Electronic individual zone control equipment

The purpose of this standard is to specify the applications, functionality set and application performance for electronic individual zone control equipment. The applications are for cooling and hot water or electrical heating as described in Annex B. This standard applies specifically to individual zone control equipment for maintaining temperature, humidity and air flow as a function of occupancy and demand operated with auxiliary electrical energy. Information required for the operation of the equipment may be processed using either analogue or digital techniques or a combination of both. Safety requirements remain unaffected by this standard. This standard refers to the input and output requirements of the controller and not of the input and output devices as e. g. sensors and actuators. This standard covers fixed-function, configurable and programmable controllers. The control equipment may or may not be connected to a data-network however communications aspects are not covered by this standard. These devices could be applied for any kind of building, intermittent or non-intermittent occupation, residential or non residential (see Annex B).

Elektronische Regel- und Steuereinrichtungen für einzelne Räume oder Zonen

Der Zweck dieser Norm besteht in der Festlegung der Anwendungen, des Funktionalitätensatzes und der anwendungsbezogenen Leistung der elektronischen Einzelzonenregel  und  steuergeräte für folgende Zwecke:
-   Heizung für elektrische und Warmwasseranwendungen;
-   Anwendungen bei Gebläsekonvektoren und Induktionsgeräten;
-   VVS , CAV  und Kühldeckenanwendungen.
Diese Norm gilt insbesondere für Einzelzonenregel  und  steuergeräte, die der Aufrechterhaltung der Temperatur, der Luftfeuchte und der Luftströmung als Funktion der Belegung und des Bedarfs dienen und mit elektrischer Hilfsenergie betrieben werden.
Die für den Betrieb der Geräte erforderlichen Informationen dürfen entweder mit analogen oder mit digitalen Verfahren oder mit einer Kombination aus beiden verarbeitet werden. Anforderungen an die Sicherheit bleiben in dieser Norm unberücksichtigt.
Die Regel  und Steuergeräte dürfen an ein Datennetz angeschlossen sein, brauchen dies jedoch nicht; Kommunikationsaspekte sind von dieser Norm jedoch nicht abgedeckt.

Régulateur électronique de zone pour le chauffage

La présente norme a pour objet de spécifier les applications, ensembles de fonctionnalités et performances
d'application des régulateurs électroniques de zone. Les applications concernent le refroidissement, et le
chauffage à eau chaude ou électrique, comme décrit dans l'Annexe B.
La présente norme s'applique spécifiquement aux régulateurs électroniques de zone pour le maintien de la
température, de l'humidité et du débit d'air en fonction des conditions d'occupation et de la demande,
fonctionnant avec une énergie électrique auxiliaire.
Les informations nécessaires au fonctionnement de l'équipement peuvent être traitées par des techniques
analogiques et/ou numériques. Les exigences en matière de sécurité ne font pas l'objet de la présente norme.
Cette norme fait référence aux spécifications des entrées-sorties du régulateur et non aux dispositifs d’entréesortie
comme, par exemple, les capteurs et actionneurs.
Cette norme concerne les appareils dont les fonctions sont dédiées, configurables ou programmables.
L'équipement de régulation peut ou non être connecté à un réseau de transmission de données. Toutefois,
les aspects liés à la communication ne sont pas abordés dans la présente norme.
Ces dispositifs peuvent être prévus pour toute sorte de bâtiment, intermittent ou non, résidentiel ou non
(voir Annexe B).

