Residual current operated circuit-breakers with integral overcurrent protection for household and similar uses (RCBO's) -- Part 1: General rules

This International Standard applies to residual current operated circuit-breakers with integral overcurrent protection functionally independent of, or functionally dependent on, line voltage for household and similar uses (hereafter referred to as RCBOs), for rated voltages not exceeding 440 V a.c. with rated frequencies of 50 Hz, 60 Hz or 50/60 Hz and rated currents not exceeding 125 A and rated short-circuit capacities not exceeding 25 000 A for operation at 50 Hz or 60 Hz. These devices are intended to protect people against indirect contact, the exposed conductive parts of the installation being connected to an appropriate earth electrode and to protect against overcurrents the wiring installations of buildings and similar applications. They may be used to provide protection against fire hazards due to a persistent earth fault current, without the operation of the overcurrent protective device. RCBOs having a rated residual operating current not exceeding 30 mA are also used as a means for additional protection in the case of failure of the protective means against electric shock. This standard applies to devices performing simultaneously the function of detection of the residual current, of comparison of the value of this current with the residual operating value and of opening of the protected circuit when the residual current exceeds this value, and also of performing the function of making, carrying and breaking overcurrents under specified conditions. RCBOs of the general type are resistant to unwanted tripping, including the case where surge voltages (as a result of switching transients or induced by lightning) cause loading currents in the installation without occurrence of flashover. RCBOs of type S are considered to be sufficiently proof against unwanted tripping even if the surge voltage causes a flashover and a follow-on current occurs. RCBOs are suitable for isolation. RCBOs complying with this standard, with the exception of those with an uninterrupted neutral, are suitable for use in IT systems. Special precautions (e.g. lightning arresters) may be necessary when excessive overvoltages are likely to occur on the supply side (for example in the case of supply through overhead lines) (see IEC 60364-4-44). This standard also applies to RCBOs obtained by the assembly of an adaptable residual current device with a circuit-breaker. The mechanical assembly shall be effected in the factory by the manufacturer, or on site, in which case the requirements of Annex G shall apply. It also applies to RCBOs having more than one rated current, provided that the means for changing from one discrete rating to another is not accessible in normal service and that the rating cannot be changed without the use of a tool. Supplementary requirements may be necessary for RCBOs of the plug-in type. Particular requirements are necessary for RCBOs incorporated in or intended only for association with plugs and socket-outlets or with appliance couplers for household and similar general purposes and if intended to be used at frequencies other than 50 Hz or 60 Hz. This standard does not apply to: - RCBOs intended to protect motors; - RCBOs the current setting of which is adjustable by means accessible to the user in normal service. The requirements of this standard apply for normal environmental conditions. Additional requirements may be necessary for RCBOs used in locations having severe environmental conditions. RCBOs including batteries are not covered by this standard. A guide for the coordination of RCBOs with fuses is given in Annex F.

Fehlerstrom-/Differenzstrom-Schutzschalter mit eingebautem Überstromschutz (RCBOs) für Hausinstallationen und für ähnliche Anwendungen -- Teil 1: Allgemeine Anforderungen

Interrupteurs automatiques à courant différentiel résiduel avec protection contre les surintensités incorporée pour installations domestiques et analogues (DD) -- Partie 1: Règles générales

Odklopniki na preostali (residualni) tok z vgrajeno nadtokovno zaščito za gospodinjsko in podobno rabo (RCBO's) – 1. del: Splošna pravila

