Automatic electrical controls - Part 2-15: Particular requirements for automatic electrical air flow, water flow and water level sensing controls

This part of IEC 60730 applies to automatic electrical air flow, water flow and water level
sensing controls for use in, or in association with, boilers with a maximum pressure rating of
2 000 kPA (20 bar) and equipment for general household and similar use including controls
for heating, air-conditioning and similar applications.
NOTE Examples are water flow and water level sensing controls of the float or electrode-sensor type used in
boiler applications and air flow, water flow and water level sensing controls for swimming pool pumps, water tank
pumps, cooling towers, dishwashers, washing machines, air conditioning chillers and ventilation applications.
This document also applies to automatic electrical air flow, water flow and water level sensing
controls for equipment that may be used by the public, such as equipment intended to be
used in shops, offices, hospitals, farms and commercial and industrial applications.

Automatische elektrische Regel- und Steuergeräte - Teil 2-15: Besondere Anforderungen an automatische elektrische luftstrom-, wasserstrom- und wasserstandsabhängige Regel- und Steuergeräte

Dispositifs de commande électrique automatiques - Partie 2-15: Exigences particulières pour les dispositifs de commande électrique automatiques détecteurs de débit d'air, de débit d'eau et de niveau d'eau

IEC 60730-2-15:2017 s’applique aux dispositifs de commande électrique automatiques détecteurs de débit d'air, de débit d’eau et de niveau d'eau utilisés dans, ou avec, les chaudières de pression assignée maximale de 2 000 kPa (20 bar) et les matériels à usage domestique et analogue, y compris les dispositifs de commande pour le chauffage, le conditionnement d'air et les applications analogues. Ce sont, par exemple, les dispositifs de commande détecteurs de débit d'eau et de niveau d'eau du type à flotteur ou à électrode utilisés dans les réalisations de chaudières, ainsi que les dispositifs de commande détecteurs de débit d'air, de débit d'eau et de niveau d'eau pour les pompes de piscine, les pompes de réservoir d'eau, les tours de refroidissement, les machines à laver le linge, les lave-vaisselles, les réfrigérants de conditionnement d'air et les réalisations de ventilation. Le présent document s’applique également aux dispositifs de commande électrique automatiques détecteurs de débit d'air, de débit d'eau et de niveau d'eau pour des matériels qui peuvent être utilisés par le public, tels que les matériels destinés à être utilisés dans des magasins, des bureaux, des hôpitaux, des fermes et des applications commerciales et industrielles. Cette troisième édition annule et remplace la seconde édition publiée en 2008. Cette édition constitue une révision technique. Cette édition comprend les modifications techniques majeures suivantes par rapport à l'édition précédente ; modifications pour alignement avec la cinquième édition de l'IEC 60730-1, y compris le titre modifié. La présente Partie 2-15 doit être utilisée conjointement avec l'IEC 60730-1. Elle a été établie sur la base de la cinquième édition de cette norme (2013). Les éditions futures de l'IEC 60730-1, ou ses amendements, pourront être pris en compte. La présente Partie 2-15 complète ou modifie les articles correspondants de l'IEC 60730-1 de façon à la transformer en norme IEC: Exigences particulières pour les dispositifs de commande électrique automatiques détecteurs de débit d'air, de débit d'eau et de niveau d'eau. Lorsque le présent document spécifie "addition", "modification" ou "remplacement", il convient que l'exigence, la modalité d'essai ou le commentaire correspondant de la Partie 1 soit adapté en conséquence. Lorsqu'aucune modification n'est nécessaire, le présent document indique que l'article ou le paragraphe approprié s’applique. Mots clés: commande électrique, commande détecteur de niveau, débit d'air, débit d'eau, niveau d'eau

Avtomatske električne krmilne naprave - 2-15. del: Posebne zahteve za avtomatska električna tipala, ki zaznavajo pretok zraka, pretok vode in vodni nivo

Ta del standarda IEC 60730 se uporablja za avtomatska električna tipala, ki zaznavajo pretok zraka, pretok vode in vodni nivo, ki se uporabljajo v kotlih z največjo stopnjo tlaka 2000 kPA (20 barov) in opremo za splošno gospodinjsko ali podobno uporabo, vključno s krmilnimi napravami za ogrevanje, klimatskimi napravami ter podobnimi napravami, ali v povezavi z njimi.
OPOMBA: Primeri so plavajoča ali elektrodna tipala, ki zaznavajo pretok vode in vodni nivo, ki se uporabljajo v grelnikih, ter tipala, ki zaznavajo pretok zraka, pretok vode in vodni nivo, namenjena za črpalke plavalnih bazenov, črpalke vodnih rezervoarjev, hladilne stolpe, pomivalne stroje, pralne stroje, ohlajevalne klimatske naprave in prezračevalne naprave.
Ta dokument se uporablja tudi za avtomatska električna tipala, ki zaznavajo pretok zraka, pretok vode in vodni nivo, ki se uporabljajo za opremo za javno uporabo, kot je oprema, namenjena za uporabo v trgovinah, pisarnah, bolnišnicah, na kmetijah ter za komercialno in industrijsko uporabo.

