IEC 60115-8-10:2026 is applicable to the drafting of detail specifications for surface mount (SMD) low-power film resistors, classified to level G, based on the definition of the product classification levels in IEC 60115‑1:2020, 3.4. This edition includes the following significant technical changes with respect to the previous edition IEC 60115‑8‑1:2014: a) it supports solderability testing for both traditional lead-bearing soldering and up-to-date lead-free soldering, as required; b) it supports the provision of detailed visual acceptance criteria; c) it includes the requirement for a visual examination of the primary and proximity packaging; d) it provides for the inclusion of specific visual acceptance criteria, to be applied in addition to those given in Annex B of the sectional specification IEC 60115‑8:2023.

  • Draft
    48 pages
    English language
    e-Library read for
  • Draft
    73 pages
    English language
    e-Library read for

NOTE Throughout this standard, the abbreviation ACS (ASSEMBLY for construction site, see 3.1.101) is used for a low-voltage switchgear and controlgear assembly intended for use on construction and similar sites. This part of 61439 defines the specific requirements of ACS as follows: - ASSEMBLIES for which the rated voltage does not exceed 1 000 V in case of AC or 1 500 V in case of DC; - ASSEMBLIES where the nominal primary voltage and the nominal secondary voltage of transformers incorporated in ACS are within the limits specified above; - ASSEMBLIES intended for use on construction sites, both indoors and outdoors, i.e. temporary places of work to which the public do not generally have access and where building construction, installation, repairs, alteration or demolition of property (buildings) or civil engineering (public works) or excavation or any other similar operations are carried out; - transportable (semi-fixed) or mobile ASSEMBLIES with enclosure. The manufacture and/or assembly may be carried out other than by the original manufacturer. This standard does not apply to individual devices and self-contained components, such as motor starters, fuse switches, electronic equipment, etc. which will comply with the relevant product standards. This standard does not apply to ASSEMBLIES for use in the administrative centres of construction sites (offices, cloakrooms, ASSEMBLY rooms, canteens, restaurants, dormitories, toilets, etc.). Requirements for electrical protection provided by equipment manufactured according to this International Standard are given in IEC 60364-7-704.

  • Standard
    31 pages
    English language
    e-Library read for

This part of IEC 60695 summarises the test methods that are used in the assessment of the corrosivity of fire effluent. It presents a brief summary of test methods in common use, either as international standards, national or industry standards. It includes special observations on their relevance, for electrotechnical products and their materials, to real fire scenarios and gives recommendations on their use.

  • Standard
    27 pages
    English language
    e-Library read for

IEC/IEEE 62395-2:2024 provides detailed recommendations for the system design, installation, maintenance and repair of electrical resistance trace heating systems in industrial and commercial applications. This document does not include or provide for any applications in potentially explosive atmospheres. This standard cancels and replaces IEC 62395-2:2013. This edition constitutes a technical revision. This standard includes the following significant technical changes with respect to IEC 62395-2:2013: a) Design considerations for trace heating on sprinkler systems have been expanded and a figure has been added to illustrate how to avoid undue shadowing of spray patterns from insulated sprigs close to sprinkler heads; b) Specific details of design considerations for trace heating for emergency eyewash units and safety showers have been added.