Ta mednarodni standard se uporablja za odklopnike na preostali (residualni) tok z vgrajeno nadtokovno zaščito, ki so funkcionalno neodvisni ali odvisni od linijske napetosti, za gospodinjsko in podobno rabo (v nadaljnjem besedilu: RCBO), za nazivne napetosti do vključno 440 V izmenične napetosti, pri čemer nazivna frekvenca dosega 50 Hz, 60 Hz ali 50/60 Hz, nazivni tok ne presega 125 A, nazivne kratkostične zmogljivosti pa ne presegajo 25000 A med delovanjem pri 50 Hz ali 60 Hz. Te naprave so namenjene zaščiti oseb pred posrednim stikom, pri čemer so izpostavljeni prevodni deli inštalacije povezani z ustreznim ozemljilom, in zaščiti napeljav stavb in podobnih aplikacij pred nadtoki. Uporabljajo se lahko za zaščito pred požarom zaradi stalnega ozemljitvenega okvarnega toka brez naprave za nadtokovno zaščito. Tudi odklopniki na preostali (residualni) tok z vgrajeno nadtokovno zaščito (RCBO) z nazivnim preostalim operativnim tokom do vključno 30 mA se uporabljajo kot dodatna zaščita v primeru odpovedi zaščitnega sredstva pred električnim udarom. Ta standard se uporablja za naprave, ki hkrati izvajajo funkcije zaznavanja preostalega (residualnega) toka, primerjanja vrednosti tega toka s preostalo operativno vrednostjo in odprtja zaščitenega tokokroga, kadar preostali tok presega to vrednost, ter tudi funkcijo ustvarjanja, prenosa in prekinitve nadtokov pod določenimi pogoji. Odklopniki RCBO splošnega tipa se ne morejo po nesreči odklopiti, tudi kadar previsoka napetost (zaradi prehodnih preklapljanj ali udara strele) povzroči obremenilne tokove v inštalaciji brez nastanka preboja. Odklopniki RCBO tipa S naj bi v zadostni meri ščitili pred neželenim odklopom, celo kadar previsoka napetost povzroči preboj in nastane nadaljnji tok. Odklopniki RCBO so primerni za izolacijo. Odklopniki RCBO, ki so skladni s tem standardom, razen odklopnikov z neprekinjeno nevtralno točko, so primerni za uporabo v sistemih IT. Posebni zaščitni ukrepi (npr. prenapetostni odvodniki) so lahko potrebni, kadar lahko na strani dobave nastane prekomerna prenapetost (na primer v primeru dobave prek nadzemnih vodov) (glejte standard 60364-4-44). Ta standard se uporablja tudi za odklopnike RCBO, ki se pridobijo z montažo naprave s prilagodljivim preostalim (residualnim) tokom z odklopnikom. Mehansko montažo izvede proizvajalec v tovarni ali se opravi na kraju samem, v tem primeru pa se uporabljajo zahteve Dodatka G. Uporablja se tudi za odklopnike RCBO z več kot enim nazivnim tokom, če sredstvo za spreminjanje nazivnega toka ni na voljo med običajnim delovanjem in se nazivni tok ne more spremeniti brez uporabe orodja. Dodatne zahteve so lahko potrebne za vtične odklopnike RCBO. Posebne zahteve so potrebne za odklopnike RCBO, vgrajene v ali namenjene le uporabi z vtiči in vtičnicami ali s spojkami naprave za gospodinjsko in podobno splošno rabo in če so namenjeni uporabi pri frekvencah, ki niso 50 Hz ali 60 Hz. Ta standard se ne uporablja za: – odklopnike RCBO, namenjene zaščiti motorjev; – odklopnike RCBO, katerih trenutno nastavitev je mogoče prilagoditi s sredstvi, ki so uporabniku na voljo med običajnim delovanjem. Zahteve tega standarda se uporabljajo za običajne okoljske pogoje. Dodatne zahteve so lahko potrebne za odklopnike RCBO, ki se uporabljajo na lokacijah z neugodnimi okoljskimi pogoji. Ta standard ne zajema odklopnikov RCBO z akumulatorji. V Dodatku F so zajeta navodila za usklajevanje odklopnikov RCBO z varovalkami.

General Information

Status
Withdrawn
Publication Date
04-May-2008
Withdrawal Date
16-May-2017
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
16-May-2017
Due Date
08-Jun-2017
Completion Date
17-May-2017

