SIST EN IEC 62619:2022
(Main)Secondary cells and batteries containing alkaline or other non-acid electrolytes - Safety requirements for secondary lithium cells and batteries, for use in industrial applications
Secondary cells and batteries containing alkaline or other non-acid electrolytes - Safety requirements for secondary lithium cells and batteries, for use in industrial applications
This document specifies requirements and tests for the safe operation of secondary lithium cells and batteries used in industrial applications, including stationary applications.
When there exists an IEC International Standard specifying test conditions and requirements for cells used in special applications and which is in conflict with this document, the former takes precedence (e.g., IEC 62660 series on road vehicles).
The following are some examples of applications that utilize cells and batteries under the scope of this document:
- Stationary applications: telecom, uninterruptible power supplies (UPS), electrical energy storage system, utility switching, emergency power, and similar applications.
- Motive applications: forklift truck, golf cart, automated guided vehicle (AGV), railway vehicles, and marine vehicles, with the exception of road vehicles.
Since this document covers batteries for various industrial applications, it includes those requirements which are common and minimum to the various applications.
Electrical safety is included only as a part of the risk analysis of Clause 8. In regard to details for addressing electrical safety, the end use application standard requirements need to be considered.
This document applies to cells and batteries. If the battery is divided into smaller units, the smaller unit can be tested as the representative of the battery. The manufacturer clearly declares the tested unit. The manufacturer can add functions, which are present in the final battery to the tested unit.
This document addresses first life cells and batteries. Reuse, repurpose, second life use or similar are not taken into considered by this document.
Akkumulatoren und Batterien mit alkalischen oder anderen nicht säurehaltigen Elektrolyten - Sicherheitsanforderungen für Lithium-Akkumulatoren und -Batterien für die Verwendung in industriellen Anwendungen
Accumulateurs alcalins et autres accumulateurs à électrolyte non acide - Exigences de sécurité pour les accumulateurs au lithium pour utilisation dans des applications industrielles
IEC 62619:2022 spécifie les exigences et les essais pour le fonctionnement en toute sécurité des accumulateurs au lithium utilisés dans des applications industrielles, y compris les applications stationnaires. Lorsqu'il existe une Norme internationale IEC qui spécifie des conditions d'essai et des exigences pour des éléments destinés à des applications particulières, et qui est en contradiction avec le présent document, la publication particulière est appliquée en priorité (par exemple, la série IEC 62660 sur les véhicules routiers). Ci-après figurent des exemples d’applications qui emploient les éléments et les batteries inclus dans le domaine d’application du présent document :
- applications stationnaires: télécommunications, alimentation sans interruption (ASI), système de stockage d'énergie électrique, sélecteur de service, alimentation de secours et applications similaires;
- applications mobiles: chariot élévateur à fourche, voiturette de golf, véhicule à guidage automatique (AGV, automated guided vehicle), véhicules ferroviaires et marins, à l'exclusion des véhicules routiers.
Sekundarni členi in baterije z alkalnimi ali drugimi nekislinskimi elektroliti - Varnostne zahteve za sekundarne litijeve člene in baterije za industrijsko uporabo
Ta dokument določa zahteve in preskuse za varno uporabo sekundarnih litijevih členov in baterij za industrijsko rabo, vključno s stacionarno uporabo.
Če obstaja mednarodni standard IEC, ki določa preskusne pogoje in zahteve za člene za posebno uporabo ter je v nasprotju s tem dokumentom, ima prednost prvi (npr. skupina standardov IEC 62660 o cestnih vozilih).
V nadaljevanju je navedenih nekaj primerov uporabe členov in baterij v okviru tega dokumenta.
• Stacionarna uporaba: telekomunikacije, napajalniki za neprekinjeno napajanje (UPS), sistem za shranjevanje električne energije, preklapljanje storitev, zasilno napajanje in podobni načini uporabe.
• Pogonska uporaba: viličar, voziček za golf, samodejno vodeno vozilo (AGV), železniška in pomorska vozila, razen cestnih vozil.
Ker ta dokument zajema baterije za različno industrijsko rabo, vključuje skupne in minimalne zahteve za različne načine uporabe.
Električna varnost je vključena samo kot del analize tveganja v točki 8. V povezavi s podrobnostmi za obravnavanje električne varnosti je treba upoštevati standardne zahteve za končno uporabo.
Ta dokument se uporablja za člene in baterije. Če je baterija razdeljena na manjše enote, je mogoče manjšo enoto preskusiti kot reprezentativno za baterijo. Proizvajalec jasno deklarira preskušeno enoto. Proizvajalec lahko preskušeni enoti doda funkcije, ki jih vsebuje končna baterija.
Ta dokument se uporablja za člene in baterije v prvem življenjskem ciklu. Ta dokument ne upošteva vnovične uporabe, spremenjenega namena uporabe, uporabe v drugem življenjskem ciklu in podobnih načinov uporabe.
General Information
- Status
- Published
- Publication Date
- 17-Aug-2022
- Technical Committee
- ISCB - Secondary cells and batteries
- Current Stage
- 6060 - National Implementation/Publication (Adopted Project)
- Start Date
- 06-Jul-2022
- Due Date
- 10-Sep-2022
- Completion Date
- 18-Aug-2022
Relations
- Effective Date
- 05-Jul-2022
- Effective Date
- 27-Nov-2018
Overview - EN IEC 62619:2022 (CLC)
EN IEC 62619:2022 specifies safety requirements and type tests for secondary lithium cells and batteries intended for industrial applications, including stationary uses (telecom, UPS, electrical energy storage, utility switching, emergency power) and motive applications (forklifts, golf carts, AGVs, railway and marine vehicles - excluding road vehicles). It is a Europe‑adopted version of IEC 62619:2022 and supersedes EN 62619:2017. The standard applies to first‑life cells and batteries; reuse or second‑life use is not covered.