  • Corrigendum
    1 page
    English language
    e-Library read for

The scope of this part of IEC 62351 is to facilitate role-based access control (RBAC) for power system management. RBAC assigns human users, automated systems, and software applications (collectively called "subjects" in this document) to specified "roles", and restricts their access to only those resources, which the security policies identify as necessary for their roles.
As electric power systems become more automated and cyber security concerns become more prominent, it is becoming increasingly critical to ensure that access to data (read, write, control, etc.) is restricted. As in many aspects of security, RBAC is not just a technology; it is a way of running a business. RBAC is not a new concept; in fact, it is used by many operating systems to control access to system resources. Specifically, RBAC provides an alternative to the all-ornothing super-user model in which all subjects have access to all data, including control commands.
RBAC is a primary method to meet the security principle of least privilege, which states that no subject should be authorized more permissions than necessary for performing that subject’s task. With RBAC, authorization is separated from authentication. RBAC enables an organization to subdivide super-user capabilities and package them into special user accounts' termed roles for assignment to specific individuals according to their associated duties. This subdivision enables security policies to determine who or what systems are permitted access to which data in other systems. RBAC thus provides a means of reallocating system controls as defined by the organization policy. In particular, RBAC can protect sensitive system operations from inadvertent (or deliberate) actions by unauthorized users. Clearly RBAC is not confined to human users though; it applies equally well to automated systems and software applications, i.e., software parts operating independent of user interactions.
The following interactions are in scope:
– local (direct wired) access to the object by a human user, a local and automated computer agent, or a built-in human machine interface (HMI) or panel;
– remote (via dial-up or wireless media) access to the object by a human user;
– remote (via dial-up or wireless media) access to the object by a remote automated computer agent, e.g., another object at another substation, a distributed energy resource at an enduser’s facility, or a control centre application.
While this document defines a set of mandatory roles to be supported, the exchange format for defined specific or custom roles is also in scope of this document. This is achieved by defining two different encoding approaches to handle the definition of custom roles, either based on specific permissions or based on constraints to existing permissions. The definition on handling custom based roles was started in IEC 62351-90-1 and taken over into the IEC 62351-8:2020. Moreover, additionally to the definition of custom roles based on associated permissions, this document also includes options how to assign permissions to objects in a general way. Referencing documents will provide a mapping to a concrete data model to ensure an interoperability for standard roles used in different data models as well as for custom defined roles. Referencing documents might be standards such as IEC PAS 61850-90-19 or IEC 60870-5-7:2025 or also definitions by an operator.
Out of scope for this document are all topics which are not directly related to the definition of roles and access tokens for local and remote access, especially administrative or organizational tasks, such as:
– definition of usernames and password definitions/policies;
– management of keys and/or key exchange;
– engineering process of roles;
– assignment of roles;
– selection of trusted certification authorities issuing credentials (access tokens);
– defining the tasks of a security officer;
– integrating local policies in RBAC.
NOTE Specifically, the manage

  • Draft
    111 pages
    English language
    e-Library read for

This part of IEC 63287 gives guidelines for the development of reliability qualification plans using the early failure assessment, based on the environmental conditioning and
proposed usage of the product. This document is not intended for military- and spacerelated applications.

  • Standard
    19 pages
    English language
    e-Library read for

This part of IEC 63223 series [2] provides an overview of asset management, its principles and value creation options for the management of network assets in power systems.
This document can be applied to all types of network assets and by all types and sizes of power network companies. The term power network company does not necessarily refer to legally structured companies.
In this document, network assets refer mainly to the physical assets of the electrical energy network, meaning items, equipment, or systems that have potential or actual value for the electric company and are part of the power lines and substations responsible for the transmission and distribution of electrical energy. Examples of network assets that can be included in the asset portfolio of a power network company are presented in IEC 63223-2:2026 [6], 4.2.2.

  • Standard
    25 pages
    English language
    e-Library read for

This part of IEC 63478 describes the measurement methods for users’ quality of experience (QoE) parameters on multimedia conferencing services.

  • Draft
    23 pages
    English language
    e-Library read for

IEC/IEEE 62395-1:2024 specifies requirements for electrical resistance trace heating systems and includes general test requirements. This first edition cancels and replaces the second edition published in 2013. This edition constitutes a technical revision. This edition includes the following significant technical changes, apart from general revisions of IEC 62395-1 and harmonization with IEEE 515 [1] and IEEE 515.1 [2], with respect to the previous edition: a) Added control and monitoring requirements for fire sprinkler systems and safety showers. b) Provided a supplemental ice bath method for verification of rated output. c) Provided constructional and type test requirements for glands used to terminate heating devices to an exposed enclosure.

  • Corrigendum
    1 page
    English language
    e-Library read for

This document is applicable to electrical insulating matting made of flexible insulating material for use as a covering of the surface on which the worker is positioned and for worker´s electrical protection on electrical installations up to 36 000 V AC for AC use or 36 000 V AC and 54 000 V DC for AC/DC use.
NOTE 1 The electric potential of the surface on which the worker is positioned is usually that of earth.
NOTE 2 See 4.2 for maximum use voltage.
NOTE 3 DC only rated matting is not specified in this document.
NOTE 4 This document does not cover the use of insulating blankets (see IEC 61112)

  • Draft
    36 pages
    English language
    e-Library read for

This part of IEC 60679 describes the general properties, performance characteristics and usage precautions for quartz crystal oscillators. This document mainly describes crystal oscillators, but some descriptions also apply to oscillators other than crystal units (e.g. MEMS resonators).

