Smoke and heat control systems - Part 4: Installed SHEVS systems for smoke and heat ventilation

This Technical Report applies to SHEVS when installed in a building. This Technical Report specifies the ability of the system to meet the required performances of the SHEVS as specified by the design of the system. This Technical Report requires that a detailed engineering design of the system exists but this standard does not state how the design is made. This Technical Report also covers requirements on components and compatibility between components to ensure that the requirements on the installed system will be met. This Technical report includes requirements for the assembly, installation, commissioning, function testing, maintenance, periodic servicing and routine testing of a SHEVS.

Rauch- und Wärmefreihaltung - Teil 4: Anlagen zur Rauch- und Wärmefreihaltung im eingebauten Zustand

Systemes pour le contrôle des fumées et de la chaleur - Partie 4: Systemes SEFCV installés pour l'évacuation de fumées et de chaleur par ventilation

Le présent Rapport technique s’applique aux SEFC lorsqu’ils sont installés dans un bâtiment. Le présent
Rapport technique spécifie la capacité du systeme a satisfaire aux performances requises des SEFC, tel que
spécifié par la conception du systeme. Le présent Rapport technique exige qu’une conception technique
détaillée existe, mais la présente norme ne spécifie pas la maniere dont la conception est réalisée. Le présent
Rapport technique traite également des exigences relatives aux composants et a la compatibilité entre les
composants permettant de garantir que les exigences relatives au systeme installé soient satisfaites. Le
présent Rapport technique comprend les exigences relatives au montage, a l'installation, a la mise en service,
aux essais de fonctionnement, a la maintenance, a l’entretien périodique et aux essais périodiques d'un SEFC.

Sistemi za nadzor dima in toplote - 4. del: Vgrajeni sistemi »SHEVS« za odvod dima in toplote s prezračevanjem

General Information

Status
Withdrawn
Publication Date
28-Feb-2007
Withdrawal Date
21-Oct-2010
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
20-Oct-2010
Due Date
12-Nov-2010
Completion Date
22-Oct-2010

Relations

Buy Standard

Technical report
TP CEN/TR 12101-4:2007
English language
50 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST-TP CEN/TR 12101-4:2007
01-marec-2007
6LVWHPL]DQDG]RUGLPDLQWRSORWHGHO9JUDMHQLVLVWHPLª6+(96©]DRGYRG
GLPDLQWRSORWHVSUH]UDþHYDQMHP
Smoke and heat control systems - Part 4: Installed SHEVS systems for smoke and heat
ventilation
Rauch- und Wärmefreihaltung - Teil 4: Anlagen zur Rauch- und Wärmefreihaltung im
eingebauten Zustand
Systemes pour le contrôle des fumées et de la chaleur - Partie 4: Systemes SEFCV
installés pour l'évacuation de fumées et de chaleur par ventilation
Ta slovenski standard je istoveten z: CEN/TR 12101-4:2006
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
91.140.30 3UH]UDþHYDOQLLQNOLPDWVNL Ventilation and air-
VLVWHPL conditioning
SIST-TP CEN/TR 12101-4:2007 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST-TP CEN/TR 12101-4:2007

---------------------- Page: 2 ----------------------

SIST-TP CEN/TR 12101-4:2007
TECHNICAL REPORT
CEN/TR 12101-4
RAPPORT TECHNIQUE
TECHNISCHER BERICHT
December 2006
ICS 13.220.20; 23.120

English Version
Smoke and heat control systems - Part 4: Installed SHEVS
systems for smoke and heat ventilation
Systèmes pour le contrôle des fumées et de la chaleur - Rauch- und Wärmefreihaltung - Teil 4: Anlagen zur Rauch-
Partie 4: Systèmes SEFCV installés pour l'évacuation de und Wärmefreihaltung im eingebauten Zustand
fumées et de chaleur par ventilation
This Technical Report was approved by CEN on 1 August 2006. It has been drawn up by the Technical Committee CEN/TC 191.
CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,
Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania,
Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36  B-1050 Brussels
© 2006 CEN All rights of exploitation in any form and by any means reserved Ref. No. CEN/TR 12101-4:2006: E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------

