Automatic electrical controls for household and similar use - Part 2-5: Particular requirements for automatic electrical burner control systems (IEC 60730-2-5:2000/A2:2008, modified)

Applies to automatic electrical burner control systems for the automatic control of buners for oil, gas, coal or other combustibles for household and similar use including heating, air conditioning and similar use. This part is applicable to a complete burner control system and to separate programming unit. Is also applicable to a separate electronic high-voltage ignition source and to a separate flame detector.

Automatische elektrische Regel- und Steuergeräte für den Hausgebrauch und ähnliche Anwendungen - Teil 2-5: Besondere Anforderungenan automatische elektrische Brenner-Steuerungs- und Überwachungssysteme (IEC 60730-2-5:2000/A2:2008, modifiziert)

Dispositifs de commande électrique automatiques à usage domestique et analogue - Partie 2-5: Règles particulières pour les systèmes de commande électrique automatiques des brûleurs (CEI 60730-2-5:2000/A2:2008, modifié)

Avtomatske električne krmilne naprave za uporabo v gospodinjstvu in za podobno uporabo - 2-5. del: Posebne zahteve za avtomatske električne krmilne sisteme (regulatorje) gorilnikov (IEC 60730-2-5:2000/A2:2008, spremenjen)

Uporablja se za avtomatske električne krmilne sisteme (regulatorje) gorilnikov, za avtomatsko krmiljenje gorilnikov za olje, plin, premog ali druga goriva za uporabo v gospodinjstvu in za podobno uporabo, vključno z ogrevanjem, klimatizacijo in podobno uporabo. Ta del se uporablja za celotne krmilne sisteme (regulatorje) gorilnikov in za posamezne enote za programiranje. Uporablja se tudi za posamezne elektronske visokonapetostne vire vžiga in za posamezne plamenske javljalnike.

General Information

Status
Withdrawn
Publication Date
08-Jul-2010
Withdrawal Date
06-Feb-2018
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
30-Jan-2018
Due Date
22-Feb-2018
Completion Date
07-Feb-2018

Relations

Buy Standard

Amendment
EN 60730-2-5:2002/A2:2010
English language
22 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 60730-2-5:2002/A2:2010
01-september-2010
$YWRPDWVNHHOHNWULþQHNUPLOQHQDSUDYH]DXSRUDERYJRVSRGLQMVWYXLQ]DSRGREQR
XSRUDERGHO3RVHEQH]DKWHYH]DDYWRPDWVNHHOHNWULþQHNUPLOQHVLVWHPH
UHJXODWRUMH JRULOQLNRY ,(&$VSUHPHQMHQ
Automatic electrical controls for household and similar use - Part 2-5: Particular
requirements for automatic electrical burner control systems (IEC 60730-2-
5:2000/A2:2008, modified)
Automatische elektrische Regel- und Steuergeräte für den Hausgebrauch und ähnliche
Anwendungen - Teil 2-5: Besondere Anforderungenan automatische elektrische Brenner
-Steuerungs- und Überwachungssysteme (IEC 60730-2-5:2000/A2:2008, modifiziert)
Dispositifs de commande électrique automatiques à usage domestique et analogue -
Partie 2-5: Règles particulières pour les systèmes de commande électrique
automatiques des brûleurs (CEI 60730-2-5:2000/A2:2008, modifié)
Ta slovenski standard je istoveten z: EN 60730-2-5:2002/A2:2010
ICS:
97.120 Avtomatske krmilne naprave Automatic controls for
za dom household use
SIST EN 60730-2-5:2002/A2:2010 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 60730-2-5:2002/A2:2010

---------------------- Page: 2 ----------------------

SIST EN 60730-2-5:2002/A2:2010

EUROPEAN STANDARD
EN 60730-2-5/A2

NORME EUROPÉENNE
March 2010
EUROPÄISCHE NORM

ICS 97.120


English version


Automatic electrical controls for household and similar use -
Part 2-5: Particular requirements for automatic
electrical burner control systems
(IEC 60730-2-5:2000/A2:2008, modified)


Dispositifs de commande électrique Automatische elektrische Regel- und
automatiques à usage domestique Steuergeräte für den Hausgebrauch
et analogue - und ähnliche Anwendungen -
Partie 2-5: Règles particulières pour Teil 2-5: Besondere Anforderungen
les systèmes de commande électrique an automatische elektrische Brenner-
automatiques des brûleurs Steuerungs- und Überwachungssysteme
(CEI 60730-2-5:2000/A2:2008, modifié) (IEC 60730-2-5:2000/A2:2008, modifiziert)




This amendment A2 modifies the European Standard EN 60730-2-5:2002; it was approved by CENELEC on
2010-03-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this amendment the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This amendment exists in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CENELEC member into its own language and notified to the
Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia,
Spain, Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: Avenue Marnix 17, B - 1000 Brussels


