ISO/FDIS 23466
(Main)Critères de conception du calorifuge des principaux équipements et des tuyauteries du circuit primaire principal des centrales nucléaires REP
General Information
Standards Content (sample)
DRAFT INTERNATIONAL STANDARD
ISO/DIS 23466
ISO/TC 85/SC 6 Secretariat: DIN
Voting begins on: Voting terminates on:
2019-12-18 2020-03-11
Design criteria for the thermal insulation of reactor
coolant system main equipments and piping of PWR
nuclear power plants
ICS: 27.120.20
THIS DOCUMENT IS A DRAFT CIRCULATED
FOR COMMENT AND APPROVAL. IT IS
THEREFORE SUBJECT TO CHANGE AND MAY
NOT BE REFERRED TO AS AN INTERNATIONAL
STANDARD UNTIL PUBLISHED AS SUCH.
IN ADDITION TO THEIR EVALUATION AS
BEING ACCEPTABLE FOR INDUSTRIAL,
This document is circulated as received from the committee secretariat.
TECHNOLOGICAL, COMMERCIAL AND
USER PURPOSES, DRAFT INTERNATIONAL
STANDARDS MAY ON OCCASION HAVE TO
BE CONSIDERED IN THE LIGHT OF THEIR
POTENTIAL TO BECOME STANDARDS TO
WHICH REFERENCE MAY BE MADE IN
Reference number
NATIONAL REGULATIONS.
ISO/DIS 23466:2019(E)
RECIPIENTS OF THIS DRAFT ARE INVITED
TO SUBMIT, WITH THEIR COMMENTS,
NOTIFICATION OF ANY RELEVANT PATENT
RIGHTS OF WHICH THEY ARE AWARE AND TO
PROVIDE SUPPORTING DOCUMENTATION. ISO 2019
---------------------- Page: 1 ----------------------
ISO/DIS 23466:2019(E)
COPYRIGHT PROTECTED DOCUMENT
© ISO 2019
All rights reserved. Unless otherwise specified, or required in the context of its implementation, no part of this publication may
be reproduced or utilized otherwise in any form or by any means, electronic or mechanical, including photocopying, or posting
on the internet or an intranet, without prior written permission. Permission can be requested from either ISO at the address
below or ISO’s member body in the country of the requester.ISO copyright office
CP 401 • Ch. de Blandonnet 8
CH-1214 Vernier, Geneva
Phone: +41 22 749 01 11
Fax: +41 22 749 09 47
Email: copyright@iso.org
Website: www.iso.org
Published in Switzerland
ii © ISO 2019 – All rights reserved
---------------------- Page: 2 ----------------------
ISO/DIS 23466:2019(E)
Contents Page
Foreword ........................................................................................................................................................................................................................................iv
Introduction ..................................................................................................................................................................................................................................v
1 Scope ................................................................................................................................................................................................................................. 1
2 Normative references ...................................................................................................................................................................................... 1
3 Terms and definitions ..................................................................................................................................................................................... 1
4 General design procedure........................................................................................................................................................................... 2
4.1 General requirements ....................................................................................................................................................................... 2
4.2 Requirements for reactor safety .............................................................................................................................................. 2
4.3 Material selection ................................................................................................................................................................................. 3
4.3.1 General requirements .................................................................................................................................................. 3
4.3.2 Main insulating material ........................................................................................................................................... 3
4.3.3 Outer cladding/sealing material ........................................................................................................................ 4
4.3.4 Support/fixation material ........................................................................................................................................ 4
4.4 Thermal behaviourr design and test .................................................................................................................................... 4
4.4.1 Thermal behaviourr design .................................................................................................................................... 4
4.4.2 Thermal behaviourr test ........................................................................................................................................... 6
4.5 Mechanical properties design and test .............................................................................................................................. 6
4.5.1 Mechanical properties design .............................................................................................................................. 6
4.5.2 Mechanical properties test ...................................................................................................................................... 7
4.6 Other requirements ............................................................................................................................................................................ 8
5 Design requirement of thermal insulation of RPV ............................................................................................................ 8
5.1 General requirement .......................................................................................................................................................................... 8
5.2 Safety requirement .............................................................................................................................................................................. 9
5.3 Material selection ................................................................................................................................................................................. 9
5.4 Thermal behaviour requirement ............................................................................................................................................. 9
5.5 Mechanical properties and structure requirement ..............................................................................................10
6 Design requirement of thermal insulation of RCS piping and other equipment ............................10
6.1 General requirement .......................................................................................................................................................................10
6.2 Safety requirement ...........................................................................................................................................................................10
6.3 Material selection ..............................................................................................................................................................................11
6.4 Thermal behaviour requirement ..........................................................................................................................................11
6.5 Mechanical properties and structure requirement ..............................................................................................11
Annex A (informative) Structure description of metallic thermal insulation ........................................................13
Annex B (informative) Structure description of non-metallic thermal insulation............................................16
Annex C (informative) A kind of RPV thermal insulation bearing RPV external cooling
safety function......................................................................................................................................................................................................19
Annex D (informative) A kind of RPV thermal insulation bearing radiation shield safety
function .......................................................................................................................................................................................................................22
© ISO 2019 – All rights reserved iii---------------------- Page: 3 ----------------------
ISO/DIS 23466:2019(E)
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work of preparing International Standards is normally carried out
through ISO technical committees. Each member body interested in a subject for which a technical
committee has been established has the right to be represented on that committee. International
organizations, governmental and non-governmental, in liaison with ISO, also take part in the work.