SIST-TP CEN/TR 12101-4:2007
CEN/TR 12101-4:2006 (E)
Contents Page
Foreword.4
Introduction .5
1 Scope .6
2 Normative references .6
3 Definitions .7
4 Description of the principles of operation for smoke and heat control sytems .9
4.1 Smoke and heat control system which rely on the principle of the creation of a smoke
layer.10
4.2 Smoke free areas by differential pressure systems.10
4.3 Air renewal of the room with fresh air by dilution of smoke.10
5 Description of the combination of products for construction of SHEVS .11
5.1 General.11
5.2 General requirements.11
5.3 Requirements for smoke layer systems with natural ventilators .12
5.4 Requirements for smoke layer systems with powered ventilators .12
5.5 Requirements for smoke free area systems by differential pressure.13
5.6 Requirements for smoke control by air renewal of the room with fresh air by dilution of
smoke.13
6 Air Inlet.13
6.1 General requirements.13
6.2 Fire behaviour requirements .14
6.3 Geometric areas for natural air inlets.14
7 Tubes, cables and accessories.15
7.1 General requirements.15
7.2 Fire behaviour requirements .15
7.4 Requirements for pneumatic .17
8 Requirements for installation.17
8.1 General requirements for installation.17
8.2 Requirements for installation of a SHEVS .17
8.3 Requirements for installation of power supplies .18
8.4 Requirements for installation of controls .18
8.5 Access to components .18
8.6 Requirements for installation of powered SHEVS .19
8.7 Requirements for installation of air inlets.19
8.8 General requirements for installation of smoke barriers .19
8.9 Functional test .20
9 Handing-over and commissioning.20
9.1 Requirements for commissioning of the system .20
9.2 Requirements for acceptance report of the system.21
9.3 Technical information report.21
9.4 Specific requirements for powered smoke ventilation systems .21
10 Routine checking.22
11 Maintenance .22
11.1 General.22
11.2 Scope of maintenance.22
11.3 Functional test .22
2

---------------------- Page: 4 ----------------------

SIST-TP CEN/TR 12101-4:2007
CEN/TR 12101-4:2006 (E)
11.4 Maintenance operations .22
11.5 Availability.22
Annex A (normative) Pneumatic system leakage testing .24
Annex B (normative) Air flow measurements.25
B.1 Air flow requirements in powered ventilation systems.25
B.2 Measurement of air flow for ducted systems .25
Annex C (informative) Drawings of example systems .26
Annex D (informative) Detailed engineering plan .36
D.1 Detailed engineering plan for smoke flow and pressure control within the premises .36
D.2 Requirements for assembly, commissioning, inspection, testing and maintenance of
natural smoke exhaust systems .37
Annex E (informative) Requirements specific to powered smoke exhaust systems (powered fans,
dampers, ducts etc) – Mounting and testing.39
E.1 Requirements for mounting and commissioning .39
E.2 Requirements for acceptance and testing.45
E.3 Requirements for routine checking.48
E.4 Requirements for maintenance.48
Bibliography.50

3

---------------------- Page: 5 ----------------------

SIST-TP CEN/TR 12101-4:2007
CEN/TR 12101-4:2006 (E)
Foreword
This document (CEN/TR 12101-4:2006) has been prepared by Technical Committee CEN/TC 191 “Fixed
firefighting systems”, the secretariat of which is held by BSI.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.
This European document (Technical Report) has the general title "Smoke and heat control systems" and
consists of the following separate parts:
 Part 1: Specifications for smoke barriers
 Part 2: Specification for natural smoke and heat exhaust ventilators
 Part 3: Specification for powered smoke and heat exhaust ventilators
 Part 4: Installed SHEVS systems for smoke and heat ventilation.
 Part 5: Guidelines on functional recommendations and calculation methods for smoke and heat exhaust
ventilation systems (published as CEN/TR 12101-5)
 Part 6: Specification for pressure differential systems - Kits
 Part 7: Smoke control ducts
 Part 8: Smoke control dampers
 Part 9: Control panels
 Part 10: Power supplies


