Uninterruptible power systems (UPS) -- Part 1-1: General and safety requirements for UPS used in operator access areas

applies to electronic uninterruptible power systems (UPS) with an electrical energy storage device in the d.c. link. It is to be used with EN 60950-1 which is referred to in this standard as RD.

Unterbrechungsfreie Stromversorgungssysteme (USV) -- Teil 1-1: Allgemeine Anforderungen und Sicherheitsanforderungen an USV außerhalb abgeschlossener Betriebsräume

Alimentations sans interruption (ASI) -- Partie 1-1: Prescriptions générales et règles de sécurité pour les ASI utilisées dans des locaux accessibles aux opérateurs

s'applique aux alimentations sans interruption électroniques (ASI) possédant un dispositif d'accumulation de l'énergie sur la liaison à courant continu. Elle est utilisée conjointement avec la EN 60950-1, qui est référencée RD dans la présente norme.

Uninterruptible power systems (UPS) - Part 1-1: General and safety requirements for UPS used in operator access areas (IEC 62040-1-1:2002 + Corrigendum 2002)

General Information

Status
Withdrawn
Publication Date
31-May-2003
Withdrawal Date
17-Dec-2008
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
05-Dec-2008
Due Date
28-Dec-2008
Completion Date
18-Dec-2008

Relations

Buy Standard

Standard
EN 62040-1-1:2003
English language
49 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI SIST EN 62040-1-1:2003

STANDARD
junij 2003
Uninterruptible power systems (UPS) - Part 1-1: General and safety requirements
for UPS used in operator access areas (IEC 62040-1-1:2002 + Corrigendum 2002)
ICS 29.200 Referenčna številka
SIST EN 62040-1-1:2003(en)
©  Standard je založil in izdal Slovenski inštitut za standardizacijo. Razmnoževanje ali kopiranje celote ali delov tega dokumenta ni dovoljeno

---------------------- Page: 1 ----------------------

EUROPEAN STANDARD EN 62040-1-1
NORME EUROPÉENNE
EUROPÄISCHE NORM January 2003

ICS 29.200 Supersedes EN 50091-1-1:1996


English version


Uninterruptible power systems (UPS)
Part 1-1: General and safety requirements for UPS
used in operator access areas
(IEC 62040-1-1:2002 + corrigendum 2002)


Alimentations sans interruption (ASI) Unterbrechungsfreie
Partie 1-1: Prescriptions générales Stromversorgungssysteme (USV)
et règles de sécurité pour les ASI Teil 1-1: Allgemeine Anforderungen
utilisées dans des locaux und Sicherheitsanforderungen
accessibles aux opérateurs an USV außerhalb abgeschlossener
(CEI 62040-1-1:2002 + corrigendum 2002) Betriebsräume
(IEC 62040-1-1:2002 + Corrigendum 2002)





This European Standard was approved by CENELEC on 2002-11-01. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and
notified to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Czech Republic,
Denmark, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Luxembourg, Malta,
Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels


© 2003 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.

Ref. No. EN 62040-1-1:2003 E

---------------------- Page: 2 ----------------------

EN 62040-1-1:2003 - 2 -
Foreword

The text of document 22H/22/FDIS, future edition 1 of IEC 62040-1-1, prepared by SC 22H,
Uninterruptible power systems (UPS), of IEC TC 22, Power electronic systems and equipment, was
submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as EN 62040-1-1 on
2002-11-01.

This European Standard supersedes EN 50091-1-1:1996.

The following dates were fixed:

– latest date by which the EN has to be implemented
 at national level by publication of an identical
 national standard or by endorsement (dop) 2003-08-01

– latest date by which the national standards conflicting
 with the EN have to be withdrawn (dow) 2005-11-01

Annexes designated "normative" are part of the body of the standard.
Annexes designated "informative" are given for information only.
In this standard, annexes L, M, N and ZA are normative and annexes H and X are informative.
Annex ZA has been added by CENELEC.

