Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 2: Fire resistance of hinged and pivoted steel doorsets

This European Standard covers single and double leaf, hinged and pivoted, steel based doorsets. It prescribes the methodology for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1. Subject to the completion of the appropriate test or tests, the extended application may cover all or some of the following examples: - integrity (E), integrity/radiation (EW) or integrity/insulation (EI1 or EI2) classification; - door leaf; - ventilation grilles and/or louvres - wall/ceiling fixed elements (frame/suspension system); - glazing for door leaf, side, transom and flush over panels; - items of building hardware; - decorative finishes; - intumescent, smoke, draught or acoustic seals; - alternative supporting construction(s).

Erweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit und/oder Rauchdichtigkeit von Feuerschutzabschlüssen und Fenstern einschließlich ihrer Baubeschläge - Teil 2: Feuerwiderstandsfähigkeit von Drehflügeltüren aus Stahl

Diese Europäische Norm deckt ein- und zweiflügelige Drehflügeltüren aus Stahl ab. Sie legt die Methodologie zur Erweiterung der Anwendung von Ergebnissen aus Feuerwiderstandsprüfungen nach EN 1634-1 fest.
In Abhängigkeit von der Durchführung der entsprechenden Prüfung oder Prüfungen kann der erweiterte Anwendungsbereich einige oder alle der nachstehend aufgeführten Beispiele abdecken:
-   Klassifizierung von nicht wärmegedämmten Abschlüssen (E) sowie solchen mit Anforderungen an die Strahlung (EW) oder wärmegedämmten Abschlüssen (EI1 oder EI2);
-   Türflügel;
-   Lüftungsgitter;
-   an der Wand/Decke befestigte Elemente (Zarge/Aufhängungssysteme);
-   Verglasungen für Türflügel, Seitenteile, Oberteile und obere Türblenden;
-   Baubeschläge;
-   dekorative Beschichtungen;
-   dämmschichtbildende Dichtungen sowie Dichtungen zur Behinderung von Rauchübertragung, Durchzug oder Schallübertragung;
-   alternative Tragkonstruktion(en).

Application étendue des résultats d'essais en matière de résistance au feu et/ou d'étanchéité à la fumée des blocs-portes, blocs-fermetures et fenêtres, y compris leurs éléments de quincaillerie - Partie 2 : Résistance au feu des blocs-portes battants et pivotants en acier

La présente Norme Européenne couvre les blocs-portes battants et pivotants en acier, à simple et à double vantail. Elle prescrit la méthodologie permettant d'étendre l'application des résultats obtenus à partir d’un ou plusieurs essai(s) de résistance au feu effectué(s) conformément à l'EN 1634-1.
Sous réserve de la réalisation de l'essai ou des essais appropriés, l'application étendue peut couvrir tout ou partie des exemples suivants :
-   classement de l'étanchéité au feu (E), de l'étanchéité au feu/rayonnements (EW) ou de l'étanchéité au feu/isolation thermique (EI1 ou EI2) ;
-   vantail ;
-   jalousies et/ou grilles de ventilation ;
-   éléments fixés au mur/plafond (dormant/système de suspension) ;
-   vitrage pour vantail, panneaux latéraux et d’impostes ;
-   éléments de quincaillerie de bâtiment ;
-   finitions décoratives ;
-   joints intumescents, joints d'étanchéité à la fumée, joints d'étanchéité à l'air ou joints acoustiques ;
-   autre(s) construction(s) support.

Razširjena uporaba rezultatov preskusov požarne odpornosti in/ali dimotesnosti za vrata, zaporne elemente in okna, ki se odpirajo, vključno z njihovim okovjem - 2. del: Jeklena vrata z vrtljivim krilom

Ta evropski standard zajema enoslojna in dvoslojna jeklena vrata z vrtljivim krilom. Predpisuje metodologijo za razširitev uporabe rezultatov preskusa, pridobljenih iz preskusov požarne odpornosti, izvedenih v skladu s standardom EN 1634-1. Razširjena uporaba lahko (glede na opravljene ustrezne preskuse) pokriva vse naslednje primere ali nekatere od njih: – razvrstitev integriteta (E), integriteta/sevanje (EW) ali integriteta/izolacija (EI1 ali EI2); – vratno krilo; – prezračevalne rešetke in/ali žaluzijske lopute; – stenska/stropna okovja (okvir/sistem vzmetenja); – steklo za vratno krilo, stranice, tramove in poravnane podboje; – elementi stavbnega okovja; – okrasni zaključki; – intumescentna, dimna, akustična tesnila in tesnila za preprečevanje prepiha; – druge podporne gradbene enote.