4

---------------------- Page: 6 ----------------------

SIST-TP CEN/TR 12101-4:2007
CEN/TR 12101-4:2006 (E)
Introduction
Smoke and heat exhaust ventilation systems create a smoke free layer above the floor by removing smoke
and thus improve the conditions for the safe escape and/or rescue of people and animals. It contributes to the
protection of property and permits the fire to be fought while still in its early stages. They also exhaust hot
gases released by a fire in the developing stage.
The use of smoke and heat exhaust ventilation systems to create smoke free areas beneath a buoyant smoke
layer has become widespread. Their value in assisting in the evacuation of people from construction works,
reducing fire damage and financial loss by preventing smoke logging, facilitating fire fighting, reducing roof
temperatures and retarding the lateral spread of fire is firmly established. For these benefits to be obtained it
is essential that smoke and heat exhaust ventilators operate fully and reliably whenever called upon to do so
during their installed life. A heat and smoke exhaust ventilation system is a scheme of safety equipment
intended to perform a positive role in a fire emergency.
Components for smoke and heat exhaust ventilation systems should be installed as part of a properly
designed smoke and heat exhaust ventilation system.
Smoke and heat exhaust ventilation systems help to:
 keep the escape and access routes free from smoke;
 facilitate fire fighting operations by creating a smoke free layer;
 delay and/or prevent flashover and thus full development of the fire;
 protect equipment and furnishings;
 reduce thermal effects on structural components during a fire;
 reduce damages caused by thermal decomposition products and hot gases.
A powered smoke exhaust system can also be used for the realisation of the following purposes:
 creation of a negative pressure differential facing the direction of escape for the prevention of the spread
of smoke;
 local dilution of smoke within occupied zones.
Natural smoke and heat exhaust ventilators are devices fitted into the roof and /or upper walls of a
construction works to allow smoke and fire gases to be exhausted from the construction works when driven by
thermal buoyancy inherent in those gases. It is essential that they are able to open, and/or to remain open in
the event of a fire and to fulfil their function even when climatic and weather conditions are unfavourable.
Depending on the building geometry and siting of the building with regard to neighbouring buildings, and
design criteria, natural smoke and heat exhaust ventilators can be used instead of powered smoke and heat
ventilators.
This Technical Report sets down the testing requirements for the system when installed to ensure that it
operates in a safe and reliable manner. Commissioning, periodic maintenance and servicing requirements are
stated as well as the users’ responsibilities for ensuring that the system is always for use in case of fire.
Components of the SHEVS should be designed or chosen to meet the specific performance requirement of
the system.
Without proper installation of all of its components, the SHEVS could not operate correctly nor meet the
performance targets for which it has been designed.
Commissioning is necessary to check the SHEVS operates in accordance with its design. The system has to
be permanently available for operation. This can only be achieved when checked and maintained.
5

---------------------- Page: 7 ----------------------

SIST-TP CEN/TR 12101-4:2007
CEN/TR 12101-4:2006 (E)
1 Scope
This Technical Report applies to SHEVS when installed in a building. This Technical Report specifies the
ability of the system to meet the required performances of the SHEVS as specified by the design of the
system. This Technical Report requires that a detailed engineering design of the system exists but this
standard does not state how the design is made. This Technical Report also covers requirements on
components and compatibility between components to ensure that the requirements on the installed system
will be met. This Technical report includes requirements for the assembly, installation, commissioning,
function testing, maintenance, periodic servicing and routine testing of SHEVS.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 12101-1, Smoke and heat control systems — Part 1: Specification for smoke barriers
EN 12101-2, Smoke and heat control systems — Part 2: Specification for natural smoke and heat exhaust
ventilators
EN 12101-3, Smoke and heat control systems — Part 3: Specification for powered smoke and heat exhaust
ventilators
EN 12101-6. Smoke and heat control systems — Part 6: Specification for pressure differential systems_- kits
prEN 12101-9, Smoke and heat control systems — Part 9: Control panels
EN 12101-10, Smoke and heat control systems — Part 10: Power supplies
EN 1366-8, Fire resistance tests for service installations — Part 8: Smoke extraction ducts
prEN 1366-9, Fire resistance tests for service installations — Part 9: Single compartment smoke extraction
ducts
prEN 1366-10, Fire resistance tests for service installations — Part 10: Smoke control dampers
EN 13501-1, Fire classification of construction products and building elements — Part 1: Classification using
test data from reaction to fire tests
EN 13501-2, Fire classification of construction products and building elements —
Part 2: Classification using data from fire resistance tests, excluding ventilation services
EN 13501-3, Fire classification of construction products and building elements —
Part 3: Classification using data from fire resistance tests on products and elements used in building service
installations: fire resisting ducts and fire dampers
prEN 13501-4, Fire classification of construction products and building elements —
Part 4: Classification using data from fire resistance tests on components of smoke control systems
EN 60529, Specification for degrees of protection provided by enclosures (IP code) —
Safety signs directive (92/58/EEC)
EN ISO 5167-1, Measurement of fluid flow by means of pressure differential devices inserted in circular cross-
section conduits running full - Part 1: General principles and requirements (ISO 5167-1:2003)
ISO 2408, Steel wire ropes for general purposes – Minimum requirements
6

