CEN/TC 126 - Acoustic properties of building products and of buildings
Standardization in the field of acoustic properties of building elements and of buildings, including: - laboratory methods, expression of results and accuracy; - rating of acoustic properties of elements; - field measurement methods, expression of results and accuracy; - rating of acoustic properties of buildings; - methods for determining the acoustic of buildings from the performance of its elements.
Akustične lastnosti gradbenih proizvodov in stavb
Standardization in the field of acoustic properties of building elements and of buildings, including: - laboratory methods, expression of results and accuracy; - rating of acoustic properties of elements; - field measurement methods, expression of results and accuracy; - rating of acoustic properties of buildings; - methods for determining the acoustic of buildings from the performance of its elements.
General Information
This document specifies procedures to measure in laboratory the impact sound level reduction of isolated heavy landings connected to a heavy wall, isolated heavy flights of stairs connected to a heavy landing, lower or upper floor, and lightweight stairs connected to a heavy wall, lower or upper floor.
This document also considers the characterization of isolating elements for heavy landings or heavy flights of stairs in terms of an insertion loss expressed as an impact sound level difference. The corresponding procedure is given in a normative annex (Annex A), separated from the other procedures for the sake of clarity.
The tests are performed in defined test configurations and the test results are firstly restricted to the test configurations as described in the test report. The data can be used for comparing the performance of products and as input for EN ISO 12354-2:2017, Annex F, to calculate the sound pressure levels produced by the same stairs and isolating elements when installed in buildings.
The test procedures defined in this document comprise the frequency range from 50 Hz to 5000 Hz.
- Standard30 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies an engineering method for the measurement of sound pressure levels in rooms from service equipment installed in the building.
This document covers specifically measurements of sound from sanitary installations, mechanical ventilation, heating and cooling service equipment, lifts, rubbish chutes, heating devices, blowers, pumps and other auxiliary service equipment, and motor driven car park doors. It can also be applied to measurements of sounds from other types of equipment or activities within the building, e.g. noise from sport facilities or restaurants.
The measurement of noise from external sound sources generating air-borne or ground-borne noise in the building are not included in this document.
The methods are suitable for rooms with volumes of approximately 300 m3 or less for instance, in dwellings, hotels, schools, offices and hospitals.
The methods are not intended for measurements in large auditoria or concert halls.
- Standard29 pagesEnglish languagesale 10% offe-Library read for1 day
This test method covers the use of an impedance tube, two microphone locations and a frequency
analysis system for the determination of the sound absorption coefficient of sound absorbing materials
for normal incidence sound incidence. It can also be applied for the determination of the acoustical
surface impedance or surface admittance of sound absorbing materials. As an extension, it can also be
used to assess intrinsic properties of homogeneous acoustical materials such as their characteristic
impedance, characteristic wavenumber, dynamic mass density and dynamic bulk modulus.
The test method is similar to the test method specified in ISO 10534-1[1] in that it uses an impedance
tube with a sound source connected to one end and the test sample mounted in the tube at the other
end. However, the measurement technique is different. In this test method, plane waves are generated
in a tube by a sound source, and the decomposition of the interference field is achieved by the
measurement of acoustic pressures at two fixed locations using wall-mounted microphones or an intube
traversing microphone, and subsequent calculation of the complex acoustic transfer function and
quantities reported in the previous paragraph. The test method is intended to provide an alternative,
and generally much faster, measurement technique than that of ISO 10534-1[1].
Normal incidence absorption coefficients coming from impedance tube measurements are not
comparable with random incidence absorption coefficients measured in reverberation rooms according
to ISO 354[2]. The reverberation room method will (under ideal conditions) determine the sound
absorption coefficient for diffuse sound incidence. However, the reverberation room method requires
test specimens which are rather large. The impedance tube method is limited to studies at normal and
plane incidence and requires samples of the test object which are of the same size as the cross-section
of the impedance tube. For materials that are locally reacting only, diffuse incidence sound absorption
coefficients can be estimated from measurement results obtained by the impedance tube method (see
Annex E).
Through the whole document, a e+ jt time convention is used.
- Standard39 pagesEnglish languagesale 10% offe-Library read for1 day
This document characterizes waste water or rain water piping systems as airborne sound source and structure-borne sound source using the same method as the one described in EN 15657 for characterizing building service equipment. It therefore applies to equipment installed in any type of buildings (heavy or lightweight).
This document:
- specifies laboratory measuring methods for determining the input data required for both comparing products and materials, and predicting sound levels in buildings using EN 12354 5. These input quantities are the piping system sound power level for airborne sound and three quantities for structure-borne sound (piping system free velocity, blocked force and mobility), from which the piping system installed power, source input for EN 12354 5, is determined;
- specifies the method for the measurement of the equipment airborne sound power;
- only considers piping systems connected to one supporting building element in a first step;
NOTE Simultaneous structure-borne transmissions to wall and floor are more difficult to handle. In the configurations proposed in this document, the piping system is only connected to one supporting element and mechanically decoupled from the other elements.
