SIST EN 14313:2010
Thermal insulation products for building equipment and industrial installations - Factory made polyethylene foam (PEF) products - Specification
Thermal insulation products for building equipment and industrial installations - Factory made polyethylene foam (PEF) products - Specification
This European Standard specifies the requirements for factory made flexible polyethylene foam products which are used for the thermal insulation of building equipment and industrial installations with an operating temperature in the range of approximately - 80 °C to + 150 °C. The products are manufactured in the form of tubes, profiles, sheets, rolls and tapes with or without coating and/or self-adhesive backing and/or different closure systems. This standard describes product characteristics and includes procedures for testing, evaluation of conformity, marking and labelling. Products covered by this standard are also used in prefabricated thermal insulation systems and composite panels; the performance of systems incorporating these products is not covered. This standard does not specify the required level of a given property that shall be achieved by a product to demonstrate fitness for purpose in a particular application. The levels required for a given application can be found in regulations and invitations to tender. Products with a declared thermal conductivity greater than 0,050 W/(m•K) at 10 °C are not covered by this standard. This standard does not cover products for the insulation of the building structure. The normative part of this standard does not cover compressive stress (see Annex C, C.4).
Wärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie - Werkmäßig hergestellte Produkte aus Polyethylenschaum (PEF) - Spezifikation
Dieses Dokument legt die Anforderungen für werkmäßig hergestellte Produkte aus flexiblem Polyethylenschaum fest, die als Wärmedämmstoffe für die Haustechnik und betriebstechnische Anlagen im Temperaturbereich von etwa 80 °C bis + 150 °C benutzt werden.
ANMERKUNG 1 Spannung im Dämmprodukt sollte bei der Anwendung von PEF vermieden werden. Dies ist vor allem für die Anwendung von PEF auf Objekten mit Betriebstemperaturen von - 50 °C bis - 80 °C von Bedeutung. Die Spannung sollte auf ein Mindestmaß beschränkt bleiben, indem der Schaum "unter Druck" angewandt wird, d. h. indem die Teile großzügig zugeschnitten werden. In jedem Fall sollten die Empfehlungen des Herstellers beachtet werden.
Die Produkte werden in der Form von Schläuchen, Profilen, Platten, Rollen und Bändern mit oder ohne Beschichtung und/oder selbstklebende Trägerschicht und/oder verschiedene Verschlusssysteme hergestellt.
Dieses Dokument beschreibt die Stoffeigenschaften und enthält die Prüfverfahren und Festlegungen für die Konformitätsbewertung, die Kennzeichnung und die Etikettierung.
In diesem Dokument beschriebene Produkte werden auch in vorgefertigten Wärmedämmsystemen und Mehrschicht-Verbundplatten angewendet; die Eigenschaften von Systemen, in die diese Produkte integriert sind, werden nicht behandelt.
Dieses Dokument legt keine Leistungsstufen für eine vorgegebene Eigenschaft fest, die ein Produkt erreichen muss, um für einen bestimmten Anwendungsfall tauglich zu sein. Für bestimmte Anwendungen benötigte Anforderungen können Regelwerken oder übereinstimmenden Normen entnommen werden.
Dieses Dokument gilt nicht für Produkte, deren Nennwert der Wärmeleitfähigkeit größer ist als 0,050 W/(m×K) bei 10 °C.
Dieses Dokument gilt nicht für Produkte, die zur Dämmung von Gebäudehüllen bestimmt sind.
Unter üblichen Bedingungen unterliegen Produkte aus Polyethylenschaum keiner Druckspannung (siehe D.2). Deshalb wird diese Eigenschaft nicht im normativen Teil dieser Norm behandelt.
Produits isolants thermiques pour l'équipement du bâtiment et les installations industrielles - Produits manufacturés en mousse de polyéthylene (PEF) - Spécification
La présente Norme européenne spécifie les exigences relatives aux produits manufacturés en mousse de polyéthylène souple, utilisés pour l’isolation thermique de l’équipement du bâtiment et des installations industrielles, dont la température de service est approximativement comprise entre - 80 °C et + 150 °C.
