SIST EN IEC 60332-3-22:2018
(Main)Tests on electric and optical fibre cables under fire conditions - Part 3-22: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category A (IEC 60332-3-22:2018)
Tests on electric and optical fibre cables under fire conditions - Part 3-22: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category A (IEC 60332-3-22:2018)
This part of IEC 60332 covers category A for methods of test for the assessment of vertical
flame spread of vertically mounted bunched wires or cables, electrical or optical, under
defined conditions.
This document relates to cables installed on the test ladder to achieve a nominal total volume
of non-metallic material of 7 l/m of test sample. The flame application time is 40 min. The
method of mounting uses the front of the ladder, a standard or wide ladder being used for
cables having a conductor cross-section greater than 35 mm2 according to the number of test
pieces required, and a standard ladder for conductor cross-sections 35 mm2 and smaller. The
category is intended for general use where high volumes of non-metallic material are required
to be evaluated.
The test is intended for type approval testing. The requirements for the selection of cables for
testing are given in Annex A. The flame spread is measured as the extent of damage of the
cable sample. This procedure can be used to demonstrate the cable’s ability to limit flame
spread.
A recommended performance requirement is given in Annex B.
NOTE For the purposes of this document the term "electric wire or cable" covers all insulated metallic conductor
cables used for the conveyance of energy or signals.
Prüfungen an Kabeln, isolierten Leitungen und Glasfaserkabeln im Brandfall - Teil 3-22: Prüfung der vertikalen Flammenausbreitung von vertikal angeordneten Bündeln von Kabeln und isolierten Leitungen - Prüfart A (IEC 60332-3-22:2018)
Essais des câbles électriques et des câbles à fibres optiques soumis au feu - Partie 3-22: Essai de propagation verticale de la flamme des fils ou câbles montés en nappes en position verticale - Catégorie A (IEC 60332-3-22:2018)
NEW!IEC 60332-3-22:2018 est disponible sous forme de IEC 60332-3-22:2018 RLV qui contient la Norme internationale et sa version Redline, illustrant les modifications du contenu technique depuis l'édition précédente.
L’IEC 60332-3-22:2018 couvre la catégorie A pour les méthodes d'essai pour l'évaluation de la propagation verticale de la flamme des fils ou câbles, électriques ou optiques, disposés en nappes en position verticale, dans des conditions définie. Le présent document concerne les câbles montés sur l'échelle d'essai afin d’obtenir un volume total nominal de matériau non métallique de 7 l/m d'échantillon d'essai. La durée d'application de la flamme est de 40 min. La méthode de montage utilise la face avant de l'échelle, celle-ci étant du type standard ou du type large pour les câbles dont au moins un conducteur est de section supérieure à 35 mm2 selon le nombre d'éprouvettes exigé, et du type standard pour les câbles dont tous les conducteurs sont de sections inférieures ou égales à 35 mm2. Cette catégorie est prévue pour une utilisation générale lorsqu’il est requis d'évaluer le comportement de volumes élevés de matériau non métallique. L'essai est prévu pour les essais d'acceptation de type. Les exigences pour la sélection des câbles pour l'acceptation de type sont données à l'Annexe A. La propagation de la flamme est mesurée comme étant l'étendue de la partie endommagée de l'échantillon de câble. Cette procédure peut être utilisée pour démontrer l’aptitude du câble à limiter la propagation de la flamme. L’Annexe B donne une recommandation pour l'exigence de performance. Cette deuxième édition annule et remplace la première édition parue en 2000 et l'Amendement 1:2008. Cette édition constitue une révision technique. Cette édition inclut les modifications techniques majeures suivantes par rapport à l'édition précédente:
a) des ajustements ont été apportés au titre, et ailleurs, afin de souligner que la Norme s’applique aux câbles à fibre optique, ainsi qu’aux types de conducteurs métalliques;
b) les détails sur la manière dont les câbles sont montés sur l'échelle ont été mieux définis afin d'améliorer la répétabilité et la reproductibilité.
Elle a le statut d’une publication groupée de sécurité conformément au Guide IEC 104.
Preskusi na električnih kablih in kablih iz optičnih vlaken v požarnih razmerah - 3-22. del: Preskus navpičnega širjenja ognja po navpično pritrjenih snopih žic ali kablov - Kategorija A (IEC 60332-3-22:2018)
Ta del standarda IEC 60332 zajema kategorijo A za preskusne metode za ocenjevanje navpičnega širjenja ognja po navpično pritrjenih snopih žic ali kablov, električnih ali iz optičnih vlaken, v določenih razmerah. Ta dokument se nanaša na kable, nameščene na preskusni lestvi, da se doseže skupna nazivna prostornina nekovinskih materialov 7 l/m preskusnega vzorca. Čas uporabe ognja je 40 minut. Način montaže uporablja sprednji del lestve (standardne ali široke), ki se uporablja za vodnike s prerezom, večjim od 35 mm2, glede na število zahtevanih preskusnih delov, ter standardno lestev za vodnike s prerezom 35 mm2 in manjšim. Kategorija je namenjena za splošno uporabo, pri kateri je treba oceniti velike prostornine nekovinskih materialov.