General Information

Status
Published
Publication Date
14-May-2019
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
11-Oct-2017
Due Date
16-Dec-2017
Completion Date
15-May-2019

RELATIONS

Buy Standard

Standard
SIST EN IEC 60730-2-15:2019
English language
33 pages
sale 10% off
Preview
sale 10% off
Preview

e-Library read for
1 day
Standard
SIST EN 60730-2-15:2019
English language
33 pages
sale 10% off
Preview
sale 10% off
Preview

e-Library read for
1 day

Standards Content (sample)

SLOVENSKI STANDARD
SIST EN IEC 60730-2-15:2019
01-junij-2019
Nadomešča:
SIST EN 60730-2-15:2010
Avtomatske električne krmilne naprave - 2-15. del: Posebne zahteve za avtomatska
električna tipala, ki zaznavajo pretok zraka, pretok vode in vodni nivo

Automatic electrical controls - Part 2-15: Particular requirements for automatic electrical

air flow, water flow and water level sensing controls
Ta slovenski standard je istoveten z: EN IEC 60730-2-15:2019
ICS:
97.120 Avtomatske krmilne naprave Automatic controls for
za dom household use
SIST EN IEC 60730-2-15:2019 en

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
SIST EN IEC 60730-2-15:2019
---------------------- Page: 2 ----------------------
SIST EN IEC 60730-2-15:2019
EUROPEAN STANDARD EN IEC 60730-2-15
NORME EUROPÉENNE
EUROPÄISCHE NORM
April 2019
ICS 97.120 Supersedes EN 60730-2-15:2010
English Version
Automatic electrical controls - Part 2-15: Particular requirements
for automatic electrical air flow, water flow and water level
sensing controls
(IEC 60730-2-15:2017)

Dispositifs de commande électrique automatiques - Partie Automatische elektrische Regel- und Steuergeräte - Teil 2-

2-15: Exigences particulières pour les dispositifs de 15: Besondere Anforderungen an automatische elektrische

commande électrique automatiques détecteurs de débit luftstrom-, wasserstrom- und wasserstandsabhängige

d'air, de débit d'eau et de niveau d'eau Regel- und Steuergeräte
(IEC 60730-2-15:2017) (IEC 60730-2-15:2017)

This European Standard was approved by CENELEC on 2018-10-23. CENELEC members are bound to comply with the CEN/CENELEC

Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC

Management Centre or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by translation

under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the

same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,

Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,

Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden,

Switzerland, Turkey and the United Kingdom.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels

© 2019 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.

Ref. No. EN IEC 60730-2-15:2019 E
---------------------- Page: 3 ----------------------
SIST EN IEC 60730-2-15:2019
EN IEC 60730-2-15:2019 (E)
European foreword

The text of document (72/1080/FDIS), future edition 3 of IEC 60730-2-15, prepared by IEC/TC 72

"Automatic electrical controls" was submitted to the IEC-CENELEC parallel vote and approved by

CENELEC as EN IEC 60730-2-15:2019.
The following dates are fixed:

• latest date by which the document has to be implemented at national (dop) 2019-10-05

level by publication of an identical national standard or by endorsement

• latest date by which the national standards conflicting with the (dow) 2022-04-05

document have to be withdrawn
This document supersedes EN 60730-2-15:2010.

Attention is drawn to the possibility that some of the elements of this document may be the subject of

patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.

Endorsement notice

The text of the International Standard IEC 60730-2-15:2017 was approved by CENELEC as a

European Standard without any modification.

In the official version, for Bibliography, the following notes have to be added for the standards

indicated:
IEC 60364-7-702 NOTE Harmonized as HD 60364-7-702
IEC 60669 series NOTE Harmonized as EN 60669 series
IEC 60730-2-6 NOTE Harmonized as EN 60730-2-6
---------------------- Page: 4 ----------------------
SIST EN IEC 60730-2-15:2019
IEC 60730-2-15
Edition 3.0 2017-08
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Automatic electrical controls –

Part 2-15: Particular requirements for automatic electrical air flow, water flow and

water level sensing controls
Dispositifs de commande électrique automatiques –
Partie 2-15: Exigences particulières pour les dispositifs de commande électrique
automatiques détecteurs de débit d'air, de débit d'eau et de niveau d'eau
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 97.120 ISBN 978-2-8322-4696-2

Warning! Make sure that you obtained this publication from an authorized distributor.

Attention! Veuillez vous assurer que vous avez obtenu cette publication via un distributeur agréé.

® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale
---------------------- Page: 5 ----------------------
SIST EN IEC 60730-2-15:2019
– 2 – IEC 60730-2-15:2017 © IEC 2017
CONTENTS

FOREWORD ........................................................................................................................... 3

1 Scope and normative references ..................................................................................... 6

2 Terms and definitions ...................................................................................................... 7

3 General requirements ...................................................................................................... 9

4 General notes on tests .................................................................................................... 9

5 Rating.............................................................................................................................. 9

6 Classification ................................................................................................................... 9

7 Information .................................................................................................................... 10

8 Protection against electric shock ................................................................................... 11

9 Provision for protective earthing .................................................................................... 12

10 Terminals and terminations ............................................................................................ 12

11 Constructional requirements .......................................................................................... 12

12 Moisture and dust resistance ......................................................................................... 14

13 Electric strength and insulation resistance ..................................................................... 14

14 Heating .......................................................................................................................... 15

15 Manufacturing deviation and drift ................................................................................... 15

16 Environmental stress ..................................................................................................... 15

17 Endurance ..................................................................................................................... 16

18 Mechanical strength ...................................................................................................... 17

19 Threaded parts and connections .................................................................................... 18

20 Creepage distances, clearances and distances through solid insulation ......................... 18

21 Resistance to heat, fire and tracking .............................................................................. 18

22 Resistance to corrosion ................................................................................................. 18

23 Electromagnetic compatibility (EMC) requirements – Emission ...................................... 19

24 Components .................................................................................................................. 19

25 Normal operation ........................................................................................................... 19

26 Electromagnetic compatibility (EMC) requirements – Immunity ...................................... 19

27 Abnormal operation ....................................................................................................... 19

28 Guidance on the use of electronic disconnection ........................................................... 19

Annex H (normative) Requirements for electronic controls .................................................. 20

Annex AA (normative) Independently mounted controls for boiler applications .................... 28

Annex BB (normative) Requirements for response delay ...................................................... 29

Annex CC (normative) Independently mounted air flow and water flow sensing controls ...... 30

Bibliography .......................................................................................................................... 31

Table H.101 – Compliance criteria ........................................................................................ 23

Table AA.1 – Number of cycles ............................................................................................. 28

Table BB.1 – Deviation and Drift Limits ................................................................................. 29

Table CC.1 – Number of cycles ............................................................................................. 30

---------------------- Page: 6 ----------------------
SIST EN IEC 60730-2-15:2019
IEC 60730-2-15:2017 © IEC 2017 – 3 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
AUTOMATIC ELECTRICAL CONTROLS –
Part 2-15: Particular requirements for automatic electrical
air flow, water flow and water level sensing controls
FOREWORD

1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising

all national electrotechnical committees (IEC National Committees). The object of IEC is to promote

international co-operation on all questions concerning standardization in the electrical and electronic fields. To

this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,

Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC

Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested

in the subject dealt with may participate in this preparatory work. International, governmental and non-

governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely

with the International Organization for Standardization (ISO) in accordance with conditions determined by

agreement between the two organizations.