Key topics and technical requirements
EN IEC 62619:2022 focuses on safety, test methods and documentation. Major topics include:
- Type test conditions and sample sizes for cells, cell blocks, battery packs and battery systems.
- Mechanical and electrical abuse tests such as external short‑circuit, impact, drop, thermal abuse, overcharge and forced discharge.
- Internal short‑circuit design evaluation and propagation testing to assess thermal runaway risks and cell‑to‑cell propagation in battery systems.
- Battery system safety with emphasis on Battery Management System (BMS) requirements: overcharge/overcurrent control, overheating protection and functional safety considerations.
- Operating region guidance (temperature, voltage, charge/discharge conditions) for safe use of lithium cells.
- Information for safety, marking, packaging and transport requirements and documentation that manufacturers must provide.
- EMC considerations and inclusion of electrical safety within the risk analysis; end‑use electrical safety requirements are addressed by application standards.
- Quality plan and manufacturer responsibilities, including testing a representative unit (smaller unit may represent the battery) and declaring any added functions in the tested configuration.
Practical applications - who uses this standard
EN IEC 62619:2022 is used by:
- Cell and battery manufacturers designing lithium battery products for industrial and stationary markets.
- Battery system integrators and OEMs that build UPS, telecom power, energy storage systems, AGVs, forklifts, railway and marine traction systems.
- Test laboratories and certification bodies performing type tests and safety evaluations.
- Design and safety engineers responsible for BMS design, thermal management, system-level risk assessment and compliance documentation.
- Regulatory and procurement teams who need to verify safety conformity for industrial battery installations.
Using this standard helps demonstrate compliance with recognized safety tests, reduce thermal‑runaway and propagation risks, and support safe integration of lithium cells into industrial systems.
Related standards
Standards referenced alongside EN IEC 62619:2022 include:
- IEC 62133‑2 (portable lithium safety tests)
- IEC 62620 (secondary lithium cells and batteries for industrial use - performance)
- IEC 62660 series (road‑vehicle lithium systems - takes precedence for conflicting road‑vehicle requirements)
- Other relevant IEC/ISO standards on functional safety, EMC, packaging and testing (see Annex ZA of EN IEC 62619:2022).
Frequently Asked Questions
SIST EN IEC 62619:2022 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Secondary cells and batteries containing alkaline or other non-acid electrolytes - Safety requirements for secondary lithium cells and batteries, for use in industrial applications". This standard covers: This document specifies requirements and tests for the safe operation of secondary lithium cells and batteries used in industrial applications, including stationary applications. When there exists an IEC International Standard specifying test conditions and requirements for cells used in special applications and which is in conflict with this document, the former takes precedence (e.g., IEC 62660 series on road vehicles). The following are some examples of applications that utilize cells and batteries under the scope of this document: - Stationary applications: telecom, uninterruptible power supplies (UPS), electrical energy storage system, utility switching, emergency power, and similar applications. - Motive applications: forklift truck, golf cart, automated guided vehicle (AGV), railway vehicles, and marine vehicles, with the exception of road vehicles. Since this document covers batteries for various industrial applications, it includes those requirements which are common and minimum to the various applications. Electrical safety is included only as a part of the risk analysis of Clause 8. In regard to details for addressing electrical safety, the end use application standard requirements need to be considered. This document applies to cells and batteries. If the battery is divided into smaller units, the smaller unit can be tested as the representative of the battery. The manufacturer clearly declares the tested unit. The manufacturer can add functions, which are present in the final battery to the tested unit. This document addresses first life cells and batteries. Reuse, repurpose, second life use or similar are not taken into considered by this document.
This document specifies requirements and tests for the safe operation of secondary lithium cells and batteries used in industrial applications, including stationary applications. When there exists an IEC International Standard specifying test conditions and requirements for cells used in special applications and which is in conflict with this document, the former takes precedence (e.g., IEC 62660 series on road vehicles). The following are some examples of applications that utilize cells and batteries under the scope of this document: - Stationary applications: telecom, uninterruptible power supplies (UPS), electrical energy storage system, utility switching, emergency power, and similar applications. - Motive applications: forklift truck, golf cart, automated guided vehicle (AGV), railway vehicles, and marine vehicles, with the exception of road vehicles. Since this document covers batteries for various industrial applications, it includes those requirements which are common and minimum to the various applications. Electrical safety is included only as a part of the risk analysis of Clause 8. In regard to details for addressing electrical safety, the end use application standard requirements need to be considered. This document applies to cells and batteries. If the battery is divided into smaller units, the smaller unit can be tested as the representative of the battery. The manufacturer clearly declares the tested unit. The manufacturer can add functions, which are present in the final battery to the tested unit. This document addresses first life cells and batteries. Reuse, repurpose, second life use or similar are not taken into considered by this document.
SIST EN IEC 62619:2022 is classified under the following ICS (International Classification for Standards) categories: 29.220.30 - Alkaline secondary cells and batteries. The ICS classification helps identify the subject area and facilitates finding related standards.
SIST EN IEC 62619:2022 has the following relationships with other standards: It is inter standard links to SIST EN 62619:2018, SIST EN 62619:2018. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
You can purchase SIST EN IEC 62619:2022 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of SIST standards.