General Information

Status
Published
Public Enquiry End Date
30-Mar-2012
Publication Date
26-Dec-2012
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
09-Oct-2012
Due Date
14-Dec-2012
Completion Date
27-Dec-2012

Relations

Buy Standard

Standard
EN 15269-2:2013
English language
101 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Erweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit und/oder Rauchdichtigkeit von Feuerschutzabschlüssen und Fenstern einschließlich ihrer Baubeschläge - Teil 2: Feuerwiderstandsfähigkeit von Drehflügeltüren aus StahlApplication étendue des résultats d'essais en matière de résistance au feu et/ou d'étanchéité à la fumée des blocs-portes, blocs-fermetures et fenêtres, y compris leurs éléments de quincaillerie - Partie 2 : Résistance au feu des blocs-portes battants et pivotants en acierExtended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 2: Fire resistance of hinged and pivoted steel doorsets91.060.50Vrata in oknaDoors and windows13.220.50Požarna odpornost gradbenih materialov in elementovFire-resistance of building materials and elementsICS:Ta slovenski standard je istoveten z:EN 15269-2:2012SIST EN 15269-2:2013en,fr,de01-januar-2013SIST EN 15269-2:2013SLOVENSKI
STANDARD



SIST EN 15269-2:2013



EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 15269-2
September 2012 ICS 13.220.50; 91.060.50 English Version
Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 2: Fire resistance of hinged and pivoted steel doorsets
Application étendue des résultats d'essais en matière de résistance au feu et/ou d'étanchéité à la fumée des blocs-portes, blocs-fermetures et fenêtres, y compris leurs éléments de quincaillerie - Partie 2: Résistance au feu des blocs-portes battants et pivotants en acier
Erweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit und/oder Rauchdichtigkeit von Türen, Toren und Fenstern einschließlich ihrer Baubeschläge - Teil 2: Feuerwiderstandsfähigkeit von Drehflügeltüren aus Stahl This European Standard was approved by CEN on 20 July 2012.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2012 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 15269-2:2012: ESIST EN 15269-2:2013



EN 15269-2:2012 (E) 2 Contents Page Foreword .3Introduction .41 Scope .52 Normative references .53 Terms and definitions .64 Determination of the field of extended application .64.1 General .64.2 How to use extended application rules in Annex A .64.3 Procedure for maximum field of extended application .74.4 Analysis of test results .85 Extended application report .86 Classification report .8Annex A (normative)
Construction parameter variations .9Annex B (normative)
Arrangements for doorsets incorporating side and / or over panels . 94Annex C (informative)
Figures . 101 SIST EN 15269-2:2013



EN 15269-2:2012 (E) 3 Foreword This document (EN 15269-2:2012) has been prepared by Technical Committee CEN/TC 127 “Fire safety in buildings”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by March 2013, and conflicting national standards shall be withdrawn at the latest by March 2013. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association. EN 15269, Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware, consists of the following parts:  Part 1: General requirements  Part 2: Fire resistance of hinged and pivoted steel doorsets (the present document)  Part 3: Fire resistance of hinged and pivoted timber doorsets and openable timber framed windows  Part 5: Fire resistance of hinged and pivoted, metal framed, glazed doorsets and openable windows1)
 Part 6: Fire resistance of sliding timber doorsets1)  Part 7: Fire resistance of sliding steel doorsets  Part 10: Fire resistance of steel rolling shutter assemblies
 Part 11: Fire resistance of operable fabric curtains1)  Part 20: Smoke control for hinged and pivoted steel, timber and metal framed glazed doorsets According to the CEN/CENELEC Internal Regulations, the national standards organisations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.
1) In preparation. SIST EN 15269-2:2013



EN 15269-2:2012 (E) 4 Introduction This document is one of a series of standards intended to be used for the purpose of producing an extended application report based on the evaluation of one or more fire resistance and/or smoke control tests. These European Standards may also be used to identify the best selection of test specimens required to cover a wide range of product variations. Before there can be any consideration for extended application, the doorset will need to have been tested in accordance with EN 1634-1 to achieve a test result which could generate a classification in accordance with EN 13501-2 at least equal to the classification subsequently required from extended application considerations. SIST EN 15269-2:2013



