ETSI EN 305 200-3-1 V1.1.1 (2018-02)
Access, Terminals, Transmission and Multiplexing (ATTM); Energy management; Operational infrastructures; Global KPIs; Part 3: ICT Sites; Sub-part 1: DCEM
Access, Terminals, Transmission and Multiplexing (ATTM); Energy management; Operational infrastructures; Global KPIs; Part 3: ICT Sites; Sub-part 1: DCEM
REN/ATTM-005
Dostop, terminali, prenos in multipleksiranje (ATTM) - Upravljanje z energijo - Operativna infrastruktura - Globalni ključni kazalniki uspešnosti (KPI) - 3. del: Strani ICT - 1. poddel: DCEM
Ta dokument določa zahteve za globalni KPI za upravljanje z energijo (KPIDCEM) in njegove temeljne ciljne KPI-je, ki naslavljajo naslednje cilje za mesta IKT za širokopasovno uporabo:
• poraba energije;
• učinkovitost opravil;
• ponovna uporaba energije;
• obnovljiva energija.
KPIDCEM je poenostavljena različica KPIEM v standardu ETSI EN 305 200-2-1 [i.13] in zahteve so preslikane v splošne zahteve standarda ETSI EN 305 200-1 [i.12].
Upravljanje z energijo mest IKT je sestavljeno iz več neodvisnih slojev. Ta dokument naslavlja učinkovitost infrastruktur, ki podpirajo običajno delovanje gostujoče opreme IKT (npr. distribucija električne energije, okoljski nadzor, zaščita in varnost). Ta dokument ne naslavlja drugih slojev, kot so učinkovitost same opreme IKT, učinkovitost uporabe razpoložljive zmogljivosti procesorja in sloji, povezani s končno dostavljeno storitvijo (npr. potrebna moč obdelave glede na rezultat po elementih) ali prekrivni sloji (npr. poraba energije glede na rezultat po elementih).
Učinek na okolje in upravljanje različnih virov energije ne spadata na področje uporabe tega dokumenta.
V tem dokumentu:
• točka 4 opisuje energijske parametre za mesta IKT, skupaj z vključitvami/izključitvami različnih energetskih prispevkov;
• točka 5 določa zahteve za merjenje, izračun, razvrstitev in poročanje za KPIDCEM.
General Information
Buy Standard
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Access, Terminals, Transmission and Multiplexing (ATTM) - Energy management - Operational infrastructures - Global KPIs - Part 3: ICT Sites - Sub-part 1: DCEM35.020Informacijska tehnika in tehnologija na splošnoInformation technology (IT) in general27.015VSORãQREnergy efficiency. Energy conservation in generalICS:Ta slovenski standard je istoveten z:ETSI EN 305 200-3-1 V1.1.1 (2018-02)SIST EN 305 200-3-1 V1.1.1:2018en01-april-2018SIST EN 305 200-3-1 V1.1.1:2018SLOVENSKI
STANDARD
SIST EN 305 200-3-1 V1.1.1:2018
ETSI EN 305 200-3-1 V1.1.1 (2018-02) Access, Terminals, Transmission and Multiplexing (ATTM); Energy management; Operational infrastructures; Global KPIs; Part 3: ICT Sites; Sub-part 1: DCEM
EUROPEAN STANDARD SIST EN 305 200-3-1 V1.1.1:2018
ETSI ETSI EN 305 200-3-1 V1.1.1 (2018-02)2
Reference REN/ATTM-005 Keywords broadband, energy management, ICT, sustainability ETSI 650 Route des Lucioles F-06921 Sophia Antipolis Cedex - FRANCE
Tel.: +33 4 92 94 42 00
Fax: +33 4 93 65 47 16
Siret N° 348 623 562 00017 - NAF 742 C Association à but non lucratif enregistrée à la Sous-Préfecture de Grasse (06) N° 7803/88
Important notice The present document can be downloaded from: http://www.etsi.org/standards-search The present document may be made available in electronic versions and/or in print. The content of any electronic and/or print versions of the present document shall not be modified without the prior written authorization of ETSI. In case of any existing or perceived difference in contents between such versions and/or in print, the only prevailing document is the print of the Portable Document Format (PDF) version kept on a specific network drive within ETSI Secretariat. Users of the present document should be aware that the document may be subject to revision or change of status. Information on the current status of this and other ETSI documents is available at https://portal.etsi.org/TB/ETSIDeliverableStatus.aspx If you find errors in the present document, please send your comment to one of the following services: https://portal.etsi.org/People/CommiteeSupportStaff.aspx Copyright Notification No part may be reproduced or utilized in any form or by any means, electronic or mechanical, including photocopying and microfilm except as authorized by written permission of ETSI. The content of the PDF version shall not be modified without the written authorization of ETSI. The copyright and the foregoing restriction extend to reproduction in all media.
© ETSI 2018. All rights reserved.