  • Standard
    50 pages
    English language
    e-Library read for

This part of IEC 61076 specifies circular connectors with bayonet locking size B12, B17, B23 and B40, typically used for power, signal and data transmissions in industrial applications.
These connectors consist of fixed and free connectors either rewirable or non-rewirable.
NOTE B indicates that the connector is equipped with bayonet locking, while 12, 17, 23, 40 are the approximate dimensions in millimetres of the contact carrier diameter of these circular connectors.
Power contacts of male connectors are round contacts with Ø 1 mm, Ø 1,5 mm, Ø 1,8 mm, Ø 2,25 mm and Ø 4 mm, with current ratings up to 64 A per pole and rated voltage of 50 V, 300 V or 600 V AC/DC. Power contact groups are classified by type and identified throughout this document as “P” followed by two digits “01” through “09” (see 4.3, Table 1).
Signal contacts of male connectors are round contacts with Ø 1 mm and Ø 1,8 mm, with current ratings up to 20 A per pole and rated voltage of 50 V AC/DC. Signal contact groups are classified by type and identified throughout this document as “S” followed by “0”, “1”, or “2” (see 4.3, Table 2).
Male data contacts are round with Ø 0,8 mm and Ø 1 mm, with current ratings up to 4 A and rated voltage of 50 V AC/DC, Data modules are classified by type and identified throughout this document as “D” followed by “1”, or “2” (see 4.3, Table 3). D1 modules provide data transmission with frequencies from 1 MHz to 100 MHz; D2 modules provide data transmission with frequencies from 0,1 MHz to 600 MHz.
Besides the size of their bayonet locking (B12, B17, B23 or B40), connectors according to this document can be identified by data module (D) and complementing power (P) and signal (S) contact groups and optionally by number of poles, and finally by their application.
These connectors are designated for two main target applications, which differ as follows:
– Application A is for data transmission with power over data.
– Application B is for data transmission without power over data.
Connectors with power, signal and data contacts of the same gender are intended to also transmit power over the data contacts (application A), while connectors with data contacts not of the same gender of power and signal contacts are not intended to transmit power over the data contacts (application B).
The codings provided by this document prevent the mating to any other connector with similarly sized interfaces covered by this document.

  • Standard
    109 pages
    English language
    e-Library read for

This part of IEC 62146 includes generalities of capacitors used on alternating current circuitbreakers and introduces specifications for grading capacitors. Regarding grading capacitors, their function is to control the voltage distribution across the individual interrupter units of a multi-break circuit-breaker.
Capacitors can also be used in parallel to the interrupter unit on single break circuit-breakers to modify the Transient Recovery Voltage (TRV). This TRV capacitor application is covered by IEC 62146-2:2023.
Capacitors for high-voltage alternating circuit breakers are sub-components for the circuitbreaker and are specified in accordance with the circuit-breaker specifications according to IEC 62271-1, IEC 62271-100, and if applicable to IEC 62271-203.
This document applies to grading capacitors falling into one or both of the following categories for:
− mounting on air-insulated circuit-breakers.
− mounting on enclosed circuit-breakers (for example immersed in insulating gas, in oil, etc.).
The testing for each of the above applications is in some cases different.
The object of this document is:
− to define uniform rules regarding performances, testing and rating;
− to define specific safety rules;
− to provide a guidance for installation and operation.
NOTE CIGRÉ TB-368 presents a study about the operating environment of voltage grading capacitors applied to high-voltage circuit-breakers (see [2]1).
This document does not apply to capacitors not directly associated with high-voltage alternating current circuit-breakers.

  • Standard
    46 pages
    English language
    e-Library read for

CORRECTED VERSION 2026-07 IEC 60034-8:2026 applies to AC and DC machines and specifies: a) rules for the identification of winding connection points; b) marking of winding terminals; c) direction of rotation; d) relationship between terminal markings and direction of rotation; e) terminal marking of auxiliary devices; f) connection diagrams of machines for common applications. This fourth edition cancels and replaces the third edition published in 2007 and Amendment 1:2014. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) The inclusion of turbine-type synchronous machines in the scope. The content of the corrigendum 1 (2026-07) has been included in this copy.

