SIST EN 81-58:2004
(Main)Safety rules for the construction and installation of lifts - Examination and tests - Part 58: Landing doors fire resistance test
Safety rules for the construction and installation of lifts - Examination and tests - Part 58: Landing doors fire resistance test
This European Standard specifies the method of test for determining the fire resistance of lift landing doors which may be exposed to a fire from the landing side. The procedure applies to all types of lift landing doors used as a means of access to lifts in buildings and which are intended to provide a fire barrier to the spread of fire via the lift well. The procedure allows for the measurement of integrity and if required the measurement of radiation and thermal insulation. No requirements are included for mechanical conditioning as these are included in the relevant product standard.
Sicherheitsregeln für die Konstruktion und den Einbau von Aufzügen - Überprüfung und Prüfverfahren - Teil 58: Prüfung der Feuerwiderstandsfähigkeit von Fahrschachttüren
Diese Europäische Norm legt ein Prüfverfahren für die Bestimmung der Feuerwiderstandsfähigkeit von Fahrschachttüren fest, die einem Brand auf der Flurseite ausgesetzt sein können. Das Verfahren gilt für sämtliche Arten von Fahrschachttüren, die für den Zugang zu Aufzügen in Gebäuden eingesetzt werden und die Aufgabe haben, die Ausbreitung von Feuer über den Fahrschacht zu verhindern.
Das Prüfverfahren ermöglicht die Messung des Raumabschlusses und, falls erforderlich, die Messung von Strahlung und Wärmedämmung.
Anforderungen hinsichtlich der mechanischen Vorbehandlung vor der Brandprüfung, außer der Überprüfung, dass der Probekörper funktionsfähig ist, sind nicht Gegenstand dieser Norm, da diese in den entsprechenden Produktnormen enthalten sind.
Regles de sécurité pour la construction et l'installation des élévateurs - Examen et essais - Partie 58: Essais de résistance au feu des portes palieres
Cette norme européenne spécifie la méthode d'essai pour déterminer la résistance au feu des portes palieres d'ascenseur qui peuvent etre exposées a un feu du côté palier. Le mode opératoire s'applique a tous les types de portes palieres d'ascenseur utilisées comme moyen d'acces aux ascenseurs dans des bâtiments et destinées a constituer une barriere contre l'extension d'un feu par la gaine d'ascenseur.
Le mode opératoire permet de mesurer l'étanchéité et si nécessaire, le rayonnement et l'isolation thermique.
Aucune prescription, autre que la vérification du fonctionnement du spécimen, ne concerne le conditionnement mécanique, car ce domaine releve de la norme appropriée concernant le produit.
Varnostna pravila za konstruiranje in vgradnjo dvigal (liftov) - Pregled in preskusi - 58. del: Preskus odpornosti vrat proti požaru
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 81-58:2004
01-april-2004
Varnostna pravila za konstruiranje in vgradnjo dvigal (liftov) - Pregled in preskusi -
58. del: Preskus odpornosti vrat proti požaru
Safety rules for the construction and installation of lifts - Examination and tests - Part 58:
Landing doors fire resistance test
Sicherheitsregeln für die Konstruktion und den Einbau von Aufzügen - Überprüfung und
Prüfverfahren - Teil 58: Prüfung der Feuerwiderstandsfähigkeit von Fahrschachttüren
Regles de sécurité pour la construction et l'installation des élévateurs - Examen et essais
- Partie 58: Essais de résistance au feu des portes palieres
Ta slovenski standard je istoveten z: EN 81-58:2003
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
91.140.90 'YLJDOD7HNRþHVWRSQLFH Lifts. Escalators
SIST EN 81-58:2004 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
EUROPEAN STANDARD
EN 81-58
NORME EUROPÉENNE
EUROPÄISCHE NORM
July 2003
ICS 91.140.90
English version
Safety rules for the construction and installation of lifts -
Examination and tests - Part 58: Landing doors fire resistance
test
Règles de sécurité pour la construction et l'installation des Sicherheitsregeln für die Konstruktion und den Einbau von
élévateurs - Examen et essais - Partie 58: Essais de Aufzügen - Überprüfung und Prüfverfahren - Teil 58:
résistance au feu des portes palières Prüfung der Feuerwiderstandsfähigkeit von
Fahrschachttüren
This European Standard was approved by CEN on 18 March 2003.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the official
versions.
CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,
Hungary, Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and United
Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36 B-1050 Brussels
© 2003 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 81-58:2003 E
worldwide for CEN national Members.
---------------------- Page: 2 ----------------------
EN 81-58:2003 (E)
Contents
Foreword.4
Introduction .5
1 Scope .6
2 Normative references .6
3 Terms and definitions.6
4 Test principle.7
5 Test equipment .7
6 Test conditions .7
7 Test specimen .8
7.1 Construction.8
7.2 Number of specimens .8
7.3 Size of specimen.8
7.4 Installation of specimen .8
8 Supporting construction .8
9 Conditioning.8
10 Pre-test examination.8
10.1 General.8
10.2 Constructional details .9
10.3 Clearance gap measurements and depth of penetration .9
10.4 Functionality test .13
11 Test instrumentation .14
11.1 Furnace thermocouples .14
11.2 Furnace CO concentration.14
2
11.3 Gas flow measuring system instrumentation.14
11.4 Furnace pressure.14
11.5 Unexposed face temperature.14
11.6 Radiation measurement .15
11.7 Deformation measurement .15
11.8 Flow measurement verification .16
12 Test procedure .16
13 Test termination .16
14 Assessment of performance.16
15 Criteria of performance .17
15.1 Integrity (E) .17
15.2 Thermal insulation (I).17
15.3 Radiation (W).17
16 Direct field of application.17
17 Classification procedure and declaration of performance.18
17.1 Performance criteria .18
17.2 Classification periods.18
17.3 Designatory letters .18
17.4 Declaration of performance .18
17.5 Classes.18
18 Test report .19
Annex A (normative) Description of the canopy and measuring system.20
2
---------------------- Page: 3 ----------------------
EN 81-58:2003 (E)
Annex B (normative) Standard supporting construction.23
Annex C (normative) Verification procedure for leakage rate measurement .24
Annex D (normative) Calculation of leakage rate .25
D.1 Calculation of leakage rate when measuring according to EN ISO 5167-1 with an orifice plate.25
D.2 Pressure correction:.26
D.3 Interpreting the leakage rate curve.27
Annex ZA (informative) Relationship of this European Document with EC Directives .28
Bibliography .29
3
---------------------- Page: 4 ----------------------
EN 81-58:2003 (E)
Foreword
This document EN 81-58:2003 has been prepared by Technical Committee CEN/TC 10 “Lifts, escalators and
moving walks”, the secretariat of which is held by AFNOR.
This European Standard shall be given the status of a national standard, either by publication of an identical text or
by endorsement, at the latest by January 2004, and conflicting national standards shall be withdrawn at the latest
by January 2004.
This document has been prepared under a mandate given to CEN by the European Commission and the European
Free Trade Association, and supports essential requirements of EU Directive(s).
For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document.
Annexes A to D are normative.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Czech Republic, Denmark, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal,
Slovakia, Spain, Sweden, Switzerland and the United Kingdom.
4
---------------------- Page: 5 ----------------------
EN 81-58:2003 (E)
Introduction
This document is a type C standard as stated in EN 1070.
When provisions of this type C standard are different from those which are stated in type A or B standards, the
provisions of this type C standard take precedence over the provisions of the other standards for lift landing doors
that have been designed and built according to the provisions of this type C standard.
EN 81 has identified the need for certain lift doors to act as fire barriers against the transfer of a fire via the lift well.
This European Standard specifies a procedure for this purpose. It follows the general principle of EN 1363-1, Fire
resistance tests – Part 1: General requirements, and where appropriate the procedure of EN 1634-1, Fire
resistance tests for door and shutter assemblies – Part 1: Fire doors and shutters. Additionally a tracer gas
technique for establishing the integrity of a lift landing door is used.
Lift landing doors are not included in the scope of EN 1634-1.
Lift landing doors, with additional applications, that may already have been tested for other than passenger lift
landing door use to EN 1634-1, are considered to satisfy the corresponding classification according to this
European standard.
5
---------------------- Page: 6 ----------------------
EN 81-58:2003 (E)
1 Scope
This European Standard specifies the method of test for determining the fire resistance of lift landing doors which
may be exposed to a fire from the landing side. The procedure applies to all types of lift landing doors used as a
means of access to lifts in buildings and which are intended to provide a fire barrier to the spread of fire via the lift
well.