- includes configurations of vertical pipes with offset (deviated horizontally) connected to walls and horizontal pipes connected to ceilings, for which the measuring method is the same as the one defined for straight vertical pipes connected to walls. These complementary configurations are described in (normative) Annex A;
- specifies laboratory test procedures for determining the performance of mitigation measures such as pipe enclosures (technical shaft) and pipe lining. The corresponding specifications are given in (normative) Annex B;
- defines the expression of the results for use in comparing products and materials and for use as input data for prediction; however, the Single Number Quantities used to compare products cannot be used as a prediction or proof of compliance with requirements in a building;
- indicates a method to transform the quantities measured according to EN 14366:2004+A1:2019, to the quantities used in this document; however, the calculated values cannot be used as certified values obtained by test, but only for comparison with new tests. This method is given in (informative) Annex C.
This document is applicable to waste water piping systems and parts thereof, but not to the actual sources of waste water, e.g. lavatories, toilets and bathtubs or any active units, which are considered separately in EN 12354 5 and are characterized separately. It applies to pipes with natural ventilation and made of any common material in commonly used diameters (up to 150 mm).
- Standard32 pagesEnglish languagesale 10% offe-Library read for1 day
This document describes calculation models to estimate the sound pressure level in buildings due to service equipment. As for the field measurement documents (EN ISO 16032 for the engineering method and EN ISO 10052 for the survey method), it covers sanitary installations, mechanical ventilation, heating and cooling, service equipment, lifts, rubbish chutes, boilers, blowers, pumps and other auxiliary service equipment, and motor driven car park doors, but can also be applied to others equipment attached to or installed in buildings. The estimation is generally based on measured data that characterizes both the equipment (source) and the sound transmission through the building. The same equipment can be composed of different airborne and/or structure borne sources at different locations in the building; the standard gives some information on these sources and how they can be characterized; however, models of the equipment itself are out of the scope of this standard.
This document describes the principles of the calculation models, lists the relevant input and output quantities and defines its applications and restrictions. The models given are applicable to calculations in frequency bands. It is intended for acoustical experts and provides the framework for the development of application documents and tools for other users in the field of building construction, considering local circumstances.
The calculation models described use the most general approach for engineering purposes, with a link to measurable input quantities that specify the performance of building elements and equipment. However, it is important for users to be aware that other calculation models also exist, each with their own applicability and restrictions.
The models are based on experience with predictions for dwellings and offices; they could also be used for other types of buildings provided the dimensions of constructions are not too different from those in dwellings.
- Standard74 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies a method for the measurement of room acoustic parameters in unoccupied open-plan offices. It specifies measurement procedures, the apparatus needed, the coverage required, the method for evaluating the data, and the presentation of the test report.
This document describes a group of single-number quantities indicating the room acoustic performance of an open-plan office in a condition when one person is speaking. They focus on spatial decay of speech while the quantities in ISO 3382-2 focus on temporal decay of sound.
- Standard25 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies field survey methods for measuring
a) airborne sound insulation between rooms,
b) impact sound insulation of floors,
c) airborne sound insulation of façades, and
d) sound pressure levels in rooms caused by service equipment.
The methods described in this document are applicable for measurements in rooms of dwellings or in rooms of comparable size with a maximum of 150 m3.
For airborne sound insulation, impact sound insulation and façade sound insulation the method gives values which are (octave band) frequency dependent. They can be converted into a single number characterising the acoustical performances by application of ISO 717-1 and ISO 717-2. For heavy/soft impact sound insulation, the results also are given as A-weighted maximum impact sound pressure level. For service equipment sound the results are given directly in A - or C -weighted sound pressure levels.
- Standard41 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies test requirements for the laboratory measurement of the sound insulation of building elements and products, including detailed requirements for the preparation and mounting of the test elements, and for the operating and test conditions. It also specifies the applicable quantities, and provides additional test information for reporting.
The general procedures for airborne and impact sound insulation measurements are given in ISO 10140‑2 and ISO 10140-3, respectively.
- Standard63 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies laboratory methods for measuring the impact sound insulation of floor assemblies.
The test results can be used to compare the sound insulation properties of building elements, classify elements according to their sound insulation capabilities, help design building products which require certain acoustic properties and estimate the in situ performance in complete buildings.
The measurements are performed in laboratory test facilities in which sound transmission via flanking paths is suppressed. The results of measurements made in accordance with this document are not applicable directly to the field situation without accounting for other factors affecting sound insulation, such as flanking transmission, boundary conditions, and loss factor.