© 2010 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 60730-2-5:2002/A2:2010 E

---------------------- Page: 3 ----------------------

SIST EN 60730-2-5:2002/A2:2010
EN 60730-2-5:2002/A2:2010 - 2 -
Foreword
The text of amendment 2:2008 to the International Standard IEC 60730-2-5:2000, prepared by
IEC TC 72, Automatic controls for household use, together with the common modifications prepared
by the Technical Committee CENELEC TC 72, Automatic controls for household use, was submitted
to the CENELEC formal vote and was approved as amendment A2 to the EN 60730-2-5:2002 on
2010-03-01.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN and CENELEC shall not be held responsible for identifying any or all such patent
rights.

The following dates were fixed:
– latest date by which the amendment has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2011-03-01

– latest date by which the national standards conflicting
with the amendment have to be withdrawn (dow) 2013-03-01

This amendment to Part 2-5 is to be used in conjunction with EN 60730-1:2000, Automatic electrical
controls for household and similar use – Part 1: General requirements and any subsequent
amendments.

---------------------- Page: 4 ----------------------

SIST EN 60730-2-5:2002/A2:2010
- 3 - EN 60730-2-5:2002/A2:2010
Endorsement notice
The text of amendment 2:2008 to the International Standard IEC 60730-2-5:2000 was approved by
CENELEC as an amendment to the European Standard with the following common modifications.

COMMON MODIFICATIONS

11 Constructional requirements
11.3.5 Contacts – General
11.3.5.101
11.3.5.101.1 Measures to prevent common mode errors
Delete the following:
“Requirements and test methods are under consideration.”
J.20 Creepage distances, clearances and distances through insulation
Delete the following:
“Replace the existing text with the following new text:
This clause of Part 1 is replaced as follows: “Under consideration.” ”
Table H.27.1 – Electrical/electronic component fault modes
Delete the last paragraph of footnote 7:
“In Canada, Japan and the USA, the short-circuit mode is excluded for relays successfully tested to Clause 17. The successful
test can be substituted by the use of a relay certified for the application.”

---------------------- Page: 5 ----------------------

SIST EN 60730-2-5:2002/A2:2010
EN 60730-2-5:2002/A2:2010 - 4 -
Annex ZA
(normative)

Normative references to international publications
with their corresponding European publications
Delete the following reference:

Publication Year Title EN/HD Year

IEC 60384-16 1982 Fixed capacitors for use in electronic equipment- -
Part 16: Sectional specification: Fixed metallized
polypropylene film dielectric d.c. capacitors


Add the following references:

Publication Year Title EN/HD Year

IEC 60127-1 2006 Miniature fuses EN 60127-1 2006
Part 1: Definitions for miniature fuses and general
requirements for miniature fuse-links

IEC 60947-1 2007 Low-voltage switchgear and controlgear EN 60947-1 2007
Part 1: General rules

IEC 60947-5-1 2003 Low-voltage switchgear and controlgear EN 60947-5-1 2004
Part 5-1: Control circuit devices and switching
elements - Electromechanical control circuit devices


______________

---------------------- Page: 6 ----------------------

SIST EN 60730-2-5:2002/A2:2010
IEC 60730-2-5
Edition 3.0 2008-11
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
AMENDMENT 2
AMENDEMENT 2
Automatic electrical controls for household and similar use –
Part 2-5: Particular requirements for automatic electrical burner control systems

Dispositifs de commande électrique automatiques à usage domestique et
analogue –
Partie 2-5: Règles particulières pour les systèmes de commande électrique
automatiques des brûleurs

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
R
CODE PRIX
ICS 97.120 ISBN 2-8318-1015-8
® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale

---------------------- Page: 7 ----------------------

SIST EN 60730-2-5:2002/A2:2010
– 2 – 60730-2-5 Amend. 2 © IEC:2008
FOREWORD
This amendment has been prepared by IEC technical committee 72: Automatic controls for
household use.
The text of this amendment is based on the following documents:
FDIS Report on Voting
72/770/FDIS 72/773/RVD

Full information on the voting for the approval of this amendment can be found in the report
on voting indicated in the above table.
This amendment is based on 60730-2-5, Edition 3 (2000) and its Amendment 1 (2004).
The committee has decided that the contents of this amendment and the base publication will
remain unchanged until the maintenance result date indicated on the IEC web site under
"http://webstore.iec.ch" in the data related to the specific publication. At this date, the
publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.

_____________

Page 5
FOREWORD
Replace, on page 7, the third paragraph after the report on voting table by the following new
paragraph:
This Part 2-5 is intended to be used in conjunction with IEC 60730-1. It was established on
the basis of the third edition (1999) and Amendment 1 (2003) and Amendment 2 (2007) of that
publication. Consideration may be given to future editions of, or amendments to, IEC 60730-1.