NOTE 1 Il convient d’éviter toute contrainte de traction sur le produit isolant lors de l’application de PEF. Ceci est encore plus important lors de l’application de PEF sur des conduits dont la température de fonctionnement est comprise entre - 50 °C et - 80 °C. Il est recommandé de réduire au minimum la contrainte de traction en appliquant la mousse « sous pression », c’est-à-dire en découpant les pièces à une taille légèrement supérieure. Il convient de se référer systématiquement aux conseils du fabricant.
Les produits sont manufacturés sous la forme de tubes, de profilés, de feuilles, de rouleaux et de rubans, avec ou sans enduit de finition et/ou envers autocollant et/ou différents systèmes de fermeture.
La présente norme décrit les caractéristiques des produits et comporte des modes opératoires d’essai, d’évaluation de conformité, de marquage et d’étiquetage.
Les produits couverts par la présente norme sont également utilisés dans les systèmes d’isolation thermique préfabriqués et les panneaux composites ; les performances des systèmes incorporant ces produits ne sont pas traitées.
La présente norme ne spécifie pas le niveau requis pour une propriété donnée que doit posséder un produit pour démontrer son aptitude à une application particulière. Les niveaux requis pour une application donnée peuvent être trouvés dans les réglementations et les appels d’offre.
Les produits dont la conductivité thermique déclarée est supérieure à 0,050 W/(m K) à 10 °C ne sont pas couverts par la présente norme.
La présente norme ne couvre pas les produits destinés à être utilisés pour l’isolation de la structure des bâtiments.
[...]
Toplotnoizolacijski proizvodi za opremo stavb in industrijske inštalacije - Proizvodi iz polietilenske pene (PEF) - Specifikacija
Ta evropski standard določa zahteve za proizvode iz polietilenske pene, ki se uporabljajo za toplotno izolacijo za opremo stavb in industrijske inštalacije z delovnim temperaturnim razponom med približno -80°C in + 150°C. Proizvodi so narejeni v obliki cevi, profilov, listov, zvitkov in trakov s prevleko in/ali samolepilno podlago in/ali različnimi zapornimi sistemi ali brez njih. Ta standard opisuje značilnosti proizvodov in vključuje postopke preskušanja, vrednotenja skladnosti, označevanja in uporabe nalepk. Proizvodi, ki jih zajema ta standard, se uporabljajo pri montažnih termoizolacijskih sistemih in vezanih ploščah; zmogljivost sistemov, ki vključujejo te proizvode, ni zajeta. Ta standard ne določa zahtevane ravni določene lastnosti, ki jo mora doseči proizvod, da ustreza zahtevam za uporabnosti pri določenem načinu uporabe. Zahtevane ravni za določen način uporabe so navedene v pravilih in javnih razpisih. Ta standard ne zajema proizvodov z nazivno toplotno prevodnostjo nad 0,050 W/(m•K) pri 10°C. Ta standard ne zajema proizvodov za izolacijo gradbenih konstrukcij. Normativni del tega standarda ne zajema tlačne obremenitve (glej Dodatek C, C.4).