A test method is specified that uses the standard tapping machine (see ISO 10140-5:2021, Annex E) to simulate impact sources like human footsteps when a person is wearing shoes. Alternative test methods, using a modified tapping machine or a heavy/soft impact source (see ISO 10140-5:2021, Annex F) to simulate impact sources with strong low frequency components, such as human footsteps (bare feet) or children jumping, are also specified.
This document is applicable to all types of floors (whether heavyweight or lightweight) with all types of floor coverings. The test methods apply only to laboratory measurements.
- Standard24 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the basic measurement procedures for airborne and impact sound insulation of building elements in laboratory test facilities.
- Standard21 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies laboratory test facilities and equipment for sound insulation measurements of building elements, such as:
— components and materials;
— building elements;
— technical elements (small building elements);
— sound insulation improvement systems.
It is applicable to laboratory test facilities with suppressed radiation from flanking elements and structural isolation between source and receiving rooms.
This document specifies qualification procedures for use when commissioning a new test facility with equipment for sound insulation measurements. It is intended that these procedures be repeated periodically to ensure that there are no issues with the equipment and the test facility.
- Standard48 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies a laboratory method for measuring the airborne sound insulation of building products, such as walls, floors, doors, windows, shutters, façade elements, façades, glazing, small technical elements, for instance transfer air devices, airing panels (ventilation panels), outdoor air intakes, electrical raceways, transit sealing systems and combinations, for example walls or floors with linings, suspended ceilings or floating floors.
The test results can be used to compare the sound insulation properties of building elements, classify elements according to their sound insulation capabilities, help design building products which require certain acoustic properties and estimate the in situ performance in complete buildings.
The measurements are performed in laboratory test facilities in which sound transmission via flanking paths is suppressed. The results of measurements made in accordance with this document are not applicable directly to the field situation without accounting for other factors affecting sound insulation, such as flanking transmission, boundary conditions and total loss factor.
- Standard23 pagesEnglish languagesale 10% offe-Library read for1 day
This document
a) defines single-number quantities for impact sound insulation in buildings and of floors,
b) gives rules for determining these quantities from the results of measurements carried out in one-third-octave bands in accordance with ISO 10140-3 and ISO 16283-2, and in octave bands in accordance with that option in ISO 16283-2 for field measurements only,
c) defines single-number quantities for the impact sound reduction of floor coverings and floating floors calculated from the results of measurements carried out in accordance with ISO 10140-3, and
d) specifies a procedure for evaluating the weighted reduction in impact sound pressure level by floor coverings on lightweight floors.
The single-number quantities in accordance with this document are intended for rating impact sound insulation and for simplifying the formulation of acoustical requirements in building codes. An additional single-number evaluation in steps of 0,1 dB is indicated where it is needed for the expression of uncertainty (except for spectrum adaptation terms). Numerical values of the single-number quantities are specified where required for calculations.
The rating of measurements over an enlarged frequency range is given in Annex A.
A method for obtaining single-number quantities for bare heavy floors according to their performance in combination with floor coverings is given in Annex B.
Example calculations of single-number quantities are given in Annex C.
The rating of measurements with a heavy and soft impact source (rubber ball) is given in Annex D.
- Standard31 pagesEnglish languagesale 10% offe-Library read for1 day
This document
a) defines single-number quantities for airborne sound insulation in buildings and of building elements such as walls, floors, doors, and windows,
b) takes into consideration the different sound level spectra of various noise sources such as noise sources inside a building and traffic outside a building, and
c) gives rules for determining these quantities from the results of measurements carried out in one-third-octave or octave bands for example in accordance with ISO 10140-2 and ISO 16283-1.
The single-number quantities in accordance with this document are intended for rating airborne sound insulation and for simplifying the formulation of acoustical requirements in building codes. An additional single-number evaluation in steps of 0,1 dB is indicated for the expression of uncertainty (except for spectrum adaptation terms). The required numerical values of the single-number quantities are specified according to varying needs. The single-number quantities are based on results of measurements in one-third-octave bands or octave bands.
For laboratory measurements made in accordance with ISO 10140-2, single-number quantities are calculated using one-third-octave bands only.
The rating of results of measurements carried out over an enlarged frequency range is dealt with in Annex B.
- Standard34 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies a laboratory measurement method to determine noise radiated from a floor covering on a standard concrete floor when excited by a standard tapping machine.
- Standard18 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies procedures for assessing the measurement uncertainty of sound insulation in building acoustics. It provides for
— a detailed uncertainty assessment;
— a determination of uncertainties by inter-laboratory tests;
— an application of uncertainties.
Furthermore, typical uncertainties are given for quantities determined according to ISO 10140 (all parts), ISO 16283 (all parts) and ISO 717 (all parts).
- Standard29 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies an alternating airflow method for the determination of the airflow resistance[5], [6] of porous materials for acoustical applications.
Determination of the airflow resistance based on static flow is described in ISO 9053‑1.
