Protection against lightning - Part 3: Physical damage to structures and life hazard

IEC 62305-3:2024 provides the requirements for protection of a structure against physical damage by means of a lightning protection system (LPS), and for protection against injury to human beings due to touch and step voltages in the vicinity of an LPS (see IEC 62305-1).
This document is applicable to the:
a) design, installation, inspection and maintenance of an LPS for structures without limitation of their height,
b) establishment of measures for protection against injury to human beings primarily due to touch and step voltages.
This third edition cancels and replaces the second edition published in 2010. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
a) Minimum thicknesses of metal sheets or metal pipes are given in Table 4 for air-termination systems where it is necessary to prevent hot-spot problems. Maximum temperature rises ΔT (K) and time duration t50 (s) for different thicknesses and long strokes are also given.
b) Cross-reference to the IEC 62561 series is made for the use of reliable, stable, safe and appropriate LPS components.
c) The application of two methods – general and simplified – for separation distance calculation is clarified.
d) Some changes to the requirements for continuity of steel reinforcement are made.
e) Annex C is revised to address comments from IEC subcommittee 31J.
f) Revision of positioning of air-termination conductors are modified according to the three accepted methods. A more precise description of the methods for positioning of the air-termination systems are made according to the complexity of structures to be protected. The main text has been simplified, Annex A has been deleted and all detailed information has been moved to Annex D.
g) Information on the protection of green roofs is introduced in Annex D.
h) Information on the protection of protruding parts on facades of tall buildings is introduced in Annex D.
i) a new definition of “electrically insulated LPS” has been introduced to distinguish it from an LPS both electrically and physically isolated from the structure, with a slight modification of the other LPS definitions.

Blitzschutz - Teil 3: Schutz von baulichen Anlagen und Personen

Protection contre la foudre - Partie 3: Dommages physiques sur les structures et risques humains

L'IEC 62305-3:2024 spécifie les exigences pour la protection d'une structure contre les dommages physiques par un système de protection contre la foudre (SPF) et pour la protection contre les blessures d'êtres humains dues aux tensions de contact et de pas à proximité d'un SPF (voir l'IEC 62305-1).
Le présent document s'applique:
a) à la conception, l'installation, l'inspection et la maintenance d'un SPF pour des structures, sans limitation de leur hauteur;
b) à la mise en œuvre de mesures pour la protection contre les blessures d'êtres humains essentiellement dues aux tensions de contact et de pas.
Cette troisième édition annule et remplace la deuxième édition parue en 2010. Cette édition constitue une révision technique.
Cette édition inclut les modifications techniques majeures suivantes par rapport à l'édition précédente:
a) les épaisseurs minimales des tôles ou canalisations métalliques sont indiquées dans le Tableau 4 pour les dispositifs de capture à utiliser si des mesures de prévention contre les problèmes de points chauds se révèlent nécessaires. Les échauffements maximaux ΔT (K) et la durée t50 (s) pour différentes épaisseurs et pour des coups de longue durée sont également donnés;
b) un renvoi à la série IEC 62561 est établi en ce qui concerne l'utilisation de composants appropriés fiables, stables et sûrs du système de protection contre la foudre (SPF);
c) l'application de deux méthodes (générale et simplifiée) de calcul de la distance de séparation est clarifiée;
d) certaines exigences relatives à la continuité des armatures en acier ont été modifiées;
e) l'Annexe C est révisée pour tenir compte des remarques formulées par le sous-comité 31J de l'IEC;
f) Le positionnement des conducteurs de capture a été révisé en fonction des trois méthodes admises. Les méthodes de positionnement des dispositifs de capture sont décrites avec davantage de précision compte tenu de la complexité des structures à protéger. Le texte principal a été simplifié, l'Annexe A a été supprimée et toutes les informations supplémentaires ont été déplacées à l'Annexe D;
g) des informations relatives à la protection de toitures végétalisées ont été ajoutées à l'Annexe D;
h) des informations relatives à la protection des parties saillantes sur les façades de bâtiments hauts ont été ajoutées à l'Annexe D;
i) une nouvelle définition de la “SPF isolée électriquement” a été introduite pour la distinguer de la SPF isolée électriquement et physiquement de la structure, avec une légère modification des autres définitions de la SPF.

Zaščita pred delovanjem strele - 3. del: Fizična škoda na zgradbah in življenjska ogroženost

Standard IEC 62305-3:2024 določa zahteve za zaščito zgradb pred fizično škodo s pomočjo sistema zaščite pred delovanjem strele (LPS) ter zaščito pred poškodbami ljudi zaradi napetosti dotika in koraka v bližini takšnega sistema (glej standard IEC 62305-1).
Ta dokument se uporablja za:
a) načrtovanje, namestitev, pregledovanje in vzdrževanje sistema zaščite pred delovanjem strele za zgradbe brez omejitve glede njihove višine;
b) določanje zahtev glede zaščite pred poškodbami ljudi predvsem zaradi napetosti dotika in koraka.
Tretja izdaja razveljavlja in nadomešča drugo izdajo, objavljeno leta 2010. Ta izdaja je tehnično popravljena izdaja.
Ta izdaja v primerjavi s prejšnjo vključuje naslednje pomembne tehnične spremembe:
a) V preglednici 4 so navedene najmanjše debeline kovinskih plošč ali kovinskih cevi za lovilne sisteme, kjer je treba preprečiti težave zaradi nastanka vročih mest. Podano je tudi največje zvišanje temperature ΔT (K) in časovno trajanje t50 (s) za različne debeline in dolge udare.
b) Uporaba zanesljivih, stabilnih, varnih in ustreznih komponent sistema zaščite pred delovanjem strele je zagotovljena z navzkrižnim sklicevanjem na skupino standardov IEC 62561.
c) Pojasnjena je uporaba dveh metod – splošne in poenostavljene – za izračun ločilne razdalje.
d) Zahteve za neprekinjenost jeklene ojačitve so bile nekoliko spremenjene.
e) Dodatek C je bil spremenjen tako, da obravnava pripombe pododbora IEC 31J.
f) Postavitev lovilnih vodnikov je bila pregledana in spremenjena v skladu s tremi sprejetimi metodami. Metode za postavitev lovilnih sistemov so natančneje opisane glede na kompleksnost zgradb, ki jih je treba zaščititi. Glavno besedilo je bilo poenostavljeno, dodatek A je bil izbrisan in vse podrobne informacije so bile premaknjene v dodatek D.
g) Dodatek D vsebuje informacije o zaščiti zelenih streh.
h) Dodatek D vsebuje tudi informacije o zaščiti štrlečih delov na fasadah visokih zgradb.
i) Uvedena je bila nova definicija »električno izoliranega sistema zaščite pred delovanjem strele«, da ga je mogoče razlikovati od sistema zaščite pred delovanjem strele, ki je tako električno kot fizično izoliran od zgradbe, pri čemer so bile nekoliko spremenjene tudi druge definicije sistemov zaščite pred delovanjem strele.