Elektronske naprave za regulacijo posameznih con

General Information

Status
Withdrawn
Publication Date
02-Nov-2008
Withdrawal Date
11-Apr-2018
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
26-Mar-2018
Due Date
18-Apr-2018
Completion Date
12-Apr-2018

Relations

Buy Standard

Standard
EN 15500:2008
English language
66 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Elektronske naprave za regulacijo posameznih conElektronische Regel- und Steuereinrichtungen für einzelne Räume oder ZonenRégulateur électronique de zone pour le chauffageElectronic individual zone control equipment97.120Avtomatske krmilne naprave za domAutomatic controls for household useICS:Ta slovenski standard je istoveten z:EN 15500:2008SIST EN 15500:2008en,fr,de01-december-2008SIST EN 15500:2008SLOVENSKI
STANDARD



SIST EN 15500:2008



EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 15500July 2008ICS 97.120 English VersionControl for heating, ventilating and air-conditioning applications -Electronic individual zone control equipmentRégulation pour les applications CVC - Régulateursélectroniques de zone pour le chauffageAutomation von HLK-Anwendungen - Elektronische Regel-und Steuereinrichtungen für einzelne Räume oder ZonenThis European Standard was approved by CEN on 3 November 2007.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the CEN Management Centre or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as theofficial versions.CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2008 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 15500:2008: ESIST EN 15500:2008



EN 15500:2008 (E) 2 Contents Page Foreword.4 Introduction.5 1 Scope.6 2 Normative references.7 3 Terms and definitions.7 4 Abbreviations.10 5 Functionality.11 5.1 General.11 5.1.1 Functional objective.11 5.1.2 Minimum operating mode.11 5.1.3 Controller functions.12 5.1.4 Function blocks.14 5.2 Heating application.17 5.2.1 Central generation.17 5.2.2 Direct heating.17 5.2.3 Storage system (for direct or central heating).18 5.3 Fan coil and induction application.19 5.3.1 Four pipe fan coil units.19 5.3.2 Functional objective.20 5.3.3 Two pipe Fan Coil Units.21 5.3.4 2 Pipes 2 Wires Fan Coil Units.23 5.3.5 Induction units.25 5.4 VAV, CAV and Chilled Ceiling Applications.27 5.4.1 Functionality requirements.27 5.4.2 Factory settings for fixed-function controllers.28 5.4.3 Pressure dependent VAV systems.29 5.4.4 Pressure independent VAV systems.30 5.4.5 Fan assisted VAV systems.32 5.4.6 CAV Systems.34 5.4.7 Chilled ceilings.36 5.4.8 Dewpoint control function.38 5.5 Functionality and hardware.38 5.5.1 General.38 5.5.2 Power supply and data protection.38 5.5.3 Inputs.38 5.5.4 Outputs.39 5.5.5 Sensor requirements.39 5.6 Temperature control accuracy.40 5.7 Human System Interface (HSI).41 5.8 Electrical requirements.42 5.8.1 General.42 5.8.2 Supply voltage.42 5.8.3 Protection against electric shock.42 5.8.4 Electromagnetic compatibility.42 5.8.5 Degrees of protection.42 5.8.6 Environmentally induced stress due to temperature.42 5.8.7 Materials.42 6 Test method.43 6.1 Power supply and data protection.43 6.2 Operating modes.43 SIST EN 15500:2008



EN 15500:2008 (E) 3 6.2.1 Economy mode.43 6.2.2 Frost protection.43 6.3 Human System Interface (HSI).43 6.4 Temperature control accuracy compliance.43 6.5 Electrical tests.43 6.6 Supply voltage.43 6.7 Protection against electric shock.43 6.8 Electromagnetic compatibility.43 6.9 Degrees of protection.44 6.10 Environmental individual stress due to temperature.44 7 Classification and designation.44 8 Marking and documentation.44 8.1 Marking.44 8.2 Documentation.45 8.2.1 Installation instructions.45 8.2.2 Factory settings and adjustment possibilities.45 8.2.3 User operating instructions.45 Annex A (normative)
Functional and acceptance test.46 A.1 Objective.46 A.2 Testing procedures.46 A.2.1 Test principle.46 A.2.2 Test parameters.47 A.2.3 Product configuration.48 A.2.4 Definition of the Control Accuracy (CA).49 A.3 Test facility description.54 A.3.1 General layout.54 A.3.2 Sensor side interface.56 A.3.3 Actuator side interface.59 A.3.4 Interface between real and simulated environment.61 A.3.5 Simulated environment.62 A.3.6 Data acquisition system.62 Annex B (informative)
Data.63 B.1 Objective.63 B.2 Applications.63 B.3 Building and zone types.63 B.3.1 Building types.63 B.3.2 Zone types.64 B.4 Default time test parameters.64 Bibliography.66
SIST EN 15500:2008