The procedure allows for the measurement of integrity and if required the measurement of radiation and thermal
insulation.
No requirements other than the verification that the specimen is operational, are included for mechanical
conditioning before the test as these are included in the relevant product standard.
2 Normative references
This European Standard incorporates by dated or undated reference, provisions from other publications. These
normative references are cited at the appropriate places in the text and the publications are listed hereafter. For
dated references, subsequent amendments to or revisions of any of these publications apply to this European
Standard only when incorporated in it by amendment or revision. For undated references the latest edition of the
publication referred to applies (including amendments).
EN 81-1, Safety rules for the construction and installation of lifts – Part 1: Electric lifts.
EN 81-2, Safety rules for the construction and installation of lifts – Part 2: Hydraulic lifts.
EN 1070:1998, Safety of machinery - Terminology
EN 1363-1:1999, Fire resistance tests – Part 1: General requirements.
EN 1363-2, Fire resistance tests – Part 2: Alternative and additional procedures.
EN 1634-1, Fire resistance tests for door and shutter assemblies – Part 1: Fire doors and shutters.
EN ISO 5167-1, Measurement of fluid flow by means of pressure differential devices inserted in circular cross-
section conduits running full – Part 1: General principles and requirements (ISO 5167-1:2003)
ISO 5221, Air distribution and air diffusion – Rules to methods of measuring air flow rates in an air handling duct.
ISO 9705, Fire tests – Full scale room test for surface products.
3 Terms and definitions
For the purposes of this European Standard, the terms and definitions given in EN 1070:1998 and in EN 1363-
1:1999 apply.
Additional definitions specifically needed for this document are added below:
3.1
lift landing door
door designed to be installed in the lift well opening on a landing to provide access to the lift
3.2
thermally uninsulated lift landing door
lift landing door which is not intended to satisfy the insulation criteria of EN 1363-1 and 15.2 of this standard.
NOTE Most lift landing doors fall in this category
6
---------------------- Page: 7 ----------------------
EN 81-58:2003 (E)
3.3
thermally insulated lift landing door
lift landing door which is intended to satisfy the insulation criteria of EN 1363-1 and 15.2 of this standard
3.4
door opening
width of the clear opening allowing free passage through the open lift landing door
3.5
door assembly
complete assembly, including any frame or guide, door leaf or leaves, which is provided for access to and from the
lift and the landing. It includes all panels, hardware, sealing materials and any operating components
3.6
supporting construction
construction provided in the opening of the test frame or the furnace front in order to accommodate the test
specimen
3.7
leakage rate
total flow rate of hot gases passing through openings and gaps of the door assembly, due to overpressure on the
landing side
4 Test principle
4.1 EN 1634-1 contains a procedure for the determination of fire resistance of doors which may be exposed to a
fire in a building from either side and are required to prevent the transfer of fire from one side to the other. Lift
landing doors represent a special use of doors where the fire exposure is expected to be from a specified direction,
i.e. the landing side, and where the hazard exists only subsequent to the entry of a fire into the lift well. Such a door
is generally not designed to possess the same resistance to the passage of hot gases as a door separating
adjacent spaces on the same floor.
4.2 The test consists of exposing the landing side of a lift landing door to the heating conditions specified in
EN 1363-1 for the period for which the door has to be assessed for its fire resistance. During the test, positive
pressure exists over the whole height of the door on the exposed side, inducing the leakage of furnace gases to the
unheated side. A canopy is provided on the unexposed side which collects the leaked gases and a suction fan
draws these through a duct provided with a system for measuring the volume flow (see annex A). The
concentration of CO , used as a tracer gas, is measured in the furnace and at the airflow measuring point, and by
2
monitoring the gas flow rate and its temperature it is possible to calculate the leakage rate of hot gases through the
test door. The method gives a record of the hot gas leakage as a function of time which is corrected for normal
conditions. This provides a basis for assessing the ability of the door to act as an effective fire barrier.
5 Test equipment
5.1 The test furnace shall be as described in EN 1363-1.
5.2 The canopy shall be as specified in annex A.
5.3 The measuring system for leakage rate shall be as specified in annex A.
6 Test conditions
6.1 The furnace shall be controlled to follow the temperature/time curve as specified in EN 1363-1.
6.2 The furnace shall maintain positive pressure on the exposed side over the whole height of the specimen
such that the pressure at sill level is in the range of (2 ± 2) Pa.
