Standard Specification for Plastic Insert Fittings Utilizing a Copper Crimp Ring, or Alternate Stainless Steel Clamps for SDR9 Cross-linked Polyethylene (PEX) Tubing and SDR9 Polyethylene of Raised Temperature (PE-RT) Tubing

ABSTRACT
This specification establishes requirements for sulfone plastic insert fittings utilizing a copper crimp ring for SDR9 cross-linked polyethylene (PEX) tubing for cold- and hot-water distribution systems. Material for fitting shall be molded from sulfone plastic. Molded part shall not crack, split, or shatter and be free of visible splay. Fittings shall be tested for performance requirements such as hydrostatic burst, hydrostatic sustained pressure strength, thermocycling, excessive temperature-pressure capability, dimensions, workmanship, finish, appearance, assembly, crimp joint, and insert crush test.
SCOPE
1.1 This specification establishes requirements for sulfone plastic insert fittings and copper crimp rings, or alternate stainless steel clamps for four sizes (3/8 , 1/2 , and 3/4 and 1) of cross-linked polyethylene (PEX) tubing that meet the requirements for Specification F876 or F3253 and polyethylene of raised temperature (PE-RT) tubing that meet the requirements of Specifications F2623 and F2769. These fittings are intended for use in 100 psi (690 kPa) cold- and hot-water distribution systems operating at temperatures up to and including 180 °F (82 °C). Included are the requirements for material, molded part properties, performance, workmanship, dimensions, and markings to be used on the fittings and rings.  
1.2 Units—The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.3 The following is an index of the appendix in this specification:    
GO/NO-GO Crimp Gauges  
Appendix X1  
1.4 The following precautionary caveat pertains only to the test method portions, Sections 11 and 12, of this specification.  This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