Preskus je namenjen za homologacijsko preskušanje. Zahteve za izbiro kablov za preskušanje so podane v dodatku A. Širjenje ognja se izmeri kot obseg škode na vzorcu kabla. Ta postopek je mogoče uporabiti za prikaz zmožnosti kabla za omejitev širjenja ognja.
Priporočena zahteva glede učinkovitosti je podana v dodatku B.
OPOMBA: Za namene tega dokumenta izraz »električna žica ali kabel« zajema vse izolirane kovinske vodnike, ki se uporabljajo za prenos energije ali signalov.
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN IEC 60332-3-22:2018
01-december-2018
1DGRPHãþD
SIST EN 60332-3-22:2010
3UHVNXVLQDHOHNWULþQLKNDEOLKLQNDEOLKL]RSWLþQLKYODNHQYSRåDUQLKUD]PHUDK
GHO3UHVNXVQDYSLþQHJDãLUMHQMDRJQMDSRQDYSLþQRSULWUMHQLKVQRSLKåLFDOL
NDEORY.DWHJRULMD$,(&
Tests on electric and optical fibre cables under fire conditions - Part 3-22: Test for
vertical flame spread of vertically-mounted bunched wires or cables - Category A (IEC
60332-3-22:2018)
Prüfungen an Kabeln, isolierten Leitungen und Glasfaserkabeln im Brandfall - Teil 3-22:
Prüfung der vertikalen Flammenausbreitung von vertikal angeordneten Bündeln von
Kabeln und isolierten Leitungen - Prüfart A (IEC 60332-3-22:2018)
Essais des câbles électriques et des câbles à fibres optiques soumis au feu - Partie 3-
22: Essai de propagation verticale de la flamme des fils ou câbles montés en nappes en
position verticale - Catégorie A (IEC 60332-3-22:2018)
Ta slovenski standard je istoveten z: EN IEC 60332-3-22:2018
ICS:
13.220.40 Sposobnost vžiga in Ignitability and burning
obnašanje materialov in behaviour of materials and
proizvodov pri gorenju products
29.060.20 Kabli Cables
SIST EN IEC 60332-3-22:2018 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST EN IEC 60332-3-22:2018
---------------------- Page: 2 ----------------------
SIST EN IEC 60332-3-22:2018
EUROPEAN STANDARD EN IEC 60332-3-22
NORME EUROPÉENNE
EUROPÄISCHE NORM
October 2018
ICS 13.220.40; 29.020; 29.060.20 Supersedes EN 60332-3-22:2009
English Version
Tests on electric and optical fibre cables under fire conditions -
Part 3-22: Test for vertical flame spread of vertically-mounted
bunched wires or cables - Category A
(IEC 60332-3-22:2018)
Essais des câbles électriques et des câbles à fibres Prüfungen an Kabeln, isolierten Leitungen und
optiques soumis au feu - Partie 3-22: Essai de propagation Glasfaserkabeln im Brandfall - Teil 3-22: Prüfung der
verticale de la flamme des fils ou câbles montés en nappes vertikalen Flammenausbreitung von vertikal angeordneten
en position verticale - Catégorie A Bündeln von Kabeln und isolierten Leitungen - Prüfart A
(IEC 60332-3-22:2018) (IEC 60332-3-22:2018)
This European Standard was approved by CENELEC on 2018-08-17. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden,
Switzerland, Turkey and the United Kingdom.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2018 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 60332-3-22:2018 E
---------------------- Page: 3 ----------------------
SIST EN IEC 60332-3-22:2018
EN IEC 60332-3-22:2018 (E)
European foreword
The text of document 20/1799/FDIS, future edition 2 of IEC 60332-3-22, prepared by IEC/TC 20
"Electric cables" was submitted to the IEC-CENELEC parallel vote and approved by CENELEC as
EN IEC 60332-3-22:2018.
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2019-05-17
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2021-08-17
document have to be withdrawn
This document supersedes EN 60332-3-22:2009.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
Endorsement notice
The text of the International Standard IEC 60332-3-22:2018 was approved by CENELEC as a
European Standard without any modification.
In the official version, for Bibliography, the following note has to be added for the standard indicated:
ISO 13943:2017 NOTE Harmonized as EN ISO 13943:2017 (not modified)
2
---------------------- Page: 4 ----------------------
SIST EN IEC 60332-3-22:2018
EN IEC 60332-3-22:2018 (E)
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1 Where an International Publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.
NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is available here:
www.cenelec.eu.