General Information

Status
Published
Public Enquiry End Date
30-Dec-2023
Publication Date
12-Nov-2024
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
07-Nov-2024
Due Date
12-Jan-2025
Completion Date
13-Nov-2024

Relations

Overview

SIST EN IEC 62305-3:2024 - Protection against lightning: Part 3: Physical damage to structures and life hazard provides requirements for designing, installing, inspecting and maintaining a lightning protection system (LPS) to protect structures (of any height) and to reduce injury to people from touch and step voltages near an LPS. This third edition is a technical revision that supersedes the previous edition and updates practical rules for external and internal LPS design, earthing, equipotential bonding and protection measures.

Key topics and technical requirements

  • Scope & applicability
    • Applies to design, installation, inspection and maintenance of LPSs without limitation of structure height.
    • Covers establishment of measures to protect people primarily from touch and step voltages.
  • External LPS components
    • Air-termination systems: positioning methods clarified; three accepted methods for air-termination conductor placement are described.
    • Down-conductors and earth-termination systems: guidance on placement, continuity, test joints/test points, and earthing arrangements.
    • Minimum metal thicknesses and temperature-rise limits for air-termination materials are specified to avoid hot-spot problems.
  • Internal LPS and equipotential bonding
    • Requirements for lightning equipotential bonding (EB) of metal installations, external conductive parts and lines entering the structure.
    • Separation distance calculation clarified - both the general and simplified methods are permitted and explained.
  • Protection against human injury
    • Measures to limit dangerous touch and step voltages and practical methods for mitigation are provided.
  • Special topics and annexes
    • Additional requirements for structures with explosion risk (Annex C, normative).
    • Expanded explanatory guidance moved into Annex D (informative), including green roof protection and façade protrusion protection.
    • New definition of “electrically insulated LPS” and cross‑references to the IEC 62561 series for LPS components.

Practical applications - who uses this standard

  • Electrical and lightning protection engineers designing LPSs for buildings, towers and industrial plants.
  • Architects and structural engineers integrating external and internal protection measures.
  • LPS installers, inspectors and maintenance teams responsible for compliance, test joints and earthing.
  • Safety managers, facility owners, insurers and compliance officers assessing life hazard reduction and asset protection - including high-risk sites (explosive atmospheres, green roofs, tall façades).

Related standards and references

  • IEC 62305-1 (General principles), IEC 62305-2 (Risk management), IEC 62305-4 (Electrical/electronic systems).
  • IEC 62561 series (LPSC components) - referenced for reliable, safe LPS components.
  • Other referenced standards (e.g., IEC 60079 series for explosive atmospheres) provide complementary requirements for specific environments.

This standard is essential for professionals seeking to implement compliant, effective lightning protection systems (LPS) that reduce physical damage and life hazard while aligning with current IEC/CENELEC practice.

Standard
SIST EN IEC 62305-3:2024 - BARVE
English language
140 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Frequently Asked Questions

SIST EN IEC 62305-3:2024 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Protection against lightning - Part 3: Physical damage to structures and life hazard". This standard covers: IEC 62305-3:2024 provides the requirements for protection of a structure against physical damage by means of a lightning protection system (LPS), and for protection against injury to human beings due to touch and step voltages in the vicinity of an LPS (see IEC 62305-1). This document is applicable to the: a) design, installation, inspection and maintenance of an LPS for structures without limitation of their height, b) establishment of measures for protection against injury to human beings primarily due to touch and step voltages. This third edition cancels and replaces the second edition published in 2010. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) Minimum thicknesses of metal sheets or metal pipes are given in Table 4 for air-termination systems where it is necessary to prevent hot-spot problems. Maximum temperature rises ΔT (K) and time duration t50 (s) for different thicknesses and long strokes are also given. b) Cross-reference to the IEC 62561 series is made for the use of reliable, stable, safe and appropriate LPS components. c) The application of two methods – general and simplified – for separation distance calculation is clarified. d) Some changes to the requirements for continuity of steel reinforcement are made. e) Annex C is revised to address comments from IEC subcommittee 31J. f) Revision of positioning of air-termination conductors are modified according to the three accepted methods. A more precise description of the methods for positioning of the air-termination systems are made according to the complexity of structures to be protected. The main text has been simplified, Annex A has been deleted and all detailed information has been moved to Annex D. g) Information on the protection of green roofs is introduced in Annex D. h) Information on the protection of protruding parts on facades of tall buildings is introduced in Annex D. i) a new definition of “electrically insulated LPS” has been introduced to distinguish it from an LPS both electrically and physically isolated from the structure, with a slight modification of the other LPS definitions.