Standards Content (Sample)
SLOVENSKI STANDARD
01-september-2022
Nadomešča:
SIST EN 62619:2018
Sekundarni členi in baterije z alkalnimi ali drugimi nekislinskimi elektroliti -
Varnostne zahteve za sekundarne litijeve člene in baterije za industrijsko uporabo
Secondary cells and batteries containing alkaline or other non-acid electrolytes - Safety
requirements for secondary lithium cells and batteries, for use in industrial applications
Akkumulatoren und Batterien mit alkalischen oder anderen nicht säurehaltigen
Elektrolyten - Sicherheitsanforderungen für Lithium-Akkumulatoren und -Batterien für die
Verwendung in industriellen Anwendungen
Accumulateurs alcalins et autres accumulateurs à électrolyte non acide - Exigences de
sécurité pour les accumulateurs au lithium pour utilisation dans des applications
industrielles
Ta slovenski standard je istoveten z: EN IEC 62619:2022
ICS:
29.220.30 Alkalni sekundarni členi in Alkaline secondary cells and
baterije batteries
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD EN IEC 62619
NORME EUROPÉENNE
EUROPÄISCHE NORM July 2022
ICS 29.220.30 Supersedes EN 62619:2017
English Version
Secondary cells and batteries containing alkaline or other non-
acid electrolytes - Safety requirements for secondary lithium
cells and batteries, for use in industrial applications
(IEC 62619:2022)
Accumulateurs alcalins et autres accumulateurs à Akkumulatoren und Batterien mit alkalischen oder anderen
électrolyte non acide - Exigences de sécurité pour les nicht-säurehaltigen Elektrolyten - Sicherheitsanforderungen
accumulateurs au lithium pour utilisation dans des für Lithium-Akkumulatoren und -Batterien für die
applications industrielles Verwendung in industriellen Anwendungen
(IEC 62619:2022) (IEC 62619:2022)
This European Standard was approved by CENELEC on 2022-06-28. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2022 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 62619:2022 E
European foreword
The text of document 21A/785/FDIS, future edition 2 of IEC 62619, prepared by SC 21A "Secondary
cells and batteries containing alkaline or other non-acid electrolytes" of IEC/TC 21 "Secondary cells
and batteries" was submitted to the IEC-CENELEC parallel vote and approved by CENELEC as
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2023-03-28
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2025-06-28
document have to be withdrawn
This document supersedes EN 62619:2017 and all of its amendments and corrigenda (if any).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
Any feedback and questions on this document should be directed to the users’ national committee. A
complete listing of these bodies can be found on the CENELEC website.
Endorsement notice
The text of the International Standard IEC 62619:2022 was approved by CENELEC as a European
Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards
indicated:
IEC 60730-1:2013 NOTE Harmonized as EN 60730-1:2016 (modified)
IEC 60812 NOTE Harmonized as EN IEC 60812
IEC 61000-4-2 NOTE Harmonized as EN 61000-4-2
IEC 61000-6-1 NOTE Harmonized as EN IEC 61000-6-1
IEC 61000-6-2 NOTE Harmonized as EN IEC 61000-6-2
IEC 61000-6-3 NOTE Harmonized as EN IEC 61000-6-3
IEC 61000-6-4 NOTE Harmonized as EN IEC 61000-6-4
IEC 61000-6-7 NOTE Harmonized as EN 61000-6-7
IEC 61025 NOTE Harmonized as EN 61025
IEC 61434 NOTE Harmonized as EN 61434
IEC 61508 (series) NOTE Harmonized as EN 61508 (series)
IEC 61511-1 NOTE Harmonized as EN 61511-1
IEC 61513 NOTE Harmonized as EN 61513
IEC 61960-3:2017 NOTE Harmonized as EN 61960-3:2017 (not modified)
IEC 62660 (series) NOTE Harmonized as EN IEC 62660 (series)
IEC 62281 NOTE Harmonized as EN IEC 62281
IEC 62109-1 NOTE Harmonized as EN 62109-1
IEC 62368-1 NOTE Harmonized as EN IEC 62368-1
ISO 9001:2015 NOTE Harmonized as EN ISO 9001:2015 (not modified)
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1 Where an International Publication has been modified by common modifications, indicated by (mod), the
relevant EN/HD applies.
NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is available
here: www.cenelec.eu.
Publication Year Title EN/HD Year
IEC 62133-2 2017 Secondary cells and batteries containing EN 62133-2 2017
alkaline or other non-acid electrolytes -
Safety requirements for portable sealed
secondary lithium cells, and for batteries
made from them, for use in portable
applications - Part 2: Lithium systems
IEC 62620 2014 Secondary cells and batteries containing EN 62620 2015
alkaline or other non-acid electrolytes -
Secondary lithium cells and batteries for
use in industrial applications
ISO/IEC Guide 51 - Safety aspects - Guidelines for their - -
inclusion in standards
IEC 62619 ®
Edition 2.0 2022-05
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
Secondary cells and batteries containing alkaline or other non-acid
electrolytes – Safety requirements for secondary lithium cells and batteries,
for use in industrial applications
Accumulateurs alcalins et autres accumulateurs à électrolyte non acide –
Exigences de sécurité pour les accumulateurs au lithium pour utilisation dans
des applications industrielles
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.220.30 ISBN 978-2-8322-2497-7
– 2 – IEC 62619:2022 © IEC 2022
CONTENTS
FOREWORD . 4
1 Scope . 6
2 Normative references . 6
3 Terms and definitions . 7
4 Parameter measurement tolerances . 10
5 General safety considerations . 10
5.1 General . 10
5.2 Insulation and wiring . 11
5.3 Venting . 11
5.4 Temperature/voltage/current management . 11
5.5 Terminal contacts of the battery pack and/or battery system . 11
5.6 Assembly of cells, modules, or battery packs into battery systems . 11
5.6.1 General . 11
5.6.2 Battery system design . 12
5.7 Operating region of lithium cells and battery systems for safe use . 12
5.8 System lock (or system lock function) . 12
5.9 Quality plan . 12
6 Type test conditions . 12
6.1 General . 12
6.2 Test items . 13