General Information
Relations
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Toplotnoizolacijski proizvodi za opremo stavb in industrijske inštalacije - Proizvodi iz polietilenske pene (PEF) - SpecifikacijaWärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie - Werkmäßig hergestellte Produkte aus Polyethylenschaum (PEF) - SpezifikationProduits isolants thermiques pour l'équipement du bâtiment et les installations industrielles - Produits manufacturés en mousse de polyéthylene (PEF) - SpécificationThermal insulation products for building equipment and industrial installations - Factory made polyethylene foam (PEF) products - Specification91.100.60Thermal and sound insulating materialsICS:Ta slovenski standard je istoveten z:EN 14313:2009SIST EN 14313:2010en,fr,de01-april-2010SIST EN 14313:2010SLOVENSKI
STANDARD
SIST EN 14313:2010
EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 14313
November 2009 ICS 91.100.60 English Version
Thermal insulation products for building equipment and industrial installations - Factory made polyethylene foam (PEF) products -Specification
Produits isolants thermiques pour l'équipement du bâtiment et les installations industrielles - Produits manufacturés en mousse de polyéthylène (PEF) - Spécification
Wärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie - Werkmäßig hergestellte Produkte aus Polyethylenschaum (PEF) - Spezifikation This European Standard was approved by CEN on 29 September 2009.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2009 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 14313:2009: ESIST EN 14313:2010
EN 14313:2009 (E) 2 Contents Page Foreword .31Scope .52Normative references .53Terms, definitions, symbols, units and abbreviated terms .74Requirements .95Test methods . 156Designation code . 197Evaluation of conformity . 198Marking and labelling . 20Annex A (normative)
Factory production control . 21Annex B (normative)
Determination of minimum service temperature . 23Annex C (informative)
Additional properties . 26Annex ZA (informative)
Clauses of this European Standard addressing the provisions of the EU Construction Products Directive. 28Bibliography . 36Figures Figure ZA.1 — Example of CE marking information . 35Tables Table 1 — Dimensional tolerances (length, width, thickness, squareness) . 11Table 2 — Dimensional tolerances (inside diameter) . 11Table 3 — Levels for water absorption . 13Table 4 — Test methods, test specimens and conditions. 16Table A.1 — Minimum product testing frequencies . 21Table A.2 — Minimum product testing frequencies for the reaction to fire characteristics . 22Table C.1 — Test methods, test specimens and conditions . 27Table ZA.1 — Relevant clauses . 29Table ZA.2 — System(s) of attestation of conformity . 30Table ZA.3 — Assignment of evaluation of conformity tasks for products under system 1 . 31Table ZA.4 — Assignment of evaluation of conformity tasks for products under system 3 or system 3 combined with system 4 for reaction to fire . 32 SIST EN 14313:2010
EN 14313:2009 (E) 3 Foreword This European Standard (EN 14313:2009) has been prepared by Technical Committee CEN/TC 88 “Thermal insulating materials and products”, the secretariat of which is held by DIN. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by May 2010, and conflicting national standards shall be withdrawn at the latest by August 2011. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive 89/106/EEC. For relationship with EU Directive 89/106/EEC, see informative Annex ZA, which is an integral part of this document. Locally responsible authorities and contracting entities, who are bound by EU Directives to specify their re-quirements using European harmonized product standards, are allowed to demand additional properties out-side the provisions of this standard if this is technically necessary because of prevailing operational conditions of the building equipment or the industrial installation projected or because of safety regulations. This European Standard contains four annexes: Annex A (normative), Factory production control Annex B (normative), Determination of minimum service temperature Annex C (informative), Additional properties Annex ZA (informative), Clauses of this European Standard addressing the provisions of the EU Con-struction Products Directive This document includes a bibliography. This European Standard is one of a series of standards for insulation products used in building equipment and industrial installations, but this standard can be used in other areas, where appropriate. In pursuance of Resolution BT 20/1993 revised, CEN/TC 88 have proposed defining the standards listed be-low as a European package of standards, setting 21 months after availability as the date of withdrawal (dow) of national standards which conflict with the European Standards of this package. The package of standards comprises the following group of interrelated standards for the specifications of fac-tory made thermal insulation products, all of which come within the scope of CEN/TC 88: EN 14303, Thermal insulation products for building equipment and industrial installations — Factory made mineral wool (MW) products — Specification EN 14304, Thermal insulation products for building equipment and industrial installations — Factory made flexible elastomeric foam (FEF) products — Specification EN 14305, Thermal insulation products for building equipment and industrial installations — Factory made cellular glass (CG) products — Specification SIST EN 14313:2010
