kSIST FprEN 50699:2020
(Main)This document specifies the requirements of the test procedures to be applied for recurrent tests of current-using electrical equipment and appliances for the verification of the effectiveness of the protective measures and the permissible limits for product compliance.
This procedure is applicable to current-using electrical equipment connected to final circuits. They can be either pluggable equipment type A connected to final circuits at work places via a plug or permanently connected equipment, with a rated voltage above 25 V AC and 60 V DC up to 1 000 V AC and 1 500 V DC, and currents up to 63A.
This document does not cover:
— Test after repair defined in FprEN 50678;
— type tests, routine tests, sample tests, special tests and acceptance tests for product safety nor for product functional requirements.
This document does not apply to:
— devices and equipment that are part of the fixed electrical installations defined in HD 60364 (all parts);
— uninterruptible Power Supply (UPS), photovoltaic inverters and power converters, e.g. AC/DC converters;
— charging stations for electro-mobility;
— stationary power supplies (generators);
— programmable Logic Controllers (PLC);
— power Drives;
— devices for EX-zones or for mining applications in general;
— products already covered by standards addressing similar topics such as:
— medical equipment covered by EN 60601 1. For these devices, EN 62353 applies;
— arc welding equipment covered by EN 60974 1. For these devices, EN 60974 4 applies;
— Machinery covered by EN 60204 1. For these devices, EN 60204 1 applies.
Wiederholungsprüfung für elektrische Geräte
Dieses Dokument legt die Anforderungen an die Prüfverfahren fest, die anlässlich einer wiederkehrenden Prüfung elektrischer Verbrauchsmittel und Geräte zur Überprüfung der Wirksamkeit der Schutzmaßnahmen auf Einhaltung der zulässigen Grenzwerte anzuwenden sind. Dieses Verfahren gilt für [...]
Essais récurrents des appareils électriques
Ponavljalni preskus električne opreme
General Information
Standards Content (sample)
SLOVENSKI STANDARD
oSIST prEN 50699:2020
01-februar-2020
Ponavljalni preskus električne opreme
Recurrent Test of Electrical Equipment
Ta slovenski standard je istoveten z: prEN 50699
ICS:
29.020 Elektrotehnika na splošno Electrical engineering in
general
oSIST prEN 50699:2020 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------oSIST prEN 50699:2020
---------------------- Page: 2 ----------------------
oSIST prEN 50699:2020
EUROPEAN STANDARD DRAFT
prEN 50699
NORME EUROPÉENNE
EUROPÄISCHE NORM
December 2019
ICS
English Version
Recurrent Test of Electrical Equipment
To be completed To be completed
This draft European Standard is submitted to CENELEC members for enquiry.
Deadline for CENELEC: 2020-03-19.
It has been drawn up by CLC/BTTF 160-1.
If this draft becomes a European Standard, CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
This draft European Standard was established by CENELEC in three official versions (English, French, German).