NOTE It is found that the pressure gradient over the height of the specimen is around 8,5 pascals per meter height.
7
---------------------- Page: 8 ----------------------
EN 81-58:2003 (E)
7 Test specimen
7.1 Construction
The test specimen shall be fully representative of the door assembly on which information is required.
7.2 Number of specimens
As information is required when the door is exposed to heating from the landing side only, one specimen is tested.
A second specimen may be required according to 10.2 to verify the door construction.
7.3 Size of specimen
The specimen shall be full size or the maximum size that can be accommodated in the furnace. The typical size of
the front opening of the furnace is 3 m · 3 m. In order to expose a required minimum width of 200 mm of supporting
construction for a typical 3 m · 3 m furnace, the opening in the supporting construction is restricted to 2,6 m · 2,8
m (width x height).
7.4 Installation of specimen
The specimen shall be mounted in a supporting construction having adequate fire resistance. The supporting
construction shall be built first within the test frame leaving an aperture of the specified size. The width of the
supporting construction on the two vertical sides and the top shall be not less than 200 mm.
The design of the connection between the door and the supporting construction, including any materials used to
make the junction, shall be as used in practice with the type of the supporting construction. The position of the door
assembly in relation to the supporting construction shall be as in practice.
The clearances shall correspond to the maximum that is permissible by EN 81-1 and EN 81-2 when the lift landing
doors are put into service, unless designed for another maximum gap size, which shall then apply.
8 Supporting construction
In view of the field of direct application of test results, the lift landing doors shall be erected in the standard
supporting construction as described in annex B.
NOTE In special cases the supporting construction may be of a type with which the door is intended to be used in practice.
In such cases the field of application of the test results is restricted to that construction.
9 Conditioning
9.1 The test specimen as well as the supporting construction and any sealing materials used, shall be
conditioned in accordance with the requirements of EN 1363-1 and EN 1634-1. No special conditioning procedures
are required where the specimen is constructed primarily from non-hygroscopic materials. Full conditioning of the
supporting construction may not be required if it is known that there will be no effect on the behaviour of the
specimen or the fixing system.
9.2 Samples of materials used in the test door shall be supplied to determine moisture content when necessary.
10 Pre-test examination
10.1 General
Before the test, it shall be verified that the constructional details and clearance gap measurements and depth of
penetration conform to the production and assembly drawings for the door system. It shall also be verified that the
test specimen is operational.
8
---------------------- Page: 9 ----------------------
EN 81-58:2003 (E)
10.2 Constructional details
A full detailed specification of the test specimen shall be provided by the test sponsor prior to its installation at the
laboratory. This specification shall be to a level of detail sufficient to allow the laboratory to conduct a detailed
examination of the specimen before the test and to agree the accuracy of the information supplied. The verification
of the test specimen shall be carried out in accordance with the guidance given in EN 1363-1.
When the method of construction precludes a detailed survey of the specimen, without having to permanently
damage it or if it is considered that it will subsequently be impossible to evaluate construction details from post test
examination, then one of two options shall be exercised by the laboratory, either:
a) the laboratory shall request to oversee the manufacturing of the door or shutter assembly(ies) which is to be
the subject of the test; or
b) the sponsor shall be requested to supply an additional assembly or part of the assembly (e.g. a door leaf) to
the number required for test. The laboratory shall then choose freely which of these shall be submitted to the
test and which shall be used to verify the construction.
10.3 Clearance gap measurements and depth of penetration
The clearances between the moving components and the fixed parts of the door assembly shall be measured prior
to the test. Sufficient measurements shall be made to adequately describe the nature of the gaps and there shall
be a minimum of three measurements along each side or edge. The gap sizes shall be described to an accuracy of
± 0,5 mm. Figure 1 to Figure 4 show different types of lift landing doors and indicate the gaps (g) which need to be
recorded. The depth of penetration and safety guides (if any) shall be measured and recorded.