  • Draft
    36 pages
    English language
    e-Library read for

This part of IEC 60851 specifies the following tests:
– Test 5: Electrical resistance;
– Test 13: Breakdown voltage;
– Test 14: Continuity of insulation;
– Test 19: Dielectric dissipation factor;
– Test 23: Pin hole.
For definitions and general notes on methods of test, Clause 3 of IEC 60851-1:2021 applies.
This part of IEC 60851 also specifies methods for determining the dissipation factor of enamelled winding wire, provided in Annex A.

  • Standard
    35 pages
    English language
    e-Library read for

This document specifies the fundamental aspects of semantic interoperability for the S2 interface and the related data exchange between a CEM and the resource managers within the premises. It provides a technology independent set of data models and interaction patterns in order to enable applications for energy management within the premises. This document does not include:
– mappings to concrete data representations (XML, JSON and similar);
– mappings to application protocols for the message passing;
– security related aspects.
This group EE publication is primarily intended to be used as an EE standard for the products mentioned in the scope, but is also intended to be used by TCs in the preparation of publications for products which are included in the boundary mentioned in the scope of this document.

  • Draft
    104 pages
    English language
    e-Library read for

This part of IEC 60947 provides additional requirements to those given in IEC 60947-5-2 and IEC 60947-5-1:2024, Annex D (reed contact magnetic switches). It addresses the fault performance aspects of proximity devices with a defined behaviour under fault conditions (PDDB). It does not address any other characteristics that can be required for specific applications.
This document does not apply to protective equipment to directly detect the presence of persons, that are covered by the IEC 61496 series or IEC TS 62998 series.
NOTE 1 A PDDB device can be used to detect indirectly the presence of a person, for example by detecting the position of a platform on which the operator stands (example, garbage trucks).
This document does not specify requirements for the analogue output of PDDB, if any.
This document does not deal with any specific requirements on acoustic noise as the noise emission of proximity devices is not considered to be a relevant hazard.
A PDDB product is intended to be used as sensing subsystem of a safety related control system according to IEC 62061 or ISO 13849-1. Depending on construction principles and complexity, this document is based on product development of the IEC 61508 series to meet the product specific requirements of one or more of the following:
– IEC 61508 series;
– IEC 62061;
– ISO 13849 series.
NOTE 2 The Functional safety device type classification regarding functional safety correlates with IEC 62683-2-3.
This document includes requirements for PDDB when designed for use as part of an interlocking device according to ISO 14119.
This document does not consider aspects of:
– software updates and self-evolving behaviour;
– explosive atmospheres.

  • Standard
    92 pages
    English language
    e-Library read for

This European Standard specifies methods for measuring the performance of electric storage water heaters for the production of sanitary hot water for household and similar use. The object is to state and define the principal performance characteristics of electric storage water heaters and to describe the test methods for measuring these characteristics. NOTE 1 This standard does not apply to; − storage water heaters that use electricity as a secondary source of heating the water; − storage water heaters that do not use a tank to store hot water; − electric storage water heaters that do not meet the minimum (or maximum) output performance of the smallest (or biggest) load profile, as defined in Table 4. NOTE 2 This standard does not specify performance or safety requirements. For safety requirements see EN 60335-1:2020 in conjunction with EN 60335-2-21:2023