EN 15269-2:2012 (E) 5 1 Scope This European Standard covers single and double leaf, hinged and pivoted, steel based doorsets. It prescribes the methodology for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1. Subject to the completion of the appropriate test or tests, the extended application may cover all or some of the following examples:  integrity (E), integrity/radiation (EW) or integrity/insulation (EI1 or EI2) classification;  door leaf;  ventilation grilles and/or louvres  wall/ceiling fixed elements (frame/suspension system);  glazing for door leaf, side, transom and flush over panels;  items of building hardware;  decorative finishes;  intumescent, smoke, draught or acoustic seals;  alternative supporting construction(s). 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1363-1, Fire resistance tests — Part 1: General requirements EN 1634-1, Fire resistance and smoke control tests for door, shutter and openable window assemblies and elements of building hardware — Part 1: Fire resistance tests for doors, shutters and openable windows EN 1634-2, Fire resistance and smoke control tests for door, shutter and openable window assemblies and elements of building hardware — Part 2: Fire resistance characterisation test for elements of building hardware
EN 13501-2, Fire classification of construction products and building elements — Part 2: Classification using data from fire resistance tests, excluding ventilation services
EN 15254-4:2008+A1:2011, Extended application of results from fire resistance tests — Non-loadbearing walls — Part 4. Glazed constructions EN 15269-1:2010, Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware — Part 1: General requirements EN ISO 13943, Fire safety — Vocabulary (ISO 13943) SIST EN 15269-2:2013



EN 15269-2:2012 (E) 6 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN1363-1, EN ISO 13943, EN 1634-1, EN 1634-2 and EN 15269-1 and the following apply. 3.1 full scale test test of a full size doorset in accordance with EN 1634-1 3.2 small scale test test on elements of building hardware in accordance with EN 1634-2 and where the decision process, given in EN 1634-2, permits its use 3.3 effective rebate depth dimension of the door leaf thickness of overlapping adjacent edges of door leaf relative to the door frame, transom or side panel or other door leaf flush overpanel Note 1 to entry: At the meeting edges and for rebated leaves this dimension will be the rebate where the intumescent seal is fitted or, if no seal is fitted, the depth of the largest rebate. Note 2 to entry: An example is shown in Figure C.1. 3.4 panel component of a door leaf separated from other elements by joints which break through the total door thickness Note 1 to entry: A door leaf can consist of one or more panels. 4 Determination of the field of extended application
4.1 General 4.1.1 Before there can be any consideration for extended application, a representative doorset shall have been tested and classified in accordance with EN1634-1 and EN 13501-2 respectively in order to establish a classification for the doorset. 4.1.2 A review of the doorset construction parameters can indicate that one or more characteristics may be improved by a particular parameter variation. All evaluations shall be made on the basis of retaining the classifications obtainable from testing to EN 1634-1, including those lower than the test duration. However, this shall never lead to an increased classification for any specific parameter beyond that achieved during any one test unless specifically identified in the relevant Construction Parameter Variation tables. 4.1.3 If, when following the extended application procedure, any part of the classified product cannot be covered by the extended application rules, that part shall be omitted from the subsequent extended application report and classification report. 4.2 How to use extended application rules in Annex A 4.2.1 Identify the variations from the original test specimen(s) which are required to be covered by an extended application report. 4.2.2 Locate the variations in the appropriate parameter variation by reference to columns (1) and (2) of Annex A. SIST EN 15269-2:2013