2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international

consensus of opinion on the relevant subjects since each technical committee has representation from all

interested IEC National Committees.

3) IEC Publications have the form of recommendations for international use and are accepted by IEC National

Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC

Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any

misinterpretation by any end user.

4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications

transparently to the maximum extent possible in their national and regional publications. Any divergence

between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in

the latter.

5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity

assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any

services carried out by independent certification bodies.

6) All users should ensure that they have the latest edition of this publication.

7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and

members of its technical committees and IEC National Committees for any personal injury, property damage or

other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and

expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC

Publications.

8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is

indispensable for the correct application of this publication.

9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of

patent rights. IEC shall not be held responsible for identifying any or all such patent rights.

International Standard IEC 60730-2-15 has been prepared by IEC committee 72: Automatic

electrical controls.

This third edition cancels and replaces the second edition published in 2008. This edition

constitutes a technical revision.

This edition includes the following significant technical changes with respect to the previous

edition:

a) changes to align with the fifth edition of 60730-1, including the revised title.

---------------------- Page: 7 ----------------------
SIST EN IEC 60730-2-15:2019
– 4 – IEC 60730-2-15:2017 © IEC 2017
The text of this International Standard is based on the following documents:
FDIS Report on voting
72/1080/FDIS 72/1101/RVD

Full information on the voting for the approval of this International Standard can be found in

the report on voting indicated in the above table.

This document has been drafted in accordance with the ISO/IEC Directives, Part 2.

This Part 2-15 is intended to be used in conjunction with IEC 60730-1. It was established on

the basis of the fifth edition of that standard (2013). Consideration may be given to future

editions of, or amendments to, IEC 60730-1.

This Part 2-15 supplements or modifies the corresponding clauses in IEC 60730-1 so as to

convert that publication into the IEC standard: Particular requirements for automatic electrical

air flow, water flow and water level sensing controls.

Where this document states "addition", "modification", or "replacement", the relevant

requirement, test specification or explanatory matter in Part 1 should be adapted accordingly.

Where no change is necessary, this document indicates that the relevant clause or subclause

of Part 1 applies.

In the development of a fully international standard to cover automatic controls for household

and similar use, it has been necessary to take into consideration the differing requirements

resulting from practical experience in various parts of the world and to recognize the variation

in national electrical systems and wiring rules.

The “in some countries” notes regarding differing national practices are contained in the

following subclauses:
• 10.1.4,
• 12.1.101.
In this publication:
1) The following print types are used:
– Requirements proper: in roman type;
– Test specifications: in italic type;
– Notes: in small roman type;
– Words defined in Clause 2: bold.

2) Subclauses, notes, tables and figures which are additional to those in part 1 are

numbered starting from 101, additional annexes are lettered AA, BB, etc.

A list of all parts in the IEC 60730 series, published under the general title Automatic

electrical controls, can be found on the IEC website.
---------------------- Page: 8 ----------------------
SIST EN IEC 60730-2-15:2019
IEC 60730-2-15:2017 © IEC 2017 – 5 –

The committee has decided that the contents of this document will remain unchanged until the

stability date indicated on the IEC website under "http://webstore.iec.ch" in the data related to

the specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
---------------------- Page: 9 ----------------------
SIST EN IEC 60730-2-15:2019
– 6 – IEC 60730-2-15:2017 © IEC 2017
AUTOMATIC ELECTRICAL CONTROLS –
Part 2-15: Particular requirements for automatic electrical
air flow, water flow and water level sensing controls
1 Scope and normative references
This clause of Part 1 is applicable except as follows:
1.1 Scope
Replacement:

This part of IEC 60730 applies to automatic electrical air flow, water flow and water level

sensing controls for use in, or in association with, boilers with a maximum pressure rating of

2 000 kPA (20 bar) and equipment for general household and similar use including controls

for heating, air-conditioning and similar applications.

NOTE Examples are water flow and water level sensing controls of the float or electrode-sensor type used in

boiler applications and air flow, water flow and water level sensing controls for swimming pool pumps, water tank

pumps, cooling towers, dishwashers, washing machines, air conditioning chillers and ventilation applications.

This document also applies to automatic electrical air flow, water flow and water level sensing

controls for equipment that may be used by the public, such as equipment intended to be

used in shops, offices, hospitals, farms and commercial and industrial applications.

1.1.1
Replacement:

This document applies to the inherent safety, to the operating values, operating sequences

where such are associated with equipment protection, and to the testing of automatic

electrical air flow, water flow and water level sensing controls used in, or in association with,

equipment.

This document is also applicable to controls for appliances within the scope of IEC 60335-1.

Automatic electrical air flow, water flow and water level sensing controls for equipment not

intended for normal household use, but which nevertheless may be used by the public, such

as equipment intended to be used by laymen in shops, in light industry and on farms, are

within the scope of this document.

This document is also applicable to individual controls utilized as part of a control system or

controls which are mechanically integral with multifunctional controls having non-electrical

outputs.

This document is not applicable to pressure sensing controls, requirements for which are

contained in IEC 60730-2-6 .
___________

IEC 60730-2-6, Automatic electrical controls – Part 2-6: Particular requirements for automatic electrical

pressure sensing controls including mechanical requirements.
---------------------- Page: 10 ----------------------
SIST EN IEC 60730-2-15:2019
IEC 60730-2-15:2017 © IEC 2017 – 7 –

This document does not apply to air flow, water flow and water level sensing controls

designed exclusively for industrial applications unless explicitly mentioned in the relevant

equipment standard.