ISO collaborates closely with the International Electrotechnical Commission (IEC) on all matters of
electrotechnical standardization.The procedures used to develop this document and those intended for its further maintenance are
described in the ISO/IEC Directives, Part 1. In particular, the different approval criteria needed for the
different types of ISO documents should be noted. This document was drafted in accordance with the
editorial rules of the ISO/IEC Directives, Part 2 (see www .iso .org/ directives).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. ISO shall not be held responsible for identifying any or all such patent rights. Details of
any patent rights identified during the development of the document will be in the Introduction and/or
on the ISO list of patent declarations received (see www .iso .org/ patents).Any trade name used in this document is information given for the convenience of users and does not
constitute an endorsement.For an explanation on the voluntary nature of standards, the meaning of ISO specific terms and
expressions related to conformity assessment, as well as information about ISO's adherence to the
World Trade Organization (WTO) principles in the Technical Barriers to Trade (TBT) see the following
URL: www .iso .org/ iso/ foreword .html.This document was prepared by Technical Committee ISO/TC 85, Nuclear energy, nuclear technologies,
and radiological protection, Subcommittee SC 6, Reactor Technology.Any feedback or questions on this document should be directed to the user’s national standards body. A
complete listing of these bodies can be found at www .iso .org/ members .html.iv © ISO 2019 – All rights reserved
---------------------- Page: 4 ----------------------
ISO/DIS 23466:2019(E)
Introduction
For PWR nuclear power plants, the function of thermal insulation of reactor coolant system (RCS)
equipment and piping is to reduce heat loss, improve ambient condition, reduce thermal stress of RCS
equipment and piping and guarantee the normal operation of reactor.The purpose of this document is to provide internationally uniform design principle and method for
thermal insulation of RCS equipment and piping in PWR nuclear power plant, which mainly contains
the thermal behaviour, material selection, structural design, and test method requirements.
For thermal insulation which belongs to nuclear safety related class or category, or performing reactor
safety related function, the corresponding design requirements are also offered in this document.
Among thermal insulation of various RCS equipment and piping, the following two kinds of thermal
insulations would be detailed described on the basis of some common design logic and requirements:
— thermal insulation of reactor pressure vessel (RPV)— thermal insulation of RCS piping and other equipment
© ISO 2019 – All rights reserved v
---------------------- Page: 5 ----------------------
DRAFT INTERNATIONAL STANDARD ISO/DIS 23466:2019(E)
Design criteria for the thermal insulation of reactor
coolant system main equipments and piping of PWR
nuclear power plants
1 Scope
This document specifies the basic requirements related to the design of thermal insulation of reactor
coolant system (RCS) equipment and piping.This document is valid for two types of thermal insulation.
— metallic thermal insulation
— non-metallic thermal insulation
This document mainly applies to pressure water reactor (PWR) nuclear power plants. For other reactor
types, this document can be taken as reference.2 Normative references
The following standards are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced standards (including any amendments) applies.
