DAHS) - 2. del: Specifikacija zahtev za sisteme za zajem in vrednotenje podatkov
General Information
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 17255-2:2020
01-julij-2020
Emisije nepremičnih virov - Sistemi za zajem in vrednotenje podatkov (DAHS) - 2.
del: Specifikacija zahtev za sisteme za zajem in vrednotenje podatkov
Stationary source emissions - Data acquisition and handling systems - Part 2:
Specification of requirements on data acquisition and handling systems
Emissionen aus stationären Quellen - Datenerfassungs- und Auswerteeinrichtungen -
Teil 2: Festlegung von Anforderungen an Datenerfassungs- und Auswerteeinrichtungen
Émissions de sources fixes - Systèmes d’acquisition et de traitement de données - Partie
2 : Spécification des exigences relatives aux systèmes d’acquisition et de traitement de
donnéesTa slovenski standard je istoveten z: EN 17255-2:2020
ICS:
13.040.40 Emisije nepremičnih virov Stationary source emissions
SIST EN 17255-2:2020 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------SIST EN 17255-2:2020
---------------------- Page: 2 ----------------------
SIST EN 17255-2:2020
EN 17255-2
EUROPEAN STANDARD
NORME EUROPÉENNE
April 2020
EUROPÄISCHE NORM
ICS 13.040.40
English Version
Stationary source emissions - Data acquisition and
handling systems - Part 2: Specification of requirements on
data acquisition and handling systems
Émissions de sources fixes - Systèmes d'acquisition et Emissionen aus stationären Quellen - Datenerfassungs-
de traitement de données - Partie 2 : Spécification des und Auswerteeinrichtungen - Teil 2: Festlegung von
exigences relatives aux systèmes d'acquisition et de Anforderungen an Datenerfassungs- und
traitement de données AuswerteeinrichtungenThis European Standard was approved by CEN on 7 March 2020.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2020 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 17255-2:2020 E
worldwide for CEN national Members.---------------------- Page: 3 ----------------------
SIST EN 17255-2:2020
EN 17255-2:2020 (E)
Contents Page
European foreword ....................................................................................................................................................... 4
Introduction .................................................................................................................................................................... 5
1 Scope .................................................................................................................................................................... 6
2 Normative references .................................................................................................................................... 6
3 Terms and definitions ................................................................................................................................... 6
4 Symbols and abbreviations ......................................................................................................................... 8
5 Principles ........................................................................................................................................................... 8
6 Performance requirements ......................................................................................................................... 9
6.1 General ................................................................................................................................................................ 9
6.2 Data acquisition ............................................................................................................................................ 10
6.2.1 Overview ......................................................................................................................................................... 10
6.2.2 Interfaces ........................................................................................................................................................ 10
6.2.3 Manual data input ........................................................................................................................................ 11
6.2.4 Remote data logger unit ............................................................................................................................ 11
6.3 Input data processing ................................................................................................................................. 11
6.3.1 Validity of input data .................................................................................................................................. 11
6.3.2 First level data (FLD) .................................................................................................................................. 12
6.4 Reported data ................................................................................................................................................ 12
6.4.1 General ............................................................................................................................................................. 12
6.4.2 Warnings, alarms and violations ............................................................................................................ 12
6.5 Reports ............................................................................................................................................................. 12
6.5.1 General ............................................................................................................................................................. 12
6.5.2 Emission reports .......................................................................................................................................... 13
6.5.3 System reports .............................................................................................................................................. 13
6.6 Data storage ................................................................................................................................................... 13
6.6.1 General ............................................................................................................................................................. 13
6.6.2 Time stamping ............................................................................................................................................... 13
6.6.3 Storage of FLD ................................................................................................................................................ 13
6.6.4 Storage of STA ................................................................................................................................................ 13
6.6.5 Storage of standardized STA (SSTA)...................................................................................................... 14
6.6.6 Storage of validated STA (VSTA) ............................................................................................................. 14