EN 15269-2:2012 (E) 7 4.2.3 Review the type of classification to be retained from column (3) and establish from the contents of column (4) whether any extended application is available beyond the direct application rules in EN 1634-1 without the need for further testing. 4.2.4 Where this is deemed possible, it can be recorded in the extended application report together with any appropriate restrictions and the stated rules from column (4) of Annex A. 4.2.5 Where the variations required can only be achieved from additional testing, the additional test can be made on a similar specimen type i.e. a doorset of the same or more onerous configuration where the leaf construction is fundamentally the same as tested. Alternatively, column (5) identifies an option for alternative testing and relevant test parameters. 4.3 Procedure for maximum field of extended application 4.3.1 It is possible to provide an extended field of application from a single test. However, if a manufacturer intends to produce a range of doors incorporating single doors and also double doors, with or without side, transom or flush over panels, with or without glazing, with or without louvres or ventilation grilles, with alternative elements of building hardware, etc., it is recommended that careful consideration be given to the complete range of doorset designs and options in order to minimise the testing required before testing commences. 4.3.2 Establish all the parameter variations which are required to be part of the product range. 4.3.3 Determine which are the most important specification requirements and incorporate as many as possible into the specimen(s) for the first tests in the series. 4.3.4 Conduct the first fire resistance test or a series of tests and then establish which of the original desired parameter variations have not been covered by the fire resistance tests, including direct application possibilities. 4.3.5 Identify these parameter variations in Annex A and establish if any extended application is possible without further testing. 4.3.6 Record this for the extended application report together with any restrictions and rules given in column (4) in Annex A. 4.3.7 Evaluate which, if any, of the desired parameter variations have not been covered by the field of direct application or the initial field of extended application derived from 4.3.5. 4.3.8 Determine if the product range is to include only single leaf doorsets or if the range is to also include double leaf configurations. Where only single doorsets are to be part of the product range, the outstanding construction parameter variations shall only be incorporated into specimens for the single leaf doorsets. Where single leaf and double leaf doorsets are to be included in the product range, the outstanding construction parameter variations for the extended application of single leaf doorsets may be incorporated into either repeated single leaf doorset tests or, in the weakest option, as defined in column (5) of the table in Annex A, double leaf doorset configurations. 4.3.9 Select the required outstanding parameter variations from column (1) and column (2) of Annex A and observe from column (5) in Annex A which are the most appropriate, weakest specimen options for further testing. 4.3.10 If the complete selection of required parameter variations has not been covered by the tests completed in accordance with 4.3.8 and 4.3.9 above, then an appropriate test or tests may be repeated with the additional product variations incorporated. SIST EN 15269-2:2013



EN 15269-2:2012 (E) 8 4.4 Analysis of test results 4.4.1 In order to maximise the extended field of application, it is important that the test reports shall record details of any premature integrity and/or insulation failure also record details of any distortion to evaluate low, medium and high distortion (see Annex A). 4.4.2 Where a series of tests have been conducted, the field of extended application shall be based on the lowest performance achieved from the complete series of tests unless premature failure has been attributed to one or more specific construction parameter variations. 4.4.3 Where it has been possible to identify specific parameter failures, the extended application for all other construction parameter variations can be based on the performance achieved after isolating the premature failure(s).
5 Extended application report Prepare an extended application report in accordance with the requirements of EN 15269-1:2010, Clause 6 based on the results of evaluations in accordance with the above. 6 Classification report The classification report shall be determined from the results of the extended application report and presented in accordance with EN 13501-2.
SIST EN 15269-2:2013



EN 15269-2:2012 (E) 9 Annex A (normative)
Construction parameter variations The table below
is designed to be used by experts competent in the field of fire resistance testing of hinged and pivoted steel doorsets. The table shall only be used to assess a field of extended application when at least one positive fire resistance test to EN 1634-1 has generated a classification according to EN 13501-2.
The first two columns identify possible variations to the construction details of the specimen tested.
The influence of variation on performance characteristic is identified from column (3) as integrity, insulation or radiation (E, I or W respectively). For some parameters, it is necessary to evaluate whether the specimen displayed a high, medium or low level of distortion during the test. Where this is the case, the following levels shall be used to establish high, medium and low distortion doorsets as measured using the maximum relative movement at any position between the edge of the door leaf and door frame or between the meeting edges of door leaves or the relative movement of the framing members for panelled systems. The measurements shall be taken from the start of the test at any time during the complete required classification period. The deflections shall be measured at the positions given in EN 1634-1:  low <40 % of effective rebate depth;  medium ≥ 40 % and ≤ 85 % of effective rebate depth;  high >85 % of effective rebate depth. The effect of the change in each parameter is evaluated for each characteristic in column (3) under E for effects on integrity, I for effects on insulation (whether an I1 or I2) and W for the effects on radiation. These evaluations lead to the judgement of the possibility of extending the field of application, the results of which are given in column (4). In certain cases in column (4), it is a requirement to achieve Category B, the requirements for which are given in EN 1634-1. Where additional tests are deemed to be necessary, the type of specimen approved for incorporation of the changed parameter is defined in column (5). Where it is possible to use information from tests performed on one configuration for evidence on a different configuration, this allowance has been made in order to reduce the overall number of tests required for extended application evaluation e.g. single action doorsets to double action doorsets. Where an additional test is required in column (5), the test is a full scale test with the specimen opening outwards (away from the furnace) unless otherwise specified. In order to maximise the possible field of application from a minimum number of tests, the parameter changes have been spread over a series of test specimens. The recommended tests for each parameter is dependant upon the classification required and the preferred direction of testing as indicated in column (5). Where more than a single parameter variation is required, the influence on other variations shall also be taken into account.
SIST EN 15269-2:2013



