oSIST prEN 54-30:2009
(Main)Fire detection and fire alarm systems - Part 30: Multi-sensor fire detectors - Point detectors using a combination of carbon monoxide and heat sensors
Fire detection and fire alarm systems - Part 30: Multi-sensor fire detectors - Point detectors using a combination of carbon monoxide and heat sensors
This European Standard specifies requirements, test methods and performance criteria for point-type multi-sensor fire detectors fur use in fire detection systems installed in buildings (see EN 54-1), incorporating in one mechanical enclosure at least one carbon monoxide sensor and at least one heat sensor. The overall fire detection performance is determined utilizing the combination of the detected phenomena.
Multi-sensor fire detectors having special characteristics suitable for the detection of specific fire risks are not covered by this standard. The performance requirements for any additional functions are beyond the scope of this standard (e.g. additional features or enhanced functionality for which this standard does not define a test or assessment method).
Brandmeldeanlagen - Teil 30: Mehrfachsensor-Brandmelder - Punktförmige Melder mit kombinierten CO- und Wärmesensoren
Système de détection et d'alarme incendie - Partie 30: Détecteurs d'incendie multicapteurs - Détecteurs ponctuels combinant l'utilisation de capteurs de monoxyde de carbone et de capteurs de chaleur
La présente Norme européenne spécifie les exigences, les méthodes d'essai et les critères de performance relatifs aux détecteurs d'incendie multicapteur ponctuels destinés à être utilisés dans les systèmes de détection d'incendie installés dans les bâtiments (voir EN 54-1), incorporant dans une seule enveloppe mécanique au moins un capteur de monoxyde de carbone et au moins un capteur de chaleur. La performance globale de détection d'incendie est déterminée en utilisant la combinaison des phénomènes détectés.
Les détecteurs d'incendie multicapteur possédant des caractéristiques particulières adaptées à la détection des risques d'incendie spécifiques ne sont pas pris en compte dans la présente norme. Les exigences de performance relatives à toute autre fonction supplémentaire ne relèvent pas du domaine d'application de la présente norme (par exemple, caractéristiques supplémentaires ou fonctionnalité améliorée pour lesquelles la présente norme ne définit pas de méthode d'essai ou d'évaluation).
Sistemi za odkrivanje in javljanje požara ter alarmiranje - 30. del: Večsenzorski javljalniki požara - Točkovni javljalniki s senzorjema za zaznavanje ogljikovega monoksida in toplote
General Information
Standards Content (Sample)
SLOVENSKI STANDARD
oSIST prEN 54-30:2009
01-julij-2009
6LVWHPL]DRGNULYDQMHLQMDYOMDQMHSRåDUDWHUDODUPLUDQMHGHO9HþVHQ]RUVNL
MDYOMDOQLNLSRåDUD7RþNRYQLMDYOMDOQLNLVVHQ]RUMHPD]D]D]QDYDQMHRJOMLNRYHJD
PRQRNVLGDLQWRSORWH
Fire detection and fire alarm systems - Part 30: Multi-sensor fire detectors - Point
detectors using a combination of carbon monoxide and heat sensors
Brandmeldeanlagen - Teil 30: Mehrfachsensor-Brandmelder - Punktförmige Melder mit
kombinierten CO- und Wärmesensoren
Système de détection et d'alarme incendie - Partie 30: Détecteurs d'incendie
multicapteurs - Détecteurs ponctuels combinant l'utilisation de capteurs de monoxyde de
carbone et de capteurs de chaleur
Ta slovenski standard je istoveten z: prEN 54-30
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
oSIST prEN 54-30:2009 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
oSIST prEN 54-30:2009
---------------------- Page: 2 ----------------------
oSIST prEN 54-30:2009
EUROPEAN STANDARD
DRAFT
prEN 54-30
NORME EUROPÉENNE
EUROPÄISCHE NORM
March 2009
ICS
English Version
Fire detection and fire alarm systems - Part 30: Multi-sensor fire
detectors - Point detectors using a combination of carbon
monoxide and heat sensors
Système de détection et d'alarme incendie - Partie 30: Brandmeldeanlagen - Teil 30: Mehrfachsensor-
Détecteurs d'incendie multicapteur - Détecteurs ponctuels Brandmelder - Punktförmige Melder mit kombinierten CO-
utilisant une combinaison de capteurs de monoxide de und Wärmesensoren
carbone et de température
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 72.
If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the
same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.
Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2009 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 54-30:2009: E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
oSIST prEN 54-30:2009
prEN 54-30:2009 (E)
Contents Page
Foreword .4
Introduction .4
1 Scope .5
2 Normative references .5
3 Terms and definitions .6
4 Requirements .6
4.1 Compliance .6
4.2 Individual alarm indication .6
4.3 Connection of ancillary devices .6
4.4 Monitoring of detachable detectors .6
4.5 Manufacturer's adjustments .7
4.6 On-site adjustment of response behaviour .7
4.7 Rate-sensitive CO response .7
4.8 Position of the heat sensors .7
4.9 Marking .7
4.10 Data .8
4.11 Additional requirements for software controlled detectors .8
5 Test methods .9
5.1 General .9
5.2 Repeatability of CO response . 13
5.3 Directional dependence of CO response . 13
5.4 Directional dependence of heat response . 14
5.5 Lower limit of heat response . 14
5.6 Reproducibility of CO . 15
5.7 Reproducibility of heat response . 15
5.8 Long term stability (operational) . 15
5.9 Variation in supply parameters . 16
5.10 Air movement . 16
5.11 Dry heat (operational) . 17
5.12 Dry heat (endurance) . 18
5.13 Cold (operational) . 19
5.14 Damp heat, cyclic (operational) . 20
5.15 Damp heat, steady state (operational) . 21
5.16 Damp heat, steady state (endurance) . 22
5.17 Low humidity, steady state (operational) . 23
5.18 Sulphur dioxide SO corrosion (endurance) . 24
2
5.19 Shock (operational) . 25
5.20 Impact (operational). 26
5.21 Vibration, sinusoidal, (operational). 27
5.22 Vibration, sinusoidal (endurance) . 28
5.23 Exposure to chemical agents at environmental concentrations . 30
5.24 Exposure to high level of carbon monoxide . 31
5.25 Electromagnetic Compatibility (EMC), immunity tests (operational) . 32
5.26 Fire sensitivity . 32
Annex A (normative) Gas test chamber for CO response threshold value and cross-sensitivity to
chemical agents . 35
Annex B (normative) Fire test room . 36
2
---------------------- Page: 4 ----------------------
oSIST prEN 54-30:2009
prEN 54-30:2009 (E)
Annex C (normative) Measuring instruments for smoke and CO . 38
C.1 General . 38
C.2 CO measuring instrument . 38
C.3 Obscuration meter . 38
C.4 Measuring ionization chamber (MIC) . 38
Annex D (informative) Establishing exposure levels of chemical agents . 39
D.1 General . 39
D.2 Establishing concentration of chemical agents for test gases 1 to 9 of 5.23 . 39
D.3 Verification of test chamber leakage . 39
D.4 Establishing concentration of ozone . 39
Annex E (normative) Heat tunnel for heat response value . 41
Annex F (normative) Smouldering (pyrolysis) wood fire (TF2) . 42
F.1 General . 42
F.2 Fuel . 42
F.3 Hotplate . 42
F.4 Arrangement . 42
F.5 Heating rate . 42
F.6 End-of-test condition . 42
F.7 Test validity criteria . 43
Annex G (normative) Glowing smouldering cotton fire (TF3) . 45
G.1 Introduction . 45
G.2 Fuel . 45
G.3 Arrangement . 45
G.4 Ignition . 46
G.5 End-of-test condition . 46
G.6 Test validity criteria . 46
Annex H (normative) Open plastics (polyurethane) fire (TF4) . 48
H.1 Introduction . 48
H.2 Fuel . 48
H.3 Conditioning . 48
H.4 Arrangement . 48
H.5 Ignition . 48
H.6 Method of ignition . 48
H.7 End-of-test condition . 48
H.8 Test validity criteria . 49
Annex I (normative) Liquid (heptane) fire (TF5) . 50
I.1 Introduction . 50
I.2 Fuel . 50
I.3 Arrangement . 50
I.4 Ignition . 50
I.5 End-of-test condition . 50
I.6 Test validity criteria . 50
Annex J (informative) Information concerning the construction of the gas test chamber . 52
Annex K (informative) Construction of the heat tunnel . 54
Annex L (informative) Apparatus for impact test . 57
Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU
Construction Products Directive (89/106/EEC) . 59
ZA.1 Scope and relevant clauses . 59
ZA.2 Procedures for the attestation of conformity of control and indicating equipment covered
by this standard . 60
ZA.3 CE marking and labelling and accompanying documentation . 65
ZA.4 EC certificate of conformity and EC declaration of conformity . 66
3
---------------------- Page: 5 ----------------------
oSIST prEN 54-30:2009
prEN 54-30:2009 (E)
Foreword
This document (prEN 54-30:2009) has been prepared by Technical Committee CEN/TC 72 “Fire detection
and fire alarm systems”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports essential requirements of EU Directive(s).
For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document.