  • Draft
    11 pages
    English language
    e-Library read for

This part of IEC 60730 applies to automatic electrical motor-starting relays
– intended to control the start windings of single phase motors;
– for use in, on, or in association with equipment for household appliance and similar use;
NOTE 1 Throughout this document, the word "equipment" means "appliance and equipment" and "control" means "motor-starting relays".
– intended for appliances within the scope of IEC 60335;
– for equipment that is used in building automation within the scope of ISO 16484 series and IEC 63044 series (HBES/BACS);
– for equipment that is used by the public, such as equipment intended to be used in shops, offices, hospitals, farms and commercial and industrial applications;
EXAMPLE 1 Controls for commercial catering, heating and air-conditioning equipment.
– used in, on, or in association with equipment that are smart enabled;
EXAMPLE 2 Smart grid control, remote interfaces/control of energy-consuming equipment.
– that are AC or DC powered with a rated voltage not exceeding 690 V AC or 600 V DC;
– used in, on, or in association with equipment that use electricity, gas, oil, solid fuel, solar thermal energy, etc., or a combination thereof;
– utilized as part of a control system or controls which are mechanically integral with multifunctional controls having non-electrical outputs;
– using NTC or PTC thermistors, requirements for which are contained in Annex J;
– that are mechanically or electrically operated, responsive to or controlling such characteristics as current and voltage, or combinations thereof;
EXAMPLE 3 Centrifugal motor-starting devices.
– as well as manual controls when such are electrically and/or mechanically integral with automatic controls.
NOTE 2 Requirements for manually actuated mechanical switches not forming part of an automatic control are contained in IEC 61058-1-1.
This document applies to
– the inherent safety of motor-starting control, and
– functional safety of motor-starting control and safety related systems (when required),
– controls where the performance (for example the effect of EMC phenomena) of the product can impair the overall safety and performance of the controlled system,
– the operating values, operating times, and operating sequences where such are associated with equipment safety,
– motor-starting controls incorporating electronic devices, thermistor elements, thermal elements or magnetic elements.
This document specifies the requirements for construction, operation and testing of automatic electrical motor-starting relays used in, on, or in association with an equipment.
This document does not
– apply to motor-starting relays designed exclusively for industrial process applications unless explicitly mentioned in the relevant equipment standard. However, this document can be applied to motor-start relays for equipment intended specifically for industrial applications in cases where no relevant safety standard exists;
– take into account the response value of an automatic action of a control, if such a response value is dependent upon the method of mounting the control in the equipment. Where a response value is of significant purpose for the protection of the user, or surroundings, the value defined in the appropriate equipment standard or as determined by the manufacturer will apply;
– apply to general purpose relays or to contactors and motor starters of the type covered by IEC 60947 series;
– apply to mechanically operated motor-starting devices.

  • Standard
    20 pages
    English language
    e-Library read for

This part of IEC 60730 applies to automatic electrical motor-starting relays
– intended to control the start windings of single phase motors;
– for use in, on, or in association with equipment for household appliance and similar use;
NOTE 1 Throughout this document, the word "equipment" means "appliance and equipment" and "control" means "motor-starting relays".
– intended for appliances within the scope of IEC 60335;
– for equipment that is used in building automation within the scope of ISO 16484 series and IEC 63044 series (HBES/BACS);
– for equipment that is used by the public, such as equipment intended to be used in shops, offices, hospitals, farms and commercial and industrial applications;
EXAMPLE 1 Controls for commercial catering, heating and air-conditioning equipment.
– used in, on, or in association with equipment that are smart enabled;
EXAMPLE 2 Smart grid control, remote interfaces/control of energy-consuming equipment.
– that are AC or DC powered with a rated voltage not exceeding 690 V AC or 600 V DC;
– used in, on, or in association with equipment that use electricity, gas, oil, solid fuel, solar thermal energy, etc., or a combination thereof;
– utilized as part of a control system or controls which are mechanically integral with multifunctional controls having non-electrical outputs;
– using NTC or PTC thermistors, requirements for which are contained in Annex J;
– that are mechanically or electrically operated, responsive to or controlling such characteristics as current and voltage, or combinations thereof;
EXAMPLE 3 Centrifugal motor-starting devices.
– as well as manual controls when such are electrically and/or mechanically integral with automatic controls.
NOTE 2 Requirements for manually actuated mechanical switches not forming part of an automatic control are contained in IEC 61058-1-1.
This document applies to
– the inherent safety of motor-starting control, and
– functional safety of motor-starting control and safety related systems (when required),
– controls where the performance (for example the effect of EMC phenomena) of the product can impair the overall safety and performance of the controlled system,
– the operating values, operating times, and operating sequences where such are associated with equipment safety,
– motor-starting controls incorporating electronic devices, thermistor elements, thermal elements or magnetic elements.
This document specifies the requirements for construction, operation and testing of automatic electrical motor-starting relays used in, on, or in association with an equipment.
This document does not
– apply to motor-starting relays designed exclusively for industrial process applications unless explicitly mentioned in the relevant equipment standard. However, this document can be applied to motor-start relays for equipment intended specifically for industrial applications in cases where no relevant safety standard exists;
– take into account the response value of an automatic action of a control, if such a response value is dependent upon the method of mounting the control in the equipment. Where a response value is of significant purpose for the protection of the user, or surroundings, the value defined in the appropriate equipment standard or as determined by the manufacturer will apply;
– apply to general purpose relays or to contactors and motor starters of the type covered by IEC 60947 series;
– apply to mechanically operated motor-starting devices.