ISO 7345, Thermal performance of buildings and building components — Physical quantities and definitions
ISO 8302, Thermal insulation — Determination of steady-state thermal resistance and related properties —
Guarded hot plate apparatusISO 8497, Thermal insulation — Determination of steady-state thermal transmission properties of thermal
insulation for circular pipesISO 8990, Thermal insulation — Determination of steady-state thermal transmission properties —
Calibrated and guarded hot boxISO 9229, Thermal insulation — Vocabulary
3 Terms and definitions
For the purposes of this document, the terms and definitions given in ISO 7345, ISO 9229 and the
following apply.ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https:// www .iso .org/ obp— IEC Electropedia: available at http:// www .electropedia .org/
3.1
metallic thermal insulation
thermal insulation with metallic material as main insulating material
Note 1 to entry: The metallic thermal insulation is composed by amounts of thermal insulation panels. Single
thermal insulation panel consists of outer cladding and inner packed metallic reflective foils/sheets. The
geometry of inner packed foils/sheets can be embossed or parallel liners.© ISO 2019 – All rights reserved 1
---------------------- Page: 6 ----------------------
ISO/DIS 23466:2019(E)
Note 2 to entry: The detailed description of typical geometry of metallic thermal insulation is shown in Annex A.
The geometry mentioned in Annex A can be taken as reference for designer.3.2
non-metallic thermal insulation
thermal insulation with non-metallic material as main insulating material
Note 1 to entry: Geometry of non-metallic thermal insulation can be divided into three kinds:
— Thermal insulation composed by amounts of thermal insulation panels. Single thermal insulation panel
consists of outer cladding and inner packed non-metallic insulating material.— Thermal insulation strapped layer by layer with non-metallic insulating material.
— Thermal insulation matresses (non-metallic insulation material stuffed in fiber cloth).
Note 2 to entry: The detailed description of typical geometry of non-metallic thermal insulation is shown in
Annex B. The geometry mentioned in Annex B can be taken as reference for designer.
3.3chimney effect
air circulation between inside and outside of thermal insulation derived by heat source
EXAMPLE If any gap was existed between thermal insulation and equipment or piping insulated, meanwhile
amounts of heat exchange paths were existed in most part of thermal insulation, thermal pressure or density
difference would be formed between the inner and outer side of thermal insulation. Initiated by this difference,
the cold air would enter the inside through the lower gaps, move upward and be heated, finally escape to the
outside through the top gaps.3.4
thermal bridge
path with high heat flow, caused by geometry with high thermal conductivity material connecting the
inner and outer surface of thermal insulation directly4 General design procedure
4.1 General requirements
All requirements for thermal insulation function realization shall be comprehensively considered
in the design procedure of thermal insulation. The safety class, quality assurance classification and
seismic category requirements, which are specified by equipment specification or other corresponding
documents, shall be satisfied. The design of thermal insulation can be performed as following
subsequence:— Consideration of requirements about reactor safety
— Material selection
— Thermal behavior design and test
— Mechanical properties design and test, including seismic resistance, vibration resistance, etc.
Besides, other requirements including installation, remove, maintenance, in-service inspection and
replacement shall also be considered in the design of thermal insulation.4.2 Requirements for reactor safety
Design of thermal insulation shall be satisfied with safety requirements about thermal insulation
specified in regulations, codes and standards of locality in which the product is to be manufactured
and used. Thermal insulation shall be carefully selected and methods for their application shall be
specified to ensure the fulfilment of their safety functions and to minimize interference with other
2 © ISO 2019 – All rights reserved---------------------- Page: 7 ----------------------
ISO/DIS 23466:2019(E)
safety functions in the event of deterioration of thermal insulation. Meanwhile, the safety requirements
of the RCS component shall also be considered and specified in data sheets for thermal insulation.
As an output of thermal insulation design and an input for safety facilities, the debris source caused by
thermal insulation shall not influence the normal operation of emergency core cooling system (ECCS),
pit strainer and other safety facilities. Both the quantity and granulometry of debris shall be considered.
This requirement is for the whole thermal insulation system but not for a single part.
For thermal insulation parts where workers may contact or be close to, the temperature of thermal
insulation outer surface shall be limited to protect the physical security of the workers.