IEC 62305-3:2024 provides the requirements for protection of a structure against physical damage by means of a lightning protection system (LPS), and for protection against injury to human beings due to touch and step voltages in the vicinity of an LPS (see IEC 62305-1). This document is applicable to the: a) design, installation, inspection and maintenance of an LPS for structures without limitation of their height, b) establishment of measures for protection against injury to human beings primarily due to touch and step voltages. This third edition cancels and replaces the second edition published in 2010. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) Minimum thicknesses of metal sheets or metal pipes are given in Table 4 for air-termination systems where it is necessary to prevent hot-spot problems. Maximum temperature rises ΔT (K) and time duration t50 (s) for different thicknesses and long strokes are also given. b) Cross-reference to the IEC 62561 series is made for the use of reliable, stable, safe and appropriate LPS components. c) The application of two methods – general and simplified – for separation distance calculation is clarified. d) Some changes to the requirements for continuity of steel reinforcement are made. e) Annex C is revised to address comments from IEC subcommittee 31J. f) Revision of positioning of air-termination conductors are modified according to the three accepted methods. A more precise description of the methods for positioning of the air-termination systems are made according to the complexity of structures to be protected. The main text has been simplified, Annex A has been deleted and all detailed information has been moved to Annex D. g) Information on the protection of green roofs is introduced in Annex D. h) Information on the protection of protruding parts on facades of tall buildings is introduced in Annex D. i) a new definition of “electrically insulated LPS” has been introduced to distinguish it from an LPS both electrically and physically isolated from the structure, with a slight modification of the other LPS definitions.

SIST EN IEC 62305-3:2024 is classified under the following ICS (International Classification for Standards) categories: 91.120.40 - Lightning protection. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST EN IEC 62305-3:2024 has the following relationships with other standards: It is inter standard links to SIST EN 62305-3:2011. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

You can purchase SIST EN IEC 62305-3:2024 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of SIST standards.

Standards Content (Sample)


SLOVENSKI STANDARD
01-december-2024
Nadomešča:
SIST EN 62305-3:2011
Zaščita pred delovanjem strele - 3. del: Fizična škoda na zgradbah in življenjska
ogroženost
Protection against lightning - Part 3: Physical damage to structures and life hazard
Blitzschutz - Teil 3: Schutz von baulichen Anlagen und Personen
Protection contre la foudre - Partie 3: Dommages physiques sur les structures et risques
humains
Ta slovenski standard je istoveten z: EN IEC 62305-3:2024
ICS:
91.120.40 Zaščita pred strelo Lightning protection
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN IEC 62305-3

NORME EUROPÉENNE
EUROPÄISCHE NORM October 2024
ICS 29.020; 91.120.40 Supersedes EN 62305-3:2011
English Version
Protection against lightning - Part 3: Physical damage to
structures and life hazard
(IEC 62305-3:2024)
Protection contre la foudre - Partie 3: Dommages physiques Blitzschutz - Teil 3: Schutz von baulichen Anlagen und
sur les structures et risques humains Personen
(IEC 62305-3:2024) (IEC 62305-3:2024)
This European Standard was approved by CENELEC on 2024-10-17. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Türkiye and the United Kingdom.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2024 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 62305-3:2024 E

European foreword
The text of document 81/764/FDIS, future edition 3 of IEC 62305-3, prepared by TC 81 "Lightning
protection" was submitted to the IEC-CENELEC parallel vote and approved by CENELEC as
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2025-10-31
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2027-10-31
document have to be withdrawn
This document supersedes EN 62305-3:2011 and all of its amendments and corrigenda (if any).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
Any feedback and questions on this document should be directed to the users’ national committee. A
complete listing of these bodies can be found on the CENELEC website.
Endorsement notice
The text of the International Standard IEC 62305-3:2024 was approved by CENELEC as a European
Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standard indicated:
IEC 61400-24 NOTE Approved as EN IEC 61400-24
ISO 1182 NOTE Approved as EN ISO 1182
ISO 11925-2 NOTE Approved as EN ISO 11925-2
IEC 60071-2 NOTE Approved as EN IEC 60071-2
IEC 60079-17 NOTE Approved as EN IEC 60079-17
IEC 62858 NOTE Approved as EN IEC 62858
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1  Where an International Publication has been modified by common modifications, indicated by (mod),
the relevant EN/HD applies.
NOTE 2  Up-to-date information on the latest versions of the European Standards listed in this annex is available
here: www.cencenelec.eu.
Publication Year Title EN/HD Year
IEC 60079-10-1 2020 Explosive atmospheres - Part 10-1: EN IEC 60079-10-1 2021
Classification of areas - Explosive gas
atmospheres
IEC 60079-10-2 2015 Explosive atmospheres - Part 10-2: EN 60079-10-2 2015
Classification of areas - Explosive dust
atmospheres
IEC 60079-14 - Explosive atmospheres - Part 14: Electrical EN IEC 60079-14 -
installation design, selection and
installation of equipment, including initial
inspection
IEC 60364-5-53 - Low-voltage electrical installations -- Part - -
5-53: Selection and erection of electrical
equipment - Protection, isolation,
switching, control and monitoring
IEC 61643-11 - Low-voltage surge protective devices - Part EN 61643-11 -
11: Surge protective devices connected to
low-voltage power systems - Requirements
and test methods
IEC 61643-21 - Low voltage surge protective devices - Part EN 61643-21 -
21: Surge protective devices connected to
telecommunications and signalling
networks - Performance requirements and
testing methods
IEC 62305-1 2024 Protection against lightning - Part 1: EN IEC 62305-1 2024
General principles
IEC 62305-2 2024 Protection against lightning - Part 2: Risk EN IEC 62305-2 2024
management
IEC 62305-4 2024 Protection against lightning - Part 4: EN IEC 62305-4 2024
Electrical and electronic systems within
structures
IEC 62561 series Lightning protection system components EN IEC 62561 series
(LPSC) - Part 1: Requirements for
connection components
Publication Year Title EN/HD Year
IEC 62561-1 2017 Lightning protection system components EN 62561-1 2017
(LPSC)
IEC/TS 62561-8 2018 Lightning protection system components - -
(LPSC) - Part 8: Requirements for
components for isolated LPS
ISO 3864-1 - Graphical symbols - Safety colours and - -
safety signs - Part 1: Design principles for
safety signs and safety markings

IEC 62305-3 ®
Edition 3.0 2024-09
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Protection against lightning –