In this standard, the following print types are used:
- Requirements proper and normative annexes: in roman type;
- Compliance statements and test specifications: in italic type;
- Notes and other informative matter: in smaller roman type;
- Normative conditions within tables: in smaller roman type;
- Terms that are defined in clause 3: bold.
__________

Endorsement notice

The text of the International Standard IEC 62040-1-1:2002 and its corrigendum December 2002 was
approved by CENELEC as a European Standard without any modification.
__________

---------------------- Page: 3 ----------------------

- 3 - EN 62040-1-1:2003
Annex ZA
(normative)

Normative references to international publications
with their corresponding European publications
This European Standard incorporates by dated or undated reference, provisions from other
publications. These normative references are cited at the appropriate places in the text and the
publications are listed hereafter. For dated references, subsequent amendments to or revisions of any
of these publications apply to this European Standard only when incorporated in it by amendment or
revision. For undated references the latest edition of the publication referred to applies (including
amendments).
NOTE When an international publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.
Publication Year Title EN/HD Year
IEC 60417 Series Graphical symbols for use on EN 60417 Series
equipment

IEC 60529 1989 Degrees of protection provided by EN 60529 1991
enclosures (IP Code) + corr. May 1993

IEC/TR 60755 1983 General requirements for residual - -
A1 1988 current operated protective devices
A2 1992

IEC 60950-1 (mod) 2001 Information technology equipment - EN 60950-1 2001
Safety
Part 1: General requirements

IEC 61000-2-2 2002 Electromagnetic compatibility (EMC) EN 61000-2-2 2002
Part 2-2: Environment - Compatibility
levels for low-frequency conducted
disturbances and signalling in public
low-voltage power supply systems

1)
IEC 61008-1 1996 Residual current operated circuit-- -
breakers without integral overcurrent
protection for household and similar
uses (RCCBs)
Part 1: General rules

2)
IEC 61009-1 1996 Residual current operated circuit-- -
breakers with integral overcurrent
protection for household and similar
uses (RCBO's)
Part 1: General rules


1)
The European Standard EN 61008-1:1994 (IEC 61008-1:1990 + A1:1992, mod.) + corrigendum December 1997 + A2:1995
(IEC/A2:1995) + A11:1995 + A12:1998 + corrigendum April 1998 + A13:1998 + A14:1998 applies.
2)
The European Standard EN 61009-1:1994 (IEC 61009-1:1991, mod.) + corrigendum December 1997 + A1:1995 (IEC/A1:1995)
+ A11:1995 + A2:1998 + A13:1998 + corrigendum April 1998 + A14:1998 + A15:1998 + A17:1998 applies.

---------------------- Page: 4 ----------------------

EN 62040-1-1:2003 - 4 -
Publication Year Title EN/HD Year
IEC 62040-1-2 2002 Uninterruptible power systems (UPS)
+ corr. December 2002 Part 1-2: General and safety EN 62040-1-2 2003
requirements for UPS used in
restricted access locations

IEC 62040-2 1999 Part 2: Electromagnetic compatibility - -
(EMC) requirements

IEC 62040-3 (mod) 1999 Part 3: Method of specifying the EN 62040-3 2001
performance and test requirements

---------------------- Page: 5 ----------------------

NORME CEI
INTERNATIONALE
IEC



62040-1-1
INTERNATIONAL


Première édition
STANDARD

First edition

2002-08


Alimentations sans interruption (ASI) –
Partie 1-1:
Exigences générales et règles de sécurité
pour les ASI utilisées dans des locaux
accessibles aux opérateurs

Uninterruptible power systems (UPS) –
Part 1-1:
General and safety requirements
for UPS used in operator access areas
 IEC 2004 Droits de reproduction réservés  Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni No part of this publication may be reproduced or utilized in any
utilisée sous quelque forme que ce soit et par aucun procédé, form or by any means, electronic or mechanical, including
électronique ou mécanique, y compris la photocopie et les photocopying and microfilm, without permission in writing from
microfilms, sans l'accord écrit de l'éditeur. the publisher.
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch Web: www.iec.ch
CODE PRIX
X
PRICE CODE
Commission Electrotechnique Internationale
International Electrotechnical Commission
МеждународнаяЭлектротехническаяКомиссия
Pour prix, voir catalogue en vigueur
For price, see current catalogue