9
---------------------- Page: 10 ----------------------
EN 81-58:2003 (E)
Key
g Gap measurement location H Clear height
d Deformation measurement location W Clear width
Figure 1 — Clearance gaps (g) and deformation measurements (d) – Single panel swing door
10
---------------------- Page: 11 ----------------------
EN 81-58:2003 (E)
Key
g Gap measurement location H Clear height
d Deformation measurement location W Clear width
Figure 2 — Clearance gaps (g) and deformation measurements (d) – Double leaf telescopic door
11
---------------------- Page: 12 ----------------------
EN 81-58:2003 (E)
Key
g Gap measurement location H Clear height
d Deformation measurement location W Clear width
Figure 3 — Clearance gaps (g) and deformation measurements (d) – Central opening door
12
---------------------- Page: 13 ----------------------
EN 81-58:2003 (E)
Key
g Gap measurement location H Clear height
d Deformation measurement location W Clear width
Figure 4 — Clearance gaps (g) and deformation measurements (d) – Multi sliding door
10.4 Functionality test
Prior to the test, the door shall be checked for functionality by opening and closing to the maximum possible, with a
minimum opening of width 150 mm.
13
---------------------- Page: 14 ----------------------
EN 81-58:2003 (E)
11 Test instrumentation
11.1 Furnace thermocouples
The nature, number and the location of furnace thermocouples shall be in agreement with the specification given in
EN 1634-1 for tests on doors.
11.2 Furnace CO concentration
2
There shall be provision for continuous monitoring of CO concentration in the furnace during the test. The
2
instrument shall have a range of 0 % to 20 % CO concentration and the calibration shall be established prior to the
2
test by using a sample of known concentration. The accuracy of measurement for CO , i.e. the instruments and the
2
measurement system shall be within ± 0,5 % CO .
2
11.3 Gas flow measuring system instrumentation
One or more thermocouples shall be provided close to the gas flow measuring system, within a distance of
100 mm, to measure the temperature of the exhaust gases drawn from the canopy.
Gas sample shall be drawn from the vicinity of the measuring system to monitor continuously the CO
2
concentration. The instrument is expected to have a range of 0 % to 2,5 % and the accuracy of measurement shall
be within 0,05 % CO , it shall be checked prior to the test by using a sample of known concentration of CO in the
2 2
range of 1 % to 2,5 %.
Provision shall be made at the gas flow measuring system to monitor the pressure differential of the flow measuring
device and the absolute pressure in relation to the ambient conditions. The range of the instrument shall be
compatible with the flow rate generated by the suction fan.
The accuracy of determination of leakage rate shall be within 10 %.
11.4 Furnace pressure
Furnace pressure shall be measured continuously at a minimum of two locations over the height of the furnace to
ensure that the pressure conforms to the specification in 6.2.
11.5 Unexposed face temperature
11.5.1 General
This clause specifies additional details for testing insulating capacity of lift landing doors designed for installation
within openings incorporated in vertical lift shafts.
Where compliance with the insulation criteria is required to be evaluated, thermocouples of the type specified in
EN 1363-1 shall be attached to the unexposed face as indicated below for the purpose of obtaining the average
and maximum surface temperatures. General principles for the attachment of thermocouples given in EN 1363-1
shall apply.
NOTE Where no evaluation against the insulation criteria is required of the door, or any part thereof, no temperature
measurements are required.
11.5.2 Position of the thermocouples to determine the average temperature
11.5.2.1 Door leaf (leaves)
Position five thermocouples per door leaf, one as close as possible to the centre of the door leaf (leaves) and one
as close as possible to the centre of each quarter section. These shall not be located closer than 100 mm to any
joint, stiffener or through component, nor closer than 100 mm to the edge of the leaf (leaves).
14
---------------------- Page: 15 ----------------------
EN 81-58:2003 (E)
The number of thermocouples on the door leaves may be restricted to 12, evenly distributed over all door leaves .
In the event the door leaf (leaves) are of small size (i.e. less than 400 mm wide) such that the conventional five
thermocouples cannot be fixed and/or the 100 mm minimum cannot be respected or the number of thermocouples
is exceeding the maximum, then a limited number of thermocouples will be evenly distributed on the centre and
diagonals of the clear entrance surface of the door.
2
When the total area of a single part of the door assembly is equal or smaller than 0,2 m , it shall be disregarded for
the purpose of ascertaining the mean unexposed face temperature.
11.5.2.2 Door frame
The door frame of lift landing doors can include the following parts; the horizontal top member which may include
the door mechanism (on sliding and folding doors), two vertical members and an over panel. No thermocouples
shall be placed on the horizontal top member including the door mechanism.
The side panels and over panels of more than 300 mm width or height shall be provided with one thermocouple for
each square meter or part thereof, subject to a minimum of two thermocouples.
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.