A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to
the CEN-CENELEC Management Centre has the same status as the official versions.CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2019 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Project: 67716 Ref. No. prEN 50699 E---------------------- Page: 3 ----------------------
oSIST prEN 50699:2020
prEN 50699:2019 (E)
1 Contents Page
2 European foreword ...................................................................................................................................3
3 Introduction ...............................................................................................................................................4
4 1 Scope ...............................................................................................................................................5
5 2 Normative references .......................................................................................................................5
6 3 Terms and definitions .......................................................................................................................6
7 4 Requirements ...................................................................................................................................9
8 5 Tests .................................................................................................................................................9
9 5.1 General ...................................................................................................................................9
10 5.1.1 General test conditions ...................................................................................................9
11 5.1.2 Visual inspection ......................................................................................................... 10
12 5.1.3 Test of the protective measures against electric hazards ........................................... 10
13 5.1.4 Confirmation of the compliance of additional protective measures............................. 10
14 5.1.5 Documentation and evaluation of test ......................................................................... 11
15 5.2 Visual inspection .................................................................................................................. 11
16 5.3 Measuring of protective bonding resistance ........................................................................ 12
17 5.4 Measurement of the insulation resistance ........................................................................... 14
18 5.5 Measurement of protective conductor current ..................................................................... 19
19 5.6 Measurement of the touch current ...................................................................................... 23
20 5.7 Confirmation of the compliance of the specifications for the protective measure
21 SELV/PELV ......................................................................................................................... 26
22 5.8 Measurement of the leakage current produced by a floating input (measuring- and
23 control input) with a rated input voltage above 50 V a.c or 120 V d.c ................................. 26
24 5.9 Confirmation of the operation of further protective measures ............................................. 27
25 5.10 Final verification of marking ................................................................................................. 27
26 6 Documentation and evaluation of test ........................................................................................... 27
27 7 Test equipment .............................................................................................................................. 28
28 Annex A (informative) General guidance and rationale ....................................................................... 29
29 Annex B (informative) Schematics for test sequences ......................................................................... 33
30 Annex C (normative) Special National Conditions ............................................................................... 35
31 Bibliography ........................................................................................................................................... 36
---------------------- Page: 4 ----------------------oSIST prEN 50699:2020
prEN 50699:2019 (E)
32 European foreword
33 This document (prEN 50699:2019) has been prepared by CLC/BTTF 160-1 “Recurrent Test of
34 Electrical Equipment”.35 This document is currently submitted to the second Enquiry.
36 The following dates are proposed:
• latest date by which the existence of this (doa) dor + 6 months
document has to be announced at national
level
latest date by which this document has to be (dop) dor + 12 months
implemented at national level by publication of
an identical national standard or by
endorsement
• latest date by which the national standards (dow) dor + 36 months
conflicting with this document have to be (to be confirmed or
withdrawn
modified when voting)
---------------------- Page: 5 ----------------------
oSIST prEN 50699:2020
prEN 50699:2019 (E)
37 Introduction
38 This document provides a uniform procedure for an employer/work place to test the effectiveness of
39 the basic protective measures for recurrent tests of current using electrical equipment and appliances
40 during their operating life time41 This document can be considered to support compliance with the European Directive 2009/104/EC
42 concerning the minimum safety and health requirements for the use of work equipment by workers at
43 work and does not necessarily involve the manufacturer.44 In general, test procedures for verification of products is the responsibility of the related product
45 technical committees. This document can be taken into consideration by product technical committees
46 if they need to take into consideration modified or additional tests for verification of products falling
47 within their scope.”48 The described tests are simple and fast, well approved and safe for the testing person.
49 They can be carried out on site and/or in laboratories.---------------------- Page: 6 ----------------------
oSIST prEN 50699:2020
prEN 50699:2019 (E)
50 1 Scope
51 This document specifies the requirements of the test procedures to be applied for recurrent tests of
52 current-using electrical equipment and appliances for the verification of the effectiveness of the
53 protective measures and the permissible limits for product compliance.54 This procedure is applicable to current-using electrical equipment connected to final circuits. They can
55 be either pluggable equipment type A connected to final circuits at work places via a plug or
56 permanently connected equipment, with a rated voltage above 25 V AC and 60 V DC up to 1 000 V
57 AC and 1 500 V DC, and currents up to 63A.58 This document does not cover:
59 — Test after repair defined in FprEN 50678;
60 — type tests, routine tests, sample tests, special tests and acceptance tests for product safety nor
61 for product functional requirements.62 This document does not apply to:
63 — devices and equipment that are part of the fixed electrical installations defined in
64 HD 60364 (all parts);65 — uninterruptible Power Supply (UPS), photovoltaic inverters and power converters, e.g. AC/DC
66 converters;67 — charging stations for electro-mobility;
68 — stationary power supplies (generators);
69 — programmable Logic Controllers (PLC);
70 — power Drives;
71 — devices for EX-zones or for mining applications in general;
72 — products already covered by standards addressing similar topics such as:
73 — medical equipment covered by EN 60601-1. For these devices, EN 62353 applies;
74 — arc welding equipment covered by EN 60974-1. For these devices, EN 60974-4 applies;
75 — Machinery covered by EN 60204-1. For these devices, EN 60204-1 applies.76 2 Normative references
77 The following documents are referred to in the text in such a way that some or all of their content
78 constitutes requirements of this document. For dated references, only the edition cited applies. For
79 undated references, the latest edition of the referenced document (including any amendments) applies.