Page 7
Replace the “in some countries” note by the following new note:
The “in some countries” notes regarding differing national practices are contained in the following subclauses:
– 2.3.127
– 6.11
– 15.7
– 17.16.102.1
– H.26.10
– H.26.11.103
– Table H.27.1, Note 7

---------------------- Page: 8 ----------------------

SIST EN 60730-2-5:2002/A2:2010
60730-2-5 Amend. 2 © IEC:2008 – 3 –
– H.27.1.3

Page 11
1.5 Normative references
Delete the following reference:
IEC 60384-16:1982, Fixed capacitors for use in electronic equipment – Part 16: Sectional
specification: Fixed metallized polypropylene film dielectric d.c. capacitors
Add the following new references:
IEC 60127-1:2006, Miniature fuses – Part 1: Definitions for miniature fuses and general
requirements for miniature fuse-links
IEC 60947-1:2007, Low-voltage switchgear and controlgear – Part 1: General rules
IEC 60947-5-1:2003, Low-voltage switchgear and controlgear – Part 5-1: Control circuit
devices and switching elements – Electromechanical control circuit devices

Page 13
2 Definitions
Replace, on page 17, definitions 2.3.112, 2.2.112.1 and 2.3.112.2 by the following:
2.3.112
lock-out
process in which the system goes into one of the following lock-out conditions, following
safety shutdown
2.3.112.1
non-volatile lock-out
condition such that a restart can only be accomplished by a manual reset of the system and
by no other cause
2.3.112.2
volatile lock-out
condition such that a restart can be accomplished by either a manual reset of the system or
by an interruption of the power supply and its subsequent restoration

Page 25
4.1.1 Revise the font of the text to italics.

---------------------- Page: 9 ----------------------

SIST EN 60730-2-5:2002/A2:2010
– 4 – 60730-2-5 Amend. 2 © IEC:2008
Page 29
6.7 According to ambient temperature limits of the system and system components
Delete the modification to replace the title of the subclause.

Page 31
7.2.9 Replace “Replacement:” with “Modification:”.

Page 33
Table 7.2
In the table, delete Items 52 and 57.
Replace items 119 and 126 as follows:
Information Clause or subclause Method
119 See Annex H
102)
11.3.107, 13.2.101 D
126 Electronic high-voltage ignition spark gap

Add the following new rows:

135 Type of lock-out 2.3.112, 11.3.108, H.27.1.3.101 D
136 See Annex H

Page 37
8.1.101 High-voltage ignition sources
Replace item a) with the following item:
a) for continuous spark ignition (pulses within the mains frequency range):
– the maximum voltage is higher than 10 kV (peak), and/or
– the maximum current is higher than 0,7 mA (peak);
Figure 101
Replace the existing figure title with the following new title:
Figure 101 – Pulse spark generation

---------------------- Page: 10 ----------------------

SIST EN 60730-2-5:2002/A2:2010
60730-2-5 Amend. 2 © IEC:2008 – 5 –
Page 39
11 Constructional requirements
Add the following new subclause:
11.3.5 Contacts – General
Additional subclauses:
11.3.5.101 The system shall include at least two switching elements to directly de-energize
the safety relevant valve terminals.
NOTE A single relay operating two independent contacts is considered to be only one switching element.
11.3.5.101.1 Measures to prevent common mode errors
Requirements and test methods are under consideration.

Page 41
11.3.105
Replace the last paragraph with the following new paragraph:
Compliance is checked by H.26.5.4.
Delete subclauses 11.3.105.1 to 11.3.105.6 inclusive including the ”in some countries” note.

Page 47
Add, after 11.4.15, the following text:
Additional subclauses:

Page 49
Add the following new subclause after 11.11.6:
11.13 Not applicable.

---------------------- Page: 11 ----------------------

SIST EN 60730-2-5:2002/A2:2010
– 6 – 60730-2-5 Amend. 2 © IEC:2008
Page 55
15 Manufacturing deviation and drift
Replace “Replacement:” with “This clause of Part 1 is replaced as follows:”.

Page 67
25 Normal operation
Replace “See annex H.” with “This clause of Part 1 is applicable.”
27 Abnormal operation
Delete “See annex H.”
28 Guidance on the use of electronic disconnection
Replace “See annex H.” with “This clause of Part 1 is applicable.”

Page 69
Annex H – Requirements for electronics
Replace the existing title with the following new title:
Annex H – Requirements for electronic controls
H.2.5 Definitions of type of control according to the construction
Delete the addition of definition H.2.5.101.