7 Specific requirements and tests . 14
7.1 Charging procedures for test purposes . 14
7.2 Reasonably foreseeable misuse . 15
7.2.1 External short-circuit test (cell or cell block) . 15
7.2.2 Impact test (cell or cell block) . 15
7.2.3 Drop test (cell or cell block, and battery system) . 16
7.2.4 Thermal abuse test (cell or cell block) . 18
7.2.5 Overcharge test (cell or cell block) . 19
7.2.6 Forced discharge test (cell or cell block) . 19
7.3 Considerations for internal short-circuit – Design evaluation . 20
7.3.1 General . 20
7.3.2 Internal short-circuit test (cell) . 20
7.3.3 Propagation test (battery system) . 22
8 Battery system safety (considering functional safety) . 23
8.1 General requirements . 23
8.2 Battery management system (or battery management unit) . 23
8.2.1 Requirements for the BMS . 23
8.2.2 Overcharge control of voltage (battery system) . 24
8.2.3 Overcharge control of current (battery system) . 25
8.2.4 Overheating control (battery system) . 26
9 EMC . 26
10 Information for safety . 26
11 Marking and designation . 27
12 Packaging and transport . 27
Annex A (normative) Operating region of cells for safe use . 28
IEC 62619:2022 © IEC 2022 – 3 –
A.1 General . 28
A.2 Charging conditions for safe use . 28
A.3 Considerations on charging voltage . 28
A.4 Considerations on temperature . 29
A.5 High temperature range . 29
A.6 Low temperature range . 29
A.7 Discharging conditions for safe use . 30
A.8 Example of operating region . 30
Annex B (informative) Procedure of propagation test by laser irradiation (see 7.3.3) . 32
B.1 General . 32
B.2 Test conditions . 32
B.2.1 Cell test (preliminary test) . 32
B.2.2 Battery system test (main test) . 33
Annex C (informative) Procedure of propagation test by methods other than laser (see
7.3.3) . 35
C.1 General . 35
C.2 Test conditions . 35
C.3 Methods for initiating the thermal runaway . 35
Annex D (informative) Packaging and transport . 36
Bibliography . 37
Figure 1 – Configuration of the impact test . 16
Figure 2 – Impact location . 18
Figure 3 – Configuration for the shortest edge drop test . 18
Figure 4 – Configuration for the corner drop test . 18
Figure 5 – Jig for pressing . 21
Figure 6 – Examples of BMS locations and battery system configurations . 24
Figure 7 – Example of the circuit configuration for overcharge control of voltage . 25
Figure A.1 – An example of operating region for charging of typical lithium ion cells . 30
Figure A.2 – An example of operating region for discharging of typical lithium ion cells . 31
Figure B.1 – Example of the test layout . 33
Figure B.2 – Example of typical temperature trend of the cell . 33
Table 1 – Sample size for type tests . 14
Table 2 – Drop test method and condition . 17
– 4 – IEC 62619:2022 © IEC 2022
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
SECONDARY CELLS AND BATTERIES CONTAINING
ALKALINE OR OTHER NON-ACID ELECTROLYTES –
SAFETY REQUIREMENTS FOR SECONDARY LITHIUM CELLS
AND BATTERIES, FOR USE IN INDUSTRIAL APPLICATIONS
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC Publication(s)”). Their
preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
may participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence between
any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of patent
rights. IEC shall not be held responsible for identifying any or all such patent rights.
IEC 62619 has been prepared by subcommittee 21A: Secondary cells and batteries containing
alkaline or other non-acid electrolytes, of IEC technical committee 21: Secondary cells and
batteries. It is an International Standard.
This second edition cancels and replaces the first edition published in 2017. This edition
constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
a) new requirements for moving parts;
b) addition of requirements for hazardous live parts;
c) addition of requirements for battery system design;
d) new requirements for system lock;
e) new requirements for EMC;
IEC 62619:2022 © IEC 2022 – 5 –
f) addition of procedure of propagation test by laser.
The text of this International Standard is based on the following documents:
Draft Report on voting
21A/785/FDIS 21A/787/RVD
Full information on the voting for its approval can be found in the report on voting indicated in
the above table.
The language used for the development of this International Standard is English.
This document was drafted in accordance with ISO/IEC Directives, Part 2, and developed in
accordance with ISO/IEC Directives, Part 1 and ISO/IEC Directives, IEC Supplement, available
at www.iec.ch/members_experts/refdocs. The main document types developed by IEC are
described in greater detail at www.iec.ch/standardsdev/publications.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under webstore.iec.ch in the data related to the
specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates that it
contains colours which are considered to be useful for the correct understanding of its
contents. Users should therefore print this document using a colour printer.
– 6 – IEC 62619:2022 © IEC 2022
SECONDARY CELLS AND BATTERIES CONTAINING
ALKALINE OR OTHER NON-ACID ELECTROLYTES –
SAFETY REQUIREMENTS FOR SECONDARY LITHIUM CELLS
AND BATTERIES, FOR USE IN INDUSTRIAL APPLICATIONS
1 Scope
This document specifies requirements and tests for the safe operation of secondary lithium cells
and batteries used in industrial applications, including stationary applications.
When there exists an IEC International Standard specifying test conditions and requirements
for cells used in special applications and which is in conflict with this document, the former
takes precedence (e.g., IEC 62660 series on road vehicles).
The following are some examples of applications that utilize cells and batteries under the scope
of this document:
• Stationary applications: telecom, uninterruptible power supplies (UPS), electrical energy
storage system, utility switching, emergency power, and similar applications.