6.6.7 Storage of QAL3 data ................................................................................................................................... 14
6.6.8 Storage of warnings, alarms and violations ....................................................................................... 14
6.6.9 Storage of the event-log and configuration parameters ................................................................ 14
6.7 System functions .......................................................................................................................................... 14
6.7.1 Event log .......................................................................................................................................................... 14
6.7.2 Configuration ................................................................................................................................................. 14
6.7.3 Export of data ................................................................................................................................................ 14
6.7.4 Test mode ........................................................................................................................................................ 15
6.8 Data integrity ................................................................................................................................................. 15
6.8.1 DAHS availability .......................................................................................................................................... 15
6.8.2 Tamper-proof data transfer and handling .......................................................................................... 15
6.8.3 Preventing loss of data ............................................................................................................................... 15
6.8.4 Data back-up .................................................................................................................................................. 15
6.8.5 DAHS identification ..................................................................................................................................... 16
---------------------- Page: 4 ----------------------SIST EN 17255-2:2020
EN 17255-2:2020 (E)
6.8.6 Time management ........................................................................................................................................ 16
6.9 Documentation .............................................................................................................................................. 16
Annex A (informative) Example list of configuration parameters ........................................................... 17
A.1 Measurement channel configuration .................................................................................................... 17
A.2 Data processing configuration ................................................................................................................. 18
A.3 Data storage configuration ........................................................................................................................ 19
A.4 Report configuration ................................................................................................................................... 19
Bibliography ................................................................................................................................................................. 20
---------------------- Page: 5 ----------------------SIST EN 17255-2:2020
EN 17255-2:2020 (E)
European foreword
This document (EN 17255-2:2020) has been prepared by Technical Committee CEN/TC 264 “Air
Quality”, the secretariat of which is held by DIN.This document shall be given the status of a national standard, either by publication of an identical text
or by endorsement, at the latest by October 2020, and conflicting national standards shall be withdrawn
at the latest by October 2020.Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document is Part 2 of the EN 17255 series.The EN 17255 series, published under the general title Stationary source emissions — Data acquisition
and handling systems, specifies:— requirements for the handling and reporting of data;
— requirements on data acquisition and handling systems;
— requirements for the performance test of data acquisition and handling systems;
— requirements for the installation and on-going quality assurance and quality control of data
acquisition and handling systems.According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this document: Austria, Belgium, Bulgaria, Croatia, Cyprus,
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of North
Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United
Kingdom.---------------------- Page: 6 ----------------------
SIST EN 17255-2:2020
EN 17255-2:2020 (E)
Introduction
This document forms part of a series of standards which, between them, govern the process for the
quality assurance of data received by a data acquisition and handling system (DAHS) from automated
measuring systems (AMS), being used for monitoring emissions from stationary sources and quality
ensured to EN 14181.The input data can be either in analogue representation or in digital form directly from an AMS or via a
digital bus system. Inputs can include the data from the AMS, peripheral data needed for calculation of
the reported values and information on plant conditions needed to apply data selection criteria.
The data acquisition and handling system (DAHS) receives the raw data, as they are measured, averaged
and presented by the AMS, and converts, averages, stores and reports data as required by legislation.
This series of standards suggests that the process of data handling is best performed in a dedicated DAHS.
It does not preclude the use of other options for all or part of the process provided that it can be shown
to meet all of the requirements of the standard, particularly in relation to speed, accuracy, access, security
and validation.This series of standards applies to all DAHS installed after the date of implementation of this document.
EN 17255-2 specifies the implementation of the calculations laid down in EN 17255-1 and the specific
requirements on functionality of the DAHS.---------------------- Page: 7 ----------------------
SIST EN 17255-2:2020
EN 17255-2:2020 (E)
1 Scope
This document specifies the performance requirements on data acquisition and handling systems (DAHS)
regarding implementation of the procedures defined in EN 17255-1 including— data acquisition;
— data processing;
— data storage;
— data output;
— generation of reports;
— system functions;
— data integrity;
— documentation.
This document supports the requirements of EN 14181 and legislation such as the IED and E-PRTR. It
does not preclude the use of additional features and functions provided the minimum requirements of
this document are met and that these features do not adversely affect data quality, clarity or access.