NOTE Throughout this document, the word "equipment" means "appliance and equipment".

1.1.2 Addition:

This document applies to automatic electrical controls, mechanically or electrically operated,

responsive to or controlling air flow, water flow and water level.
1.1.3 Not applicable.

NOTE Requirements for manual switches not forming part of an automatic control are contained in IEC 60669 and

IEC 61058-1.
1.1.5 Replacement:

This document applies to a.c. or d.c. automatic electrical air flow, water flow and water level

sensing controls with a rated voltage not exceeding 690 V a.c. or 600 V d.c.
1.1.6 Replacement:

This document takes into account the response value of an automatic action of a control

where such a response value is dependent upon the method of mounting the control. Where a

response value is of significant purpose for the protection of the user, or surroundings, the

value defined in the appropriate household equipment standard or as determined by the

manufacturer shall apply.
1.1.7 Replacement:

This document applies also to controls incorporating electronic devices, requirements for

which are contained in Annex H.

This document applies also to controls using NTC and PTC thermistors, requirements for

which are contained in Annex J.
2 Terms and definitions
This clause of Part 1 is applicable except as follows:
2.2 Definitions of types of control according to purpose
Additional definitions:
2.2.101
boiler water level cut-out

water level sensing control of the float or electrode-sensor type for boiler applications

intended to respond to a low water level during abnormal operating conditions and which has

no provision for setting by the user

Note 1 to entry: A water level cut-out may be of the automatic or of the manual reset type. A boiler water level

cutout is a type of water level protective control (see 2.2.105).
---------------------- Page: 11 ----------------------
SIST EN IEC 60730-2-15:2019
– 8 – IEC 60730-2-15:2017 © IEC 2017
2.2.102
boiler water level limiter

water level sensing control of the float or electrode-sensor type for boiler applications which

is intended to keep a water level below or above one particular value during normal operating

conditions and which may have provision for setting by the user

Note 1 to entry: A boiler water level limiter is normally of the automatic reset type.

2.2.103
boiler water feed control

water level sensing control of the float or electrode-sensor type for boiler applications which

is intended to keep the water level in a boiler above one particular value during normal

operating conditions and which may have provision for setting by the user

Note 1 to entry: A boiler water feed control is of the automatic reset type. A boiler water feed control is used

on a boiler to cycle a feeder pump or feeder water valve. For the purposes of this document, a type 2 boiler water

feed control is considered to be a boiler water level limiter.
2.2.104
water level operating control

control which is intended to keep the water level below or above one particular value during

normal operating conditions and which may have provision for setting by the user
Note 1 to entry: A water level operating control is of the automatic reset type.
2.2.105
water level protective control

control which is intended to prevent a hazardous situation during abnormal operation of the

equipment either by
a) keeping the water level below or above one or more particular values, or by

b) energizing or de-energizing the associated equipment at one or more particular values of

water level
2.2.106
water flow operating control

flow sensing control intended to sense or maintain the water flow between two particular

values during normal operating conditions and which may have provision for setting by the

user
Note 1 to entry: A water flow operating control is of the automatic reset type.
2.2.107
air flow operating control

flow sensing control intended to sense or maintain the air flow between two particular values

during normal operating conditions and which may have provision for setting by the user

Note 1 to entry: An air flow operating control is of the automatic reset type.
2.2.108
water flow cut-out

flow sensing control intended to respond to a lack of water flow during abnormal operating

conditions and which has no provision for setting by the user
Note 1 to entry: A water flow cut-out is of the automatic or manual reset type.
2.2.109
air flow cut-out

flow sensing control intended to respond to a lack of air flow during abnormal operating

conditions and which has no provision for setting by the user
Note 1 to entry: An air flow cut-out is of the automatic or manual reset type.
---------------------- Page: 12 ----------------------
SIST EN IEC 60730-2-15:2019
IEC 60730-2-15:2017 © IEC 2017 – 9 –
2.3 Definitions relating to the function of controls
Additional definition:
2.3.101
response delay

delay provided to increase the response value of a water level operating control for the

purpose of preventing unnecessary cycling of the equipment due to fluctuating liquid level

Note 1 to entry: This is usually expressed in units of time.
3 General requirements
This clause of Part 1 is applicable.
4 General notes on tests
This clause of Part 1 is applicable except as follows:
4.1 Conditions of test
4.1.7 Addition:

The rates of change of level or flow declared in Table 1 and used in Clause 17 (i.e. α1, β1,

α2, β2) shall have test tolerances as declared by the manufacturer.
4.3 Instructions for test
Additional subclause:

4.3.1.101 The values in Table AA.1 apply for the testing of independently mounted water

level sensing controls used in boiler applications in Clause 17 unless a higher number is

declared. The values in Table CC.1 apply for the testing of independently mounted air and

water flow sensing controls in Clause 17 unless otherwise declared. Values for integrated

and incorporated controls are specified in the appropriate equipment standard.
4.3.5.1 Modification:

The second sentence is not applicable to combinations of boiler water level sensing controls

using a common sensing mechanism.
5 Rating
This clause of Part 1 is applicable.
6 Classification
This clause of Part 1 is applicable except as follows:
6.3 According to their purpose
6.3.9
Additional subclauses:
---------------------- Page: 13 ----------------------
SIST EN IEC 60730-2-15:2019
– 10 – IEC 60730-2-15:2017 © IEC 2017
6.3.9.101 – boiler water level cut-out;
6.3.9.102 – boiler water level limiter;
6.3.9.103 – boiler water feed control;
6.3.9.104 – water level operating control;
6.3.9.105 – water level protective control;
6.3.9.106 – air flow operating control;
6.3.9.107 – water flow operating control;
6.3.9.108 – air flow cut-out;
6.3.9.109 – water flow cut-out.
6.4 According to features of automatic action
6.4.1
Additional subclause:

6.4.1.101 – Boiler water feed controls within the scope of this document are classified as

having type 1 action.
For the purpose of this document, a type 2 boiler water feed control is
considered to be a boiler water level limiter.
6.4.2
Additional subclause:

6.4.2.101 – Boiler water level cut-outs and boiler water level limiters within the scope of

this document are classified as having type 2 action.
6.4.3
Additional subclauses:

6.4.3.101 – manual reset boiler water level sensing controls within the scope of this

document shall have a trip-free mechanism classified as type 2.D, 2.H or 2.J
action;
6.4.3.102 – an action incorporating response delay (type 1.AJ or 2.AJ).
6.5 According to the degree of protection and control pollution degree
6.5.2 Addition:

Controls declared in Table 1, requirement 107, to be wholly or partially submerged in water

during usage shall have enclosures classified as IPX8 which provide protection against

continuous immersion in water as specified in IEC 60529.
7 Information
This clause of Part 1 is applicable except as follows:
---------------------- Page: 14 ----------------------
SIST EN IEC 60730-2-15:2019
IEC 60730-2-15:2017 © IEC 2017 – 11 –

Table 1 – (7.2 of edition 3) – Required information and methods of providing information

Information Clause or Method
subclause
Modifications:
Temperature limits of mounting surfaces (T )
23 6.12.2, 14.1, 17.3 D
101
27 Number of automatic cycles (A) for each automatic action 6.11, 17.8, 17.9 X
34 Not applicable
44 Not applicable
Additional requirements:
101 Maximum fluid temperature (T ) in °C 14.5.1 D
102 Response time, if applicable, for boiler water level sensing controls 15 C
104
103 Maximum working pressure, if applicable 2.3.29, 18.102 C/D
Method of determining response time for boiler water level sensing
104 15.6.101 X
controls
105 Test method for 18.101.2 for boiler water level sensing controls 18.101.2 X

106 Any special environmental conditions in which the control is intended 12.1.101 D

102
to be used (other than declared in Table 1, requirement 15)

107 Cord-connected float control which may be wholly or partially 6.5.2, 11.7.1.1, D

submerged in water or any other special environmental conditions 11.7.1.2.1,
declared in requirement 106 11.7.1.2.2,
12.1.101
108 Response delay 2.3.101, 6.4.3.102, D
11.4.101,
H.11.12.8,
Table BB.1
109 Unique or common type reference of special mounting means, if 11.6.3.1 C
103
any
110 Leveling indication for mounting, if any 11.11.101 C
Additional notes:
101

The minimum number of automatic cycles is 6 000 for water level sensing controls of the float type.

102

This information may be taken from the appropriate IEC equipment standard or may be as declared by

the manufacturer.
103
The unique or common type reference(s) shall be marked on both the mounting
...

SLOVENSKI STANDARD
SIST EN 60730-2-15:2019
01-junij-2019
Nadomešča:
SIST EN 60730-2-15:2010
Avtomatske električne krmilne naprave - 2-15. del: Posebne zahteve za avtomatska
električna tipala, ki zaznavajo pretok zraka, pretok vode in vodni nivo

Automatic electrical controls - Part 2-15: Particular requirements for automatic electrical

air flow, water flow and water level sensing controls
Ta slovenski standard je istoveten z: EN IEC 60730-2-15:2019
ICS:
97.120 Avtomatske krmilne naprave Automatic controls for
za dom household use
SIST EN 60730-2-15:2019 en

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
SIST EN 60730-2-15:2019
---------------------- Page: 2 ----------------------
SIST EN 60730-2-15:2019
EUROPEAN STANDARD EN IEC 60730-2-15
NORME EUROPÉENNE
EUROPÄISCHE NORM
April 2019
ICS 97.120 Supersedes EN 60730-2-15:2010
English Version
Automatic electrical controls - Part 2-15: Particular requirements
for automatic electrical air flow, water flow and water level
sensing controls
(IEC 60730-2-15:2017)

Dispositifs de commande électrique automatiques - Partie Automatische elektrische Regel- und Steuergeräte - Teil 2-

2-15: Exigences particulières pour les dispositifs de 15: Besondere Anforderungen an automatische elektrische

commande électrique automatiques détecteurs de débit luftstrom-, wasserstrom- und wasserstandsabhängige

d'air, de débit d'eau et de niveau d'eau Regel- und Steuergeräte
(IEC 60730-2-15:2017) (IEC 60730-2-15:2017)

This European Standard was approved by CENELEC on 2018-10-23. CENELEC members are bound to comply with the CEN/CENELEC

Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC

Management Centre or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by translation

under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the

same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,

Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,

Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden,

Switzerland, Turkey and the United Kingdom.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels

© 2019 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.

Ref. No. EN IEC 60730-2-15:2019 E
---------------------- Page: 3 ----------------------
SIST EN 60730-2-15:2019
EN IEC 60730-2-15:2019 (E)
European foreword

The text of document (72/1080/FDIS), future edition 3 of IEC 60730-2-15, prepared by IEC/TC 72

"Automatic electrical controls" was submitted to the IEC-CENELEC parallel vote and approved by

CENELEC as EN IEC 60730-2-15:2019.
The following dates are fixed:

• latest date by which the document has to be implemented at national (dop) 2019-10-05

level by publication of an identical national standard or by endorsement

• latest date by which the national standards conflicting with the (dow) 2022-04-05

document have to be withdrawn
This document supersedes EN 60730-2-15:2010.

Attention is drawn to the possibility that some of the elements of this document may be the subject of

patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.

Endorsement notice

The text of the International Standard IEC 60730-2-15:2017 was approved by CENELEC as a

European Standard without any modification.