80 EN 61557-1, Electrical safety in low voltage distribution systems up to 1 000 V a.c. and 1 500 V d.c. -
81 Equipment for testing, measuring or monitoring of protective measures - Part 1: General requirements
82 EN 61557-2, Electrical safety in low voltage distribution systems up to 1 000 V a.c. and 1 500 V d.c. -
83 Equipment for testing, measuring or monitoring of protective measures - Part 2: Insulation resistance
---------------------- Page: 7 ----------------------oSIST prEN 50699:2020
prEN 50699:2019 (E)
84 EN 61557-4, Electrical safety in low voltage distribution systems up to 1 000 V a.c. and 1 500 V d.c. -
85 Equipment for testing, measuring or monitoring of protective measures - Part 4: Resistance of earth
86 connection and equipotential bonding87 EN 61557-16, Electrical safety in low voltage distribution systems up to 1 000 V a.c. and 1 500 V d.c. -
88 Equipment for testing, measuring or monitoring of protective measures - Part 16: Equipment for testing
89 the effectiveness of the protective measures of electrical equipment and/or medical electrical
90 equipment91 IEC 60417, Graphical Symbols for Use on Equipment
92 3 Terms and definitions
93 For the purposes of this document, the following terms and definitions apply.
94 ISO and IEC maintain terminological databases for use in standardization at the following addresses:
95 — IEC Electropedia: available at http://www.electropedia.org/96 — ISO Online browsing platform: available at http://www.iso.org/obp
97 NOTE Some of the definitions are different from those in the product standards for type testing, as different
98 measuring methods are used.99 3.1
100 electrical safety
101 protection within a piece of equipment which limits the effects of electrical current on a user or other
102 individuals103 Note 1 to entry: Safety is defined as freedom from unacceptable risk (refer to ISO 14971:2007, definition
104 2.24).105 3.2
106 testing
107 process of visually controlling, measuring or proving the electrical equipment in order to assure that
108 equipment remains safe to use109 3.3
110 electrically skilled person
111 skilled person
112 person with relevant education and experience to enable him or her to perceive risks and to avoid
113 hazards which electricity can create114 [SOURCE: IEV 195-04-01]
115 3.4
116 electrically instructed person
117 instructed person
118 person adequately advised or supervised by electrically skilled persons to enable him or her to
119 perceive risks and to avoid hazards which electricity can create120 [SOURCE: IEV, 195-04-02]
---------------------- Page: 8 ----------------------
oSIST prEN 50699:2020
prEN 50699:2019 (E)
121 3.5
122 electrical equipment
123 single apparatus using electrical energy and connected by plug or permanently connected to a final
124 circuit of the distribution system125 Note 1 to entry: Equipment includes those accessories as defined by the manufacturer that are necessary to
126 enable the normal use of the equipment.127 3.6
128 final circuit
129 electric circuit intended to directly supply electric current to current-using equipment or
130 socket-outlets131 [SOURCE: IEV 826-14-03]
132 3.7
133 leakage current
134 current flowing from live parts of the equipment to earth
135 [SOURCE: IEV 442-01-24 modified – the term has changed and a reference to the absence of an
136 insulation fault has been removed.]137 3.8
138 touch current
139 current passing through a human or animal body when it touches one or more accessible parts of a
140 piece of electrical equipment not connected to protective earth141 [SOURCE: IEV 195-05-21 modified – the wording of the definition has been narrowed]
142 3.9143 protective conductor current
144 electric current which flows in a protective conductor and is frequency weighted according to the
145 characteristics of the human body146 [SOURCE: IEV 826-11-21, modified – the wording of the definition has been expanded.]
