EN 54-2:1997/A1:2006
(Amendment)Fire detection and fire alarm systems - Part 2: Control and indicating equipment
Fire detection and fire alarm systems - Part 2: Control and indicating equipment
DOW = 2007-12-31 (SV on 2005-11-24)
Brandmeldeanlagen - Teil 2: Brandmelderzentralen
Systèmes de détection et d'alarme incendie - Partie 2: Equipement de contrôle et de signalisation
Sistemi za odkrivanje in javljanje požara ter alarmiranje - 2. del: Požarna centrala
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-marec-2007
Sistemi za odkrivanje in javljanje požara ter alarmiranje - 2. del: Požarna centrala
Fire detection and fire alarm systems - Part 2: Control and indicating equipment
Brandmeldeanlagen - Teil 2: Brandmelderzentralen
Systemes de détection et d'alarme incendie - Partie 2: Equipement de contrôle et de
signalisation
Ta slovenski standard je istoveten z: EN 54-2:1997/A1:2006
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD
EN 54-2:1997/A1
NORME EUROPÉENNE
EUROPÄISCHE NORM
October 2006
ICS 13.220.20
English Version
Fire detection and fire alarm systems - Part 2: Control and
indicating equipment
Systèmes de détection et d'alarme incendie - Partie 2: Brandmeldeanlagen - Teil 2: Brandmelderzentralen
Equipement de contrôle et de signalisation
This amendment A1 modifies the European Standard EN 54-2:1997; it was approved by CEN on 27 April 2006.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for inclusion of this
amendment into the relevant national standard without any alteration. Up-to-date lists and bibliographical references concerning such
national standards may be obtained on application to the Central Secretariat or to any CEN member.
This amendment exists in three official versions (English, French, German). A version in any other language made by translation under the
responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,
Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania,
Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36 B-1050 Brussels
© 2006 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 54-2:1997/A1:2006: E
worldwide for CEN national Members.
Contents Page
Foreword.4
Foreword.5
2 Normative references .5
3 Definitions and abbreviations .5
5 General requirements for indications.8
7 The fire alarm condition .8
7.5 Other indications during the fire alarm condition.9
7.8 Output to fire alarm devices (option with requirements – see also 8.2.5 a) and 9.4.2 a)) .9
7.9 Control of fire alarm routing equipment (options with requirements).10
7.9.1 Output to fire alarm routing equipment (option with requirements – see also 8.2.5 b) and
9.4.2 b)) .10
7.9.2 Alarm confirmation input from fire alarm routing equipment (option with requirements) .10
7.10 Outputs to fire protection equipment (options with requirements) .10
7.10.1 Output type A (option with requirement – see also 8.2.4 f) and 9.4.1 b)).10
7.10.2 Output type B (option with requirement – see also 8.2.4 f) and 9.4.1 b)).10
7.10.3 Output type C (option with requirement – see also 8.2.4 f) and 9.4.1 b)).10
7.10.4 Fault monitoring of fire protection equipment (option with requirement – see also 8.2.4 f)).10
7.11 Delays to outputs (option with requirements; see also Annex E) .10
7.12 Dependencies on more than one alarm signal (options with requirement) .11
7.12.1 Type A dependency (option with requirement) .11
7.12.2 Type B dependency (option with requirement) .12
7.12.3 Type C dependency (option with requirement) .12
8 Fault warning condition (see also Annex F) .12
8.2 Indication of faults.13
8.4 Total loss of the power supply (option with requirements) .14
8.8 Fault output .14
8.9 Output to fault warning routing equipment (option with requirements - see also 8.2.4.g)
and 9.4.1.c)) .14
9 Disabled condition.14
10 Test condition (option with requirements).15
10.3 Indication of zones in the test state.15
11 Standardized input/output interface (option with requirements – see also Annex G) .16
12 Design requirements .16
13 Additional design requirements for software controlled control and indicating equipment .18
13.4 Program monitoring (see also Annex I) .18
13.5 The storage of programs and data (see also Annex I).19
13.6 The monitoring of memory contents .19
14 Marking .19
15 Tests.20
15.1.5 Provision for tests .20
15.3 Environmental tests .20
15.3.1 General.20
15.3.2 Tests for one specimen.21
15.3.3 Tests for more than one specimen .21
15.8 Electromagnetic Compatibility (EMC), Immunity tests (operational).22
Annex A (informative) Explanation of access levels .25
Annex B (informative) Optional functions with requirements and alternatives .26
Annex E (informative) Delays to outputs .27
Annex H (informative) Integrity of transmission paths .29
Annex I (informative) Design requirements for software controlled control and indicating
equipment.30
Bibliography.40
Foreword
This document (EN 54-2:1997/A1:2006) has been prepared by Technical Committee CEN/TC 72 “Fire
detection and fire alarm systems”, the secretariat of which is held by BSI.