Part 3: Physical damage to structures and life hazard

Protection contre la foudre –
Partie 3: Dommages physiques sur les structures et risques humains

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.020, 91.120.40 ISBN 978-2-8322-9059-0

– 2 – IEC 62305-3:2024 © IEC 2024
CONTENTS
FOREWORD . 7
INTRODUCTION . 10
1 Scope . 12
2 Normative references . 12
3 Terms and definitions . 13
4 Lightning protection system (LPS) . 18
4.1 Class of LPS . 18
4.2 Design of the LPS . 19
5 External lightning protection system . 19
5.1 General . 19
5.1.1 Application of an external LPS . 19
5.1.2 Application of an isolated LPS or an electrically insulated LPS . 19
5.1.3 Use of natural components . 20
5.2 Air-termination systems . 20
5.2.1 General . 20
5.2.2 Positioning . 20
5.2.3 Air terminations against flashes to the side of tall structures . 25
5.2.4 Construction . 26
5.2.5 Natural components . 26
5.3 Down-conductor systems . 29
5.3.1 General . 29
5.3.2 Positioning of an isolated LPS . 29
5.3.3 Positioning of an attached LPS . 29
5.3.4 Construction . 30
5.3.5 Natural components . 32
5.3.6 Test joints and test points . 33
5.4 Earth-termination system . 33
5.4.1 General . 33
5.4.2 Earthing arrangement in general conditions . 33
5.4.3 Installation of earth electrodes . 35
5.4.4 Natural earth electrodes . 36
5.5 Components . 36
5.5.1 General . 36
5.5.2 Fixing . 37
5.5.3 Connections . 38
5.5.4 Components of an electrically insulated LPS . 38
5.6 Materials and dimensions . 38
5.6.1 Materials . 38
5.6.2 Dimensions . 38
6 Internal lightning protection system . 41
6.1 General . 41
6.2 Lightning equipotential bonding . 41
6.2.1 General . 41
6.2.2 Lightning equipotential bonding for metal installations . 42
6.2.3 Lightning equipotential bonding for external conductive parts . 43
6.2.4 Lightning equipotential bonding for internal systems . 43

IEC 62305-3:2024 © IEC 2024 – 3 –
6.2.5 Lightning equipotential bonding for lines connected to the structure to
be protected . 44
6.3 Separation distance . 45
6.3.1 General approach . 45
6.3.2 Simplified approach . 46
7 Maintenance and inspection of an LPS . 47
7.1 General . 47
7.2 Maintenance . 47
7.3 Objective of inspections . 47
7.4 Need for inspection . 48
8 Protection measures against injury to human beings due to touch and step
voltages . 48
8.1 Protection measures against touch voltages . 48
8.2 Protection measures against step voltages . 49
Annex A (normative) Minimum cross-section of the entering cable screen to avoid
dangerous sparking . 50
Annex B (informative) Evaluation of the separation distance s . 51
Annex C (normative) Additional requirements for LPSs in the case of structures with a
risk of explosion . 56
C.1 General . 56
C.2 Basic requirements . 56
C.2.1 General . 56
C.2.2 Required information . 56
C.2.3 Earthing . 56
C.3 Structures containing solid explosive material . 57
C.4 Structures with hazardous areas . 57
C.4.1 General . 57
C.4.2 Structures with Zones 2 and 22 . 58
C.4.3 Structures with Zones 1 and 21 . 58
C.4.4 Structures with Zones 0 and 20 . 58
C.4.5 Specific applications . 58
C.5 Maintenance and inspection . 59
Annex D (informative) Explanatory text concerning the design, construction,
maintenance and inspection of lightning protection systems . 60
D.1 General . 60
D.2 Structure of Annex D . 60
D.3 Additional information . 60
D.4 Design of lightning protection systems (LPSs) . 60
D.4.1 General remarks . 60
D.4.2 Design of the LPS . 62
D.5 External lightning protection system . 66
D.5.1 General . 66
D.5.2 Air-termination systems . 67
D.5.3 Down-conductor systems . 87
D.5.4 Earth-termination systems . 108
D.5.5 Components . 117
D.5.6 Materials and dimensions . 117
D.6 Internal lightning protection system . 122
D.6.1 General . 122

– 4 – IEC 62305-3:2024 © IEC 2024
D.6.2 Lightning equipotential bonding (EB) . 122
D.6.3 Electrical isolation of the external LPS . 128
D.6.4 Protection against effects of induced currents in internal systems . 132
D.7 Maintenance and inspection of the LPS . 132
D.7.1 General . 132
D.7.2 Inspection . 132
D.7.3 Testing . 134
D.7.4 Maintenance . 135
Bibliography . 136

Figure 1 – Protection angle corresponding to the class of LPS . 22
Figure 2 – Contacting the rolling sphere with the structure to be protected. 23
Figure 3 – Application of the protection angle method . 24
Figure 4 – Loop in a down conductor . 31
Figure 5 – Minimum length l of each earth electrode according to the class of LPS . 34
Figure B.1 – Values of coefficient k in the case of a wire air-termination system . 51
c
Figure B.2 – Values of coefficient k in the case of a multiple down-conductor system . 52
c
Figure B.3 – Values of coefficients k in the case of multiple down conductors with an
c
interconnecting ring of down conductors at each level . 53
Figure B.4 – Values of coefficient k in the case of a meshed air-termination system,
c
with a multiple down-conductor system . 54
Figure D.1 – LPS design flow diagram . 61
Figure D.2 – Space protected by two parallel air-termination horizontal wires or two

air-termination rods (r > d/2) . 69
Figure D.3 – Designing the protection volume of catenary wire . 70
Figure D.4 – Horizontal section of the protected area at a given height . 71
Figure D.5 – Three examples of design of attached LPS air termination according to
the mesh method air-termination design . 73
Figure D.6 – Lateral protected volume constructed from the rolling sphere and the
lateral protection angle methods near the height equal to the radius of the sphere . 74
Figure D.7 – Application of the protection angle method for lateral impact with heights

up to 60 m . 75
Figure D.8 – Air termination and visually concealed conductors for buildings less than
20 m high with sloping roofs. 76
Figure D.9 – Construction of an LPS using natural components on the roof of the
structure . 78
Figure D.10 – Positioning of the external LPS on a structure made of insulating
material (e.g. wood or bricks) with a height up to 60 m with flat roof and with roof
fixtures . 79
Figure D.11 – Connection of natural air-termination rod to air-termination conductor . 81
Figure D.12 – Construction of the bridging between the segments of the metallic
facade plates . 82
Figure D.13 – Air-termination rod used for protection of a metallic roof fixture with

electric power installations which are not bonded to the air-termination system . 83
Figure D.14 – Method of achieving electrical continuity on metallic parapet capping . 84
Figure D.15 – Examples of air termination for a house with an antenna using an
attached LPS . 86