147 3.10148 residual current
149 vectorial sum of the currents flowing in the live conductors of the mains circuit of the equipment and
150 frequency weighted according to the characteristics of the human body151 [SOURCE: IEV 442-05-19 modified – the wording of the definition has been expanded]
152 3.11153 insulation resistance
154 resistance under specified conditions between two conductive elements separated by insulating
155 materials156 [SOURCE: IEV 151-15-43]
---------------------- Page: 9 ----------------------
oSIST prEN 50699:2020
prEN 50699:2019 (E)
157 3.12
158 protective bonding resistance
159 resistance between any accessible conductive part, which is connected for safety purposes to the
160 protective earth terminal, and the161 — protective terminal of the mains plug, or
162 — protective terminal of the equipment inlet, or
163 — protective terminal permanently connected to the supply mains;
164 3.13
165 SELV
166 electric system in which the voltage cannot exceed the value of extra-low voltage:
167 — under normal conditions, and168 — under single fault conditions, including earth faults in other electric circuits
169 Note 1 to entry: SELV is the abbreviation for safety extra-low voltage.170 [SOURCE: IEV 826-12-31]
171 3.14
172 PELV
173 electric system in which the voltage cannot exceed the value of extra-low voltage:
174 — under normal conditions, and175 — under single fault conditions, except earth faults in other electric circuits
176 Note 1 to entry: PELV is the abbreviation for protective extra-low voltage.177 [SOURCE: IEV 826-12-32]
178 3.15
179 recurrent test
180 periodic verification of the effectiveness of protective measures of electrical equipment
181 3.16182 permanently connected equipment
183 equipment that can only be electrically connected to or disconnected from the mains by the use of a
184 tool185 3.17
186 pluggable equipment type A
187 equipment that is intended for connection to the mains via a non-industrial plug and socket outlet or
188 via a non-industrial appliance coupler, or both189 Note 1 to entry: Examples are plugs and socket-outlets covered by standards such as EN 60320-1.
190 3.18191 current-using equipment
192 electrical equipment intended to convert electrical energy into another form of energy, for example
193 light, heat, mechanical energy194 [SOURCE: IEC 60050-826:2004, 826-16-02]
---------------------- Page: 10 ----------------------
oSIST prEN 50699:2020
prEN 50699:2019 (E)
195 3.19
196 hazardous live parts
197 live part which, under certain conditions, can give a harmful electric shock
198 [SOURCE: IEC 60050-826:2004, 826-12-13]
199 4 Requirements
200 Recurrent tests shall be performed by an electrically skilled person or by an electrically instructed
201 person, supervised by an electrically skilled person.202 Additional requirements (e.g. for the mechanical safety or for fire protection) according to the
203 requirements from the product safety standard shall be taken into account.204 If testing the equipment requires additional knowledge or additional test and measurement equipment,
205 for example equipment for microwaves, tests shall be done according to the instructions of the
206 manufacturer.207 All tests shall be performed in such a manner that the risk for testing personnel or other individuals
208 shall be reduced by appropriate protective measures.209 If not otherwise stated, all values for current and voltage are the r.m.s. values of an alternating, direct
210 or composite voltage or current.211 The applicable tests as listed in Clause 5 shall be used to advise that:
212 — there are no visible faults on safety related parts, which are accessible by the user and
213 — by the intended use of the equipment, minimized hazard for the user or the environment
214 originates.215 The electrically skilled person who is responsible for the test shall decide if additional tests are
216 required to meet the protective measures.217 During a recurrent test the equipment shall not be disassembled. The electrically skilled person may
218 decide that, for equipment that is connected to the distribution system with fixed and protected wiring
219 and is not intended to be hand-held during operation, the test is carried out according to this document
220 and/or according to HD 60364-6.221 The test procedure shall be interrupted and the equipment shall be disconnected from mains and
222 marked as failed, if it is found that during the test:223 — reduced safety levels are present due to damage or from unintended use;
224 and/or
225 — functional hazards could occur.
226 5 Tests
227 5.1 General
228 5.1.1 General test conditions
229 The tests may be performed at the ambient temperature, humidity and atmospheric pressure present
230 at the location of testing.231 If it is obvious that the equipment is contaminated by dust or moisture, it is allowed to clean the
232 equipment under test and/or to allow it to dry before starting the tests233 The operational limits of the test equipment and the equipment under test shall be taken into account.