---------------------- Page: 6 ----------------------

62040-1-1  IEC:2004 – 3 –
CONTENTS
FOREWORD.7

1 Scope and specific applications .11
1.1 Scope.11
1.2 Specific applications.11
2 Normative references.13
3 Definitions.15
4 General conditions for tests .21
4.1 Operating parameters for tests .21
4.2 Loads for tests .21
4.3 Components.23
4.4 Power interfaces.23
4.5 Marking and instructions.23
5 Fundamental design requirements .33
5.1 Protection against electric shock and energy hazards .33
5.2 Insulation.37
5.3 Limited current circuits .37
5.4 Provisions for protective earthing .37
5.5 AC and d.c. power isolation.37
5.6 Overcurrent and earth fault protection .39
5.7 Protection of personnel – Safety interlocks.43
5.8 Clearances, creepage distances and distances through insulation.45
5.9 External signalling circuits.45
5.10 Limited power source.45
6 Wiring, connections and supply.47
6.1 General.47
6.2 Connection to power .47
6.3 Wiring terminals for external power conductors .47
7 Physical requirements.47
7.1 Enclosure.47
7.2 Stability.49
7.3 Mechanical strength.49
7.4 Construction details.49
7.5 Resistance to fire.51
7.6 Battery location.51
7.7 Temperature rise.55
8 Electrical requirements and simulated abnormal conditions.57
8.1 General.57
8.2 Electric strength.57
8.3 Abnormal operating and fault conditions.57
9 Connection to telecommunication networks.59

---------------------- Page: 7 ----------------------

62040-1-1  IEC:2004 – 5 –
Annex H (informative) Guidance on protection against ingress of water and foreign objects . 63
Annex L (normative) Backfeed protection test .67
Annex M (normative) Examples of reference load conditions .71
Annex N (normative) Ventilation of battery compartments .79
Annex X (informative) Guidance for disconnection of batteries during shipment .85

Bibliography.89

Figure L.1 – Potential load faults .69
Figure X.1 – Precautionary label for products shipped with the battery disconnected .85
Figure X.2 – Precautionary label for products shipped with the battery connected .87

Table 1 – Location of battery protective device(s) .41
Table 2 – Temperature-rise limits.55
Table 3 – Permitted temperature limits for magnetic windings at the end of stored
energy mode operation .55
Table H.1 – Degrees of protection against foreign objects indicated by the first
characteristic numeral.63
Table H.2 – Degrees of protection against water indicated by the second characteristic
numeral .65

---------------------- Page: 8 ----------------------

62040-1-1  IEC:2004 – 7 –
UNINTERRUPTIBLE POWER SYSTEMS (UPS) –

Part 1-1: General and safety requirements for UPS
used in operator access areas


FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 62040-1-1 has been prepared by subcommittee 22H: Uninter-
ruptible power systems (UPS), of IEC technical committee 22: Power electronic systems and
equipment.
This bilingual version (2004-02) replaces the English version and its corrigenda 1 (2002-12)
and 2 (2004-02).
The text of this standard is based on the following documents:
FDIS Report on voting
22H/22/FDIS 22H/24/RVD

Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
The French version of this standard has not been voted upon.

---------------------- Page: 9 ----------------------

62040-1-1  IEC:2004 – 9 –
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
It is to be used with IEC 60950-1 which is referred to in this standard as "RD".
In this standard, the following print types are used:
– Requirements proper and normative annexes: in roman type.
– Compliance statements and test specifications: in italic type.
– Notes and other informative matter: in smaller roman type.
– Normative conditions within tables: in smaller roman type.
– Terms that are defined in Clause 3: bold.
The committee has decided that the contents of this publication will remain unchanged until
2006. At this date, the publication will be
• reconfirmed;
• withdrawn;
• replaced by a revised edition, or
• amended.