IEC 62305-3:2024 © IEC 2024 – 5 –
Figure D.16 – Installation of external LPS on a structure of insulating material with
different roof levels . 90
Figure D.17 – LPS design for a cantilevered part of a structure . 91
Figure D.18 – Use of a metallic facade covering as a natural down-conductor system
on a structure of steel-reinforced concrete . 93
Figure D.19 – Use of metallic facade as natural down-conductor system and
connection of facade supports . 94
Figure D.20 – Connection of the continuous strip windows to a metal facade covering . 95
Figure D.21 – Measuring the overall electrical resistance of steel reinforcement . 96
Figure D.22 – Equipotential bonding in a structure with a steel reinforcement . 98
Figure D.23 – Typical methods of joining reinforcing rods in concrete (where permitted) . 99
Figure D.24 – Examples of clamps used as joints between reinforcing rods and
conductors . 100
Figure D.25 – Examples of connection points to the reinforcement in a reinforced
concrete wall . 101
Figure D.26 – Internal down conductors in industrial structures . 104
Figure D.27 – Installation of bonding conductors on plate-like prefabricated reinforced
concrete parts by means of bolted or welded conductor links . 106
Figure D.28 – Installation of bonding conductors in reinforced concrete structures and
flexible bonds between two reinforced concrete parts . 107
Figure D.29 – Combined foundation earth electrode . 112
Figure D.30 – Construction of foundation earth ring for structures of different
foundation design . 113
Figure D.31 – Example of a Type A earthing arrangement with a vertical conductor
type electrode . 114
Figure D.32 – Example of a Type A earthing arrangement with a vertical rod type
electrode . 115
Figure D.33 – Meshed earth-termination system of a plant . 118
Figure D.34 – Example of an equipotential bonding arrangement . 124
Figure D.35 – Example of bonding arrangement in a structure with multiple entry points
of external conductive parts using a ring electrode for interconnection of bonding bars . 125
Figure D.36 – Example of bonding in the case of multiple entry points of external
conductive parts and an electric power or communication line, using an internal ring
conductor for interconnection of the bonding bars . 126
Figure D.37 – Example of bonding arrangement in a structure with multiple entry points

of external conductive parts entering the structure above ground level. 127
Figure D.38 – Directions for calculations of the separation distance, s, for a worse case
lightning interception point at a distance, l, from the reference point according to 6.3 . 130

Table 1 – Relation between lightning protection levels (LPL) and class of LPS (see
IEC 62305-1) . 18
Table 2 – Values of rolling sphere radius, mesh size and protection angle
corresponding to the class of LPS . 21
Table 3 – Minimum thickness of metal sheets or metal pipes in air-termination systems . 27
Table 4 – Maximum temperature rises ∆T (K) of inner surface and time duration t (s)
for different thickness t’’ (mm) and long strokes according to LPL I (Q = 200 C) . 28
LONG
Table 5 – Preferred values of the distance between down conductors by LPS according
to the class of LPS . 30

– 6 – IEC 62305-3:2024 © IEC 2024
Table 6 – LPS materials and conditions of use . 37
Table 7 – Material, configuration and minimum cross-sectional area of air-termination

conductors, air-termination rods, earth lead-in conductors and down conductors . 39
Table 8 – Material, configuration and minimum dimensions of earth electrodes . 40
Table 9 – Minimum dimensions of conductors connecting different bonding bars or

connecting bonding bars to the earth-termination system . 42
Table 10 – Minimum dimensions of conductors connecting internal metal installations
to the bonding bar . 42
Table 11 – Separation distance – Values of coefficient k . 45
i
Table 12 – Separation distance – Values of coefficient k . 45
m
Table 13 – Separation distance – Approximated values of coefficient k . 47
c
Table A.1 – Cable length to be considered according to the condition of the screen . 50
Table D.1 – Suggested fixing centres . 75

IEC 62305-3:2024 © IEC 2024 – 7 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
PROTECTION AGAINST LIGHTNING –