Publication Year Title EN/HD Year
IEC 60332-3-10 - Tests on electric and optical fibre cables EN IEC 60332-3-10 -
under fire conditions - Part 3-10: Test for
vertical flame spread of vertically-mounted
bunched wires or cables - Apparatus
IEC 60811-606 - Electric and optical fibre cables - Test EN 60811-606 -
methods for non-metallic materials - Part
606: Physical tests - Methods for
determining the density
3
---------------------- Page: 5 ----------------------
SIST EN IEC 60332-3-22:2018
---------------------- Page: 6 ----------------------
SIST EN IEC 60332-3-22:2018
IEC 60332-3-22
®
Edition 2.0 2018-07
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
GROUP SAFETY PUBLICATION
PUBLICATION GROUPÉE DE SÉCURITÉ
Tests on electric and optical fibre cables under fire conditions –
Part 3-22: Test for vertical flame spread of vertically-mounted bunched wires or
cables – Category A
Essais des câbles electriques et des câbles à fibres optiques soumis au feu –
Partie 3-22: Essai de propagation verticale de la flamme des fils ou câbles
montés en nappes en position verticale – Catégorie A
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 13.220.40; 29.060.20 ISBN 978-2-8322-5798-2
Warning! Make sure that you obtained this publication from an authorized distributor.
Attention! Veuillez vous assurer que vous avez obtenu cette publication via un distributeur agréé.
® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale
---------------------- Page: 7 ----------------------
SIST EN IEC 60332-3-22:2018
– 2 – IEC 60332-3-22:2018 © IEC 2018
CONTENTS
FOREWORD . 3
INTRODUCTION . 5
1 Scope . 6
2 Normative references. 6
3 Terms and definitions . 6
4 Test apparatus . 7
4.1 General . 7
4.2 Ignition source . 7
5 Test procedure . 7
5.1 Test sample . 7
5.2 Determination of the number of test pieces . 7
5.3 Mounting of the test sample . 8
2
5.3.1 Cables having at least one conductor above 35 mm . 8
2
5.3.2 Cables having conductors 35 mm and below and optical cables . 9
5.4 Flame application time . 9
6 Evaluation of test results . 10
7 Performance requirements . 10
8 Retest procedure . 10
9 Test report. 10
Annex A (normative) Guidance on cable selection for type approval testing . 12
Annex B (informative) Recommended performance requirements . 13
Bibliography . 14
Figure 1 – Spaced cables mounted on the front side of the standard ladder . 11
Figure 2 – Spaced cables mounted on the front side of the wide ladder . 11
Figure 3 – Touching cables mounted on front side of the standard ladder (arrays of
cables in contact) . 11
Table A.1 – Summary of test conditions . 12
---------------------- Page: 8 ----------------------
SIST EN IEC 60332-3-22:2018
IEC 60332-3-22:2018 © IEC 2018 – 3 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
TESTS ON ELECTRIC AND OPTICAL FIBRE CABLES
UNDER FIRE CONDITIONS –
Part 3-22: Test for vertical flame spread of
vertically-mounted bunched wires or cables – Category A
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60332-3-22 has been prepared by IEC technical committee 20:
Electric cables.
This second edition cancels and replaces the first edition published in 2000 and
Amendment 1:2008. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
a) adjustments have been made to the title, and elsewhere, to emphasise the standard is
applicable to optical fibre cables as well as metallic conductor types;
b) details of the way in which cables are mounted on the ladder have been better defined in
order to improve repeatability and reproducibility.
---------------------- Page: 9 ----------------------
SIST EN IEC 60332-3-22:2018
– 4 – IEC 60332-3-22:2018 © IEC 2018
It has the status of a group safety publication in accordance with IEC Guide 104.
The text of this International Standard is based on the following documents:
FDIS Report on voting
20/1799/FDIS 20/1816/RVD
Full information on the voting for the approval of this International Standard can be found in
the report on voting indicated in the above table.
This document has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all parts in the IEC 60332 series, published under the general title Tests on electric
and optical fibre cables under fire conditions, can be found on the IEC website.
Future standards in this series will carry the new general title as cited above. Titles of existing
standards in this series will be updated at the time of the next edition.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under "http://webstore.iec.ch" in the data related to
the specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
---------------------- Page: 10 ----------------------
SIST EN IEC 60332-3-22:2018
IEC 60332-3-22:2018 © IEC 2018 – 5 –
INTRODUCTION
IEC 60332-3-22 is part of a series of publications dealing with tests on electric and optical
fibre cables under fire conditions.
The IEC 60332-1 and IEC 60332-2 series specify methods of test for flame spread
characteristics for a single vertical insulated wire or cable. It cannot be assumed that,
because a cable or wire meets the requirements of the IEC 60332-1 and IEC 60332-2 series,
a vertical bunch of similar cables or wires will behave in a similar manner. This is because
flame spread along a vertical bunch of cables depends on a number of features, such as
a) the volume of combustible material exposed to the fire and to any flame which may be
produced by the combustion of the cables;
b) the geometrical configuration of the cables and their relationship to an enclosure;
c) the temperature at which it is possible to ignite the gases emitted from the cables;
d) the quantity of combustible gas released from the cables for a given temperature rise;
e) the volume of air passing through the cable installation;
f) the co
...