Relations

Buy Standard

Amendment
EN 61009-1:2005/A11:2008
English language
23 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 61009-1:2005/A11:2008
01-junij-2008
2GNORSQLNLQDSUHRVWDOL UHVLGXDOQL WRN]YJUDMHQRQDGWRNRYQR]DãþLWR]D
JRVSRGLQMVNRLQSRGREQRUDER 5&%2
V ±GHO6SORãQDSUDYLOD
Residual current operated circuit-breakers with integral overcurrent protection for
household and similar uses (RCBO's) - Part 1: General rules
Fehlerstrom-/Differenzstrom-Schutzschalter mit eingebautem Überstromschutz (RCBOs)
für Hausinstallationen und für ähnliche Anwendungen - Teil 1: Allgemeine Anforderungen
Interrupteurs automatiques a courant différentiel résiduel avec protection contre les
surintensités incorporée pour installations domestiques et analogues (DD) - Partie 1:
Regles générales
Ta slovenski standard je istoveten z: EN 61009-1:2004/A11:2008
ICS:
29.120.50 9DURYDONHLQGUXJD Fuses and other overcurrent
PHGWRNRYQD]DãþLWD protection devices
SIST EN 61009-1:2005/A11:2008 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

EUROPEAN STANDARD
EN 61009-1/A11

NORME EUROPÉENNE
April 2008
EUROPÄISCHE NORM

ICS 29.120.50


English version


Residual current operated circuit-breakers
with integral overcurrent protection
for household and similar uses (RCBO's) -
Part 1: General rules



Interrupteurs automatiques à courant Fehlerstrom-/Differenzstrom-
différentiel résiduel avec protection Schutzschalter mit eingebautem
contre les surintensités incorporée Überstromschutz (RCBOs)
pour installations domestiques et für Hausinstallationen und
analogues (DD) - für ähnliche Anwendungen -
Partie 1: Règles générales Teil 1: Allgemeine Anforderungen




This amendment A11 modifies the European Standard EN 61009-1:2004; it was approved by CENELEC on
2007-12-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this amendment the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This amendment exists in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CENELEC member into its own language and notified to the
Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels


© 2008 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 61009-1:2004/A11:2008 E

---------------------- Page: 2 ----------------------

EN 61009-1:2004/A11:2008 – 2 –
Foreword
This amendment to the European Standard EN 61009-1:2004 was prepared by the Technical
Committee CENELEC TC 23E, Circuit breakers and similar devices for household and similar
applications.
The text of the draft was submitted to the Unique Acceptance Procedure and was approved by
CENELEC as amendment A11 to EN 61009-1:2004 on 2007-12-01.
The following dates were fixed:
− latest date by which the amendment has to be implemented

at national level by publication of an identical

national standard or by endorsement
(dop) 2008-12-01
− latest date by which the national standards conflicting

with the amendment have to be withdrawn
(dow) 2009-04-01
_________

---------------------- Page: 3 ----------------------

– 3 – EN 61009-1:2004/A11:2008

Add
Contents
Annex ZE (normative) Particular requirements for RCBOs with screwless type terminals
for external copper conductors
Annex ZF (normative) Particular requirements for RCBOs with flat quick-connect
terminations
Figure Z7 – Diagrammatic representation of a small part
Table Z3 – Requirements for marking
4 Classification
Replace the existing subclause title and text by the following new subclause:
4.10
4.10 According to the methods of connection
4.10.1 According to the fixation system:
– RCBO’s, the electrical connections of which are not associated with the
mechanical mounting;
– RCBO’s, the electrical connections of which are associated with the mechanical
mounting.
NOTE  Examples of this type are:
– plug-in type;
– bolt-on type;
– screw-in type.
Some RCBO’s may be of the plug-in type or bolt-on type on the line side only, the load terminals being
usually suitable for wiring connection.
4.10.2 According to the type of terminals:
– RCBO’s with screw-type terminals for external copper conductors;
– RCBO’s with screwless type terminals for external copper conductors;
NOTE 1  The requirements for RCBO’s equipped with this type of terminals are given in Annex ZE.
– RCBO’s with flat quick-connect terminals for external copper conductors;
NOTE 2  The requirements for RCBO’s equipped with this type of terminals are given in Annex ZF.
5 Characteristics of RCBOs
5.3.1 Replace the table by the following:

RCBO Rated voltage of RCB0s for use in systems
230 V, 230 V/400 V, 400V
230 V
Two-pole
400 V
Three-pole 400 V
Four-pole 400 V