  • Standard
    20 pages
    English language
    e-Library read for

This part of IEC 61851 applies to the EV supply equipment to provide energy transfer between the supply network and electric vehicles (EVs), with a rated maximum voltage at side A (supply network side) up to 1 000 V AC or up to 1 500 V DC and a rated maximum voltage at side B (EV side) up to 1 250 V DC.
NOTE A rated maximum voltage of the EV supply equipment at side B of up to 1 500 V DC is under consideration.
This document specifies the EV supply equipment of megawatt charging system (MCS) equipped with a coupler according to IEC TS 63379. Systems different to MCS using a coupler specified in IEC TS 63379 are under consideration.
The requirements for bidirectional power flow systems are under consideration.
This document does not cover all safety aspects related to maintenance.
This document specifies systems with protective separation between side A and side B.
The requirements for digital communication between the EV supply equipment and the EV for control of energy transfer are defined in ISO 15118-10 and ISO 15118-20.
EV supply equipment in compliance with this document is not intended to provide energy transfer to a single EV using
– multiple vehicle connectors of the same EV supply equipment, or
– multiple EV supply equipment.
The requirements for such use cases are not specified in this document but are under consideration.
The requirements for EVs mated to EV supply equipment according to this document are specified in ISO 5474-3:2024, Annex B.

  • Draft
    134 pages
    English language
    e-Library read for

This part of IEC 61076-2 covers shielded and unshielded, free and fixed circular connectors without breaking capacity (COC) for power, signal and data transmission, and specifies the common dimensions, mechanical, electrical and transmission characteristics and environmental requirements as well as test specifications, respectively.
NOTE 1 As all the connectors described in this document are equipped with shielded data transmission portions, the attribute “shielded” or “unshielded” refers to the additional presence or lack of a shielded connector body.
The connectors described in this document are equipped with an M12, M17, M23 or M40 screw-locking mechanism or a quick-locking mechanism with a size derived from those.
Fixed and rewirable connectors with male or female contacts, mateable with Mxx screw- or quick-locking plugs.
This document provides multiple mating interfaces each of which is associated with a coding preventing the mating of incompatible male and female connectors. The individual codings differ by their numbers of ways, pin layouts and thicknesses, and thus by their power and data transmission capabilities. These codings are referred to as “Type x” where ‘x’ represents an Arabic number.
The connectors described in this document are intended to be used in one-cable automation applications which require various combinations and levels of power up to 600 V AC/ DC and up to 70 A, and either signal or data transmission, or both, with frequencies up to 600 MHz.
NOTE 2 The requirements (or information) described in this document facilitate data transmission through the following Ethernet media systems as defined in IEEE 802.3:
– single-pair Ethernet (10BASE-T1, 100BASE-T1, 1000BASE-T1);
– Fast Ethernet (100BASE-TX);
– Gigabit Ethernet (1000BASE-T);
– 10-gigabit Ethernet (10GBASE-T).

  • Standard
    98 pages
    English language
    e-Library read for
  • Amendment
    12 pages
    English language
    e-Library read for

Common modification to EN IEC 61851-23 Ed.2 (63680): make Annex BB "informative" instead of "normative"

  • Amendment
    4 pages
    English language
    e-Library read for

IEC 62820‑1‑2:2026 specifies the technical requirements for the composition, functions, performance and test methods of building intercom systems using the Internet protocol (IP), and it is a supplement to IEC 62820‑1‑1. This document is applicable to the IP building intercom systems for both residential and commercial buildings.

  • Standard
    25 pages
    English language
    e-Library read for

This document specifies test methods for the determination of useful high frequency power output in equipment for industrial heating and processing of materials. It is in particular applicable to HF generators made available to users as separate units.
This document is basically applicable to equipment operating in the frequency range 100 kHz to 300 MHz, as defined in IEC 60519-1, with the following limitations.
– This document does not apply to induction heating, which it is possible to carry out in the lower part of the specified frequency band.
– The ISM centre frequencies for dielectric heating and processing of industrial interest are narrow bands about 6,78 MHz, 13,56 MHz, 27,12 MHz and 40,68 MHz.
– This document is not applicable to:
• appliances for household and similar use;
• commercial use;
• laboratory use;
• medical high frequency equipment.
For equipment working in designated ISM bands, it is a legal requirement that the frequency remains within the ISM bands according to CISPR 11, but the resonant frequency of the circuit varies with the change of dielectric parameters of the load. Therefore, the value of the mean output power in the work cycle can be much lower than the value obtained under the test conditions. This value depends upon the response of the tuning system.
NOTE 1 The following criteria are suitable for determination of the classification as industrial equipment:
– commercial equipment is typically designed and planned for series production of many identical units;
– industrial equipment is typically produced in small series or even as single units; the processed goods are consumed or ready for final use at the end of the heating process.
NOTE 2 Heating a workload with dielectric parameters which change significantly in time and/or with temperature, the value of the output power obtained with the actual charge can be different from that obtained with the test load specified in this document.
This document relates to equipment normally operating under continuous rated conditions.