Part 3: Physical damage to structures and life hazard

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as "IEC Publication(s)"). Their
preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
may participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence between
any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) IEC draws attention to the possibility that the implementation of this document may involve the use of (a)
patent(s). IEC takes no position concerning the evidence, validity or applicability of any claimed patent rights in
respect thereof. As of the date of publication of this document, IEC had not received notice of (a) patent(s), which
may be required to implement this document. However, implementers are cautioned that this may not represent
the latest information, which may be obtained from the patent database available at https://patents.iec.ch. IEC
shall not be held responsible for identifying any or all such patent rights.
IEC 62305-3 has been prepared by IEC technical committee 81: Lightning protection. It is an
International Standard.
This third edition cancels and replaces the second edition published in 2010. This edition
constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
a) Minimum thicknesses of metal sheets or metal pipes are given in Table 4 for air-termination
systems where it is necessary to prevent hot-spot problems. Maximum temperature rises
ΔT (K) and time duration t (s) for different thicknesses and long strokes are also given.
b) Cross-reference to the IEC 62561 series is made for the use of reliable, stable, safe and
appropriate LPS components.
– 8 – IEC 62305-3:2024 © IEC 2024
c) The application of two methods – general and simplified – for separation distance calculation
is clarified.
d) Some changes to the requirements for continuity of steel reinforcement are made.
e) Annex C is revised to address comments from IEC subcommittee 31J.
f) Revision of positioning of air-termination conductors are modified according to the three
accepted methods. A more precise description of the methods for positioning of the air-
termination systems is made according to the complexity of structures to be protected. The
main text has been simplified, Annex A has been deleted and all detailed information has
been moved to Annex D.
g) Information on the protection of green roofs is introduced in Annex D.
h) Information on the protection of protruding parts on facades of tall buildings is introduced in
Annex D;
i) a new definition of “electrically insulated LPS” has been introduced to distinguish it from an
LPS both electrically and physically isolated from the structure, with a slight modification of
the other LPS definitions.
The text of this International Standard is based on the following documents:
Draft Report on voting
81/764/FDIS 81/767/RVD
Full information on the voting for its approval can be found in the report on voting indicated in
the above table.
The language used for the development of this International Standard is English.
This document was drafted in accordance with ISO/IEC Directives, Part 2, and developed in
accordance with ISO/IEC Directives, Part 1 and ISO/IEC Directives, IEC Supplement, available
at www.iec.ch/members_experts/refdocs. The main document types developed by IEC are
described in greater detail at www.iec.ch/publications.
A list of all parts in the IEC 62305 series, published under the general title Protection against
lightning, can be found on the IEC website.
The following differing practices of a less permanent nature exist in the countries indicated
below.
In Austria, Annex C shall not be applied and is replaced by the National standard ÖVE/ÖNORM
EN 62305-3 Beiblatt 1:2013-11-01 Blitzschutz – Teil 3: Schutz von baulichen Anlagen und
Personen – Beiblatt 1: Zusätzliche Informationen für bauliche Anlagen mit
explosionsgefährdeten Bereichen. In Austria, Annex C shall be classified as "Informative".
In Germany, the need for lightning protection is determined by, and the class of required LPS
shall be selected according to, a national annex to the third edition of IEC 62305-1 (including
an option for a risk assessment following the third edition of IEC 62305-2).
In Germany, for a metallic or electrically-continuous connected reinforced concrete framework,
in addition, DIN EN 62305-3 Beiblatt 1 shall be applied.
In Germany, 8.1 condition b) is not applied – see DIN EN 62305-3 Beiblatt 1. Instead, the
alternate measures, as described in DIN EN 62305-3 Beiblatt 1, shall be applied.
In Germany, for 8.2, the alternate measures, as described in DIN EN 62305-3 Beiblatt 1, shall
be applied.
IEC 62305-3:2024 © IEC 2024 – 9 –
In Japan, when using country-specific lightning protection components, the manufacturer and/or
lightning protection designer shall explain that the component will withstand the electromagnetic
effects of lightning currents and possible accidental stresses without damage.
In Italy, a separation distance is not required in structures with metallic or electrically-
continuous connected reinforced concrete framework according to 5.3.5.
In Italy, in reinforced concrete structures, the reinforcement may be used for equipotential
bonding. In this case, if a ring electrode is not yet installed and connected to the reinforcement
steels, a ring conductor welded or bolted to the steel reinforcement will be installed, to which
the bonding bars should be connected via welded conductors.
In the Netherlands, in some situations, special fasteners which are necessary and which are
not available on the commercial market and are not tested according to IEC 62561-4 (because
of a small number of required special fasteners), must comply with the lateral and axial test
mentioned in IEC 62561-4. A written statement of passing these lateral and axial tests must be
issued by the designer and/or the installer of the LPS and must be a part of the commissioning
documents.
In South Africa, the class of required LPS shall be selected on the basis of a risk assessment
of either the second edition of IEC 62305-2 or the third edition of IEC 62305-2 . This note
applies also for D.4.1 and D.4.2.1.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under webstore.iec.ch in the data related to the
specific document. At this date, the document will be
• reconfirmed,
• withdrawn, or
• revised.
IMPORTANT – The "colour inside" logo on the cover page of this document indicates
that it contains colours which are considered to be useful for the correct understanding
of its contents. Users should therefore print this document using a colour printer.

– 10 – IEC 62305-3:2024 © IEC 2024
INTRODUCTION
This part of IEC 62305 deals with the protection, in and around a structure, against physical
damage and injury to human beings due to touch and step voltages.
The main and most effective measure for protection of structures and its content against
physical damage is considered to be a lightning protection system (LPS). It usually consists of
both external and internal lightning protection measures.
An external LPS is intended to
a) intercept a lightning flash to the structure (with an air-termination system),
b) conduct the lightning current safely towards earth (using a down-conductor system),
c) disperse the lightning current into the earth (using an earth-termination system).
NOTE The purpose of the external LPS is to protect the structure from a direct lightning strike by providing the
preferred attachment points, conducting and dispersing the lightning current. It will not significantly influence the
attachment process between the structure and the lightning to increase or reduce the number of direct lightning
strikes (S1) to the structure.
An internal LPS prevents dangerous sparking within the structure using either equipotential
bonding or a separation distance (and hence isolation) between the external LPS (as defined
in 3.2) and other electrically conducting elements internal to the structure.
Main protection measures against injury to human beings due to touch and step voltages are
intended to:
1) reduce dangerous current flowing through bodies by either insulating exposed conductive
parts, or by increasing the surface soil resistivity, or both,
2) reduce the occurrence of dangerous touch and step voltages by either physical restrictions
or warning notices, or both.
The type and location of an LPS should be carefully considered in the initial design of a new
structure, thereby enabling maximum advantage to be taken of the electrically conductive parts
of the structure. By so doing, design and construction of an integrated installation is made
easier, the overall aesthetic aspects can be improved, and the effectiveness of the LPS can be
increased at minimum cost and effort.
Access to the ground and the proper use of foundation steelwork for the purpose of forming an
effective earth termination may well be impossible once construction work on a site has
commenced. Therefore, soil resistivity and the nature of the earth should be considered at the
earliest possible stage of a project. This information is fundamental to the design of an earth-
termination system and can influence the foundation design work for the structure.
Regular consultation between LPS designers and installers, architects and builders is essential
in order to achieve the best result at minimum cost.
If lightning protection is to be added to an existing structure, every effort should be made to
ensure that it conforms to the principles of this document. The design of the type and location
of an LPS should take into account the features of the existing structure.
When safety is involved and significant changes are made to the structure or its use changes,
consideration of updating the lightning protection installation to the present edition of this
document is recommended.
IEC 62305-3:2024 © IEC 2024 – 11 –
National or local laws and regulations can provide guidance or minimum requirements on the
application of this document. This inclu
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...