---------------------- Page: 4 ----------------------

EN 61009-1:2004/A11:2008 – 4 –

5.3.8 Add, in the seventh column heading of Table 2, a reference to footnote e) after
"500 A".
Delete, in footnote b) of Table 2, "500 A".
Add the following new footnote e):
e)
The verification of the break times at 500 A is only made for the test of 9.9.1.2.c, but in any case
the test is not done for values exceeding the lower limit of the overcurrent instantaneous tripping
range.
6 Marking and other product information
6.Z1 Replace the whole subclause by:
6.Z1 Standard marking
Each RCBO shall be marked in a durable manner according to the following
Table Z3.
For RCBOs other than those operated by means of push-button, the open
position shall be indicated by the symbol "Ο" and the closed position by the
symbol "|" (a short straight line).
Additional national symbols are allowed for this indication. Provisionally the use
of national indications only is allowed. These indications shall be readily visible
when the RCBO is installed.
For RCBOs operated by means of two push-buttons, the push-button designed for
the opening operation only shall be RED and/or be marked with the symbol "O".
RED shall not be used for any other push-button of the RCBO.
If a push-button is used for closing the contacts and is evidently identified as
such, its depressed position is sufficient to indicate the closed position.
If a single push-button is used for closing and opening the contacts and is
identified as such, the button remaining in its depressed position is sufficient to
indicate the closed position. On the other hand, if the button does not remain
depressed, an additional means indicating the position of the contacts shall be
provided.
If it is necessary to distinguish between the supply and the load terminals, they
shall be clearly marked (e.g. by "line" and "load" placed near the corresponding
terminals or by arrows indicating the direction of power flow).
Terminals exclusively intended for the connection of the neutral circuit shall be
indicated by the letter N.
Terminals intended for the protective conductor, if any, shall be indicated
by the symbol (IEC 60417-5019 a)).

---------------------- Page: 5 ----------------------

– 5 – EN 61009-1:2004/A11:2008
NOTE The symbol (IEC 60417-5017 a)), previously recommended, shall be progressively
superseded by the preferred symbol IEC 60417-5019 a), given above.
If a degree of protection higher than IP20 is marked on the device, it shall comply
with it, whichever the method of installation. If the higher degree of protection is
obtained only by a specific method of installation and/or with the use of specific
accessories (e.g. terminal covers, enclosures, etc.), this shall be specified in the
manufacturer's literature
The suitability for isolation, which is provided by all RCBOs of this standard, may
be indicated by the symbol on the device. When affixed, this marking
may be included in a wiring diagram, where it may be combined with symbols of
other functions, (e.g. overload protection, or other symbols of IEC TC 3). When
the symbol is used on its own (i.e. not in a wiring diagram), combination with
symbols of other functions is not allowed.
The base for plug-in RCBOs shall be marked with the following:
- rated current or maximum rated current;
- trade mark.
Marking shall be indelible, easily legible and not be placed on screws, washers
or other removable parts.
Compliance is checked by inspection and by the test of 9.3.
6.Z2 Replace the whole subclause by:
6.Z2 Additional marking
Additional marking to other standards (EN or IEC or other) or additional
requirements are allowed under the following conditions:
– the RCBO shall comply with all the requirements of the additional standard;
– the relevant standard to which the additional marking refers shall be
indicated adjacent to this marking and shall be clearly differentiated or
separated from the standard marking according to 6.Z1.
Compliance is checked by inspection and by carrying out all the test sequences
required by the relevant standard. Equivalent or less severe test sequences
need not be repeated.