- Standard27 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies measurement methods to characterize in the laboratory the acoustic radiation of a building element when it is directly excited by an airborne or structure-borne source. It is applicable to single-leaf and double-leaf elements (see ISO 12354-1:2017 Annex F, F2). The measured quantity can be used as input data for prediction methods, such as ISO 12354-1 and ISO 12354-2, to compare products, or to express a requirement.
- Standard18 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies procedures to determine the impact sound insulation using sound pressure measurements with an impact source operating on a floor or stairs in a building. These procedures are intended for room volumes in the range from 10 m3 to 250 m3 in the frequency range from 50 Hz to 5 000 Hz. The test results can be used to quantify, assess and compare the impact sound insulation in unfurnished or furnished rooms where the sound field may or may not approximate to a diffuse field.
- Standard53 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies how to calculate:
— the uncertainty of sound absorption coefficients and equivalent sound absorption areas measured according to ISO 354;
— the uncertainty of the practical and weighted sound absorption coefficients determined according to ISO 11654;
— the uncertainty of the object sound absorption coefficient according to ISO 20189; and
— the uncertainty of the single number rating determined according to EN 1793‑1.
Furthermore, the use of uncertainties in reporting measured or weighted sound absorption coefficients is explained.
- Standard16 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the measurement of the determination of the static airflow resistance[1,2], in a laminar flow regime, of porous materials for acoustical applications.
- Standard16 pagesEnglish languagesale 10% offe-Library read for1 day
ISO 3822-3:2018 specifies the mounting and operating conditions to be used for in-line valves and appliances which control the flow, pressure or temperature of the water in water supply installations, when measuring noise emission resulting from water flow.
ISO 3822-3:2018 is applicable to in-line valves and appliances of maximum nominal size DN 32 and to systems in which the maximum water flow rate does not exceed 1,6 l/s.
NOTE See ISO 6708; DN is the symbol for "nominal size". The number of the nominal size is loosely related to the inside diameter (in millimetres) of the in-tine valves and appliances.
The procedures described are for general use for all types of in-line valves of conventional design.
- Standard16 pagesEnglish languagesale 10% offe-Library read for1 day
- Amendment20 pagesEnglish languagesale 10% offe-Library read for1 day
The purpose of this document is to indicate how to present the uncertainty data determined by EN ISO 12999-1 in a laboratory test report of the Sound reduction index R of a building product or a building system, determined in accordance with EN ISO 717-1 and EN ISO 10140-2:2010, Figure B.1. It is planned to include this information in EN ISO 10140-2.
- Technical report6 pagesEnglish languagesale 10% offe-Library read for1 day
ISO 10848 (all parts) specifies measurement methods to characterize the flanking transmission of one or several building components.
ISO 10848-4:2017 specifies laboratory and field measurements of buildings where at least one of the elements that form the construction under test is a Type A element (defined in ISO 10848‑1).
Laboratory measurements are used to quantify the performance of the junction with suppressed flanking transmission from the laboratory structure. Field measurements are used to characterize the in situ performance and it is not usually possible to suppress unwanted flanking transmission sufficiently; hence, the results are primarily representative of the performance of that junction when installed in that particular building structure.
The measured quantities can be used to compare different products, or to express a requirement, or as input data for prediction methods, such as ISO 12354‑1 and ISO 12354‑2.
- Standard14 pagesEnglish languagesale 10% offe-Library read for1 day
ISO 10848 (all parts) specifies measurement methods to characterize the flanking transmission of one or several building components. This document considers only laboratory measurements.
The measured quantities can be used to compare different products, or to express a requirement, or as input data for prediction methods, such as ISO 12354‑1 and ISO 12354‑2. However, the measured quantities Dn,f, Ln,f and Lne0,f only represent the performance with the dimensions for the test specimens described in this document.
ISO 10848-2:2017 is referred to in ISO 10848‑1:2017, 4.5 as being a supporting part of the frame document. It applies to Type B elements as defined in ISO 10848‑1, such as suspended ceilings, access floors, light uninterrupted façades or floating floors. The transmission from one room to another can occur simultaneously through the test element and via the plenum (if any). For measurements made according to this document, the total sound transmission is determined and it is not possible to separate the two kinds of transmission.
- Standard19 pagesEnglish languagesale 10% offe-Library read for1 day
ISO 10848 (all parts) specifies measurement methods to characterize the flanking transmission of one or several building components.
ISO 10848-3:2017 specifies laboratory and field measurements of buildings for Type B elements (defined in ISO 10848‑1) when the junction has a substantial influence.
Laboratory measurements are used to quantify the performance of the junction with suppressed flanking transmission from the laboratory structure. Field measurements are used to characterize the in situ performance and it is not usually possible to suppress unwanted flanking transmission sufficiently; hence, the results can only be considered representative of the performance of that junction when installed in that particular building structure.