EN 15500:2008 (E) 4 Foreword This document (EN 15500:2008) has been prepared by Technical Committee CEN/TC 247 “Building Automation, Controls and Building Management”, the secretariat of which is held by SNV. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by January 2009, and conflicting national standards shall be withdrawn at the latest by January 2009. This standard is for products for electronic individual zone control equipment applications for mechanical building services and covers electronic individual zone control equipment for heating, ventilation and air conditioning applications in residential and non residential buildings. This standard is part of a series of European Standards for Control for HVAC Applications. This standard, therefore, contributes to the general European policy for energy saving, particularly in the fields of the Construction Products Directive (89/106/EEC) Essential Requirements n°6 «Energy economy and heat retention» (and its interpretative document) and of the Energy Performance of Building Directive (2002/91/CE). No existing European Standard is superseded. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. SIST EN 15500:2008



EN 15500:2008 (E) 5 Introduction Equipment to control the heating, ventilation and air-conditioning (HVAC) in a building according to the actual room or zone energy demand, is necessary in order to reduce the consumption of energy and improve the quality of the air. HVAC installations should, for the purpose of energy conservation and guaranteeing indoor environmental comfort, be equipped with automatic zone control equipment acting as function of measured inside variables in buildings. Under the term “automatic zone control equipment” is understood the functional unit comprising controller, actuator and sensor. The zone control equipment controls the comfort of the environment by controlling physical variables such as temperature, humidity, air-quality or air-flow in accordance with occupancy and user requirements. This standard, which is valid for applications in all domestic and non-domestic buildings, conforms to the requirements and objectives of the interpretative documents “Energy Economy and Heat Retention” and “Hygiene, Health and the Environment” relating to the Construction Products Directive (89/106/EEC) and the preparations for a standardisation mandate from the European Commission are on-going. SIST EN 15500:2008



EN 15500:2008 (E) 6
1 Scope The purpose of this standard is to specify the applications, functionality set and application performance for electronic individual zone control equipment. The applications are for cooling and hot water or electrical heating as described in Annex B. This standard applies specifically to individual zone control equipment for maintaining temperature, humidity and air flow as a function of occupancy and demand operated with auxiliary electrical energy. Information required for the operation of the equipment may be processed using either analogue or digital techniques or a combination of both. Safety requirements remain unaffected by this standard. This standard refers to the input and output requirements of the controller and not of the input and output devices as e. g. sensors and actuators. This standard covers fixed-function, configurable and programmable controllers. The control equipment may or may not be connected to a data-network however communications aspects are not covered by this standard. These devices could be applied for any kind of building, intermittent or non-intermittent occupation, residential or non residential (see Annex B). SIST EN 15500:2008



EN 15500:2008 (E) 7
2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 12098-2, Controls for heating systems — Part 2: Optimum start-stop control equipment for hot water heating systems EN 12098-5, Controls for heating systems — Part 5: Start-stop schedulers for heating systems EN 60529, Degrees of protection provided by enclosures (IP code) (IEC 60529:1989) EN 60730 (all parts), Automatic electrical controls for household and similar use IEC 60038, IEC standard voltages 3 Terms and definitions For the purposes of this document, the following terms and definitions apply. 3.1 electronic individual zone control equipment equipment performing closed loop control functions of physical measured variable(s) (e.g. temperature, humidity, pressure) in a single room or in an area of a building 3.1.1
Fixed-function controller
application-specific controller where the manufacturer supplies one or more fixed control strategies for specific applications
NOTE see also EN ISO 16484-2
3.1.2
Configurable controller
Controller where the manufacturer supplies one or more configurable control strategies for specific applications
NOTE see also EN ISO 16484-2 3.1.3
Programmable controller
Controller where the control strategies can be programmed
NOTE 1 Programmable controllers also are named automation station.
NOTE 2 see also EN ISO 16484-2 3.2 operating mode mode that applies either to control equipment or to control functions NOTE Operating modes can be switched over by a scheduler program or manual. 3.2.1 manual mode of operation of equipment when significant control functions is overridden by the user SIST EN 15500:2008