---------------------- Page: 6 ----------------------

EN 61009-1:2004/A11:2008 – 6 –

Table Z3 – Requirements for marking
 Product information in
Marking on the RCBO itself
the catalogue
Each RCBO shall be marked in a durable manner with all or, If, for small devices the The following Alternatively the Any remaining
for small apparatus, part of the following data: space available does information may be following information information not marked
The minimum requirements are indicated by the symbol "X" not allow all the data to marked on the side or may be on the inside of shall be given in the
be marked, at least the on the back of the any cover which has to manufacturer's
following information device and be visible be removed in order to catalogues.
only before the device is
shall be marked and connect the supply
visible when the installed. wires.
device is installed.
a) the manufacturer's name or trademark; X
b) type designation, catalogue number or serial number; X
c) rated voltage(s) with the symbol ~; X
d) rated current without symbol "A", preceded by the symbol of X
overcurrent instantaneous tripping (B, C or D), for example B16;
e) rated frequency, if the RCBO is designed for frequencies other X
than 50 Hz (see 5.3.5);
f) rated residual operating current (I ) in A or in mA; X
∆n
g) deleted;
h) rated short circuit capacity, in amperes in a rectangle without X (*)
symbol "A";
j) reference calibration temperature, if different from 30 °C;  X
k) the degree of protection (only if different from IP20);  X
l) the position of use (symbol according to IEC 60051), if necessary; X
m)  X
rated residual making and breaking capacity (I ), if different from
∆m
rated short-circuit capacity (I );
cn
n) X
the symbol  S (S in a square) for type S devices;
o) symbol of the method of operation according to Table Z1 of 4.1 if X X
the RCBO is functionally dependent on the line voltage;

---------------------- Page: 7 ----------------------

– 7 – EN 61009-1:2004/A11:2008


Product information in
Marking on the RCBO itself
the catalogue
Each RCBO shall be marked in a durable manner with all or, If, for small devices the The following Alternatively the Any remaining
for small apparatus, part of the following data: space available does information may be following information information not marked
The minimum requirements are indicated by the symbol "X" not allow all the data to marked on the side or may be on the inside of shall be given in the
be marked, at least the on the back of the any cover which has to manufacturer's
catalogues.
following information device and be visible be removed in order to
shall be marked and only before the device is connect the supply
visible when the installed. wires.
device is installed.
b
q) operating means of the test device, by the letter T ; X
r) wiring diagram unless the correct mode of operation is evident; X X
operating characteristic in presence of residual currents with
s)
d.c. components
X
  - RCBOs of type AC with the symbol

X
  - RCBOs of type A with the symbol
a
t) energy limiting class (e.g. 3) in a square in accordance with X
Annex ZD if applied;
u) X
RCBOs according to 4.Z1 shall be marked with the symbol

(the value -25 included in the snow flake symbol according to
Figure 0027 of ISO 7000) if relevant;
v) indication of the terminal for the neutral with "N"; X
w) additional marking of performance to other standards or additional X
requirements according to 6.Z2.
a
 I and the energy limiting class shall be on the device and combined together.
cn
b
 It is recommended to advise the user to test the device regularly.

---------------------- Page: 8 ----------------------

EN 61009-1:2004/A11:2008 – 8 –
6.Z3 Delete this subclause.
8 Requirements for construction and operation
8.1.3 Add in item 2 of Table 5 the reference to footnote j).
Delete item 5 of Table 5.
Add the following new footnote j) in Table 5:

j)
This applies also to clearance and creepage distances between live parts of different polarity of the
RCBO and equipments mounted close to it.
Delete note 3 after Table 5.

8.1.5.1 Delete the second paragraph and the relevant note.
Replace the last paragraph by the following:
Compliance is checked by inspection, by the tests of 9.5 for screw-type terminals,
by specific tests for plug-in or bolt-on RCBO’s included in the standard, or by the
tests of Annex ZE or ZF, as relevant for the type of connection.
Replace the existing note by the following new note:
8.1.5.2
NOTE Examples of possible designs of screw-type terminals are given in Annex IC.
8.5.2.Z1 Add the following new subclause:
8.5.2.Z1 Effect of single phase loading of multi-pole RCBO on the tripping
characteristic
Single phase loading of RCBO with more than 2 current paths shall not have a
significant effect on the overcurrent tripping characteristic.
Compliance is checked by the tests of 9.9.2.Z1.
9 Tests
Replace the existing title of this subclause by the following new title:
9.5
9.5 Tests of reliability of screw-type terminals for external copper conductors
Delete item d).
9.7.2
Rename item e) as item d).

Modify the beginning of the last but one paragraph as follows:

“For the measurements according to items b) to d), ….”