ISO 10848-3:2017 is referred to in ISO 10848‑1:2017, 4.5 as being a supporting part to the frame document and applies to Type B elements that are structurally connected as defined in ISO 10848‑1.
The measured quantities can be used to compare different products, or to express a requirement, or as input data for prediction methods, such as ISO 12354‑1 and ISO 12354‑2.
The relevant quantity to be measured is selected according to ISO 10848‑1:2017, 4.5. The performance of the building components is expressed either as an overall quantity for the combination of elements and junction (such as Dn,f,ij and/or Ln,f,ij and/or Lne0,f,ij) or as the normalized direction-average velocity level difference of a junction. Dn,f,ij, Ln,f,ij, Lne0,f,ij and depend on the actual dimensions of the elements.
- Standard15 pagesEnglish languagesale 10% offe-Library read for1 day
ISO 10848 (all parts) specifies measurement methods to characterize the flanking transmission of one or several building components. These measurements are performed in a laboratory test facility or in the field.
The performance of the building components is expressed either as an overall quantity for the combination of elements and junction (such as the normalized flanking level difference and/or normalized flanking impact sound pressure level) or as the vibration reduction index of a junction or the normalized direction-average vibration level difference of a junction.
Two approaches are used for structure-borne sound sources in buildings, a normalized flanking equipment sound pressure level and a transmission function that can be used to estimate sound pressure levels in a receiving room due to structure-borne excitation by service equipment in a source room. The former approach assumes that flanking transmission is limited to one junction (or no junction if the element supporting the equipment is the separating element), and the latter considers the combination of direct (if any) and all flanking transmission paths.
ISO 10848-1:2017 contains definitions, general requirements for test elements and test rooms, and measurement methods. Guidelines are given for the selection of the quantity to be measured, depending on the junction and the types of building elements involved. Other parts of ISO 10848 specify the application for different types of junction and building elements.
The quantities characterizing the flanking transmission can be used to compare different products, or to express a requirement, or as input data for prediction methods, such as ISO 12354‑1 and ISO 12354‑2.
- Standard43 pagesEnglish languagesale 10% offe-Library read for1 day
ISO 12354-3:2017 specifies a calculation model to estimate the sound insulation or the sound pressure level difference of a façade or other external surface of a building. The calculation is based on the sound reduction index of the different elements from which the façade is constructed and it includes direct and flanking transmission. The calculation gives results which correspond approximately to the results from field measurements in accordance with ISO 16283‑3. Calculations can be carried out for frequency bands or for single number ratings.
The calculation results can also be used for calculating the indoor sound pressure level due to for instance road traffic (see Annex E).
ISO 12354-3:2017 describes the principles of the calculation model, lists the relevant quantities and defines its applications and restrictions.
- Standard37 pagesEnglish languagesale 10% offe-Library read for1 day
- Standard – translation32 pagesSlovenian languagesale 10% offe-Library read for1 day
ISO 12354-2:2017 specifies calculation models designed to estimate the impact sound insulation between rooms in buildings, primarily using measured data which characterize direct or indirect flanking transmission by the participating building elements and theoretically-derived methods of sound propagation in structural elements.
A detailed model is described for calculation in frequency bands, in the frequency range 1/3 octave 100 Hz to 3150 Hz in accordance with ISO 717‑1, possibly extended down to 1/3 octave 50 Hz if element data and junction data are available (see Annex E); the single number rating of buildings can be determined from the calculation results. A simplified model with a restricted field of application is deduced from this, calculating directly the single number rating, using the single number ratings of the elements; the uncertainty on the apparent impact sound pressure level calculated using the simplified model can be determined according to the method described in ISO 12354‑1:2017, Annex K (see Clause 5).
ISO 12354-2:2017 describes the principles of the calculation scheme, lists the relevant quantities and defines its applications and restrictions.
- Standard54 pagesEnglish languagesale 10% offe-Library read for1 day
- Standard – translation53 pagesSlovenian languagesale 10% offe-Library read for1 day
ISO 12354-4:2017 specifies a calculation model to estimate the sound power level radiated by the envelope of a building due to airborne sound inside that building, primarily by means of measured sound pressure levels inside the building and measured data which characterize the sound transmission by the relevant elements and openings in the building envelope. These sound power levels, together with those of other sound sources in or in front of the building envelope, form the basis for the calculation of the sound pressure level at a chosen distance from a building as a measure for the acoustic performance of buildings.
The prediction of the inside sound pressure level from knowledge of the indoor sound sources is outside the scope of this document.
The prediction of the outdoor sound propagation is outside the scope of this document.
NOTE For simple propagation conditions an approach is given for the estimation of the sound pressure level in Annex E.
ISO 12354-4:2017 describes the principles of the calculation model, lists the relevant quantities and defines its applications and restrictions.