Introduction
Carbon monoxide (CO) is a product of the incomplete combustion of carbon-based materials. CO fire
detectors can react promptly to smouldering fires involving carbonaceous materials because CO does not
depend solely on convection, but also moves by diffusion. CO fire detectors might be better suited to
applications where other fire detection techniques are prone to false alarms, for example due to dust, steam
and cooking vapours. Detectors based on the use of CO sensors alone are covered by EN 54-26.
Some fires may not produce a sufficient amount of CO to trigger an alarm condition from a detector complying
with EN 54-26. These are typically free-burning, open, well ventilated fires. The inclusion of heat sensing
combined with CO sensing can increase the sensitivity of such a detector to these types of fires.
A number of different methods for sensing CO are suitable. However, most sensors will also be influenced by
other gases and phenomena. Tests have therefore been included in the test schedule to assess cross-
sensitivity to substances normally present in the service environment that may affect the performance of the
detector.
Test Fires TF2, TF3, TF4 and TF5 from EN 54-7 have been included to verify the detection performance. TF4
and TF5 specifically demonstrate the influence of the heat sensor(s). For these Test Fires, the CO level and,
where applicable, the temperature is used as test validity criteria.
Detectors may have modes of operation, in which only one fire phenomenon is evaluated. This standard does
not include tests for additional alarm outputs corresponding to the sensing of only one fire phenomenon.
Reference should be made to other parts of EN 54 which may cover such modes of operation or outputs.
4
---------------------- Page: 6 ----------------------
oSIST prEN 54-30:2009
prEN 54-30:2009 (E)
1 Scope
This European Standard specifies requirements, test methods and performance criteria for point-type multi-
sensor fire detectors for use in fire detection systems installed in buildings (see EN 54-1), incorporating in one
mechanical enclosure at least one carbon monoxide sensor and at least one heat sensor. The overall fire
detection performance is determined utilizing the combination of the detected phenomena.
Multi-sensor fire detectors having special characteristics suitable for the detection of specific fire risks are not
covered by this standard. The performance requirements for any additional functions are beyond the scope of
this standard (e.g. additional features or enhanced functionality for which this standard does not define a test
or assessment method).
2 Normative references
The following referenced documents are indispensable for the application of this standard. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 54-1:1996, Fire detection and fire alarm systems — Part 1: Introduction
EN 54-5:2000, Fire detection and fire alarm systems — Part 5: Heat detectors – Point detectors
EN 54-5:2000/A1:2002, Fire detection and fire alarm systems — Part 5: Heat detectors – Point detectors
EN 54-7:2000, Fire detection and fire alarm systems — Part 7: Smoke detectors — Point detectors using
scattered light, transmitted light or ionization
EN 54-7:2000/A1:2002, Fire detection and fire alarm systems — Part 7: Smoke detectors — Point detectors
using scattered light, transmitted light or ionization
EN 54-7:2000/A2:2006, Fire detection and fire alarm systems — Part 7: Smoke detectors — Point detectors
using scattered light, transmitted light or ionization
EN 54-26, Fire detection and fire alarm systems — Part 26: Point fire detectors using carbon monoxide
sensors
EN 50130-4:1995, Alarm systems — Part 4: Electromagnetic compatibility — Product family standard:
immunity requirements for components of fire, intruder and social alarm systems
EN 50130-4:1995/A1:1998, Alarm systems — Part 4: Electromagnetic compatibility — Product family
standard: immunity requirements for components of fire, intruder and social alarm systems
EN 50130-4:1995/A2:2003, Alarm systems — Part 4: Electromagnetic compatibility — Product family
standard: immunity requirements for components of fire, intruder and social alarm systems
EN 60068-1:1994, Environmental testing — Part 1: General and guidance
EN 60068-2-1:2007, Environmental testing — Part 2-1: Tests; Test A: Cold
EN 60068-2-2:1993, Environmental testing — Part 2-2: Tests; Tests B; Dry heat
EN 60068-2-2:1993/A1:1993, Environmental testing — Part 2-2: Tests; Tests B; Dry heat
EN 60068-2-6:1995, Environmental testing — Part 2-6: Tests — Test Fc: Vibration
EN 60068-2-27:1993, Environmental testing, Test methods, Environmental testing procedures — Part 2-
27: Tests; Test Ea & Guidance: Shock
EN 60068-2-30:2005, Environmental testing — Part 2–30: Tests; Test Db: Damp heat, cyclic (12+12 hour
cycle)
5
---------------------- Page: 7 ----------------------
oSIST prEN 54-30:2009
prEN 54-30:2009 (E)
EN 60068-2-42:2003, Environmental testing, Test methods — Part 2-42: Tests; Test Kc: Sulphur dioxide test
for contacts and connections
EN 60068-2-75:1997, Environmental testing — Part 2-75: Tests — Test Eh: Hammer
EN 60068-2-78:2001, Environmental testing — Part 2-78: Tests — Test Cab: Damp heat, steady state
EN ISO 9001:2000, Quality management systems – Requirements (ISO 9001:2000)
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 54-1 and the following apply.