---------------------- Page: 11 ----------------------oSIST prEN 50699:2020
prEN 50699:2019 (E)
234 The equipment shall be tested according to the test steps in 5.1.1 to 5.1.5, as long as it is possible
235 with the equipment under test. The sequence of testing shall be as defined in this document.
236 Each individual test shall be passed before proceeding to the next test.237 If it is not possible to perform a certain test step, an electrically skilled person shall decide if the safety
238 of the equipment under test can be confirmed without the test step or by other means. This decision
239 has to be justified and reported.240 Manufacturer’s instructions on tests to be performed, shall be considered
241 The values in this document shall be used unless the product standard specifically provides in-service
242 limits in which case the product standard limits shall be used or justified values from the manufacturer.
243 External equipment could influence the tests and should be disconnected if possible.
244 NOTE In general this document does not address the measurement of DC leakage currents.
245 5.1.2 Visual inspection246 Visual inspection shall be performed according to 5.2.
247 5.1.3 Test of the protective measures against electric hazards
248 Test of the protective measures against electric hazards shall be performed according to 5.3 to 5.8.
249 — Confirmation of the effectiveness of the protective bonding to all accessible conductive parts
250 connected for safety reasons to protective earth according to 5.3.251 — Confirmation of the effectiveness of the insulation by measuring the insulation resistance between
252 live parts and accessible conductive parts:253 — connected to protective earth (primarily on class I equipment) according to 5.4;
254 — protected by double or reinforced Insulation and not connected to protective earth (primarily
255 on class II equipment but also on class I equipment) according to 5.4;256 — protected by SELV/PELV according to 5.4.
257 — Confirmation of the compliance with the limits for the leakage currents by measuring of:
258 — the protective conductor current according to 5.5;259 — The touch current of accessible conductive parts not connected to protective earth, if
260 applicable, according to 5.6.261 NOTE The measurement of leakage current can be omitted on extension leads, detachable power cables,
262 multiple socket-outlets without electrical parts between live conductors and protective earth.
263 — Confirmation of the compliance with the requirements for the protective measure SELV/PELV by
264 measuring the output voltage, if the output voltage is accessible according to 5.7.
265 — Confirmation of the compliance with the limits for the leakage currents produced by a floating
266 input (e.g. inputs for measuring and control) with a rated input voltage above 50 V a.c or
267 120 V d.c. according to 5.8.268 5.1.4 Confirmation of the compliance of additional protective measures
269 Confirmation of the compliance of additional protective measures shall be according to 5.9.
---------------------- Page: 12 ----------------------oSIST prEN 50699:2020
prEN 50699:2019 (E)
270 5.1.5 Documentation and evaluation of test
271 The documentation and the evaluation of the tests shall be according to Clause 6.
272 5.2 Visual inspection273 The visual inspection shall take place to detect external defects and, if possible, to determine the
274 qualification of the suitability of the equipment for the environment.275 Special attention shall be paid to the following (if applicable):
276 — any damage or contamination;
277 — that all cables and connectors are connected in their intended way ;
278 — checking by hand to ensure that the anchorages and the inlets of each connector are properly
279 fixed.280 — condition of the mains plug and the mains connectors and conductors;
281 — defects of the strain relief of the mains supply cord;
282 — defect of the mains lead cleat;
283 — condition of anchorage, cable clip, accessible fuse insert;
284 — damage of the housing and protective cover that could give access to live or dangerous moving
285 parts;286 — signs of overload or overheating or unintended use;
287 — signs of improper change;
288 — signs of contamination, corrosion and improper aging;
289 — contamination, blockage of cooling inlets ;
290 — condition of air filter;
291 — tightness of container for water, air, or other medium, condition of pressure control valve;
292 — usability of switches, control and setup equipment;293 — readability of all safety relevant markings or symbols, of the ratings and of the position indicators;
294 — all fuses accessible from the outside are complying with the data given by the manufacturer (rated
295 current, characteristics) and must be visible on the device;296 — safety related marking, labels and labelling is legible and complete;
297 — the integrity of mechanical parts;
298 — assess the relevant accessories together with the equipment (e.g. detachable or fixed power
299 supply cords tubing);300 — defect due to bending of cords, cables, hoses and tubing.