EN 14313:2009 (E) 4 EN 14306, Thermal insulation products for building equipment and industrial installations — Factory made calcium silicate (CS) products — Specification EN 14307,Thermal insulation products for building equipment and industrial installations — Factory made ex-truded polystyrene foam (XPS) products — Specification EN 14308, Thermal insulation products for building equipment and industrial installations — Factory made rigid polyurethane foam (PUR) and polyisocyanurate foam (PIR) products — Specification EN 14309, Thermal insulation products for building equipment and industrial installations — Factory made products of expanded polystyrene (EPS)
— Specification EN 14313, Thermal insulation products for building equipment and industrial installations — Factory made polyethylene foam (PEF) products — Specification EN 14314, Thermal insulation products for building equipment and industrial installations — Factory made phenolic foam (PF) products — Specification According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Repub-lic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. SIST EN 14313:2010
EN 14313:2009 (E) 5
1 Scope This European Standard specifies the requirements for factory made flexible polyethylene foam products which are used for the thermal insulation of building equipment and industrial installations with an operating tempera-ture in the range of approximately - 80 °C to + 150 °C. NOTE Tensile stress in the insulation product should be avoided when applying PEF. This is even more important when applying PEF on lines with operating temperatures between - 50 °C and - 80 °C. The tensile stress should be kept at the minimum by applying the foam “under pressure”, i.e. cutting the parts in a generous way. Manufacturer’s advice should be heeded in all cases. The products are manufactured in the form of tubes, profiles, sheets, rolls and tapes with or without coating and/or self-adhesive backing and/or different closure systems. This standard describes product characteristics and includes procedures for testing, evaluation of conformity, marking and labelling. Products covered by this standard are also used in prefabricated thermal insulation systems and composite panels; the performance of systems incorporating these products is not covered. This standard does not specify the required level of a given property that shall be achieved by a product to demonstrate fitness for purpose in a particular application. The levels required for a given application can be found in regulations and invitations to tender. Products with a declared thermal conductivity greater than 0,050 W/(m·K) at 10 °C are not covered by this standard. This standard does not cover products for the insulation of the building structure. The normative part of this standard does not cover compressive stress (see Annex C, C.4). 2 Normative references The following referenced documents are indispensable for the application of this document. For dated refer-ences, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 822, Thermal insulating products for building applications — Determination of length and width EN 823, Thermal insulating products for building applications — Determination of thickness EN 824, Thermal insulating products for building applications — Determination of squareness EN 1604, Thermal insulating products for building applications — Determination of dimensional stability under specified temperature and humidity conditions EN 1609, Thermal insulating products for building applications — Determination of short term water absorp-tion by partial immersion EN 12085, Thermal insulating products for building applications — Determination of linear dimensions of test specimens EN 12086, Thermal insulating products for building applications — Determination of water vapour transmis-sion properties SIST EN 14313:2010
EN 14313:2009 (E) 6 EN 12667, Thermal performance of building materials and products — Determination of thermal resistance by means of guarded hot plate and heat flow meter methods — Products of high and medium thermal resistance EN 12939, Thermal performance of building materials and products — Determination of thermal resistance by means of guarded hot plate and heat flow meter methods — Thick products of high and medium thermal re-sistance EN 13172, Thermal insulating products — Evaluation of conformity EN 13467, Thermal insulating products for building equipment and industrial installations — Determination of dimensions, squareness and linearity of preformed pipe insulation EN 13468, Thermal insulating products for building equipment and industrial installations — Determination of trace quantities of water soluble chloride, fluoride, silicate, sodium ions and pH EN 13469, Thermal insulating products for building equipment and industrial installations — Determination of water vapour transmission properties of preformed pipe insulation EN 13472, Thermal insulating products for building equipment and industrial installations — Determination of short term water absorption by partial immersion of preformed pipe insulation EN 13501-1:2007, Fire classification of construction products and building elements — Part 1: Classification using data from reaction to fire tests EN
13823, Reaction to fire tests for building products — Building products excluding floorings exposed to the thermal attack by a single burning item EN 14366:2004, Laboratory measurement of noise from waste water installations EN 14706, Thermal insulating products for building equipment and industrial installations — Determination of maximum service temperature EN 14707, Thermal insulating products for building equipment and industrial installations — Determination of maximum service temperature for preformed pipe insulation EN 15715:2009, Thermal insulation products — Instructions for mounting and fixing for reaction to fire testing — Factory made products EN ISO 354, Acoustics — Measurement of sound absorption in a reverberation room (ISO 354:2003) EN ISO 3822-1, Acoustics — Laboratory tests on noise emission from appliances and equipment used in wa-ter supply installations — Part 1: Method of measurement (ISO 3822-1:1999) EN ISO 4589-1, Plastics — Determination of burning behaviour by oxygen index — Part 1: Guidance