---------------------- Page: 10 ----------------------

62040-1-1  IEC:2004 – 11 –
UNINTERRUPTIBLE POWER SYSTEMS (UPS) –

Part 1-1: General and safety requirements for UPS
used in operator access areas



1 Scope and specific applications
1.1 Scope
This part of IEC 62040 applies to electronic uninterruptible power systems (UPS) with an
electrical energy storage device in the d.c. link. It is to be used with IEC 60950-1 which is
referred to in this standard as "RD".
When any item is referred to by the phrase "The definitions or the provisions of item/RD
apply", this phrase is intended to mean that the definitions or provisions in that item of
IEC 60950-1 apply, except any which are clearly inapplicable to uninterruptible power
systems. National requirements additional to those in IEC 60950-1 apply and are found as
notes under relevant clauses of the RD.
The primary function of the UPS covered by this standard is to ensure continuity of an
alternating power source. The UPS may also serve to improve the quality of the power source
by keeping it within specified characteristics.
This standard is applicable to UPS which are movable, stationary, fixed or for building-in, for
use on low-voltage distribution systems and intended to be installed in any operator
accessible area. It specifies requirements to ensure safety for the operator and layman who
may come into contact with the equipment and, where specifically stated, for the service
person.
This standard is intended to ensure the safety of installed UPS, both as a single UPS unit or
as a system of interconnected UPS units, subject to installing, operating and maintaining the
UPS in the manner prescribed by the manufacturer.
This standard does not cover d.c. supplied electronic ballasts (IEC 61347 and IEC 60925),
UPS intended to be installed in separated electrical locations and UPS based on rotating
machines.
The relevant general and safety requirements for UPS installed in restricted access locations
are given in IEC 62040-1-2; electromagnetic compatibility (EMC) requirements and definitions
are given in IEC 62040-2.
1.2 Specific applications
Even if this standard does not cover all types of UPS, it may be taken as a guide for such
equipment. Requirements additional to those specified in this standard may be necessary for
specific applications, for example:
– UPS intended for operation while exposed, for example, to extremes of temperature; to
excessive dust, moisture, or vibration; to flammable gases; to corrosive or explosive
atmospheres;

---------------------- Page: 11 ----------------------

62040-1-1  IEC:2004 – 13 –
– electromedical applications with the UPS located within 1,5 m from the patient contact
area;
– for UPS subject to transient overvoltages exceeding those for Overvoltage Category II
according to IEC 60664, additional protection might be necessary in the mains supply to
the UPS;
– UPS intended for use where ingress of water and foreign objects are possible, additional
requirements may be necessary; for guidance on such requirements and for relevant
testing, see annex H;
– UPS with trapezoidal output waveforms and long run times (greater than 30 min) in
addition to complying with 5.3.1.2 of IEC 62040-3 are subject to voltage distortion tests for
the purpose of load compatibility.
NOTE For UPS intended to be used in vehicles, on board ships or aircraft, in tropical countries, or on elevations
greater than 1 000 m, different requirements may be necessary.
2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
1
IEC 60417-DB:2002 , Graphical symbols for use on equipment
IEC 60529:1989, Degrees of protection provided by enclosures (IP Code)
IEC 60664 (all parts), Insulation coordination for equipment within low-voltage systems
IEC 60755:1983, General requirements for residual current operated protective devices
Amendment 1 (1988)
Amendment 2 (1992)
2
IEC 60617-DB:2001 , Graphical symbols for diagrams
IEC 60950-1:2001, Information technology equipment – Safety – Part 1: General requirements
IEC 61000-2-2:2002, Electromagnetic compatibility (EMC) – Part 2-2: Environment –
Compatibility levels for low-frequency conducted disturbances and signalling in public
low-voltage power supply systems
IEC 61008-1:1996, Residual current operated circuit-breakers without integral overcurrent
protection for household and similar uses (RCCBs) – Part 1: General rules
IEC 61009-1:1996, Residual current operated circuit-breakers with integral overcurrent
protection for household and similar uses (RCBOs) – Part 1: General rules
___________
1
“DB” refers to the IEC on-line database.
2
“DB” refers to the IEC on-line database.