SIST EN IEC 62305-3:2024は、雷保護システム(LPS)を通じて構造物が物理的ダメージから保護されるための要件と、LPSの近くでのタッチおよびステップ電圧による人間の傷害を防ぐための措置を提供します。この標準は、構造物の設計、設置、検査、保守に関するガイドラインを示し、高さに制限はなく適用されます。 この第三版は、2010年に公開された第二版を取り消し、技術的な改訂を行っています。特に注目すべきは、金属シートや金属パイプの最小厚さが第4表に示されており、ホットスポット問題を防ぐために必要な情報が提供されている点です。また、異なる厚さおよび長いストライクに対する最大温度上昇ΔT(K)と時間t50(s)が明記されています。 IEC 62561シリーズへの相互参照もなされており、信頼性が高く安定したLPSコンポーネントの用途が強調されています。分離距離の計算における一般的および簡易の二つの方法が明確にされ、鋼鉄補強の連続性要件にいくつかの変更が加えられています。 また、Annex CはIEC小委員会31Jからのコメントに対応するために改訂されており、空中終端導体の配置に関しては三つの承認された方法に基づいて変更が施されています。構造物の複雑さに応じた空中終端システムの配置方法の詳細が簡素化され、Annex Aは削除され、すべての詳細情報はAnnex Dに移されています。 さらに、緑の屋根の保護に関する情報や、高層ビルのファサードに突き出た部分の保護に関する情報が新たにAnnex Dに導入されています。新たに定義された「電気的絶縁LPS」は、構造から電気的および物理的に隔離されたLPSとの区別を如実に示しています。 この標準は、雷による物理的ダメージや人間の安全に対するリスクを軽減するための非常に重要な指針であり、最新の技術的知見を反映した設計や保護の手法を提供しています。

La norme SIST EN IEC 62305-3:2024 se concentre sur la protection contre les dommages physiques aux structures et les risques pour la vie en raison de la foudre. Son champ d'application est large et couvre le design, l'installation, l'inspection et l'entretien des systèmes de protection contre la foudre (LPS) pour des structures de toutes hauteurs, ainsi que les mesures à établir pour protéger les êtres humains contre les blessures dues aux tensions de contact et de pas. Les points forts de cette norme incluent plusieurs révisions techniques significatives par rapport à l'édition précédente publiée en 2010. Tout d'abord, les nouvelles exigences concernant les épaisseurs minimales des tôles métalliques ou des tuyaux métalliques pour les systèmes de terminaison aérienne sont clairement définies, permettant ainsi d'éviter les problèmes de points chauds. De plus, la norme introduit des données relatives aux augmentations de température (ΔT) et aux durées (t50) pour différentes épaisseurs, ce qui améliore la compréhension des risques associés. Une autre force notable est la clarification de l'application des deux méthodes – générale et simplifiée – pour le calcul des distances de séparation, ce qui faciliterait l'application de la norme pour les praticiens. Les exigences relatives à la continuité de l’armature en acier ont également été ajustées, afin de garantir une protection adéquate. En outre, les modifications apportées au positionnement des conducteurs de terminaison aérienne, qui sont décrites selon trois méthodes acceptées, ainsi que la simplification du texte principal, témoignent d’un effort considérable pour rendre le document plus accessible et pertinent pour les utilisateurs. La norme inclut des informations précieuses sur la protection des toits verts et des parties saillantes sur les façades des bâtiments hauts, élargissant ainsi son applicabilité à des structures modernes et complexes. De plus, l'introduction d'une nouvelle définition d’un LPS électriquement isolé offre une distinction claire entre les différents systèmes de protection, renforçant la précision de l'ensemble des définitions. En somme, la norme SIST EN IEC 62305-3:2024 représente une avancée significative dans les exigences de protection contre la foudre, en s'assurant que les structures sont correctement protégées contre les dommages physiques et que les individus sont à l'abri des risques électriques associés. Son actualisation technique en fait un document essentiel pour les professionnels du secteur de la protection contre la foudre.

The SIST EN IEC 62305-3:2024 standard comprehensively addresses the protection of structures from physical damage caused by lightning strikes and the associated life hazards arising from touch and step voltages. As a critical document in the field, its scope encompasses the design, installation, inspection, and maintenance of lightning protection systems (LPS) relevant to structures of any height. This ensures that even the most complex structures can be adequately protected against lightning-related dangers. One significant strength of this standard is its rigorous approach in defining minimum requirements, such as the minimum thicknesses for metal sheets or pipes in air-termination systems. By providing specific parameters to prevent hot-spot problems, it enhances the reliability of LPS installations. Furthermore, the inclusion of maximum temperature rises and the duration of exposure are critical metrics for the safe operation of these systems, demonstrating the standard's commitment to practical application. The standard also makes pertinent cross-references to the IEC 62561 series, ensuring that users can access reliable and stable LPS components, which further reinforces the integrity of lightning protection systems across various applications. This interconnectedness with existing standards fosters consistency and safety in the implementation of LPS. In its technical revision, the standard provides clarity on calculation methods for separation distances, offering both general and simplified approaches. This flexibility caters to a broad range of user needs, accommodating varying levels of expertise and project complexities. Additionally, updated requirements regarding the continuity of steel reinforcement reflect advancements in understanding material performance under lightning strike conditions. The standard’s revisions also address contemporary issues such as the protection of green roofs and protruding parts on facades of tall buildings, showcasing its adaptability to modern architectural trends. These inclusions make it highly relevant to contemporary construction practices and concerns, ensuring that current infrastructure is equipped to handle lightning-related risks effectively. Moreover, the introduction of a new definition concerning “electrically insulated LPS” differentiates this type of system from others, enhancing the specificity and applicability of LPS definitions in different contexts. Simplifying textual elements and relocating detailed information to an annex allows users to engage with the standard more effectively, ensuring that critical information is accessible without overwhelming detail in the main text. Overall, the SIST EN IEC 62305-3:2024 standard establishes a robust framework for the protection of structures against lightning, proving its relevance and strength in promoting safety and integrity in construction and engineering practices.