2 Normative referencesThe following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 14181:2014, Stationary source emissions - Quality assurance of automated measuring systems
EN 17255-1, Stationary source emissions - Data acquisition and handling systems - Part 1: Specification of
requirements for the handling and reporting of dataIEEE 754, Floating-point arithmetic
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 17255-1 and the following apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— IEC Electropedia: available at http://www.electropedia.org/— ISO Online browsing platform: available at https://www.iso.org/obp
3.1
warning signal
binary value or enumerated value signifying the need for action
Note 1 to entry: Warnings can be derived from measurement values or conditions, which are still within the
specified limits, but where the value is close to the specified limit. Warnings are for the benefit of the plant operator.
---------------------- Page: 8 ----------------------SIST EN 17255-2:2020
EN 17255-2:2020 (E)
Note 2 to entry: Warnings can be conditions communicated to the plant operator as requiring attention.
Instrument conditions like operation exceeding the upper limit of the valid calibration range are also considered as
warnings.3.2
alarm signal
binary value or enumerated value indicating an alarm state
Note 1 to entry: Examples of alarm signals are incidents where an ELV is exceeded,
Note 2 to entry: Examples of alarm signals from instruments include conditions such as out of operation, and
operation conditions like measurements outside the measurement range.Note 3 to entry: A condition, which leads to an alarm, can lead to a violation, if it persists too long according to
directives, local permits or other standards.Note 4 to entry: Alarms are conditions communicated to the plant operator indicating that the plant if it continues
in this state could enter into a condition where it is not any longer fulfilling the relevant directive conditions.
3.3violation signal
binary value or enumerated value indicating presence of a condition where requirements of directives,
operating permits or other standards are exceededNote 1 to entry: Measured values above ELV at a duration exceeding the limit in the directives can cause a
violation signal.Note 2 to entry: Instrument conditions like too many hours out of operation, and operation conditions like
exceeding the valid calibration range for too many time periods related to the short-term average can cause
violation signals.3.4
data storage
electronic memory capacity to hold data for processing or documentation
Note 1 to entry: This document does not prescribe storage technology. It is always the responsibility of the plant
operator that the capacity and reliability of the chosen storage is sufficient.3.5
permanent data storage
non-volatile data storage with the capacity to hold data for a period equal to or exceeding a required
minimum time period3.6
event
occurrence that could affect the performance or processing of the DAHS
Note 1 to entry: Events can be caused by an operator, e.g. by adding or changing configuration data, peripheral
data, limit values, QAL2 data or basic information, or by the system itself, e.g. for watchdog restart, change to or
from DST, recovery from power cut, performing automatic backup, reporting lack of communication with AMS or
external data loggers, or generating reports.---------------------- Page: 9 ----------------------
SIST EN 17255-2:2020
EN 17255-2:2020 (E)
4 Symbols and abbreviations
AMS automated measuring system
DAHS data acquisition and handling system
DST daylight saving time
ELV emission limit value
E-PRTR European pollutant release and transfer register
FLD first level data
IED industrial emissions directive
LTA long-term average
OPC open platform communication
QAL2 second quality assurance level
QAL3 third quality assurance level
SRM standard reference method
SSTA standardized short-term average
STA short-term average
UTC coordinated universal time
VSTA validated short-term average
5 Principles
This document specifies minimum requirements for the performance and functional capabilities of DAHS.
The minimum functional capabilities specified in this document are considered to be necessary to meet
the requirements of the relevant regulations (e.g. EU Directives) in terms of the provision of emissions
data for reporting. These functional capabilities also cover the traceability, security and ability to audit
reported data.The DAHS provides the time stamp for input data.
Figure 1 shows the elements of the DAHS defined in this document.
---------------------- Page: 10 ----------------------
SIST EN 17255-2:2020
EN 17255-2:2020 (E)
Key
A DAHS
B1 AMS data interface
B2 peripheral data interface
B3 plant data interface
C input processing and production of FL
...
Questions, Comments and Discussion