EN 15500:2008 (E) 8 3.2.2 automatic mode of operation of equipment when significant control functions are not overridden by the user 3.2.3 operating time override mode of operation of equipment that overrides the operating state to a predetermined other operating mode, e.g. comfort or economy for a limited pre-determined period of time 3.2.4 comfort mode of operation for a normally occupied room. The room state is in the comfort range with regard to temperature, humidity, air-quality or air-flow. NOTE Other terms for comfort mode are e. g. normal, occupied, party mode. 3.2.5 reduced or economy mode of operation for an energy saving operating for a non occupied room that does not need to be in the comfort operating mode for an extended period of time
NOTE 1 In the reduced operating mode, the control setpoint is lowered or raised with respect to the comfort setpoint. NOTE 2 Other terms for economy mode are e. g. unoccupied, night set-back, sleeping, holiday. 3.2.6 pre comfort reduced operating mode for the room to quickly reach the comfort range upon changing to a comfort operating mode 3.2.7 frost protection mode of operation to reach a minimum acceptable positive temperature preventing freezing 3.2.8 building protection mode of operation to protect the building from overheating or supercooling 3.2.9 off state where control and interlock functions are not operational 3.2.10 holiday function where a time programme is used to control a room temperature for a pre-determined period 3.2.11 tariff optimization function to control the room temperature according to the tariff rate signal from the electrical supplier 3.3 input and output devices 3.3.1 input device / sensor detector measures physical parameters such as temperature, humidity, air-quality, air-flow or occupancy. The sensor is incorporated into housing suitable for mounting and can be regarded as a functional unit which produces a signal that can be evaluated in correspondence with the quantity measured SIST EN 15500:2008



EN 15500:2008 (E) 9 3.3.2 output device / actuator changes mass-, volume- and energy-flows. The actuator can be regarded as functional unit which carries out an appropriate change according to an appropriately evaluated signal SIST EN 15500:2008



EN 15500:2008 (E) 10 4 Abbreviations For the purposes of this document, the following abbreviations and acronyms apply. ASP Actual Setpoint BACS Building Automation and Control System CA Control Accuracy CAh Control Accuracy for heating CAc Control Accuracy for cooling CAV Constant Air Volume CCS Chilled Ceiling System CP Control Parameters CSD Control Setpoint Deviation CTRL
Control to setpoint
CV Control Variation EC Electric Convector ECH Electric Ceiling Heating EFH Electric Floor Heating EUBAC European Building Automation and Controls Association FCU-2P Fan Coil Unit system - 2 Pipes FCU-2P2W Fan Coil Unit system - 2 Pipes 2 Wires FCU-4P Fan Coil Unit system - 4 Pipes h Hours HVAC Heating Ventilating and Air Conditioning IEEE Institute of Electrical and Electronics Engineers IEP Index of Energy Price K Kelvin LIM
Limit NTC Negative Thermal Coefficient OM Operating Mode OP Other Parameters OS Output Signal P-Band Proportional Band PES Price energy Signal PI Proportional plus Integral PID Proportional plus Integral plus Derivative SIST EN 15500:2008