---------------------- Page: 9 ----------------------

– 9 – EN 61009-1:2004/A11:2008
Add the following new subclause:
9.9.2.Z1
9.9.2.Z1 Test of effect of single phase loading on the over-current tripping
characteristic of RCBO with three or four current paths
This test does not apply to RCBOs obtained by the assembly of an adaptable
residual current unit on a circuit-breaker.
RCBOs with three or four current paths are loaded on 2 current paths. Where a
switched neutral pole exists, the test circuit shall include the neutral pole. The test
current having the value of 1,2 times the conventional tripping current is applied,
starting from cold.
Except for the neutral pole if applicable, the test is carried out on different poles for
each sample.
The RCBO shall trip within the conventional times as for test b according to Table 8.
Add the following definition of small parts after the note:
9.15
Small parts, where each surface lies completely within a circle of 15 mm diameter,
or where any part of the surface lies outside a 15 mm diameter circle and it is not
possible to fit a circle of 8 mm diameter on any of the surfaces, are not subjected to
the test of this subclause (see Figure Z7 for diagrammatic representation).

Figures Add the following new Figure Z7:

Figure Z7 – Diagrammatic representation of a small part

---------------------- Page: 10 ----------------------

EN 61009-1:2004/A11:2008 – 10 –

Add the following normative references to Annex ZA:
Annex ZA
IEC publication Date Title EN / EN Date
IEC 60228 - Conductors of insulated cables EN 60228 -
IEC 61210 - Connecting devices – Flat quick-connect EN 61210 -
terminations for electrical copper conductors –
Safety requirements

Add the following to Annex ZB:
Annex ZB
Clause Special national condition
ZE.1 Austria, Czech Republic, Denmark, Netherlands, Norway and
Switzerland
The upper limit of current for use of screwless terminals is 16 A.
ZE.3.3 Austria, Belgium, Denmark, France, Germany, Ireland, Italy,
Portugal, Spain, Sweden, Switzerland and United Kingdom
Only universal screwless type terminals are accepted.
ZF.1 Belgium, France, Ireland, Italy, Portugal, Spain and United Kingdom
The use of RCBOs with flat quick-connect terminations for rated currents
up to and including 20 A is accepted.
ZF.8.2.2 Belgium, France, Ireland, Italy, Portugal, Spain and United Kingdom
The use for rated currents up to and including 20 A is accepted.

Add the following new Annex ZE:
Annex ZE
Annex ZE
(normative)

Particular requirements for RCBOs with screwless type
terminals for external copper conductors
ZE.1 Scope
This annex applies to RCBOs within the scope of Clause 1, equipped with screwless terminals, for
current not exceeding 20 A primarily suitable for connecting unprepared (see ZE.3.6) copper
2
conductors of cross-section up to 4 mm .
In this annex, screwless terminals are referred to as terminals and copper conductors are referred to
as conductors.

---------------------- Page: 11 ----------------------

– 11 – EN 61009-1:2004/A11:2008
ZE.3 Definitions
As a complement to Clause 3, the following definitions apply:
ZE.3.1
clamping units
parts of the terminal necessary for mechanical clamping and the electrical connection of the
conductors including the parts which are necessary to ensure correct contact pressure
ZE.3.2
screwless-type terminal
terminal for the connection and subsequent disconnection obtained directly or indirectly by means of
springs, wedges or the like
NOTE Examples are given in Figure ZE.2.
ZE.3.3
universal terminal
terminal for the connection and disconnection of all types of conductors (rigid and flexible)
ZE.3.4
non-universal terminal
terminal for the connection and disconnection of a certain kind of conductor only (e.g. rigid-solid
conductors only or rigid-[solid or stranded] conductors only)
ZE.3.5
push-wire terminal
non-universal terminal in which the connection is made by pushing-in rigid (solid or stranded)
conductors
ZE.3.6
unprepared conductor
conductor which has been cut and the insulation of which has been removed over a certain length for
insertion into a terminal
NOTE 1 A conductor the shape of which is arranged for introduction into a terminal or of which the strands may be twisted to
consolidate the end, is considered to be an unprepared conductor.
NOTE 2 The term "unprepared conductor" means conductor not prepared by soldering of the wire, use of cable lugs, formation
...

Questions, Comments and Discussion