  • Standard
    18 pages
    English language
    e-Library read for

This document specifies test methods for surface electromyography (sEMG) sensors by evaluating the quality of sEMG signals obtained from contracting the muscles of the forearm and hand for wearable applications. It is applicable to sEMG sensors that are used to decipher movement intentions and use them as control signals in situations such as virtual reality, game, unmanned aerial vehicles (UAV), robot control, and home automation. This document does not apply to sEMG sensors intended for medical diagnosis or treatment. For medical devices, national requirements can apply.

  • Standard
    22 pages
    English language
    e-Library read for

This document specifies test methods for the determination of the efficiency of frequency conversion from the electrical input, and of the available and workload microwave output power in industrial microwave heating installations, as well as operational flexibility.
This document is in principle applicable to industrial microwave heating equipment and installations in the frequency range from 300 MHz to 300 GHz but focussed on the microwave ISM frequencies below 6 GHz.
This document relates to industrial microwave heating equipment operating as intended by the manufacturer's specifications for normal operation.
This document does not apply to appliances for household and similar use (covered by IEC 60335-2-25 [1]1), commercial use (covered by IEC 60335-2-90 [2] and IEC 60335-2-110 [3]) or laboratory use (covered by IEC 61010-2-010 [4]).

  • Standard
    19 pages
    English language
    e-Library read for

IEC 60086-2-1:2026 is applicable to primary batteries which are based on standardised electrochemical systems using aqueous electrolytes. It specifies: - the physical dimensions, - the discharge test conditions and discharge performance requirements. IEC 60086-2-1: 2026 cancels and replaces the fourteenth edition of IEC 60086 2 published in 2021. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) separation of lithium batteries into IEC 60086-2-2: Physical and electrical specifications; b) in Clause 3, terms were reordered according to their functions: electrochemical systems, electrical characteristics and specifications; c) TR03 and TR6 were added in Category 1, Round batteries; d) load of digital audio test for LR03, TR03 and R03 was changed from 50 mA to 75 mA and MAD was modified; e) personal grooming test of LR6 was added instead of high drain application test; f) high drain application test was added for TR6; g) radio /clock /remote control test was added for R6S; h) CD, digital audio, wireless gaming and accessories test was removed for LR6, R6P and R6S; i) 4,5 V of common designation was added for 3LR12, 3R12P and 3R12S; j) Annex D for common designation of IEC 60086 2:2021 was moved to IEC 60086 1:2026, as Annex H; k) Annex E for Compliance checklist of IEC 60086 2:2021 was removed and merged into Annex J of IEC 60086 1:2026.

  • Standard
    53 pages
    English language
    e-Library read for

IEC 61400-40:2026 provides the EMC requirements and test methods that apply to the individual wind turbine and all the sub systems which are part of the wind turbine. The current document applies to measurements on individual wind turbines and not multiple wind turbines. This document defines the requirements and test methods for the verification of the wind turbine performance against radiated emissions and the immunity of their components against conducted and radiated phenomena. This document is applicable to onshore and offshore wind turbines.