In the official version, for Bibliography, the following notes have to be added for the standards

indicated:
IEC 60364-7-702 NOTE Harmonized as HD 60364-7-702
IEC 60669 series NOTE Harmonized as EN 60669 series
IEC 60730-2-6 NOTE Harmonized as EN 60730-2-6
---------------------- Page: 4 ----------------------
SIST EN 60730-2-15:2019
IEC 60730-2-15
Edition 3.0 2017-08
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Automatic electrical controls –

Part 2-15: Particular requirements for automatic electrical air flow, water flow and

water level sensing controls
Dispositifs de commande électrique automatiques –
Partie 2-15: Exigences particulières pour les dispositifs de commande électrique
automatiques détecteurs de débit d'air, de débit d'eau et de niveau d'eau
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 97.120 ISBN 978-2-8322-4696-2

Warning! Make sure that you obtained this publication from an authorized distributor.

Attention! Veuillez vous assurer que vous avez obtenu cette publication via un distributeur agréé.

® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale
---------------------- Page: 5 ----------------------
SIST EN 60730-2-15:2019
– 2 – IEC 60730-2-15:2017 © IEC 2017
CONTENTS

FOREWORD ........................................................................................................................... 3

1 Scope and normative references ..................................................................................... 6

2 Terms and definitions ...................................................................................................... 7

3 General requirements ...................................................................................................... 9

4 General notes on tests .................................................................................................... 9

5 Rating.............................................................................................................................. 9

6 Classification ................................................................................................................... 9

7 Information .................................................................................................................... 10

8 Protection against electric shock ................................................................................... 11

9 Provision for protective earthing .................................................................................... 12

10 Terminals and terminations ............................................................................................ 12

11 Constructional requirements .......................................................................................... 12

12 Moisture and dust resistance ......................................................................................... 14

13 Electric strength and insulation resistance ..................................................................... 14

14 Heating .......................................................................................................................... 15

15 Manufacturing deviation and drift ................................................................................... 15

16 Environmental stress ..................................................................................................... 15

17 Endurance ..................................................................................................................... 16

18 Mechanical strength ...................................................................................................... 17

19 Threaded parts and connections .................................................................................... 18

20 Creepage distances, clearances and distances through solid insulation ......................... 18

21 Resistance to heat, fire and tracking .............................................................................. 18

22 Resistance to corrosion ................................................................................................. 18

23 Electromagnetic compatibility (EMC) requirements – Emission ...................................... 19

24 Components .................................................................................................................. 19

25 Normal operation ........................................................................................................... 19

26 Electromagnetic compatibility (EMC) requirements – Immunity ...................................... 19

27 Abnormal operation ....................................................................................................... 19

28 Guidance on the use of electronic disconnection ........................................................... 19

Annex H (normative) Requirements for electronic controls .................................................. 20

Annex AA (normative) Independently mounted controls for boiler applications .................... 28

Annex BB (normative) Requirements for response delay ...................................................... 29

Annex CC (normative) Independently mounted air flow and water flow sensing controls ...... 30

Bibliography .......................................................................................................................... 31

Table H.101 – Compliance criteria ........................................................................................ 23

Table AA.1 – Number of cycles ............................................................................................. 28

Table BB.1 – Deviation and Drift Limits ................................................................................. 29

Table CC.1 – Number of cycles ............................................................................................. 30

---------------------- Page: 6 ----------------------
SIST EN 60730-2-15:2019
IEC 60730-2-15:2017 © IEC 2017 – 3 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
AUTOMATIC ELECTRICAL CONTROLS –
Part 2-15: Particular requirements for automatic electrical
air flow, water flow and water level sensing controls
FOREWORD

1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising

all national electrotechnical committees (IEC National Committees). The object of IEC is to promote

international co-operation on all questions concerning standardization in the electrical and electronic fields. To

this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,

Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC

Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested

in the subject dealt with may participate in this preparatory work. International, governmental and non-

governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely

with the International Organization for Standardization (ISO) in accordance with conditions determined by

agreement between the two organizations.

2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international

consensus of opinion on the relevant subjects since each technical committee has representation from all

interested IEC National Committees.

3) IEC Publications have the form of recommendations for international use and are accepted by IEC National

Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC

Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any

misinterpretation by any end user.

4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications

transparently to the maximum extent possible in their national and regional publications. Any divergence

between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in

the latter.

5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity

assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any

services carried out by independent certification bodies.

6) All users should ensure that they have the latest edition of this publication.

7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and

members of its technical committees and IEC National Committees for any personal injury, property damage or

other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and

expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC

Publications.

8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is

indispensable for the correct application of this publication.

9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of

patent rights. IEC shall not be held responsible for identifying any or all such patent rights.

International Standard IEC 60730-2-15 has been prepared by IEC committee 72: Automatic

electrical controls.

This third edition cancels and replaces the second edition published in 2008. This edition

constitutes a technical revision.

This edition includes the following significant technical changes with respect to the previous

edition:

a) changes to align with the fifth edition of 60730-1, including the revised title.

---------------------- Page: 7 ----------------------
SIST EN 60730-2-15:2019
– 4 – IEC 60730-2-15:2017 © IEC 2017
The text of this International Standard is based on the following documents:
FDIS Report on voting
72/1080/FDIS 72/1101/RVD

Full information on the voting for the approval of this International Standard can be found in

the report on voting indicated in the above table.

This document has been drafted in accordance with the ISO/IEC Directives, Part 2.

This Part 2-15 is intended to be used in conjunction with IEC 60730-1. It was established on

the basis of the fifth edition of that standard (2013). Consideration may be given to future

editions of, or amendments to, IEC 60730-1.

This Part 2-15 supplements or modifies the corresponding clauses in IEC 60730-1 so as to

convert that publication into the IEC standard: Particular requirements for automatic electrical

air flow, water flow and water level sensing controls.

Where this document states "addition", "modification", or "replacement", the relevant

requirement, test specification or explanatory matter in Part 1 should be adapted accordingly.

Where no change is necessary, this document indicates that the relevant clause or subclause

of Part 1 applies.