- Standard31 pagesEnglish languagesale 10% offe-Library read for1 day
- Standard – translation30 pagesSlovenian languagesale 10% offe-Library read for1 day
ISO 12354-1:2017 specifies calculation models designed to estimate the airborne sound insulation between adjacent rooms in buildings, primarily using measured data which characterize direct or indirect flanking transmission by the participating building elements, and theoretically-derived methods of sound propagation in structural elements.
A detailed model is described for calculation in frequency bands, in the frequency range 1/3 octave 100 Hz to 3 150 Hz in accordance with ISO 717‑1, possibly extended down to 1/3 octave 50 Hz if element data and junction data are available (see Annex I); the single number rating can be determined from the calculation results. A simplified model with a restricted field of application is deduced from this, calculating directly the single number rating, using the single number ratings of the elements; a method to determine uncertainty is proposed for the simplified model (see Annex K).
ISO 12354-1:2017 describes the principles of the calculation scheme, lists the relevant quantities and defines its applications and restrictions.
- Standard102 pagesEnglish languagesale 10% offe-Library read for1 day
- Standard – translation95 pagesSlovenian languagesale 10% offe-Library read for1 day
This European Standard specifies methods for estimating the structure-borne sound power produced in buildings by services equipment (sources) from measurements under laboratory conditions. The data can be used as explained in Annex D, as input for EN 12354-5, or under certain conditions for EN ISO 12354 2, to calculate the sound pressure levels produced by the same equipment when installed in buildings. The data can also be used to compare the performance of products as explained in Annex E.
As for the document predicting the structure-borne sound levels produced in the buildings by service equipment (EN 12354-5), this European Standard covers water supply and sanitary installations, mechanical ventilation, heating and cooling devices, service equipment, lifts, rubbish chutes, boilers, blowers, pumps, motors and other auxiliary service equipment, such as motor driven car park doors; it can also be applied to other vibrating equipment attached to or installed in buildings. This standard is so far restricted to steady-state vibrating sources.
This revised European Standard:
- specifies laboratory measuring methods for determining the source input data required to calculate the source installed power, i.e. the equipment free velocity, the equipment blocked force and the equipment mobility;
- applies to equipment, which can be connected to isolated plates in the laboratory. For equipment, such as pipe systems or impacted lightweight stairs [16], which are connected to at least two building elements (wall and floor), a coupled reception plate system is specified, which requires the use of a power substitution method. The later method can also be used in situ when the equipment, such as lifts, can only be tested in situ;
- defines the expression of the source installed structure-borne power for any source-receiver mobility conditions, including lightweight and heavyweight receiving building elements. This power is used as input data in EN 12354-5, which predicts the sound pressure level generated by the source installed in situ in a building;
- defines a method to calculate the total structure-borne sound power generated by the equipment fictively mounted on two sets of reference test plates (respectively of low mobility and of high mobility); the two results will inform the manufacturers on the difference in the equipment performance between these two common but very different situations;
- does not specify any method for the measurement of the source airborne sound power. If measurements of the equipment airborne sound power are required, then refer to EN ISO 3740 to EN ISO 3747 and use the same source mounting conditions and operating conditions as in measuring using EN 15657.
- Standard31 pagesEnglish languagesale 10% offe-Library read for1 day
ISO 16283-3:2016 specifies procedures to determine the airborne sound insulation of façade elements (element methods) and whole façades (global methods) using sound pressure measurements. These procedures are intended for room volumes in the range from 10 m3 to 250 m3 in the frequency range from 50 Hz to 5 000 Hz.
The test results can be used to quantify, assess, and compare the airborne sound insulation in unfurnished or furnished rooms where the sound field can or cannot approximate to a diffuse field. The measured airborne sound insulation is frequency-dependent and can be converted into a single number quantity to characterize the acoustic performance using the rating procedures in ISO 717-1.
- Standard46 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies information additional to EN ISO 10140 1 necessary to carry out efficiently and under standardized conditions the determination of the sound reduction index of drywall systems of plasterboard with steel studs according to EN ISO 10140 2 “Acoustics — Laboratory measurement of sound insulation of -building elements — Part 2: Measurement of airborne sound insulation”. Observe that all demands in EN ISO 10140 2 should still be fulfilled. In order to decrease the uncertainty, it specifies:
- additional guidelines for testing drywall systems of plasterboard with steel studs;
and
- a method to validate laboratory by using two reference test partitions.
The results obtained are used to convert frequency-dependent sound reduction index into single number ratings, according to EN ISO 717 1. These performances can be used to compare different products, or, and to express a requirement, or, and as input into estimation methods, such as EN 12354 1.