  • Corrigendum
    1 page
    English language
    e-Library read for

This part of IEC 60909 is applicable to the calculation of short-circuit currents
– in low-voltage three-phase AC systems,
– in high-voltage three-phase AC systems, and
– operating at a nominal frequency of 50 Hz or 60 Hz.
Systems at highest voltages of 550 kV and above with long transmission lines are outside the scope of this document.
This document establishes a general, practicable and concise procedure leading to results which are generally of acceptable accuracy. For this calculation method, an equivalent voltage source at the short-circuit location is introduced. This does not exclude the use of special methods, for example the superposition method, adjusted to particular circumstances, if they give at least the same precision. The superposition method gives the short-circuit current related to the one load flow presupposed. This method, therefore, does not necessarily lead to the maximum respective minimum short-circuit current.
This document deals with the calculation of short-circuit currents in the case of balanced or unbalanced short circuits.
A single line-to-earth fault occurring in networks with isolated or resonant earthing of the neutral point is beyond the scope of this document.
For currents during two separate simultaneous single-phase line-to-earth short circuits in an isolated neutral system or a resonance earthed neutral system, see IEC 60909-3.
Short-circuit currents and short-circuit impedances can also be determined by system tests, by measurement on a network analyser, or numerical simulations with electromagnetic programs.
In existing low-voltage systems, it is possible to determine the short-circuit impedance on the basis of measurements at the location of the prospective short circuit considered.
The calculation of the short-circuit impedance is in general based on the rated data of the electrical equipment and the topological arrangement of the system and has the advantage of being possible both for existing systems and for systems at the planning stage.
In general, two types of short-circuit currents, which differ in their magnitude, are considered:
– maximum short-circuit current which determines the capacity or rating of electrical equipment;
– minimum short-circuit current which can be a basis, for example, for the selection of fuses, for the setting of protective devices, and for checking the run-up of motors.
NOTE The current in a three-phase short circuit is assumed to be made simultaneously in all poles. Investigations of non-simultaneous short circuits, which can lead to higher aperiodic components of short-circuit currents, are beyond the scope of this document.
This document does not cover short-circuit currents deliberately created under controlled conditions (short-circuit testing stations).
This document does not deal with the calculation of short-circuit currents in installations on board ships and aeroplanes.
This document does not distinguish between grid-forming and grid-following converters for the calculation of short-circuit currents.

  • Standard
    75 pages
    English language
    e-Library read for

This document specifies requirements and recommendations to maximize the sustainability of cabling systems including both customer premises infrastructure and the accommodation of information technology equipment by addressing the a) cabling design; b) selection, packaging and transportation of components and related materials; c) installation, operation and maintenance; d) management of waste materials; e) skill sets necessary for designers, installers and users.

  • Standard
    43 pages
    English language
    e-Library read for

This part of IEC 63287 specifies guidelines for a reliability qualification plan for power semiconductor modules to assure reliability targets over the entire product life.
Power semiconductor modules with incorporated control circuits are excluded. Clamped packages that need external pressure for being mounted in a system are excluded, e.g. disctype pressure pack devices.
This document is not intended for medical, military, aeronautics and astronautics-related applications.
NOTE Throughout the document, the term power semiconductor module refers to multichip semiconductor power modules as defined in 3.3.

  • Standard
    38 pages
    English language
    e-Library read for

IEC 60127-4:2026 relates to universal modular fuse-links (UMF) for printed circuits and other substrate systems, used for the protection of electric appliances, electronic equipment, and component parts thereof, normally intended to be used indoors. It does not apply to fuse-links for appliances intended to be used under special conditions, such as in a corrosive or explosive atmosphere. These fuses are normally intended to be mounted or replaced only by appropriately skilled persons using specialized equipment. This document applies in addition to the requirements of IEC 60127-1. The objectives of this part of IEC 60127 are as given in IEC 60127-1, with the additional requirement of a degree of non-interchangeability. This fourth edition cancels and replaces the third edition published in 2005, Amendment 1:2008 and Amendment 2:2012. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) align to IEC 60127-1:2023, third edition; b) enhance the rated current of UMFs to 100A and provide the corresponding maximum voltage drop and maximum sustained dissipation; c) modify the figures; d) update the normative references to the latest version. This International Standard is to be used in conjunction with IEC 60127-1:2023

  • Standard
    37 pages
    English language
    e-Library read for

This part of IEC 62271 is applicable to prefabricated solid-insulation enclosed switchgear and controlgear assemblies designed for:
– alternating current;
– rated voltages above 1 kV and up to and including 52 kV;
– service frequencies up to and including 60 Hz;
– indoor installation;
– areas limited to authorized personnel.
The assembly can include either air-insulated or fluid-filled compartments, or both. For components installed in a solid-insulation enclosed switchgear and controlgear, this
document supplements or even replaces in some cases, the requirements as stated by the individual product standards.
The list of components which can be inside the solid-insulation enclosed switchgear and controlgear is not limited to the ones explicitly cited in this document.

  • Standard
    121 pages
    English language
    e-Library read for