EN 15269-2:2012 (E) 10 Table A.1 — Construction parameter variations
Key to symbols in column (3) (which is informative only) >
-
higher performance anticipated <
-
lower performance anticipated =
- no significant change in performance anticipated ≥
- equal or higher performance anticipated

- equal or lower performance anticipated >=< - the influence on performance could be worse, equal or better hence variations not possible unless specific, limited conditions are identified
Construction Parameter Variation Influence of variation on performance characteristic Possibility of extension
Additional Evidence Required (1) (2) (3) (4) (5)
E I W
A Door leaf In certain cases, the rules given in Section A are also appropriate to side, transom and flush over panels or the door frame. Where this is the case, it is clearly indicated at the beginning of the relevant section. For double leaf doorsets, both leaves shall be of the same basic construction. A.1 General A.1.1 Number of leaves - See Figure A.1 only applicable to doorsets tested without transom and/or flush over panels. See Annex B Single leaf from double leaf test ≤ ≥ ≥ Not possible without an additional test Additional test single leaf doorset A.1.2 Number of leaves only applicable to doorsets tested without transom and/or flush over panels. See Annex B Double leaf from single leaf test < ≤ ≤ Not possible without additional test (s) Additional test (s) double leaf doorset (open outwards and inwards for EI doors, open outwards for E or W doors) SIST EN 15269-2:2013



EN 15269-2:2012 (E) 11 Construction Parameter Variation Influence of variation on performance characteristic Possibility of extension
Additional Evidence Required (1) (2) (3) (4) (5)
E I W
A.1.3 Number of panels per leaf (primary or secondary) Add (one panel per leaf – on any leaf) = = = Possible if tested at least one leaf (single, primary or secondary) with the minimum of two panels, panel size not increased and the intended jointing technique centrally located in the door leaf otherwise not possible without an additional test Additional test single leaf or double leaf doorset A.1.4 Number of panels per leaf(primary or secondary) - See Figure A.2 Reduce (one panel per leaf) = = = Possible providing the tested width of the panel is not increased otherwise not possible without an additional test Additional test single leaf or double leaf doorset A.1.5 Intumescent seals between frame and door leaf/leaves - See Figure A.3 Location towards the frame rebate >=< >=< >=< Not possible without an additional test Additional test single leaf or double leaf doorset A.1.6 Intumescent seals between frame and door leaf/leaves – See Figure A.4 Location away from the frame rebate >=< >=< >=< Not possible without an additional test Additional test single leaf or double leaf doorset A.1.7 Intumescent seals between meeting edges of the door leaves Location >=< >=< >=< Not possible without additional test (s) Additional test (s) double leaf doorset (open outwards and inwards for EI doors, open outwards for E or W doors) A.1.8 Non-intumescent seals between frame and door leaf/leaves (draught/smoke/acoustic etc.) – Euroclass A1, e.g. ceramic products (fitted in leaf or frame) - See Figure A.5 Location = = = Any movement possible providing no modifications of the construction are required otherwise not possible without an additional test Additional test single or double leaf doorset if the seal is positioned between the meeting edges of the door leaves the additional test shall be a double leaf doorset A.1.9 Non-intumescent seals between meeting edges of the door leaves (draught/smoke/acoustic etc.) - Euroclass A1, e.g. ceramic products
Location >/=/< >/=/< >/=/< No movement possible without an additional test Additional test double leaf doorset
SIST EN 15269-2:2013