- Standard28 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies additional necessary information on how to carry out efficiently and under standardized conditions the determination of the sound absorption coefficients according to EN ISO 354 “Measurement of sound absorption in a reverberation room”. It specifies the additional requirements of the sound absorption measurements and the operating and mounting conditions that should be used for the test. Observe that all demands in EN ISO 354 still should be fulfilled. The results obtained are used for design calculations with respect to room acoustics and to convert frequency-dependent sound absorption coefficients into a weighted sound absorption coefficient αw, according to EN ISO 11654.
This European Standard is applicable for the compile of the single number rating αw, to express the sound absorption performance of suspended ceiling membranes in CE marking and labelling according to EN 13964. This European Standard is not applicable for suspended ceiling kits according to EN 13964.
- Standard18 pagesEnglish languagesale 10% offe-Library read for1 day
ISO 16251-1:2014 specifies a laboratory measurement method to determine the improvement of impact sound insulation by a floor covering when laid on a standard concrete floor mock-up and excited by a standard tapping machine. The method is restricted to soft, flexible floor coverings, which transmit impact sound mainly "locally" into the floor, i.e. through the area close to the points of excitation, so that the size of the flooring specimen does not have an influence on the results. Examples of such floor coverings are carpets, PVC, and linoleum. These floor coverings correspond to ISO 10140‑1:2010, Annex H, category I.
The results only provide information about the noise radiated. A subjective classification of the quality of the floor coverings is not intended.
ISO 16251-1:2014 provides the measurement method. Product test codes can contain further requirements concerning the specimens, such as temperature range, the number of test specimens or special mounting conditions.
- Standard18 pagesEnglish languagesale 10% offe-Library read for1 day
ISO 16283-1:2014 specifies procedures to determine the airborne sound insulation between two rooms in a building using sound pressure measurements. These procedures are intended for room volumes in the range from 10 m3 to 250 m3 in the frequency range from 50 Hz to 5 000 Hz. The test results can be used to quantify, assess and compare the airborne sound insulation in unfurnished or furnished rooms where the sound field may or may not approximate to a diffuse field. The measured airborne sound insulation is frequency-dependent and can be converted into a single number quantity to characterize the acoustic performance using the rating procedures in ISO 717‑1.
- Standard52 pagesEnglish languagesale 10% offe-Library read for1 day
ISO 15186-2:2003 specifies a sound intensity method to determine the in-situ sound insulation of walls, floors, doors, windows and small building elements. It is intended for measurements that have to be made in the presence of flanking transmission. It can be used to provide sound power data for diagnostic analysis of flanking transmission or to measure flanking sound insulation parameters.
ISO 15186-2:2003 can be used by laboratories that could not satisfy the requirements of ISO 15186-1, which deals with laboratory measurements with no or little flanking transmission. ISO 15186-3 deals with measurements under laboratory conditions, at low frequencies.
ISO 15186-2:2003 also describes the effect of flanking transmission on measurements made using the specified method, and how intensity measurements can be used
-- to compare the in-situ sound insulation of a building element with laboratory measurements where flanking has been suppressed (i.e. ISO 140-3),
-- to rank the partial contributions for building elements, and
-- to measure the flanking sound reduction index for one or more transmission paths (for validation of prediction models such as those given in EN 12354-1).
This method gives values for airborne sound insulation, which are frequency dependent. They can be converted into a single number, characterizing the acoustic performance, by application of ISO 717-1.
The reproducibility of this intensity method is estimated to be equal to or better than that of the methods of ISO 140-10 and ISO 140-4, when measuring a single small and large building element, respectively.
- Standard32 pagesEnglish languagesale 10% offe-Library read for1 day
ISO 15186-3:2002 specifies a sound intensity method to determine the sound reduction index and the element-normalized level difference of building elements at low frequencies. This method has significantly better reproducibility in a typical test facility than those of ISO 140-3, ISO 140-10 and ISO 15186-1. The results are more independent of the room dimensions of the laboratory and closer to values that would be measured between rooms of volume greater than 300 m3. ISO 15186-3 is applicable in the frequency range 50 Hz to 160 Hz but is mainly intended for the frequency range 50 Hz to 80 Hz.
NOTE For elements faced with thick, porous absorbers, the recommended frequency range is 50 Hz to 80 Hz.
The main differences between the methods of ISO 15186-1 and ISO 15186-3 are that in ISO 15186-3
the sound pressure level of the source room is measured close to the surface of the test specimen, andthe surface opposite the test specimen in the receiving room is highly absorbing and converts the room acoustically into a duct with several propagating cross-modes above the lowest cut-on frequency.
The results found by the method of ISO 15186-3 can be combined with those of ISO 140-3 and ISO 15186-1 to produce data in the frequency range 50 Hz to 5 000 Hz.
The reproducibility of this intensity method is, for all frequencies, estimated to be equal to or better than that found with the method of ISO 140-3 at 100 Hz.
Some comparisons of data obtained with this part of ISO 15186 and with ISO 140-3 are given for information.