(ISO 4589-1:1996) EN ISO 8497, Thermal insulation — Determination of steady-state thermal transmission properties of thermal insulation for circular pipes (ISO 8497:1994) EN ISO 11654, Acoustics — Sound absorbers for use in buildings — Rating of sound absorption
(ISO 11654:1997) EN ISO 11925-2, Reaction to fire tests — Ignitability of building products subjected to direct impingement of flame — Part 2: Single-flame source test (ISO 11925-2:2002) EN ISO 13787, Thermal insulation products for building equipment and industrial installations — Determina-tion of declared thermal conductivity (ISO 13787:2003) SIST EN 14313:2010
EN 14313:2009 (E) 7 3 Terms, definitions, symbols, units and abbreviated terms 3.1 Terms and definitions For the purposes of this document, the following terms and definitions apply. 3.1.1 Terms and definitions as given in EN ISO 9229:2007 3.1.1.1 polyethylene foam semi-rigid or flexible cellular plastics insulation material based on polymers derived mainly from ethylene and/or propylene 3.1.1.2 tube (insulation) product for application on cylindrical objects 3.1.1.3 roll (insulation) product supplied in the form of a wound cylinder 3.1.1.4 pipe insulation insulation product designed to fit around pipes 3.1.1.5 thermal insulation process of reducing heat transfer through a system, or to describe a product, component or system which per-forms that function 3.1.1.6 test specimen single item within a sample or part of an item used for a test 3.1.1.7 Initial Type Test ITT test(s) performed on a product prior to commencing normal production to prove that the product is capable of conforming to the relevant requirements of a standard 3.1.1.8 building equipment system incorporated in a permanent manner in construction works forming part of the heating, cooling and ventilation installation of those works 3.1.1.9 industrial installation plant and associated vessels, pipes, ducts etc. used by industry to manufacture or store a product or to trans-fer a fluid 3.1.2 Additional terms and definitions 3.1.2.1 profile product for application on cylindrical and other objects shaped for special insulation SIST EN 14313:2010
EN 14313:2009 (E) 8 3.1.2.2 sheet flexible insulation product of rectangular shape with or without facing or adhesive backing 3.1.2.3 tape thin, narrow strip of insulation material with or without adhesive backing supplied in rolls 3.1.2.4 form pieces prefabricated elbows, T-pieces or else formed from tubes, sheets or rolls, etc. 3.1.2.5 level given value which is the upper or lower limit of a requirement
NOTE The level is given by the declared value of the characteristic concerned. 3.1.2.6 class combination of two levels of the same property between which the performance shall fall 3.1.2.7 production line assemblage of equipment that produces products using a continuous process 3.1.2.8 production unit assemblage of equipment that produces products using a discontinuous process 3.2 Symbols, units and abbreviated terms 3.2.1 Symbols and units used in this standard αp is the practical sound absorption coefficient
— αw is the weighted sound absorption coefficient
— b is the width
mm Di is the inside diameter
mm Di, D is the declared inside diameter of a tube or profile
mm d is the thickness
mm dD is the declared thickness of the product
mm ∆εb is the relative change in width
% ∆εd is the relative change in thickness
% ∆εl is the relative change in length
% l is the length
m or mm Lsc,A is the single number descriptor of structure-borne sound dB (A) SIST EN 14313:2010
EN 14313:2009 (E) 9 λ is the thermal conductivity
W/(m·K) λD is the declared thermal conductivity
W/(m·K) µ is the water vapour diffusion resistance factor
— v is the deviation from squareness for tubes and profiles
mm Q is the waste water volume flow
l/s Sb is the deviation from squareness for sheets and rolls on length and width
mm/m Wp is the short term water absorption
kg/m2 AW is the symbol of the declared level of weighted sound absorption coefficient CL is the symbol of the declared level of soluble chloride ions DS(TH) is the symbol of the declared value for dimensional stability under specified temperature and relative humidity conditions F is the symbol of the declared level of soluble fluoride ions MU is the symbol of the declared level for water vapour diffusion resistance factor NA is the symbol of the declared level of soluble sodium ions pH is the symbol of the declared level of the pH -value SI is the symbol of the declared level of soluble silicate ions ST(+) is the symbol of the declared level for maximum service temperature ST(–) is the symbol of the declared level for minimum service temperature SW is the symbol of the single number descriptor of structure-borne sound WS is the symbol of the declared level for short-term water absorption 3.2.2 Abbreviated terms used in this standard PEF is PolyEthylene Foam ITT is Initial Type Test ML is Manufacturer's Literature FPC is Factory Production Control 4 Requirements 4.1 General Product properties shall be assessed in accordance with Clause 5. To comply with this standard, products shall meet the requirements of 4.2, and the requirements of 4.3 as appropriate. SIST EN 14313:2010
EN 14313:2009 (E) 10 NOTE Information on additional properties is given in Annex C. One test result for a product property is the average of the measured values on the numbers of test speci-mens given in Table 4. 4.2 For all applications 4.2.1 Thermal conductivity For flat specimens, thermal conductivity shall be based upon measurements carried out in accordance with EN 12667 or EN 12939 for thick products. For cylindrical specimens EN ISO 8497 shall be used as specified in 5.3.2.