• Motive applications: forklift truck, golf cart, automated guided vehicle (AGV), railway
vehicles, and marine vehicles, with the exception of road vehicles.
Since this document covers batteries for various industrial applications, it includes those
requirements which are common and minimum to the various applications.
Electrical safety is included only as a part of the risk analysis of Clause 8. In regard to details
for addressing electrical safety, the end use application standard requirements need to be
considered.
This document applies to cells and batteries. If the battery is divided into smaller units, the
smaller unit can be tested as the representative of the battery. The manufacturer clearly
declares the tested unit. The manufacturer can add functions, which are present in the final
battery to the tested unit.
This document addresses first life cells and batteries. Reuse, repurpose, second life use or
similar are not taken into consideration by this document.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies.
For undated references, the latest edition of the referenced document (including any
amendments) applies.
IEC 62133-2:2017, Secondary cells and batteries containing alkaline or other non-acid
electrolytes – Safety requirements for portable sealed secondary lithium cells, and for batteries
made from them, for use in portable applications – Part 2: Lithium systems
IEC 62620:2014, Secondary cells and batteries containing alkaline or other non-acid
electrolytes – Secondary lithium cells and batteries for use in industrial applications
ISO/IEC Guide 51, Safety aspects – Guidelines for their inclusion in standards
IEC 62619:2022 © IEC 2022 – 7 –
3 Terms and definitions
For the purposes of this document, the terms and definitions given in ISO/IEC Guide 51, and
the following apply.
ISO and IEC maintain terminological databases for use in standardization at the following
addresses:
• IEC Electropedia: available at http://www.electropedia.org/
• ISO Online browsing platform: available at http://www.iso.org/obp
3.1
safety
freedom from unacceptable risk
3.2
risk
combination of the probability of occurrence of harm and the severity of that harm
[SOURCE: ISO/IEC Guide 51:2014, 3.9, modified – deletion of Note 1 to entry.]
3.3
harm
physical injury or damage to the health of people, or damage to property or to the environment
[SOURCE: ISO/IEC Guide 51:2014, 3.1]
3.4
hazard
potential source of harm
[SOURCE: ISO/IEC Guide 51:2014, 3.2]
3.5
intended use
use of a product, process or service in accordance with specifications, instructions and
information provided by the supplier
3.6
reasonably foreseeable misuse
use of a product, process or service in a way not intended by the supplier, but which can result
from readily predictable human behaviour
[SOURCE: ISO/IEC Guide 51:2014, 3.7, modified – "or system" has been replaced with
"process or service" and notes to entry deleted.]
3.7
secondary lithium cell
cell
secondary cell where electrical energy is derived from the insertion/extraction reactions of
lithium ions or oxidation/reduction reaction of lithium between the negative electrode and the
positive electrode
Note 1 to entry: The cell typically has an electrolyte that consists of a lithium salt and organic solvent compound in
liquid, gel or solid form and has a metal or a laminate film casing. It is not ready for use in an application because it
is not yet fitted with its final housing, terminal arrangement and electronic control device.
– 8 – IEC 62619:2022 © IEC 2022
3.8
cell block
group of cells connected together in parallel configuration with or without protective devices
(e.g. fuse or positive temperature coefficient device (PTC)) and monitoring circuitry
Note 1 to entry: The cell block is not ready for use in an application because it is not yet fitted with its final housing,
terminal arrangement and electronic control device.
3.9
module
group of cells connected together either in a series and/or parallel configuration with or without
protective devices (e.g. fuse or positive temperature coefficient device (PTC)) and monitoring
circuitry
3.10
battery pack
energy storage device, which comprises one or more cells or modules electrically connected
and has monitoring circuitry which provides information (e.g. cell voltage) to a battery system
to influence the battery's safety, performance and/or service life
Note 1 to entry: The battery pack may incorporate a protective housing and be provided with terminals or other
interconnection arrangements.
3.11
battery system
battery
system which comprises one or more cells, modules or battery packs and has a battery
management system capable of controlling current in case of overcharge, overcurrent,
overdischarge, and overheating
Note 1 to entry: Overdischarge cut-off is not mandatory if there is an agreement between the cell manufacturer and
the customer.
Note 2 to entry: The battery system may have cooling or heating units. More than one battery system may constitute
a larger battery system. The battery system is sometimes also referred to as a battery.
3.12
battery management system
BMS
electronic system associated with a battery which has functions to control current in case of
overcharge, overcurrent, overdischarge, and overheating and which monitors and/or manages
the battery's state, calculates secondary data, reports that data and/or controls its environment
to influence the battery's safety, performance and/or service life
Note 1 to entry: Overdischarge cut-off is not mandatory if there is an agreement between the cell manufacturer and
the customer.
Note 2 to entry: The function of the BMS can be assigned to the battery pack or to equipment that uses the battery.
(See Figure 6.)
Note 3 to entry: The BMS can be divided and it can be found partially in the battery pack and partially on the
equipment that uses the battery. (See Figure 6.)
Note 4 to entry: The BMS is sometimes also referred to as a BMU (battery management unit).
3.13
leakage
visible escape of liquid electrolyte
3.14
venting
release of excessive internal pressure from a cell, module, battery pack, or battery system in a
manner intended by design to preclude rupture or explosion
IEC 62619:2022 © IEC 2022 – 9 –
3.15
rupture
mechanical failure of a cell container or battery case induced by an internal or external cause,
resulting in exposure or spillage but not ejection of materials
3.16
explosion
failure that occurs when a cell container or battery case opens violently and solid components
are forcibly expelled
Note 1 to entry: Liquid, gas, and smoke are excepted.