For thermal insulation belonging to nuclear safety related class or category or performing reactor safety
related function, the following safety related requirements can be selectively conducted in the design
of thermal insulation to meet the functional requirements of NPP safety system. For thermal insulation
belonging to non-nuclear safety class or category, the following requirements are not mandatory.
— During normal operation and anticipated incidents, corresponding loads shall be carried, all
function of thermal insulation shall be normally performed for the whole design lifetime.
— During seismic conditions, impact of seismic loads on the insulated and adjacent components shall
be minimized.— If any safety function needs to be performed by thermal insulation itself, the function reliability
shall be ensured.4.3 Material selection
4.3.1 General requirements
Materials applied for thermal insulation shall meet the safety requirements of material applied in
NPP reactor according to the regulations and codes pertaining to the locality in which the product
is to be manufactured and used. Debris source caused by material itself shall be satisfied with
requirements in 4.1.Materials applied in thermal insulation mainly include main insulating material, outer cladding/sealing
material, support/fixation material, etc. Material performance degradation due to the totally received
radiation dose during whole design lifetime shall be considered in the material selection. The maximum
service temperature of all materials shall be higher than the design or operation temperature of
equipment and piping insulated and be with appropriate margin.4.3.2 Main insulating material
The safety requirement, thermal behaviour, mechanical properties and structure of thermal insulation
would be directly influenced by the main insulating material. Hence, selection of main insulating material
shall be determined firstly. The main insulating material can be classified as the following two types:
— metallic insulating material— non-metallic insulating material
Based on the two kinds of main insulating material, types of thermal insulation are also classified as
metallic thermal insulation and non-metallic thermal insulation.For metallic insulating material, the thermal insulated function is achieved by radiative heat transfer
inhibit effect due to the low surface emissivity of material. Hence, surface bright treatable metallic
material with low surface emissivity shall be selected. For instance, austenitic stainless steel, aluminum
or galvanized steel can all be recommended.© ISO 2019 – All rights reserved 3
---------------------- Page: 8 ----------------------
ISO/DIS 23466:2019(E)
Chemical composition and physical properties (including mechanical property and corrosion resistant
property, etc.) of metallic insulating material shall meet requirements specified in relevant codes and
standards, and be with good processing performance.For non-metallic insulating material, the thermal insulated function is achieved by convective
heat transfer inhibit effect due to the interior porous structure of material, such as fibre material,
microporous material, etc.Non-metallic insulating material and their products shall have good resistance to radiation. During
the lifetime, phenomenon including obvious embrittlement, pulverization, contraction and obviously
increased thermal conductivity shall be avoided. The radiation resistance performance of non-metallic
insulating material and their product shall be verified by irradiation test.Non-metallic insulating material shall be resisted to steam, moisture, fungi, disintegration and fire
during whole design lifetime and under its operation condition.Any noxious or harmful effect (formaldehyde emission, carcinogenicity and other possible harmful
factors) of non-metallic material shall be limited as far as practicable and respect the the regulations,
codes and standards of locality in which the product is to be manufactured and used. The content of
organic binder shall be controlled.For non-metallic insulating material directly contacted with equipment and piping insulated, the
influence of stress corrosion cracking tendency on equipment and piping shall be evaluated and the
result shall be available before lot production. For non-metallic insulating material directly contacted
with austenitic steel components, the leachable chloride, fluoride, sodium and silicate ions as well as pH
value of leached water shall be limited.4.3.3 Outer cladding/sealing material
The outer cladding/sealing material is used for the cladding shell, sealing panel or other outer protective
parts for the main insulating material. During the whole design lifetime, mechanical properties of
material shall be enough to sustain loads acting on the cladding or sealing parts.. In order to satisfy
sealing requirement under different operation conditions, processes including riveting, fillet welding,
intermittent welding, seal welding can be selected to assemble the cladding shell or sealing panel. If
the outer cladding/sealing material was different from the main insulating material or the adjacent
contacted equipment or piping material, the influence of corrosion or other negative tendency caused
by the contact between different types of materials shall be evaluated and the result shall be available
before lot production.4.3.4 Support/fixation material
The support/fixation material is used for support frame, support leg, strap or other supporting and
fixation parts of thermal insulation. During the whole design lifetime, mechanical properties of
material shall be enough to sustain loads acting on the support or fixation parts. If the support/fixation
material was different from the main insulating material or the adjacent contacted equipment or piping
material, the influence of corrosion or other negative tendency caused by the contact between different
types of materials shall be evaluated and the result shall be available before lot production.