This Amendment to the European Standard EN 54-2:1997 shall be given the status of a national standard,
either by publication of an identical text or by endorsement, at the latest by April 2007, and conflicting national
standards shall be withdrawn at the latest by December 2007.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports essential requirements of EU Directive(s).
For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document.
Amendment 1 to this standard improves the additional requirements for software controlled equipment and
makes a number of miscellaneous changes, to correct errors and better reflect the current state of the art. It
also replaces the descriptions of the individual electromagnetic compatibility immunity tests with a reference to
the EMC Product Family Standard EN 50130-4, makes editorial and technical changes to generally improve
clarity, and updates the normative references.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Cyprus, Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden,
Switzerland and United Kingdom.
Foreword
Replace Date of Withdrawal to read
December 2007
2 Normative references
Clause 2: Delete the existing text and substitute
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 54-1:1996, Fire detection and fire alarm systems — Part 1: Introduction
EN 54-4:1997, Fire detection and fire alarm systems — Part 4: Power supply equipment
EN 54-7:2000, Fire detection and fire alarm systems - Part 7: Smoke detectors - Point detectors using
scattered light, transmitted light or ionization
EN 50130-4:1995, Alarm systems — Part 4: Electromagnetic compatibility — Product family standard:
Immunity requirements for components of fire, intruder and social alarm systems
EN 60068-1:1994, Environmental testing - Part 1: General and guidance (IEC 60068-1:1988 + Corrigendum
1988 + A1:1992)
EN 60068-2-1:1993, Environmental testing; part 2: tests; tests A: cold (IEC 60068-2-1:1990)
EN 60068-2-6:1995, Environmental testing - Part 2: Tests - Tests Fc: Vibration (sinusoidal) (IEC 60068-2-
6:1995 + Corrigendum 1995)
EN 60068-2-47:2005, Environmental testing - Part 2-47: Test Mounting of specimens for vibration, impact and
similar dynamic tests (IEC 60068-2-47:2005)
EN 60068-2-75:1997, Environmental testing - Part 2: Tests - Test Eh: Hammer tests (IEC 60068-2-75:1997)
EN 60068-2-78:2001, Environmental testing — Part 2-78: Tests, Test Cab: Damp heat, steady state (IEC
60068-2-78:2001)
EN 60529:1991, Degrees of protection provided by enclosures (IP code) (IEC 60529:1989)
EN 60721-3-3:1995, Classification of environmental conditions - Part 3: Classification of groups of
environmental parameters and their severities - Section 3: Stationary use at weatherprotected locations (IEC
60721-3-3:1994)
3 Definitions and abbreviations
Delete 3.1.1 until 3.1.22 and substitute
3.1.1
Deleted (numbering kept)
3.1.2
addressable point
point that can be individually identified at the CIE
3.1.3
alphanumeric display
indicator that is capable of giving information by the display of messages consisting of text and/or numeric
characters
3.1.4
functional condition
state of the CIE characterised by mandatory indication(s)
NOTE The functional conditions recognized in this European Standard are the following:
- fire alarm condition, when a fire alarm is indicated,
- fault warning condition, when a fault is indicated,
- disabled condition, when the disablement of functions is indicated,
- test condition, when the testing of functions is indicated,
- quiescent condition, when the CIE is powered by a power supply conforming to EN 54-4 and no other
functional condition is indicated.
3.1.5
detection circuit
transmission path that connects points to the CIE
3.1.6
earth fault
unwanted connection between earth potential and any part of the CIE, transmission paths to the CIE, or
transmission paths between parts of the CIE
3.1.7
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.