- Standard21 pagesEnglish languagesale 10% offe-Library read for1 day
ISO 3382-1:2009 specifies methods for the measurement of reverberation time and other room acoustical parameters in performance spaces. It describes the measurement procedure, the apparatus needed, the coverage required, and the method of evaluating the data and presenting the test report. It is intended for the application of modern digital measuring techniques and for the evaluation of room acoustical parameters derived from impulse responses.
- Standard34 pagesEnglish languagesale 10% offe-Library read for1 day
- Amendment9 pagesEnglish languagesale 10% offe-Library read for1 day
ISO - Taking over of an ISO Technical Corrigendum
- Corrigendum4 pagesEnglish languagesale 10% offe-Library read for1 day
ISO 3382-2:2008 specifies methods for the measurement of reverberation time in ordinary rooms. It describes the measurement procedure, the apparatus needed, the required number of measurement positions, and the method for evaluating the data and presenting the test report.
The measurement results can be used for correction of other acoustic measurements, e.g. sound pressure level from sound sources or measurements of sound insulation, and for comparison with requirements for reverberation time in rooms.
- Standard25 pagesEnglish languagesale 10% offe-Library read for1 day
ISO 18233:2006 gives guidelines and specifies requirements for the application of new methods for the measurement of the acoustic properties of buildings and building elements. Guidelines and requirements for selection of the excitation signal, signal processing and environmental control are given, together with requirements for linearity and time-invariance for the systems to be tested.
ISO 18233:2006 is applicable to such measurements as airborne sound insulation between rooms and of façades, measurement of reverberation time and other acoustic parameters of rooms, measurement of sound absorption in a reverberation room, and measurement of vibration level differences and loss factor.
ISO 18233:2006 specifies methods to be used as substitutes for measurement methods specified in standards covering classical methods, such as ISO 140 (all parts), ISO 3382 (all parts) and ISO 17497-1.
- Standard33 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the technical requirements relating to acoustics for a product standard, European Technical Approval Guidelines (ETAG) or European Technical Approval (ETA) for a specific building product or equipment, or a family of building products or equipment. In particular, it gives advice on how to write requirements in response to the mandated characteristics on acoustics under the Construction Products Directive.
NOTE 1 In the remainder of this document, the terms used relate to CEN and product standards. The concepts are, however, equally applicable to the European Organisation for Technical Approvals (EOTA).
The purpose of this document is to assist the product Technical Committees in preparing acoustic clauses to ensure that such product standards:
- are as homogeneous as possible, with each individual product standard having the same basic structure;
- are in full accordance with the standards for the measurement of acoustic properties;
- reflect the latest technical knowledge of methods of determining the acoustical properties from the specific family of building products or equipment under consideration.
NOTE 2 Clause 2 lists the European and International Standards to be used in the drafting of acoustic provisions standard. Annex A contains an outline of a typical acoustic product standard summarizing the information that is required. Annex B contains guidance on choosing appropriate properties. Annex C describes the relevant measured acoustic properties for common products.
- Technical report35 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard describes a calculation model to estimate the total equivalent sound absorption area or reverberation time of enclosed spaces in buildings. The calculation is primarily based on measured data that characterise the sound absorption of materials and objects. Calculations can only be carried out for frequency bands.
This European Standard describes the principles of the calculation model, lists the relevant quantities and defines its applications and restrictions. It is intended for acoustical experts and provides the framework for the development of application documents and tools for other users in the field of building construction, taking into account local circumstances.
The model is based on experience with predictions for rooms, such as rooms in dwellings and offices, and common spaces in buildings, such as stairwells, corridors and rooms containing machinery and technical equipment. It is not intended to be used for very large or irregularly-shaped spaces, such as concert halls, theatres and factories.
- Standard25 pagesEnglish languagesale 10% offe-Library read for1 day
- Standard – translation24 pagesSlovenian languagesale 10% offe-Library read for1 day
- Standard17 pagesEnglish languagesale 10% offe-Library read for1 day
ISO 354:2003 specifies a method of measuring the sound absorption coefficient of acoustical materials used as wall or ceiling treatments, or the equivalent sound absorption area of objects, such as furniture, persons or space absorbers, in a reverberation room. It is not intended to be used for measuring the absorption characteristics of weakly damped resonators.
The results obtained can be used for comparison purposes and for design calculation with respect to room acoustics and noise control.
- Standard24 pagesEnglish languagesale 10% offe-Library read for1 day
Specifies a method for the determination of the sound absorption coefficient, reflection factor, surface impedance or admittance of materials and objects. The values are determined by evaluation of the standing wave pattern of a plane wave in a tube, which is generated by the superposition of an incident sinusiodal plane wave with the plane wave reflected from the test object.
- Standard23 pagesEnglish languagesale 10% offe-Library read for1 day