4.4 Thermal behaviourr design and test4.4.1 Thermal behaviourr design
For thermal behaviour design, the surface temperature or heat productivity value of equipment and
piping insulated shall be taken as design input, the heat loss limit of equipment and piping insulated
shall be taken as design target. This heat loss limit could be specified by equipment specification or
other corresponding documents and mainly described by the following parameters:— heat flux of thermal insulation outer surface
4 © ISO 2019 – All rights reserved
---------------------- Page: 9 ----------------------
ISO/DIS 23466:2019(E)
— temperature of thermal insulation outer surface
— heat loss of thermal insulation
After the above design input and target has been offered or specified, the design thickness of thermal
insulation shall be determined by theoretical calculation method. Calculation of the design thickness is
based on Equation (1) or Equation (2). Equation (1) is suitable for the calculation under flat wall heat
transfer process, Equation (2) is suitable for the calculation under cylinder wall heat transfer process.
Besides, Equation (3) can be used to obtain heat flux from heat loss, then the heat flux can be used for
the calculation of design thickness. Equation (3) also can be used to verify the heat flux calculation
result by comparing with heat loss limit.The thermal conductivity λ in Equation (1) and Equation (2) can be obtained by querying standards
or performing heat transmission test described in Clause 4.3.2. The heat transfer coefficient h
should consider both of thermal insulation outer surface heat convection transfer coefficient h and
heat radiation coefficient h , which is shown in Equation (4). For safety, appropriate margin shall be
considered for the design thickness.It shall be noted that the calculated design thickness is the net thickness of main insulating material,
not including outer cladding, sealing or any other material without thermal insulate function.
δ 1
qT=Δ / + (1)
λ h
dd
qT=Δ /l×+n (2)
2λ dh
Qq=×A (3)
hh=+h (4)
where
q is heat flux of thermal insulation
ΔT is temperature difference between inner and outer surface of thermal insulation
λ is thermal conductivity of thermal insulationδ is design thickness of thermal insulation under flat wall heat transfer process
d is design outer diameter of thermal insulation under cylinder wall heat transfer process
d is design inner diameter of thermal insulation under cylinder wall heat transfer process
h is surface coefficient of heat transfer of thermal insulationh is surface coefficient of heat convection transfer of thermal insulation
h is surface coefficient of heat radiation transfer thermal insulation
Q is heat loss of thermal insulation
A is thermal transfer area of thermal insulation
In the calculation of the outer surface heat convection transfer coefficient, the shape and direction of
thermal insulation, the ambient temperature and the ventilation condition should all be considered.
According to the different conditions, different calculation method should be selected for heat
© ISO 2019 – All rights reserved 5---------------------- Page: 10 ----------------------
ISO/DIS 23466:2019(E)
convection transfer coefficient. Heat radiation coefficient should be in accordance with the property of
main insulating material itself.Besides, influence of displacement caused by the thermal expansion of thermal insulation itself and
equipment and piping insulated should be considered, expansion and contraction during start-up and
shutdown of the reactor should also be considered. Typical insulation parts, of which the function is
obviously influenced by thermal stress or deformation, shall be verified by corresponding analysis.
Solutions based on formula calculation are acceptable if the object geometry and thermal transfer
conditions are simple enough. For calculation procedure considering various thermal transfer influence
factors or calculation object with complex and irregular geometries, finite element or other proven
equivalent analysis methods is recommended to calculate the heat flux, temperature distribution and
heat loss.If the heat exchange paths between inner and outer side of thermal insulation cannot be totally avoided,
the influence of chimney effect shall be considered in thermal behaviour calculation.
4.4.2 Thermal behaviourr testAfter the main insulating material has been selected, the thermal conductivity is recommended to be
obtained by heat transmission test. This heat transmission test can be performed for material itself or
typical thermal insulation panel. In order to obtain thermal conductivity with more approaching to real
production, the unidirectional heat transmission test for typical thermal insulation panel is preferred.
For supplier who performs thermal insulation design for first time, or new geometry, new material, new
process applied in the design and manufacturing of thermal insulation without previous experience
of lot production, a heat transmission simulation test can be selectively performed before thermal
insulation product is finally...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.