SIST EN IEC 62305-3:2024 문서는 구조물의 물리적 손상으로부터의 보호 및 인명 안전에 대한 요구사항을 다루고 있습니다. 이 표준은 번개 보호 시스템(LPS)을 통해 구조물이 물리적 손상을 입지 않도록 설계하고, LPS 주변에서 발생할 수 있는 접촉 및 단계 전압으로 인한 인명 피해를 예방하기 위한 조치를 마련합니다. 이 문서의 핵심 강점 중 하나는 LPS 설계, 설치, 검사 및 유지 관리와 관련된 포괄적인 지침을 제공한다는 점입니다. 특히 구조물의 높이에 관계없이 적용될 수 있는 점에서 그 범위가 확장되었습니다. 새로운 기술적 변경사항들은 이전 판과 비교했을 때 매우 중요하며, 이는 번개 보호의 효과성을 더욱 높이고, 인명 안전을 강화하는 데 기여합니다. 예를 들어, 금속 시트나 금속 파이프의 최소 두께에 대한 요구사항이 명확히 제시되어 있어, 열점 문제를 예방할 수 있도록 하고 있습니다. 또한, IEC 62561 시리즈에 대한 교차 참조를 통해 LPS 구성 요소의 신뢰성, 안정성 및 적합성을 보장합니다. 이는 사용자가 안전하고 효과적인 LPS를 구현할 수 있도록 돕는 중요한 요소입니다. 또한, 일반 및 단순화된 거리 계산 방법의 적용이 명확히 규정되어 있어, 사용자의 이해를 돕고 계산의 일관성을 제공합니다. 철근 연속성에 대한 요구사항의 변경도 도입되어, 제작 및 설치 과정에서의 유연성을 높였습니다. 소관단체 31J의 의견을 반영하여 부록 C가 개정되었으며, 이는 사용자에게 중요한 피드백을 반영한 결과로 볼 수 있습니다. 공기 종료 도체의 위치 조정에 관한 규정도 세 가지 승인된 방법에 따라 수정되어, 복잡한 구조물의 특성에 맞춰 더욱 정밀한 설명이 추가되었습니다. 결과적으로 주 아카이브의 내용은 간소화되었으며, 애너 이융 정보를 부록 D로 이전하였습니다. 부록 D에서는 녹색 지붕 및 고층 건물 파사드의 돌출 부분 보호에 대한 정보가 소개되어, 현대 건축에서의 안전성을 더욱 증대시키고 있습니다. 마지막으로, "전기적으로 절연된 LPS"의 새 정의는 LPS를 구조물로부터 전기적으로 및 물리적으로 분리된 시스템으로 명확히 구분하는 데 기여합니다. 이 표준은 번개 보호 시스템에 대한 종합적인 가이드라인을 제공함으로써, 건축물의 안전성을 확보하고 인명 피해를 최소화하는 중요한 문서로 자리잡고 있습니다.

Die Norm SIST EN IEC 62305-3:2024 behandelt den Schutz von Bauwerken gegen physische Schäden durch Blitzeinschläge und die Gefahren für Menschen aufgrund von Berührungs- und Schrittspannungen in der Nähe von Blitzschutzsystemen (LPS). Der Anwendungsbereich dieser Norm ist umfassend und beinhaltet sowohl die Planung, Installation, Inspektion und Wartung von LPS für Bauwerke aller Höhen als auch die Festlegung von Maßnahmen zum Schutz von Personen vor Verletzungen, die in erster Linie durch Berührungs- und Schrittspannungen entstehen. Eine der großen Stärken dieser dritten Auflage liegt in den signifikanten technischen Änderungen im Vergleich zur vorhergehenden Ausgabe von 2010. So werden beispielsweise in Tabelle 4 Mindestdicken von Metallplatten oder Metallrohren für Fangvorrichtungen angegeben, um Probleme mit Hotspots zu vermeiden. Dies ist besonders relevant für die Planung stabiler und sicherer Blitzschutzsysteme. Ein weiterer wichtiger Aspekt ist die Klarstellung der Anwendung zweier Methoden – der allgemeinen und der vereinfachten – zur Berechnung der Abstände, wodurch die Planung und Umsetzung von LPS effizienter gestaltet wird. Zudem wurden die Anforderungen an die Kontinuität der Stahlbewehrung angepasst, was zur Erhöhung der Sicherheit und Zuverlässigkeit beiträgt. Die angepassten Vorgaben zur Positionierung der Fangleiterleitungen gemäß drei anerkannten Methoden bieten eine verbesserte Anleitung zur Installation, die dem Komplexitätsgrad der zu schützenden Bauwerke Rechnung trägt. Diese Vereinfachung des Haupttextes sowie die Änderung in den Anhängen, insbesondere die Einführung von Informationen zum Schutz von begrünten Dächern und hervorspringenden Teilen an Fassaden hoher Gebäude in Annex D, zeigen die Relevanz der Norm für moderne Baupraktiken. Darüber hinaus wurde eine neue Definition für "elektrisch isolierte LPS" eingeführt, was eine wichtige Differenzierung zu anderen LPS ermöglicht und zur Klärung von Begrifflichkeiten in der Blitzschutztechnik beiträgt. Insgesamt stellt die Norm SIST EN IEC 62305-3:2024 eine wesentliche Ressource dar, die die Sicherheitsstandards im Bereich des Blitzschutzes erheblich stärkt und den aktuellen Herausforderungen und Entwicklungen im Bauwesen gerecht wird.