In the development of a fully international standard to cover automatic controls for household

and similar use, it has been necessary to take into consideration the differing requirements

resulting from practical experience in various parts of the world and to recognize the variation

in national electrical systems and wiring rules.

The “in some countries” notes regarding differing national practices are contained in the

following subclauses:
• 10.1.4,
• 12.1.101.
In this publication:
1) The following print types are used:
– Requirements proper: in roman type;
– Test specifications: in italic type;
– Notes: in small roman type;
– Words defined in Clause 2: bold.

2) Subclauses, notes, tables and figures which are additional to those in part 1 are

numbered starting from 101, additional annexes are lettered AA, BB, etc.

A list of all parts in the IEC 60730 series, published under the general title Automatic

electrical controls, can be found on the IEC website.
---------------------- Page: 8 ----------------------
SIST EN 60730-2-15:2019
IEC 60730-2-15:2017 © IEC 2017 – 5 –

The committee has decided that the contents of this document will remain unchanged until the

stability date indicated on the IEC website under "http://webstore.iec.ch" in the data related to

the specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
---------------------- Page: 9 ----------------------
SIST EN 60730-2-15:2019
– 6 – IEC 60730-2-15:2017 © IEC 2017
AUTOMATIC ELECTRICAL CONTROLS –
Part 2-15: Particular requirements for automatic electrical
air flow, water flow and water level sensing controls
1 Scope and normative references
This clause of Part 1 is applicable except as follows:
1.1 Scope
Replacement:

This part of IEC 60730 applies to automatic electrical air flow, water flow and water level

sensing controls for use in, or in association with, boilers with a maximum pressure rating of

2 000 kPA (20 bar) and equipment for general household and similar use including controls

for heating, air-conditioning and similar applications.

NOTE Examples are water flow and water level sensing controls of the float or electrode-sensor type used in

boiler applications and air flow, water flow and water level sensing controls for swimming pool pumps, water tank

pumps, cooling towers, dishwashers, washing machines, air conditioning chillers and ventilation applications.

This document also applies to automatic electrical air flow, water flow and water level sensing

controls for equipment that may be used by the public, such as equipment intended to be

used in shops, offices, hospitals, farms and commercial and industrial applications.

1.1.1
Replacement:

This document applies to the inherent safety, to the operating values, operating sequences

where such are associated with equipment protection, and to the testing of automatic

electrical air flow, water flow and water level sensing controls used in, or in association with,

equipment.

This document is also applicable to controls for appliances within the scope of IEC 60335-1.

Automatic electrical air flow, water flow and water level sensing controls for equipment not

intended for normal household use, but which nevertheless may be used by the public, such

as equipment intended to be used by laymen in shops, in light industry and on farms, are

within the scope of this document.

This document is also applicable to individual controls utilized as part of a control system or

controls which are mechanically integral with multifunctional controls having non-electrical

outputs.

This document is not applicable to pressure sensing controls, requirements for which are

contained in IEC 60730-2-6 .
___________

IEC 60730-2-6, Automatic electrical controls – Part 2-6: Particular requirements for automatic electrical

pressure sensing controls including mechanical requirements.
---------------------- Page: 10 ----------------------
SIST EN 60730-2-15:2019
IEC 60730-2-15:2017 © IEC 2017 – 7 –

This document does not apply to air flow, water flow and water level sensing controls

designed exclusively for industrial applications unless explicitly mentioned in the relevant

equipment standard.

NOTE Throughout this document, the word "equipment" means "appliance and equipment".

1.1.2 Addition:

This document applies to automatic electrical controls, mechanically or electrically operated,

responsive to or controlling air flow, water flow and water level.
1.1.3 Not applicable.

NOTE Requirements for manual switches not forming part of an automatic control are contained in IEC 60669 and

IEC 61058-1.
1.1.5 Replacement:

This document applies to a.c. or d.c. automatic electrical air flow, water flow and water level

sensing controls with a rated voltage not exceeding 690 V a.c. or 600 V d.c.
1.1.6 Replacement:

This document takes into account the response value of an automatic action of a control

where such a response value is dependent upon the method of mounting the control. Where a

response value is of significant purpose for the protection of the user, or surroundings, the

value defined in the appropriate household equipment standard or as determined by the

manufacturer shall apply.
1.1.7 Replacement:

This document applies also to controls incorporating electronic devices, requirements for

which are contained in Annex H.

This document applies also to controls using NTC and PTC thermistors, requirements for

which are contained in Annex J.
2 Terms and definitions
This clause of Part 1 is applicable except as follows:
2.2 Definitions of types of control according to purpose
Additional definitions:
2.2.101
boiler water level cut-out

water level sensing control of the float or electrode-sensor type for boiler applications

intended to respond to a low water level during abnormal operating conditions and which has

no provision for setting by the user

Note 1 to entry: A water level cut-out may be of the automatic or of the manual reset type. A boiler water level

cutout is a type of water level protective control (see 2.2.105).
---------------------- Page: 11 ----------------------
SIST EN 60730-2-15:2019
– 8 – IEC 60730-2-15:2017 © IEC 2017
2.2.102
boiler water level limiter

water level sensing control of the float or electrode-sensor type for boiler applications which

is intended to keep a water level below or above one particular value during normal operating

conditions and which may have provision for setting by the user

Note 1 to entry: A boiler water level limiter is normally of the automatic reset type.