---------------------- Page: 8 ----------------------

SIST-TP CEN/TR 12101-4:2007
CEN/TR 12101-4:2006 (E)
ISO 5801, Industrial fans -- Performance testing using standardized airways
ISO 5221, Air distribution and air diffusion - Rules to methods of measuring air flow rate in an air handling duct
ISO 5168, Measurement of fluid flow -- Procedures for the evaluation of uncertainties
3 Definitions
For the purposes of this Technical Report, the following definitions apply (see also Annex C with drawings).
3.1
access level
level of restriction for qualified persons of the access to specific equipment of a component
3.2
air inlet
device connected to outside air to allow the inlet of air from outside the construction works
3.3
automatic activation
initiation of operation of the smoke and heat venting installation without manual action
3.4
automatic and manual activation
initiation of operation of the smoke and heat venting installation, which can be both automatic and manual
3.5
commissioning
the act of ensuring that all components and the system are installed and operating in accordance with this
standard
3.6
component
component of a SHEVS is a complete product which is part of the SHEVS : ventilator, air inlet, electric cable,
silencer, etc.
3.7
control panel
device containing control and/or release devices, manual and/or automatic, used to operate the system
3.8
detailed engineering plan (DEP)
document produced by the SHEVS designer giving technical specifications of the system, from which, by
means of a detailed engineering plan, the specifications for the system may be derived. It includes details of
controls, mode tables of how the system is to operate with particular design fires and the siting of components
(see Annex D)
3.9
fire compartment
enclosed space, comprising one or more separate spaces, bounded by elements of construction having a
specified fire resistance and intended to prevent the spread of fire (in either direction) for a given period of
time
NOTE “Fire compartment” often has regulatory connotations. The term should not be confused with "room of origin"
or "fire cell".
7

---------------------- Page: 9 ----------------------

SIST-TP CEN/TR 12101-4:2007
CEN/TR 12101-4:2006 (E)
3.10
fire position, fire open position (where appropriate)
position of a component to be reached and maintained while the SHEVS is venting smoke and heat
3.11
geometric area (A )
v
area of the opening through a ventilator, measured in the plane defined by the surface of the construction
works, where it contacts the structure of the ventilator. No reduction will be made for controls, louvres or other
obstructions (see Annex C, Figure C.1)
3.12
initiation device
device which activates the operating mechanism of the component (e.g. of a smoke control damper or
ventilator) on receipt of information from a fire or smoke detection system or thermal device
3.13
input/output characteristics
characteristics of a component of a SHEVS at the interface with other components of the SHEVS, such as
voltage, current, frequency, impedance, power, pressure, speed, diameter or flow rate
3.14
manually initiated smoke and heat exhaust ventilation system
smoke and heat exhaust ventilation system which is initiated by human actions only after the outbreak of fire
(e.g. by pressing a button or pulling a handle) leading to a sequence of automatic actions in the operation of
the SHEVS
3.15
natural ventilation
ventilation caused by buoyancy forces due to differences in density of the gases because of temperature
differences (see Annex C, Figure C.2)
3.16
operating time
maximum period between the signal to operate being received by the SHEVS and the achievement of the fire
position by the smoke zone of the SHEVS with the most unfavourable route
3.17
powered ventilation
ventilation caused by the positive displacement of gases through a ventilator
NOTE Fans are usually used.
3.18
response time
period between the signal to operate being received by the component (e.g. a control panel, ventilator or
smoke control damper) and the achievement of the fire position by the component
3.19
secondary power supply
power supply to operate the system when the normal power supply has failed
3.20
smoke and heat control system
arrangement of components installed in a construction works to limit the effects of smoke and heat from a fire
3.21
smoke and heat exhaust system
system which exhausts smoke and heat from a fire in a construction works or part of a construction works
8