---------------------- Page: 12 ----------------------

62040-1-1  IEC:2004 – 15 –
IEC 62040-1-2:2004, Uninterruptible power systems (UPS) – Part 1-2: General and safety
requirements for UPS used in restricted access locations
IEC 62040-2:1999, Uninterruptible power systems (UPS) – Part 2: Electromagnetic compatibility
(EMC) requirements
IEC 62040-3:1999, Uninterruptible power systems (UPS) – Part 3: Method of specifying the
performance and test requirements
3 Definitions
3.1 General
For the purposes of this standard, the following definitions apply as well as some of the
definitions of IEC 60950-1. Where the terms "voltage" and "current" are used, they imply the
r.m.s. values, unless otherwise specified.
NOTE Care should be taken that measurement instruments give a true r.m.s. reading in the presence of non-
sinusoidal signals.
3.1.1
uninterruptible power system (UPS)
combination of convertors, switches and energy storage devices (for example, batteries),
constituting a power system for maintaining continuity of load power in case of input power
failure
3.1.2
bypass
power path alternative, either internal or external to the UPS
3.1.3
primary power
power supplied by an electrical utility company or by a user’s generator
3.1.4
backfeed
condition in which a voltage or energy available within the UPS is fed back to any of the input
terminals, either directly or by a leakage path while operating in the stored energy mode and
with primary power not available
3.1.5
backfeed protection
control scheme that reduces the risk of electric shock due to backfeed
3.1.6
stored energy mode
operation of the UPS when supplied by the following conditions:
– primary power is disconnected or is out of a given tolerance;
– battery is being discharged;
– load is within the given range;
– output voltage is within the given tolerance

---------------------- Page: 13 ----------------------

62040-1-1  IEC:2004 – 17 –
3.2 UPS electrical ratings
3.2.1
rated voltage
input or output voltage (for three-phase supply, the phase-to-phase voltage) as declared by
the manufacturer
3.2.2
rated voltage range
input or output voltage range as declared by the manufacturer, expressed by its lower and
upper rated voltages
3.2.3
rated current
maximum input or output current of the UPS as declared by the manufacturer
3.3 Load types
3.3.1
normal load
mode of operation which approximates as closely as possible the most severe conditions of
normal use in accordance with the manufacturer’s operating instructions. However, when the
conditions of actual use can obviously be more severe than the maximum load conditions
recommended by the manufacturer, a load shall be used that is representative of the
maximum that can be applied
NOTE For examples of reference normal load conditions for UPS, see Annex M.
3.3.2
linear load
load where the current drawn from the supply is defined by the relationship:
I = U/Z
where
I is the load current;
U is the supply voltage;
Z is the load impedance
3.3.3
non-linear load
load where the parameter Z (load impedance) is no longer a constant but is a variable
dependent on other parameters, such as voltage or time (see Annex M)
3.4 Connection to the supply
The definitions of 1.2.5/RD apply together with the following.
3.4.1
power cord
flexible cord or cable for interconnection purposes
3.5 Circuits and circuit characteristics
The definitions of 1.2.8/RD apply.

---------------------- Page: 14 ----------------------

62040-1-1  IEC:2004 – 19 –
3.5.1
hazardous voltage
The definition in 1.2.8.5/RD applies.
3.6 Insulation
The definitions of 1.2.9/RD apply.
3.7 Equipment mobility
The definitions of 1.2.3/RD apply.
3.8 Insulation classes of UPS
The definitions of 1.2.4/RD apply.
3.9 Enclosures
The definitions of 1.2.6/RD apply.
3.10 Accessibility
The definitions of 1.2.7/RD apply.
3.11 Components
The definitions of 1.2.11/RD apply.
3.12 Power distribution
The definitions of 1.2.8/RD apply.
3.13 Flammability
The definitions of 1.2.12/RD apply.
3.14 Miscellaneous
The definitions of 1.2.13/RD apply together with the following.
3.14.1
type test
The definition of 1.4.2/RD applies together with the following addition.
Where in this standard compliance of materials, components or subassemblies is checked by
inspection or by testing of properties, it is permitted to confirm compliance by reviewing any
relevant data or previous test results that are available instead of carrying out the specified
type tests.
NOTE For physically large units and/or power ratings, adequate test facilities to demonstrate some of the type
tests may not exist.
This situation also applies to some electrical tests for which no commercial test simulation
equipment is available or requires speciali
...