3.17
fire
emission of flames from a cell, module, battery pack, or battery system for more than 1 s
Note 1 to entry: Sparks and arcing are not considered as flames.
3.18
rated capacity
capacity value of a cell or battery determined under specified conditions and declared by the
manufacturer
Note 1 to entry: The rated capacity is the quantity of electricity C Ah (ampere-hours) declared by the manufacturer
n
which a single cell or battery can deliver during an n-hour period when charging, storing and discharging under the
conditions specified in IEC 62620:2014, 6.3.1.
[SOURCE: IEC 60050-482:2004, 482-03-15, modified – Addition of the words "cell or" in the
definition and of Note 1 to entry.]
3.19
upper limit charging voltage
highest charging voltage in the cell operating region specified by the cell
manufacturer
3.20
lower limit discharging voltage
lowest discharging voltage in the cell operating region specified by the cell
manufacturer
3.21
maximum charging current
highest charging current in the cell operating region specified by the cell
manufacturer
3.22
maximum discharging current
highest discharging current in the cell operating region specified by the cell
manufacturer
3.23
thermal runaway
uncontrolled intensive increase in the temperature of a cell driven by exothermic reaction
– 10 – IEC 62619:2022 © IEC 2022
4 Parameter measurement tolerances
The overall accuracy of controlled or measured values, relative to the specified or actual
parameters, shall be within these tolerances:
a) ±0,5 % for voltage;
b) ±1 % for current;
c) ±2 °C for temperature;
d) ±0,1 % for time;
e) ±1 % for mass;
f) ±1 % for dimensions.
These tolerances comprise the combined accuracy of the measuring instruments, the
measurement techniques used, and all other sources of error in the test procedure.
The details of the instrumentation used shall be provided in any report of results.
5 General safety considerations
5.1 General
The safety of lithium secondary cells and battery systems requires the consideration of two sets
of applied conditions:
1) intended use;
2) reasonably foreseeable misuse.
Cells and battery systems shall be designed and constructed so that they are safe under
conditions of intended use and reasonably foreseeable misuse. It may also be expected that
cells and battery systems subjected to intended use shall not only be safe but shall continue to
be functional in all respects.
It is expected that cells or battery systems subjected to misuse may fail to function. However,
even if such a situation occurs, they shall not present any significant hazards.
Potential hazards which are the subject of this document are:
a) fire,
b) burst/explosion,
c) leakage of cell electrolyte,
d) venting with continuous emission of flammable and/or toxic gas and/or smoke,
e) rupture of the casing of cell, module, battery pack, or battery system with exposure of
internal components.
Conformity with 5.1 a) and b) is checked by the tests of Clause 6, Clause 7, and 8.2, and in
accordance with the appropriate standard (see Clause 2). Conformity with 5.1 c) to e) and with
5.2 to 5.6 is checked by analysis of documents mentioned in 8.1.
Moving parts that have potential to cause human injuries shall be applied using an appropriate
design and necessary measures to reduce the risk of injuries, including those injuries that may
be incurred during installation, while cells or battery systems are being incorporated into
equipment.
IEC 62619:2022 © IEC 2022 – 11 –
5.2 Insulation and wiring
Wiring and its insulation shall be sufficient to withstand the maximum anticipated voltage,
current, temperature, altitude and humidity requirements. The design of an internal wiring shall
be such that adequate clearances and creepage distances are maintained between conductors
and live parts at different voltages or between live parts and non-current-carrying accessible
parts. Hazardous live parts of the battery system shall be protected to avoid the risk of electric
shocks, including during installation.
The mechanical integrity of the whole battery system (cell/module/BMS) and their connections
shall be sufficient to accommodate conditions of reasonably foreseeable misuse.
5.3 Venting
The casing of a cell, module, battery pack, and battery system shall incorporate a pressure
relief function that will preclude rupture or explosion. If encapsulation is used to support cells
within an outer case, the type of encapsulating material and the method of encapsulation shall
neither cause the battery system to overheat during normal operation nor inhibit pressure relief.
5.4 Temperature/voltage/current management
The design of battery systems shall be such that abnormal temperature-rise conditions are
prevented. Battery systems shall be designed within voltage, current, and temperature limits
specified by the cell manufacturer. Battery systems shall be provided with specifications and
charging instructions for equipment manufacturers so that associated chargers are designed to
maintain charging within the voltage, current and temperature limits specified.
5.5 Terminal contacts of the battery pack and/or battery system
Terminals shall have clear polarity marking(s) on the external surface of the battery pack or
battery system.
Battery packs with keyed external connectors designed for connection to specific end products
need not be marked with polarity markings if the design of the external connector prevents
reverse polarity connections.
The size and shape of the terminal contacts shall ensure that they can carry the maximum
anticipated current. External terminal contact surfaces shall be formed from conductive
materials with good mechanical strength and corrosion resistance. Terminal contacts shall be
arranged so as to minimize the risk of short-circuits, for example to minimize the risk of short-
circuits by metal tools. Compliance is determined through a review of the terminal specifications.
5.6 Assembly of cells, modules, or battery packs into battery systems
5.6.1 General
The assembly of cells, modules or battery packs to constitute the battery system shall respect
the following rules to support adequate mitigation of risks as regard to the battery system:
• Each battery system shall have an independent control and protection method(s).
NOTE For the independent control and protection method(s), see 8.2.
• The cell manufacturer shall provide recommendations about current, voltage, temperature
limits and should provide mounting advice, storage conditions, maximum number of cells in
series (for cell internal protection such as a current interrupt device (CID)) so that the battery
system manufacturer/designer may ensure proper design and assembly.
• Battery systems that are designed for the selective discharging of a portion of their series
connected cells shall incorporate separate circuitry to prevent the cell reversal caused by
uneven discharging.