In both cases, the thermal conductivity values shall be determined by the manufacturer and verified in accor-dance with EN ISO 13787. They shall be declared by the manufacturer according to measurement standards above covering the product service temperature range. The following conditions apply: the hot side temperature of the measuring device shall not exceed the maximum service temperature; the measured value shall be expressed with three significant figures; the declared thermal conductivity curve shall be given as a limit curve, defined in EN ISO 13787; the values of the declared thermal conductivity, λD, shall be rounded upwards to the nearest 0,001 W/(m·K). The declared equation/limit curve is the "declared reference" with three significant figures, that is to 0,000 1 W/(m·K) for
values below 0,1 W/(m·K) and in 0,001 W/(m·K) for
values above 0,1 W/(m·K). This shall be used as a reference for the verification of the declaration. When thermal conductivity is declared as table derived from the equation, rounding upwards to the next 0,001 W/(m·K) has to be done for the full range of the thermal conductivity. NOTE Determination of the declared thermal conductivity of pipe sections, following EN ISO 8497 having joints in the metering area, include joints as defined in EN ISO 23993. 4.2.2 Dimensions and tolerances 4.2.2.1 Linear dimensions The length, l, width, b, and thickness, d, of sheets, rolls and tapes shall be determined in accordance with EN 822 and EN 823. The length, l, thickness, d, and inside diameter, Di, of tubes shall be determined in ac-cordance with EN 13467. The dimensions of profiles and form pieces shall be measured analogously. No test result shall deviate from the declared values by more than the tolerances given in Table 1 and Table 2. 4.2.2.2 Squareness Deviations from squareness, Sb, of sheets and rolls shall be determined in accordance with EN 824. Devia-tions from squareness, v, of tubes and profiles shall be determined in accordance with EN 13467. No test re-sult shall exceed the corresponding tolerances given in Table 1.
SIST EN 14313:2010
EN 14313:2009 (E) 11
Table 1 — Dimensional tolerances (length, width, thickness, squareness) Form
of delivery Length Width Thickness a mm Squareness Declared Tolerance Tubes Profiles - 1,5 %; +2,5 % — dD ≤ 6 ± 1,0 5,0 mm for Di, D ≤ 60 mm and 10,0 mm for 60 < Di, D ≤ 120 mm
6 < dD ≤ 10 ± 1,5
10 < dD ≤ 15 ± 2,0
15 < dD ≤ 30 ± 2,5
dD > 30 ± 4,0 Sheets Rolls ± 1,5 % ± 1,0 % dD ≤ 5 ± 1,0
10 mm/m (length + width) 2,0 mm (thickness)
5 < dD ≤ 10 ± 1,5
10 < dD ≤ 15 ± 2,0
15 < dD ≤ 30 ± 2,5
dD > 30 ± 3,5 Tapes ± 1,5 % ± 2,0 mm
± 0,5 — a For profiles tolerances are defined only for the section of the profile that is designed for reduction of heat flux.