General Information

Status
Historical
Publication Date
31-Mar-2019
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM F2159-19 - Standard Specification for Plastic Insert Fittings Utilizing a Copper Crimp Ring, or Alternate Stainless Steel Clamps for SDR9 Cross-linked Polyethylene (PEX) Tubing and SDR9 Polyethylene of Raised Temperature (PE-RT) Tubing
English language
8 pages
sale 15% off
Preview
sale 15% off
Preview
Technical specification
REDLINE ASTM F2159-19 - Standard Specification for Plastic Insert Fittings Utilizing a Copper Crimp Ring, or Alternate Stainless Steel Clamps for SDR9 Cross-linked Polyethylene (PEX) Tubing and SDR9 Polyethylene of Raised Temperature (PE-RT) Tubing
English language
8 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:F2159 −19 An American National Standard
Standard Specification for
Plastic Insert Fittings Utilizing a Copper Crimp Ring, or
Alternate Stainless Steel Clamps for SDR9 Cross-linked
Polyethylene (PEX) Tubing and SDR9 Polyethylene of
1
Raised Temperature (PE-RT) Tubing
This standard is issued under the fixed designation F2159; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope* mendations issued by the World Trade Organization Technical
Barriers to Trade (TBT) Committee.
1.1 This specification establishes requirements for sulfone
plastic insert fittings and copper crimp rings, or alternate
2. Referenced Documents
stainless steel clamps for four sizes
2
3 1 3 2.1 ASTM Standards:
( ⁄8, ⁄2, and ⁄4 and 1) of cross-linked polyethylene (PEX)
D618 Practice for Conditioning Plastics for Testing
tubing that meet the requirements for Specification F876 or
D1598 Test Method for Time-to-Failure of Plastic Pipe
F3253 and polyethylene of raised temperature (PE-RT) tubing
Under Constant Internal Pressure
that meet the requirements of Specifications F2623 and F2769.
D1599 Test Method for Resistance to Short-Time Hydraulic
These fittings are intended for use in 100 psi (690 kPa) cold-
Pressure of Plastic Pipe, Tubing, and Fittings
and hot-water distribution systems operating at temperatures
D1600 Terminology forAbbreviatedTerms Relating to Plas-
up to and including 180 °F (82 °C). Included are the require-
tics
ments for material, molded part properties, performance,
D2122 Test Method for Determining Dimensions of Ther-
workmanship, dimensions, and markings to be used on the
moplastic Pipe and Fittings
fittings and rings.
D6394 Specification for Sulfone Plastics (SP)
1.2 Units—The values stated in inch-pound units are to be
F412 Terminology Relating to Plastic Piping Systems
regarded as standard. The values given in parentheses are
F876 SpecificationforCrosslinkedPolyethylene(PEX)Tub-
mathematical conversions to SI units that are provided for
ing
information only and are not considered standard.
F1498 Specification for Taper Pipe Threads 60° for Thermo-
plastic Pipe and Fittings
1.3 The following is an index of the appendix in this
F1807 Specification for Metal Insert Fittings Utilizing a
specification:
Copper Crimp Ring for SDR9 Cross-linked Polyethylene
GO/NO-GO Crimp Gauges Appendix X1
(PEX) Tubing and SDR9 Polyethylene of Raised Tem-
1.4 The following precautionary caveat pertains only to the
perature (PE-RT) Tubing
test method portions, Sections 11 and 12, of this specification.
F2098 Specification for Stainless Steel Clamps for Securing
This standard does not purport to address all of the safety
SDR9 Cross-linked Polyethylene (PEX) Tubing and
concerns, if any, associated with its use. It is the responsibility
SDR9 Polyethylene of Raised Temperature (PE-RT) to
of the user of this standard to establish appropriate safety,
Metal Insert and Plastic Insert Fittings
health, and environmental practices and determine the appli-
F2623 Specification for Polyethylene of RaisedTemperature
cability of regulatory limitations prior to use.
(PE-RT) SDR 9 Tubing
1.5 This international standard was developed in accor-
F2769 Specification for Polyethylene of RaisedTemperature
dance with internationally recognized principles on standard-
(PE-RT) Plastic Hot and Cold-Water Tubing and Distri-
ization established in the Decision on Principles for the
bution Systems
Development of International Standards, Guides and Recom-
F3253 Specification for Crosslinked Polyethylene (PEX)
Tubing with Oxygen Barrier for Hot- and Cold-Water
1
This specification is under the jurisdiction ofASTM Committee F17 on Plastic
2
Piping Systems and is the direct responsibility of Subcommittee F17.10 on Fittings. For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Current edition approved April 1, 2019. Published April 2019. Originally contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
approved 2001. Last previous edition approved in 2018 as F2159-18a. DOI: Standards volume information, refer to the standard’s Document Summary page on
10.1520/F2159-19. the ASTM website.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
F2159−19
Hydronic Distribution Systems 5.4 Alternate Stainless Steel Clamps—Clamps shall be
2.2 ASME Standard: madefromstainlesssteelinconformancewithallrequirements
3
B 1.20.1 Pipe Threads General Purpose Inch of
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: F2159 − 18a F2159 − 19 An American National Standard
Standard Specification for
Plastic Insert Fittings Utilizing a Copper Crimp Ring Ring, or
Alternate Stainless Steel Clamps for SDR9 Cross-linked
Polyethylene (PEX) Tubing and SDR9 Polyethylene of
1
Raised Temperature (PE-RT) Tubing
This standard is issued under the fixed designation F2159; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope*
1.1 This specification establishes requirements for sulfone plastic insert fittings and copper crimp rings rings, or alternate
stainless steel clamps for four sizes
3 1 3
( ⁄8, ⁄2, and ⁄4 and 1) of cross-linked polyethylene (PEX) tubing that meet the requirements for Specification F876 or F3253 and
polyethylene of raised temperature (PE-RT) tubing that meet the requirements of Specifications F2623 and F2769. These fittings
are intended for use in 100 psi (690 kPa) cold- and hot-water distribution systems operating at temperatures up to and including
180 °F (82 °C). Included are the requirements for material, molded part properties, performance, workmanship, dimensions, and
markings to be used on the fittings and rings.
1.2 Units—The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are
mathematical conversions to SI units that are provided for information only and are not considered standard.
1.3 The following is an index of the appendix in this specification:
GO/NO-GO Crimp Gauges Appendix X1
1.4 The following precautionary caveat pertains only to the test method portions, Sections 11 and 12, of this specification. This
standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user
of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory
limitations prior to use.
1.5 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
2. Referenced Documents
2
2.1 ASTM Standards:
D618 Practice for Conditioning Plastics for Testing
D1598 Test Method for Time-to-Failure of Plastic Pipe Under Constant Internal Pressure
D1599 Test Method for Resistance to Short-Time Hydraulic Pressure of Plastic Pipe, Tubing, and Fittings
D1600 Terminology for Abbreviated Terms Relating to Plastics
D2122 Test Method for Determining Dimensions of Thermoplastic Pipe and Fittings
D6394 Specification for Sulfone Plastics (SP)
F412 Terminology Relating to Plastic Piping Systems
F876 Specification for Crosslinked Polyethylene (PEX) Tubing
F1498 Specification for Taper Pipe Threads 60° for Thermoplastic Pipe and Fittings
F1807 Specification for Metal Insert Fittings Utilizing a Copper Crimp Ring, or Alternate Stainless Steel Clamps, for SDR9
Cross-linked Polyethylene (PEX) Tubing and SDR9 Polyethylene of Raised Temperature (PE-RT) Tubing
1
This specification is under the jurisdiction of ASTM Committee F17 on Plastic Piping Systems and is the direct responsibility of Subcommittee F17.10 on Fittings.
Current edition approved Nov. 1, 2018April 1, 2019. Published December 2018April 2019. Originally approved 2001. Last previous edition approved in 2018 as
F2159-18.-18a. DOI: 10.1520/F2159-18A.10.1520/F2159-19.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
F2159 − 19
F2098 Specification for Stainless Steel Clamps for Securing SDR9 Cross-linked Polyethylene (PEX) Tubing and SDR9
Polyethylene of Raised Temperature (PE-RT) to Metal Insert and Plastic Insert Fittings
F2623 Specification for Polyethylene of Raised Temperature (PE-RT) SDR 9 Tubing
F2769 Specification for Polyethylene of Raised Temperatu
...