EN 15500:2008 (E) 11 s Seconds SC Speed control
SP Setpoint SPA Setpoint Adjustment SPD Setpoint determination function
T1 Time 1 (End of the overshoot test period) T2 Time 2 (End of transient test period) TDP Dewpoint temperature TS Surface temperature TZ Zone temperature V Air (volume) flow VAV Variable Air Volume Vmax Maximum air (volume) flow limit Vmin Minimum air (volume) flow limit Vnom Nominal flow, i.e. the maximum air flow that a VAV box can handle as specified by the manufacturer Vs Volume supply air
Vx Volume exhaust air
WFH Water Floor Heating
5 Functionality 5.1 General 5.1.1 Functional objective The objective of electronic individual zone control equipment is to save energy and contribute to acceptable levels of hygiene, health and comfort, by performing the following primary functions:  control the zone variables by influencing the energy supply source (e.g. hot/chilled fluid, electrical energy, air volume);  minimise the energy supplied to the zone (e.g. operating modes: comfort, economy);  minimise running cost according to the price of energy. 5.1.2 Minimum operating mode To minimise energy consumption, heating zone controllers shall at least include the following three operating modes, as defined in 5.1.3:  comfort;  reduced or economy; SIST EN 15500:2008



EN 15500:2008 (E) 12  frost protection;  building protection. 5.1.3 Controller functions Table 1 describes the functions which the controller can be capable of carrying out, and if they have any significant benefit on energy savings, air quality, comfort and hygiene/health. Table 1 — Controller functions General functions for zone automation controls
Name Description Save energy Air quality Temp comfort Hygiene/health Local function System function Control to setpoint of the zone temperature Algorithm to maintain the room temperature to a pre-determined level x
x
x
Setpoint determination Method by which the pre-determined room temperature is set
x x Setpoint limitation Upper and/or lower control limit for the room temperature setpoint x
x
x
Limitation monitoring Checking that the controlled output complies with pre-selected high or low limit parameters x
x
x
Time scheduling Method by which the temperature level is split into pre-determined periods x
x
x x
SIST EN 15500:2008



EN 15500:2008 (E) 13
Table 1 — Controller functions (continued) Name Description Save energy Air quality Temp comfort Hygiene/health Local function System function Optimum start stop, Predictive control Algorithm to calculate advance level change period to achieve setpoint at a pre-determined time
x x Free cooling Cooling with external air
x Window open protection Monitoring the state of windows (open and closed). Signal sent to the zone controller to take action when the windows are open or closed x
Boost A heating operational mode providing maximal power (heating or cooling)
x
x x Summer/winter changeover Changing the action of the controller depending of the heating or cooling demand x
x
Summer/winter compensation Algorithm/selection to adjust temperature control for changes in load condition x
x
Operating time override Means of providing a pre-determined period of comfort level
x
Energy demand request Signal from the secondary controller with the greatest heating/cooling demand sent to the primary controller x
x
Status monitoring The monitoring of the status of Zone Controller devices, and any action which is taken to change the operation of the Zone Controller as a result of analysing the monitored values
Occupancy sensing Signal sent to the zone controller to take action when the zone is occupied/unoccupied x
x
x
Energy price optimizing Signal supplied by the utility to set the price level of electrical energy
x
SIST EN 15500:2008



EN 15500:2008 (E) 14
Table 1 — Controller functions (concluded) Name Description Save energy Air quality Temp comfort Hygiene/health Local function System function Air flush Purging a zone with fresh air immediately prior to occupancy, to improve air quality
x x
Demand controlled ventilation The amount of air is controlled based on number of persons in the zone and/or air quality x x
Frost/building protection Special damage control function for switching all relevant parts of a plant into predicted state in order to avoid frost damage
x
Manual/auto operation Functional operating mode
Operating modes concerning the comfort level in the zone:
Comfort
x x x x
Pre comfort
x
Economy
x
Protection
x
Technical/functional operating modes:
Off
Holiday
Tariff optimisation
Manual
Automatic
Exclusions:  this standard does not preclude other functions such as alarm signalling, lighting control or other integrated functions;  the controller manufacturer is not necessarily responsible for the control of the process-side of the associated equipment;  safety and related features of the associated equipment are the responsibility of the supplier of
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.