– 12 – IEC 62619:2022 © IEC 2022
• Protective circuit components should be added as appropriate and consideration given to
the end-device application.
5.6.2 Battery system design
The voltage control function of the battery system design shall ensure that the voltage of each
cell or cell block shall not exceed the upper limit charging voltage specified by the manufacturer
of the cells, except in the case where the end-devices provide the voltage control function. In
such a case, the end-devices are considered as part of the battery system. Refer to Note 2 and
Note 3 in 3.12.
The battery shall be designed so that the maximum charging current or the maximum
discharging current of the cell are not exceeded before the maximum allowed charging or
discharging current of the battery is reached.
5.7 Operating region of lithium cells and battery systems for safe use
The cell manufacturer shall specify the cell operating region. The battery system manufacturer
shall design the battery system to comply with the cell operating region. Determination of the
cell operating region is in accordance with Annex A.
5.8 System lock (or system lock function)
The battery system shall have a non-resettable function to stop operation when one or more
cells in the battery system deviates from the operating region during operation. This feature
shall not be user resettable or allow for automatic reset.
The function of the battery system may be returned after checking that the status of the battery
system complies with the battery system manufacturer manual, i.e. the battery system
maintenance manual shall clearly set out this procedure.
Depending on the application, a battery system may allow a final discharge, for example to
provide emergency functions. In this case, cell limits (e.g. lower limit discharge voltage or upper
temperature limit) may deviate once within the range where the cell does not cause dangerous
reactions. Therefore, the cell manufacturer shall provide the second set of limits in which the
cell in the battery system may accept one discharge without dangerous reactions. The cell
should not be further recharged after this last discharge.
5.9 Quality plan
The battery system manufacturer shall prepare and implement a quality plan that defines
procedures for the inspection of materials, components, cells, modules, battery packs, and
battery systems and which covers the whole process of producing each type of cell, module,
battery pack, and battery system (e.g. ISO 9001, etc.). Manufacturers should understand their
process capabilities and should institute the necessary process controls in relation to product
safety.
6 Type test conditions
6.1 General
A cell in the battery system that is used outside of its operating region may exhibit hazards
resulting from the cells or battery systems. Such risks shall be taken into consideration in order
to prepare a safe test plan.
The test facility should have sufficient structural integrity and a fire suppression system to
sustain the conditions of overpressure and fire that may occur as a result of testing. The facility
should have a ventilation system to remove and capture gas which might be produced during
the tests. Consideration should be given to high voltage hazards when applicable.
IEC 62619:2022 © IEC 2022 – 13 –
Warning: THESE TESTS USE PROCEDURES WHICH MAY RESULT IN HARM IF ADEQUATE PRECAUTIONS
ARE NOT TAKEN. TESTS SHOULD ONLY BE PERFORMED BY QUALIFIED AND EXPERIENCED
TECHNICIANS USING ADEQUATE PROTECTION. TO PREVENT BURNS, CAUTION SHOULD BE
TAKEN FOR THOSE CELLS OR BATTERY SYSTEMS WHOSE CASINGS MAY EXCEED 75 °C AS A
RESULT OF TESTING.
6.2 Test items
Tests are made with the number of cells or battery systems specified in Table 1, using cells or
battery systems that are stored for not more than six months, under conditions specified by the
cell or battery system manufacturer.
Cells or battery systems charged in accordance with the method specified in 7.1 shall deliver
the rated capacity or more according to IEC 62620:2014, 6.3.1 when they are discharged
at 25 °C ± 5 °C, at a constant current of 0,2 I A according to IEC 62620:2014, 6.3.1, down to a
t
specified final voltage. This capacity confirmation may be done during the cell manufacturer
shipping inspection. In the case of a battery system, the capacity may be calculated on the
basis of the cell capacity as measured during the cell manufacturer shipping inspection.
Unless otherwise specified, tests are carried out in an ambient temperature of 25 °C ± 5 °C.
NOTE Test conditions are for type tests only and do not imply that intended use includes operation under these
conditions. Similarly, the limit of six months is introduced for consistency and does not imply that cell and battery
system safety is reduced after six months.
– 14 – IEC 62619:2022 © IEC 2022
Table 1 – Sample size for type tests
Test items Test unit
Cell Battery system
Category Test
(see a) (see b and e)
7.2.1 External short-circuit test R -
7.2.2 Impact test R (see c) -
7.2.3 Drop test R R
7.2.4 Thermal abuse test R -
Product safety test
7.2.5 Overcharge test R (see d) -
(safety of cell and
battery system)
7.2.6 Forced discharge test R -
7.3 Considerations 7.3.2 Internal short- R* -
for internal short- circuit test
circuit (select one
7.3.3 Propagation - R
of the two options)
test
8.2.2 Overcharge control of voltage - R
Functional safety test
(safety of battery 8.2.3 Overcharge control of current - R
system)
8.2.4 Ov
...