Table 2 — Dimensional tolerances (inside diameter)
Dimensions in millimetres Form
of delivery Inside diameter Di, D ≤ 35 35 < Di, D ≤ 100 Di, D > 100 Tubes Di, D +1 to +4 Di, D +2 to +6 Di, D +3 to +8 Profiles Di, D +1 to +4 Di, D +2 to +6 Di, D +3 to +8
4.2.3 Dimensional stability Dimensional stability under specified temperature and humidity conditions shall be determined in accordance with EN 1604. The test shall be carried out after storage for 48 h exposure at (23 ± 2) °C and (90 ± 5) % rela-tive humidity. The relative reduction in thickness, ∆εd, shall not exceed 3,0 %. The relative changes in length, ∆εl, and width, ∆εb, shall not exceed 2,0 %. This test shall not be performed when the more severe test, described in 4.3.2, is used. 4.2.4 Reaction to fire of the product as placed on the market Reaction to fire classification of the product, as placed on the market, shall be determined in accordance with EN 13501-1 and the basic Mounting and Fixing rules given in EN 15715. NOTE This classification is compulsory and always included in the CE Marking label.
SIST EN 14313:2010
EN 14313:2009 (E) 12 EN 13501-1:2007, Table 1, is applicable to products applied to flat surfaces or to curved surfaces with a di-ameter greater than 300 mm. If a flat product which has a classification according to EN 13501-1 is used in a linear application it does not require further classification. EN 13501-1:2007, Table 3, is applicable for products applied on linear objects or with a diameter below or equal 300 mm. Detailed information about the test conditions and the field of application of the classification as stated in the reaction to fire classification report shall be given in the manufacturers literature. 4.2.5 Durability characteristics 4.2.5.1 General The appropriate durability characteristics have been considered and are covered in 4.2.5.2, 4.2.5.3 and 4.2.5.4. 4.2.5.2 Durability of reaction to fire against ageing/degradation and high temperature The reaction to fire performance of PEF products does not change with time or when subjected to the de-clared maximum service temperature. 4.2.5.3 Durability of thermal resistance against ageing/degradation The thermal conductivity of PEF products does not change with time. This is covered by 4.2.1 thermal conduc-tivity, 4.2.2 dimensions and tolerances and 4.2.3 dimensional stability or 4.3.2 maximum service temperature (dimensional stability). 4.2.5.4 Durability of thermal resistance against high temperature The thermal conductivity of PEF products does not change with time when subjected to the declared maxi-mum service temperature. This is covered by 4.3.2 maximum service temperature (dimensional stability). 4.3 For specific applications 4.3.1 General If there is no requirement for a property described in 4.3 for a product in use, then that property does not need to be determined and declared by the manufacturer. 4.3.2 Maximum service temperature The maximum service temperature, ST(+), shall be determined in accordance with EN 14706 for flat specimens and EN 14707 for cylindrical specimens. At the maximum service temperature, ST(+), the mean value of relative change in thickness (reduction), ∆εd, shall not exceed 7 %. The maximum service temperature, ST(+), shall be declared below 100 °C in steps of not less than 5 °C and above 100 °C in steps of not less than 10 °C. SIST EN 14313:2010
EN 14313:2009 (E) 13 4.3.3 Minimum service temperature The manufacturer of an insulation material can choose which minimum service temperature he intends to de-clare for his product. This minimum service temperature does not represent any specific physical property and cannot be deter-mined by any single standardized test method.
If a minimum service temperature is declared by the manufacturer the following physical properties in line with European test standards have to be declared at the declared minimum service temperature:
a) Thermal conductivity as a function of temperature;
b) Coefficient of thermal expansion as a function of temperature (see Annex B); c) Tensile strength and/or compressive strength and Young's modulus as a function of temperature as agreed between the parties.
In addition, other physical properties may be agreed upon by the concerned parties.
Using these temperature dependent physical data, the suitability of any specific insulation can be estimated at a given low operational temperature for industrial installations in relation to application related design features.
A low operational temperature cannot be below the minimum service temperature. The minimum service temperature, ST(–), shall be declared in levels with steps of 10 °C. Minimum service temperature within the scope of this standard but above 0 °C need not be tested. 4.3.4 Water absorption Short-term water absorption by partial immersion, Wp, shall be determined in accordance with EN 1609 for flat products or EN 13472 for tubes (method B = drainage). Tests shall be run with specimens of ≥ 15 mm thick-ness from one sample each being representa
...