301 NOTE 1 It is appropriate to determine during the visual inspection, if accessible conductive parts, that have to
302 be tested according to 5.3 to 5.8, are present.---------------------- Page: 13 ----------------------
oSIST prEN 50699:2020
prEN 50699:2019 (E)
303 NOTE 2 This list is not exhaustive
304 5.3 Measuring of protective bonding resistance
305 The integrity of the connection between:
306 — the protective earth terminal of the equipment (where applicable contact on the mains plug) and
307 — each accessible conductive part, directly connected to the protective earth.
308 NOTE 1 Not directly connected part’s (e.g. mechanical construction parts) could have higher values. On these
309 parts compliance with safety requirements is proved by touch current measurements.
310 The integrity of those connections shall be confirmed by:311 — visually inspecting the entire length of the protective earth path according to 5.2;
312 — measuring the resistance of each protective terminal; and313 NOTE 2 During the measurement, the conductor is flexing over the entire length and at the point of entry on
314 the equipment and the mains plug.315 Test circuits according to Figure 1a or Figure 1b may be used.
316 For cable lengths up to 5 m and a cross section area up to 1,5 mm2, the protective bonding resistance
317 shall not exceed 0,3 Ω. For each further 7,5 m cable length 0,1 Ω shall be added to the limit up to a
318 maximum value of 1 Ω.319 For cross section areas above 1,5 mm2 and other cable lengths the limit shall be calculated by the
320 following formula.321 R=p+=01,,ΩΩor R + 01
AAκ
322 where
R is the electrical resistance (Ω);
ρ is the standard value of electrical conductivity (m/(Ω mm2) for the metal used for the PE
conductor.;l is the length of the cable in meters (m);
A is the cross-sectional area of the conductor in square millimetres (mm2);
κ is the electrical conductivity (m/(Ω mm2).
323 NOTE 3 The value of 0,1 Ω in the formulae above takes into account the influence of the contact resistance.
324 It is recommended that care be taken to ensure that the contact resistance between the test probe and
325 the metal part under test does not influence the test result.326 When equipment under test is permanently connected to the distribution system, an earth reference
327 point on the fixed installation is required to measure the earth continuity. The protective earth
328 conductor shall not be disconnected from the installation and protective covers shall not be removed.
329 NOTE 4 During this measurement parallel earth connections, for example due to the type of installation (water
330 pipe or data line), can influence the result.331 NOTE 5 Some equipment under test could have accessible metal parts which are earthed only for functional
332 or screening purposes with protection against electric shock being provided by double or reinforced insulation.
---------------------- Page: 14 ----------------------oSIST prEN 50699:2020
prEN 50699:2019 (E)
333
334 a) Example measuring circuit for the measurement of protective earth resistance in equipment
335 that is disconnected from the supply mains---------------------- Page: 15 ----------------------
oSIST prEN 50699:2020
prEN 50699:2019 (E)
336
337 b) Example measuring circuit for the measurement of protective earth resistance in equipment,
338 which for functional reasons cannot be disconnected from supply mains, or in equipment or
339 permanently connected to mains340 Key
G generating measuring supply
1 test equipment
2 equipment under test
3 fuse or circuit breaker
4 socket
9.1 test probe to protective earth and to accessible protective parts, connected to PE
9.3 test probe to live parts10 possible earth connections
341 Figure 1 — Example measuring circuits for the measurement
342 of protective earth resistance
343 5.4 Measurement of the insulation resistance
344 The insulation resistance shall be measured:
345 — between live parts and each accessible conductive part, including protective earth (except PELV);
346 — between live parts of a SELV/PELV circuit and live parts of mains supply.---------------------- Page: 16 ----------------------
oSIST prEN 50699:2020
prEN 50699:2019 (E)
347 The test circuits and limits in Table 1 shall be used. The equipment under test shall be disconnected
348 from mainssupply. To include all insulation of all live parts, all switches, controls etc. shall be closed
349 during the measurement. If necessary, the measurements shall be repeated in all switch positions.
350 I...