---------------------- Page: 10 ----------------------

SIST-TP CEN/TR 12101-4:2007
CEN/TR 12101-4:2006 (E)
3.22
smoke and heat exhaust ventilation system (SHEVS)
set of components jointly selected to exhaust smoke and heat in order to establish a buoyant layer of warm
gases above cooler, cleaner air
3.23
smoke and heat exhaust ventilator (SHEV)
device specially designed to move smoke and hot gases out of a construction works under conditions of fire
3.24
smoke control damper
device which may be opened or closed to control the flow of smoke and hot gases. It may have the following
positions:
 Fire position: open (to exhaust smoke from fire compartment);
 closed (to avoid spreading of smoke in other zones).
 Standby position: closed.
3.25
smoke and heat exhaust duct
products used to channel the gases to and from the smoke and heat exhaust ventilator
3.26
smoke layer
layer of smoke which stabilizes underneath the roof due to the affect of temperature gradient
3.27
smoke reservoir
volume within a construction works limited or bordered by the ceiling and smoke barriers or structural
elements so as to retain a thermally buoyant smoke layer in the event of a fire (see Figure C2, Annex C)
3.28
smoke zone
room or a division of a room of a construction works for the extraction of smoke and hot gases. Each zone is
served by a SHEVS, (or sub system of a SHEVS), which is initiated by a signal from a single device or group
of initiation devices associated with the zone. A zone contains at least one smoke reservoir
3.29
stand by position
state of a component ready for operation
3.30
thermal device
temperature sensitive device which responds to initiate a subsequent action
4 Description of the principles of operation for smoke and heat control sytems
There are three principles for smoke control in construction Works:
9

---------------------- Page: 11 ----------------------

SIST-TP CEN/TR 12101-4:2007
CEN/TR 12101-4:2006 (E)
4.1 Smoke and heat control system which rely on the principle of the creation of a smoke
layer
4.1.1 Smoke layers exhausted by natural vents
The needed area of vents is measured by the free area for each zone. For efficiency of the SHEVS, the
2
maximum area of a smoke zone shall not exceed 1600 m .
Air inlets have to be provided to allow for the replacement of smoke by fresh air:
 with opening in roofs
The efficiency of the vents is measured by their aerodynamic free area: A m²
w
There shall be at least one ventilator for 200 m² of floor area.
 with opening in side-wall
The efficiency of the vents is measured by their aerodynamic free area: A m²
w
Wall mounted ventilators have to be installed on at least two different sides of the building and be monitored
by wind direction control system.
4.1.2 Layers of smoke exhausted by powered vents
Smoke and heat exhaust systems in buildings provide the possibility to remove the design amount of fire
gases from the building by applying an under pressure within the smoke compartments.
The efficiency of the powered vents is measured by the capacity of the vents measured in m³/s
The number of exhaust openings needed is determined as a function of the location and its geometry
Supply of air has to be provided to allow for the replacement of smoke by fresh air The supply air has to be
provided at a speed in accordance with the DEP and to match the needs of the largest smoke zone.
4.2 Smoke free areas by differential pressure systems
This system is taken care of by EN 12101-6, therefore, it is only given for information and not taken care of by
this Technical Report.
4.3 Air renewal of the room with fresh air by dilution of smoke
The efficiency of the sytem is measured by its capacity in m³/s.
NOTE This type of principle has to be considered to fight smoke and heat.
Nevertheless it is not an installed system, it is brought to the place in case of a fire, therefore it is not within
the scope of this standard which describes only fixed installed systems.
10

---------------------- Page: 12 ----------------------

SIST-TP CEN/TR 12101-4:2007
CEN/TR 12101-4:2006 (E)
5 Description of the combination of products for construction of SHEVS
5.1 General
The basic input to define the SHEVS, which will be used to determine the combination of products for
construction of a SHEV, is the “detailed engineering plan” . The purpose and the containt of the Detailed
engineering plan are described in Annex D .

This is valid for any principle of smoke ventilation.

The detailed engineering plan (DEP) has to be approved by the jurisdiction having authority.

5.2 General requirements
The three principles of smoke control described in 4.1 to 4.3 shall not be mixed within one room.

In the case of the layer system, natural extraction shall not be mixed with powered extraction in one smoke
zone.
Before installation, there shall be a detailed engineering plan prepared in accordance with the design
requirements and regulations valid in the place of use of the SHEVS.
The performance, the position of the components, the height of the smoke barriers and of the air inlets in
regard to the level of the smoke layer are important factors, they shall be in accordance with the DEP.
A failure of a component shall only affect the operation of that component.
Any use of the smoke and heat ventilation system for a purpose other than the ventilation of heat and smoke
under fire conditions shall not prevent the smoke and heat exhaust ventilation system from performing its
design function when required. The ventilation of heat and smoke under fire conditions shall have priority on
any other use of the system.
It shall only be possible to reset a component from the fire position to the standby position by a manual
operation.
Where one or more devices form part of the control system, components shall only be controlled by signals
coming from that control system.
All components covered by a Part of EN 12101 shall be in accordance with the relevant Part. Smoke barrier
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.