EN 15269-2:2012 (E) 12 Construction Parameter Variation Influence of variation on performance characteristic Possibility of extension
Additional Evidence Required (1) (2) (3) (4) (5)
E I W
A.1.10 Non-intumescent seals between door leaves and/or frames (draught/smoke/acoustic etc.) – < Euroclass A1 (fitted in leaf or frame) - See Figure A.6 Location >/=/< >/=/< >/=/< No movement possible without an additional test Additional test single or double leaf doorset, if the seal is positioned between the meeting edges of the door leaves the additional test shall be a double leaf doorset A.1.11 Non-intumescent seals between door leaves and/or frames (draught/smoke/acoustic etc.) - Euroclass A1, e.g. ceramic products (fitted in leaf or frame). - See Figure A.7 Add = = = Possible for doors without intumescent seals and providing the gap between door leaf and door frame is not increased otherwise not possible without an additional test Additional test single or double leaf doorset, if the seal is positioned between the meeting edges of the door leaves the additional test shall be a double leaf doorset A.1.12 Non-intumescent seals between door leaves and/or frames (draught/smoke/acoustic etc.) - Euroclass A1, e.g. ceramic products (fitted in leaf or frame) - See Figure A.8 Remove ≤ ≤ ≤ Not possible without an additional test Additional test single or double leaf doorset, if the seal is positioned between the meeting edges of the door leaves the additional test shall be a double leaf doorset A.1.13 Non-intumescent seals between door leaves and/or frames (draught/smoke/acoustic etc.) – < Euroclass A1 (fitted in leaf or frame) - See Figure A.9 Add ≤ ≤ ≤ Not possible without an additional test Additional test single or double leaf doorset, if the seal is positioned between the meeting edges of the door leaves the additional test shall be a double leaf doorset SIST EN 15269-2:2013



EN 15269-2:2012 (E) 13 Construction Parameter Variation Influence of variation on performance characteristic Possibility of extension
Additional Evidence Required (1) (2) (3) (4) (5)
E I W
A.1.14 Non-intumescent seals between door leaves and/or frames (draught/smoke/acoustic etc. – < Euroclass A1 (fitted in leaf or frame) - See Figure A.10 Remove >/=/< >/=/< = Not possible without an additional test Additional test single or double leaf doorset, if the seal is positioned between the meeting edges of the door leaves the additional test shall be a double leaf doorset A.1.15 Ventilation grilles (louvres) in door leaf tested without ventilation grille - See Figure A.11 a) Add ≤ ≤ ≤ Not possible without an additional test Additional test single or double leaf doorset A.1.16 Ventilation grilles (louvres) in door leaf - See Figure A.11 b)
Remove >/=/< ≥ ≥ Possible providing the cut out is less than 25 % of the door leaf area otherwise not possible without an additional test Additional test single or double leaf doorset A.1.17 Ventilation grilles (louvres) in door leaf tested with ventilation grille Location in vertical direction ≤ ≤ ≤ Possible for lower location than tested otherwise not possible without an additional test Additional test single or double leaf doorset A.1.18 Ventilation grilles (louvres) in door leaf tested with ventilation grille - See Figure A.12 Location in horizontal direction = = = Possible providing the distance between the edge of the louvre and the perimeter of the door leaf is not decreased and providing any internal stiffening elements are not affected otherwise not possible without an additional test Additional test single or double leaf doorset A.1.19 Ventilation grilles (louvres) in door leaf tested with ventilation grille- See Figure A.13 a) Smaller size ≥ ≥ ≥ Possible for one or more louvres smaller than that tested specimen providing the location is inside the perimeter of the tested louvre and minimum spacing between cut outs is not less than 100 mm otherwise not possible without an additional test Additional test single or double leaf doorset SIST EN 15269-2:2013



EN 15269-2:2012 (E) 14 Construction Parameter Variation Influence of variation on performance characteristic Possibility of extension
Additional Evidence Required (1) (2) (3) (4) (5)
E I W
- See Figure A.13 b) Larger size ≤ ≤ ≤ Not possible without an additional test Additional test single or double leaf doorset A.1.20 Rebate (door leaves to frames) - See Figure A.14 a) Add ≥ ≤ ≥ EI Not possible without an additional test unless the original test had additional thermocouples positioned 100 mm and/or 25 mm from the edge of the notional rebate (i.e. 100-x) where x means the width of the added rebate and dimension y (overlap) shall not be decreased by a maximum of three times the steel thickness of the door leaf
Additional test single or double leaf doorset E, EW Possible providing no decrease of dimension y (overlap) or leaf edge thickness by a maximum of three times the steel thickness of the door leaf otherwise not possible without an additional test
Additional test
...

Questions, Comments and Discussion