2.2.103
boiler water feed control

water level sensing control of the float or electrode-sensor type for boiler applications which

is intended to keep the water level in a boiler above one particular value during normal

operating conditions and which may have provision for setting by the user

Note 1 to entry: A boiler water feed control is of the automatic reset type. A boiler water feed control is used

on a boiler to cycle a feeder pump or feeder water valve. For the purposes of this document, a type 2 boiler water

feed control is considered to be a boiler water level limiter.
2.2.104
water level operating control

control which is intended to keep the water level below or above one particular value during

normal operating conditions and which may have provision for setting by the user
Note 1 to entry: A water level operating control is of the automatic reset type.
2.2.105
water level protective control

control which is intended to prevent a hazardous situation during abnormal operation of the

equipment either by
a) keeping the water level below or above one or more particular values, or by

b) energizing or de-energizing the associated equipment at one or more particular values of

water level
2.2.106
water flow operating control

flow sensing control intended to sense or maintain the water flow between two particular

values during normal operating conditions and which may have provision for setting by the

user
Note 1 to entry: A water flow operating control is of the automatic reset type.
2.2.107
air flow operating control

flow sensing control intended to sense or maintain the air flow between two particular values

during normal operating conditions and which may have provision for setting by the user

Note 1 to entry: An air flow operating control is of the automatic reset type.
2.2.108
water flow cut-out

flow sensing control intended to respond to a lack of water flow during abnormal operating

conditions and which has no provision for setting by the user
Note 1 to entry: A water flow cut-out is of the automatic or manual reset type.
2.2.109
air flow cut-out

flow sensing control intended to respond to a lack of air flow during abnormal operating

conditions and which has no provision for setting by the user
Note 1 to entry: An air flow cut-out is of the automatic or manual reset type.
---------------------- Page: 12 ----------------------
SIST EN 60730-2-15:2019
IEC 60730-2-15:2017 © IEC 2017 – 9 –
2.3 Definitions relating to the function of controls
Additional definition:
2.3.101
response delay

delay provided to increase the response value of a water level operating control for the

purpose of preventing unnecessary cycling of the equipment due to fluctuating liquid level

Note 1 to entry: This is usually expressed in units of time.
3 General requirements
This clause of Part 1 is applicable.
4 General notes on tests
This clause of Part 1 is applicable except as follows:
4.1 Conditions of test
4.1.7 Addition:

The rates of change of level or flow declared in Table 1 and used in Clause 17 (i.e. α1, β1,

α2, β2) shall have test tolerances as declared by the manufacturer.
4.3 Instructions for test
Additional subclause:

4.3.1.101 The values in Table AA.1 apply for the testing of independently mounted water

level sensing controls used in boiler applications in Clause 17 unless a higher number is

declared. The values in Table CC.1 apply for the testing of independently mounted air and

water flow sensing controls in Clause 17 unless otherwise declared. Values for integrated

and incorporated controls are specified in the appropriate equipment standard.
4.3.5.1 Modification:

The second sentence is not applicable to combinations of boiler water level sensing controls

using a common sensing mechanism.
5 Rating
This clause of Part 1 is applicable.
6 Classification
This clause of Part 1 is applicable except as follows:
6.3 According to their purpose
6.3.9
Additional subclauses:
---------------------- Page: 13 ----------------------
SIST EN 60730-2-15:2019
– 10 – IEC 60730-2-15:2017 © IEC 2017
6.3.9.101 – boiler water level cut-out;
6.3.9.102 – boiler water level limiter;
6.3.9.103 – boiler water feed control;
6.3.9.104 – water level operating control;
6.3.9.105 – water level protective control;
6.3.9.106 – air flow operating control;
6.3.9.107 – water flow operating control;
6.3.9.108 – air flow cut-out;
6.3.9.109 – water flow cut-out.
6.4 According to features of automatic action
6.4.1
Additional subclause:

6.4.1.101 – Boiler water feed controls within the scope of this document are classified as

having type 1 action.
For the purpose of this document, a type 2 boiler water feed control is
considered to be a boiler water level limiter.
6.4.2
Additional subclause:

6.4.2.101 – Boiler water level cut-outs and boiler water level limiters within the scope of

this document are classified as having type 2 action.
6.4.3
Additional subclauses:

6.4.3.101 – manual reset boiler water level sensing controls within the scope of this

document shall have a trip-free mechanism classified as type 2.D, 2.H or 2.J
action;
6.4.3.102 – an action incorporating response delay (type 1.AJ or 2.AJ).
6.5 According to the degree of protection and control pollution degree
6.5.2 Addition:

Controls declared in Table 1, requirement 107, to be wholly or partially submerged in water

during usage shall have enclosures classified as IPX8 which provide protection against

continuous immersion in water as specified in IEC 60529.
7 Information
This clause of Part 1 is applicable except as follows:
---------------------- Page: 14 ----------------------
SIST EN 60730-2-15:2019
IEC 60730-2-15:2017 © IEC 2017 – 11 –

Table 1 – (7.2 of edition 3) – Required information and methods of providing information

Information Clause or Method
subclause
Modifications:
Temperature limits of mounting surfaces (T )
23 6.12.2, 14.1, 17.3 D
101
27 Number of automatic cycles (A) for each automatic action 6.11, 17.8, 17.9 X
34 Not applicable
44 Not applicable
Additional requirements:
101 Maximum fluid temperature (T ) in °C 14.5.1 D
102 Response time, if applicable, for boiler water level sensing controls 15 C
104
103 Maximum working pressure, if applicable 2.3.29, 18.102 C/D
Method of determining response time for boiler water level sensing
104 15.6.101 X
controls
105 Test method for 18.101.2 for boiler water level sensing controls 18.101.2 X

106 Any special environmental conditions in which the control is intended 12.1.101 D

102
to be used (other than declared in Table 1, requirement 15)

107 Cord-connected float control which may be wholly or partially 6.5.2, 11.7.1.1, D

submerged in water or any other special environmental conditions 11.7.1.2.1,
declared in requirement 106 11.7.1.2.2,
12.1.101
108 Response delay 2.3.101, 6.4.3.102, D
11.4.101,
H.11.12.8,
Table BB.1
109 Unique or common type reference of special mounting means, if 11.6.3.1 C
103
any
110 Leveling indication for mounting, if any 11.11.101 C
Additional notes:
101

The minimum number of automatic cycles is 6 000 for water level sensing controls of the float type.

102

This information may be taken from the appropriate IEC equipment standard or may be as declared by

the manufacturer.
103

The unique or common type reference(s) shall be marked on both the mounting means and the control.

104
Method
...