SIST EN IEC 62619:2022 표준은 산업용 애플리케이션에서 사용되는 2차 리튬 셀과 배터리의 안전 요구 사항을 명시하고 있으며, 알칼리성 또는 기타 비산성 전해질을 포함하는 배터리를 규제합니다. 이 문서는 안전한 작동을 위한 요구 사항과 시험 방법을 제시하여, 특정 산업 환경에서의 2차 리튬 배터리의 사용을 보장합니다. 이 표준의 적용 범위는 정적 응용 프로그램(텔레콤, 무정전 전원 공급 장치(UPS), 전기 에너지 저장 시스템, 유틸리티 스위칭, 비상 전원 등)뿐만 아니라 동력 응용 프로그램(지게차, 골프 카트, 자동 유도 차량(AGV), 철도 차량 및 해양 차량)에도 걸쳐 있습니다. 그러나 도로 차량과 관련된 IEC 62660 시리즈의 특수 요구 사항이 있는 경우, 해당 표준이 우선 적용됨을 명확히 하고 있습니다. SIST EN IEC 62619:2022의 강점 중 하나는 다양한 산업 적용에 대한 공통 및 최소 요구 사항을 포함하고 있다는 점입니다. 이를 통해 사용자가 여러 유형의 응용 프로그램에서 동일한 기준을 활용할 수 있게 하여, 안전성 및 효율성을 높입니다. 전기 안전은 이 문서의 8조 리스크 분석의 일부로 포함되며, 최종 사용 애플리케이션 표준 요구 사항을 고려해야 합니다. 이러한 접근은 각기 다른 산업 응용 프로그램의 특성을 반영하여 보다 실용적인 안전 기준을 제공합니다. 또한, 이 표준은 셀과 배터리에 적용되며, 배터리를 작은 단위로 분할하는 경우, 해당 작은 단위가 배터리의 대표로 시험될 수 있도록 규정하고 있습니다. 제조업체는 시험된 단위를 명확히 선언할 수 있으며, 최종 배터리에 존재하는 기능을 시험된 단위에 추가할 수 있습니다. 마지막으로, 이 문서는 첫 생명 셀과 배터리에 집중하고 있으며, 재사용, 재목적화, 2차 생명 사용에 대한 고려는 포함되어 있지 않습니다. 이러한 명확한 범위 설정은 사용자들이 해당 표준이 무엇을 포함하고 무엇을 제외하는지를 이해하고, 자사의 기술 개발 및 안전성 준수에 효과적으로 활용할 수 있게 합니다.
The SIST EN IEC 62619:2022 standard focuses on the safety requirements and testing protocols for secondary lithium cells and batteries that utilize alkaline or other non-acid electrolytes, specifically within industrial applications. This comprehensive document covers a diverse range of applications, establishing a benchmark for safety and operational integrity that is crucial for sectors reliant on reliable energy sources. One of the strengths of SIST EN IEC 62619:2022 is its broad scope, which encompasses various industrial contexts such as stationary applications like telecommunications and uninterruptible power supplies (UPS), as well as motive applications including forklifts and automated guided vehicles (AGVs). By addressing both types of applications, the standard effectively caters to the needs of industries that depend on secondary lithium cells and batteries, ensuring their safe deployment across multiple settings. The standard is significant for its clarity in delineating the requirements and tests necessary for the safe operation of these cells and batteries. Notably, it specifies that the precedence of any conflicting IEC International Standards must be respected, reinforcing the importance of existing regulations and guidance in specialized applications. While the focus on electrical safety is included within the risk analysis framework, the document adeptly conveys that specific end-use application standards should be consulted for detailed electrical safety requirements. This feature underscores the document's practicality, allowing manufacturers to build upon the foundational safety parameters established by SIST EN IEC 62619:2022. Furthermore, the standard's approach to testing is highly commendable. By allowing smaller units of a battery to be tested as representatives of the whole, it provides manufacturers with flexibility while ensuring that safety standards are not compromised. The declaration of the tested unit by the manufacturer further reinforces transparency and accountability in the testing process. However, it is important to note that the standard exclusively addresses the first life of cells and batteries, notably excluding considerations for reuse, repurposing, or second life applications. This focused approach might limit its applicability in contexts where lifecycle management of batteries is critical, yet it allows for a concentrated exploration of safety in primary usage scenarios. Overall, the SIST EN IEC 62619:2022 document stands as a vital resource for industries using secondary lithium cells and batteries, offering robust safety requirements that align with practical application needs. Its relevance in industrial applications today cannot be overstated, as it ensures that energy solutions are not only effective but also safe for stakeholders across various sectors.
SIST EN IEC 62619:2022は、産業用途における二次リチウム電池の安全要件を詳細に規定したドキュメントです。この規格は、二次電池が使用されるさまざまな産業アプリケーションにおいて、安全に運用されるための要件やテスト方法を示しており、従ってその適用範囲は広範です。 この標準は特に、固定アプリケーション(テレコム、無停電電源装置(UPS)、電力貯蔵システム、電力切替、非常用電源など)や動力アプリケーション(フォークリフト、ゴルフカート、自動誘導車(AGV)、鉄道車両、海上車両)に関連したケースが含まれています。ただし、道路車両の電池については、IEC 62660シリーズなどの特別な用途に関する国際規格が優先されます。 この文書の強みは、産業用途ごとに共通且つ最低限の要件を包含している点です。これにより、異なる用途で使用される電池の安全性を一貫して評価できるため、ユーザーにとっての利便性が向上します。また、製造者は、単位バッテリーを小さなユニットに分割してテストすることができ、そのユニットがバッテリーの代表として扱われることを明確にしています。これにより、テストプロセスの柔軟性が確保されます。 さらに、この文書では、電気的安全性についての考慮はリスク分析の一部として扱われ、詳細はエンドユースアプリケーションの標準要件に依存しています。このアプローチにより、ユーザーは特定の使用ケースに適した安全性評価を行うことができます。 ただし、この文書は第一ライフのセルやバッテリーに焦点を当てており、再利用、再目的化、第二ライフの使用については考慮されていません。この点は、リサイクルや持続可能性がますます重要視される現代において、一部のユーザーにとっての制約となる可能性があります。 全体として、SIST EN IEC 62619:2022は、産業用途における二次リチウム電池の安全要件をシステマティックに整備した規格であり、広範囲な適用性と具体的なテスト基準を提供することで、関連産業にとって極めて重要な基準となっています。










Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...