---------------------- Page: 12 ----------------------

SIST EN 60730-2-5:2002/A2:2010
60730-2-5 Amend. 2 © IEC:2008 – 7 –
H.7 Information
Table 7.2
Add, to the existing modification, the following new instructions:
Information Clause or Method
subclause
Modify the existing requirement:
71 Not applicable
Add the following additional requirement:
119 Defined state ”out of operation” H.26.8.2 X
Add the following additional requirement: H.27.1.3.102 X
12), 104), 105)
136 Software fault/error detection time(s) for controls of software class C H.27.1.3.103
106)

NOTES:
Additional notes:
104)
The fault/error detection time is the period between the execution (after the
fault has occurred), of the relevant software segment, either for function or for
checking purposes and the completion of the declared control response.
105)
For systems designed for non-permanent operations, the fault/error detection
time for the:
• first fault shall be according to H.27.1.3.102.1 and H.27.1.3.104.1
• second fault shall be according to H.27.1.3.102.2 and H.27.1.3.104.2
106)
For systems designed for permanent operations, the fault/error detection time
for the:
• first fault shall be according to H.27.1.3.103.1 and H.27.1.3.104.1
• second fault shall be according to H.27.1.3.103.2 and H.27.1.3.104.2

Page 71
Add, after H.11.12.12, the following new subclause:
Additional subclause:
H.11.12.101 If time slot monitoring is used, it shall be sensitive to both an upper and a lower
limit of the time interval. Faults resulting in the shift of the upper and/or lower limit shall be
taken into account.

Add, after Clause H.26, the following new subclause:
H.26.1 Modification:
The third paragraph is not applicable.

---------------------- Page: 13 ----------------------

SIST EN 60730-2-5:2002/A2:2010
– 8 – 60730-2-5 Amend. 2 © IEC:2008
Page 73
H.26.5 Test of the influence of voltage dips and short voltage interruptions in the
power supply network
Replace the existing title with the following new title:
H.26.5 Voltage dips and voltage interruptions in the power supply network

H.26.5.2
Delete the existing subclause (introduced by Amendment 1) and replace with following new
subclause:
H.26.5.2 Test values
Replacement:
The system shall tolerate voltage dips, short interruptions and voltage variations in the
electricity supply so that, when tested in accordance with H.26.5.3,
a) for the values of Table H.101 criteria a): it shall continue to function in accordance with
the requirements of this standard. It shall neither proceed to safety shutdown or lock-out,
nor shall it reset from lock-out;
b) for the values of Table H.101 criteria b): either it shall perform as in a) or it may proceed
to safety shutdown followed by a system restart, or if in volatile lock-out it may proceed to
a system restart.
NOTE Non-volatile lock-out excludes the use of system restart.
When the power supply is restored, the system restart shall comply with the requirements for
a start-up sequence.
Requirement b) can be ignored, provided that the power failure is less than 60 s and occurs
within 60 s after call for heat. On restoration of the power, the programme may be continued
from the point at which it was interrupted.
A shortened start-up sequence, for example, a start-up sequence without pre-purge or waiting
time, is allowed, provided that the power failure occurs within 60 s after the end of the start-up
sequence and is shorter than 60 s.
Table H.101 – Voltage dips, short interruptions and voltage variations
ΔU
Assessment
Duration
criteria
30 % 60 % 100 %
a) Half-cycle of supply waveform  X
One cycle of supply waveform X
b) 2,5 cycles X X X
25 cycles 50 cycles X X X
X X X

The test shall be performed in accordance with H.26.5.3.

---------------------- Page: 14 ----------------------

SIST EN 60730-2-5:2002/A2:2010
60730-2-5 Amend. 2 © IEC:2008 – 9 –
H.26.5.4 Severity levels
Replace the existing title and text with the following new title and text:
H.26.5.4 Voltage variation test
Replacement:
The control shall tolerate short-term supply voltage variations.
Compliance is checked by the test of H.26.5.4.
Add the following new subclauses:
H.26.5.4.1 Purpose of the test
Replacement:
The purpose of the test is to verify the immunity of the control against voltage change taking
place over a short period which may occur due to a change of load or stored energy in local
power networks. The control shall operate according to the functional specification (see
11.3.105) at least within the voltage tolerance band of the rated voltage
+10
%, and below –15 % of the rated voltage the control shall stay safe.
−15
H.26.5.4.2 The duration and procedure
Replacement:
The duration of the voltage changes and the time for which the reduced voltages are to be
maintained are given in Table H.26.5.4.2 and illustrated in Figure H.26.5.4.2. The rate of
change of voltage shall be constant; however, the voltage is allowed to be stepped. The steps
shall be positioned at 0 crossing and shall be not larger than 10 % of V . Steps under 1 % of
R
V are evaluated as constant rate of change of voltage.
R
The control, in the running position, is supplied at rated voltage, or at the lowest rated voltage
of a rated voltage range. After approximately 1 min, the power supply voltage is reduced to a
level such that the control ceases to respond to safety related inputs and/or
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.