3.1
CO response threshold value
CO concentration in the proximity of the specimen at the moment that it generates an alarm signal, when
tested as described in 5.1.5
NOTE The response threshold value may depend on signal processing in the detector and in the control and
indicating equipment
3.2
rate-sensitive
behaviour of a detector that depends on the rate of change of CO concentration
4 Requirements
4.1 Compliance
In order to comply with this standard, the detector shall meet the requirements of this clause, which shall be
verified by visual inspection or engineering assessment, shall be tested as described in Clause 5 and shall
meet the requirements of the tests.
4.2 Individual alarm indication
Each detector shall be provided with an integral red visual indicator, by which the individual detector that
released an alarm, can be identified, until the alarm condition is reset. Where other conditions of the detector
can be visually indicated, they shall be clearly distinguishable from the alarm indication, except when the
detector is switched into a service mode. For detachable detectors, the indicator may be integral with the base
or the detector head. The visual indicator shall be visible from a distance of 6 m directly below the detector, in
an ambient light intensity up to 500 lux.
4.3 Connection of ancillary devices
Where the detector provides for connections to ancillary devices (e.g. remote indicators, control relays),
open- or short-circuit failures of these connections shall not prevent the correct operation of the detector.
4.4 Monitoring of detachable detectors
For detachable detectors, a means shall be provided for a remote monitoring system (e.g. the control and
indicating equipment) to detect the removal of the head from the base, in order to give a fault signal.
6
---------------------- Page: 8 ----------------------
oSIST prEN 54-30:2009
prEN 54-30:2009 (E)
4.5 Manufacturer's adjustments
It shall not be possible to change the manufacturer's settings except by special means (e.g. the use of a
special code or tool) or by breaking or removing a seal.
4.6 On-site adjustment of response behaviour
If there is provision for on-site adjustment of the response behaviour of the detector then:
a) for each setting at which the manufacturer claims compliance with this standard, the detector shall comply
with the requirements of this standard, and access to the adjustment means shall only be possible by the
use of a code or special tool or by removing the detector from its base or mounting;
b) any setting(s) at which the manufacturer does not claim compliance with this standard, shall only be
accessible by the use of a code or special tool, and it shall be clearly marked on the detector or in the
associated data, that if these setting(s) are used, the detector does not comply with the standard.
NOTE These adjustments may be carried out at the detector or at the control and indicating equipment.
4.7 Rate-sensitive CO response
The CO response threshold value of the detector may depend on the rate of change of CO concentration in
the vicinity of the detector. Such behaviour may be incorporated in the detector design to improve the
discrimination between ambient CO levels and those generated by a fire. If such rate sensitive behaviour is
included then it shall not lead to a significant reduction in the detector’s sensitivity to fires, nor to a significant
increase in the probability of false alarm.
Since it is not practical to make tests with all possible rates of increase in CO concentration, an assessment of
the detector's rate sensitivity shall be made by analysis of the circuit/software, and/or physical tests and
simulations.
The detector shall be deemed to meet the requirements of this clause if this assessment shows that for
constant temperatures between the lower and upper limits of the temperature range as defined by the
manufacturer:
a) for any rate of increase in CO concentration less than 1 µl/l per minute the detector will signal an alarm
condition before the CO concentration reaches 60 µl/l, and;
b) the detector does not signal an alarm condition when subjected to a step change in CO concentration of
10 µl/l, superimposed on a background level between 0 and 3 µl/l.
4.8 Position of the heat sensors
Detector shall be constructed such that, at least, part of the heat sensing element(s) of its heat sensor(s) shall
not be less than 15 mm from the mounting surface of the detector.
4.9 Marking
Each detector shall be clearly marked with the following information:
a) the number and date of this standard (i.e. EN 54-30:xxxx);
b) the name or trademark of the manufacturer or supplier;
c) the model designation (type or number);
d) the wiring terminal designations;
7
---------------------- Page: 9 ----------------------
oSIST prEN 54-30:2009
prEN 54-30:2009 (E)
e) some mark(s) or code(s) (e.g. serial number or batch code), by which the manufacturer can identify, at
least, the date or batch and place of manufacture, and the version number(s) of any software, contained
within the detector.
For detachable detectors, the detector head shall be marked with a), b), c) and e), and the base shall be
marked with, at least c) (i.e. its own model designation) and d).
Where any marking on the device uses symbols or abbreviations not in common use then these
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.