DECTTM, PLUGTESTSTM, UMTSTM and the ETSI logo are trademarks of ETSI registered for the benefit of its Members. 3GPPTM and LTETM are trademarks of ETSI registered for the benefit of its Members and of the 3GPP Organizational Partners. oneM2M logo is protected for the benefit of its Members. GSM® and the GSM logo are trademarks registered and owned by the GSM Association. SIST EN 305 200-3-1 V1.1.1:2018
ETSI ETSI EN 305 200-3-1 V1.1.1 (2018-02)3 Contents Intellectual Property Rights . 7 Foreword . 7 Modal verbs terminology . 7 Introduction . 8 1 Scope . 9 2 References . 9 2.1 Normative references . 9 2.2 Informative references . 10 3 Definitions, symbols and abbreviations . 11 3.1 Definitions . 11 3.2 Symbols . 12 3.3 Abbreviations . 12 4 Energy management of ICT sites . 13 4.1 General . 13 4.1.1 Measured energy . 13 4.1.2 Dedicated ICT sites . 13 4.1.3 Mixed-use ICT sites . 14 4.1.4 Groups of ICT sites . 14 4.2 Related standards . 14 5 Global KPI for ICT sites (KPIDCEM) . 16 5.1 General . 16 5.1.1 Global KPI (KPIDCEM) for ICT sites . 16 5.1.2 Objective KPIs . 16 5.1.2.1 Energy consumption (KPIEC) . 16 5.1.2.2 Task effectiveness (KPITE) . 17 5.1.2.3 Energy re-use (KPIREUSE) . 17 5.1.2.4 Renewable energy (KPIREN) . 18 5.2 Scale . 18 5.3 Utilization and evolution . 18 5.4 Definition of boundaries . 19 5.4.1 General . 19 5.4.2 Flows of electrical energy . 19 5.4.3 Flows of thermal energy . 20 5.4.3.1 ICT site cooling (heat discharge systems) . 20 5.4.3.2 Heat distribution networks . 21 5.4.4 Inclusion in Objective KPIs . 21 5.5 Formulae. 22 5.5.1 Global KPI for ICT sites (KPIDCEM) . 22 5.5.1.1 General . 22 5.5.1.1.1 KPIEC . 22 5.5.1.1.2 KPIEP . 22 5.5.1.2 Definition of terms . 22 5.5.1.3 Clarity . 23 5.5.1.4 Criteria . 23 5.5.1.5 Weighting factors . 23 5.5.1.5.1 General . 23 5.5.1.5.2 Energy re-use (WREUSE) . 23 5.5.1.5.3 Renewable energy (WREN) . 23 5.5.2 Objective KPIs for ICT sites . 24 5.5.2.1 Energy consumption (KPIEC) . 24 5.5.2.1.1 Formula . 24 5.5.2.1.2 Definitions of terms . 24 5.5.2.1.3 Clarity . 24 SIST EN 305 200-3-1 V1.1.1:2018
ETSI ETSI EN 305 200-3-1 V1.1.1 (2018-02)4 5.5.2.1.4 Criteria . 24 5.5.2.2 Task effectiveness (KPITE) . 25 5.5.2.2.1 Formula . 25 5.5.2.2.2 Definitions of terms . 25 5.5.2.2.3 Clarity . 25 5.5.2.2.4 Criteria . 25 5.5.2.3 Energy re-use (KPIREUSE) . 25 5.5.2.3.1 Formula . 25 5.5.2.3.2 Definitions of terms . 26 5.5.2.3.3 Clarity . 26 5.5.2.3.4 Criteria . 26 5.5.2.4 Renewable energy (KPIREN) . 26 5.5.2.4.1 Formula . 26 5.5.2.4.2 Definitions of terms . 27 5.5.2.4.3 Clarity . 27 5.5.2.4.4 Criteria . 27 5.6 Measurement points and procedures . 27 5.6.1 Objective KPIs for ICT sites . 27 5.6.1.1 Energy consumption (KPIEC) . 27 5.6.1.1.1 Measurement points . 27 5.6.1.1.2 Measurement procedures . 29 5.6.1.2 Task effectiveness (KPITE) . 29 5.6.1.2.1 Measurement points . 29 5.6.1.2.2 Measurement procedures . 30 5.6.1.3 Task effectiveness (KPITE) . 30 5.6.1.3.1 Measurement points . 30 5.6.1.3.2 Measurement procedures . 30 5.6.1.4 Energy re-use (KPIREUSE) . 30 5.6.1.4.1 Measurement points . 30 5.6.1.4.2 Measurement procedures . 30 5.6.1.5 Renewable energy (KPIREN) . 30 5.6.1.5.1 Measurement points . 30 5.6.1.5.2 Measurement procedures . 30 5.7 Classifications . 31 5.7.1 KPIEC presented as DCG . 31 5.7.2 KPIEP presented as DCCLASS . 31 5.7.3 Application to groups of ICT sites . 31 5.8 Reporting . 31 Annex A (informative):
Weighting values . 32 A.1 General . 32 A.2 Industry organizations . 32 A.2.1 CRIP . 32 A.2.2 eG4U . 33 History . 34
SIST EN 305 200-3-1 V1.1.1:2018
ETSI ETSI EN 305 200-3-1 V1.1.1 (2018-02)5 List of figures Figure 1: Schematic of the functional elements of an ICT site .13 Figure 2: Schematic of energy measurement of a dedicated ICT site .13 Figure 3: Schematic of energy measurement of a mixed-use ICT site .14 Figure 4: Electrical energy flows .19 Figure 5: Energy flows for heat sinks .20 Figure 6: Schematic of Objective and Global KPIs.21 Figure 7: Measurement points for energy consumption .26
SIST EN 305 200-3-1 V1.1.1:2018
ETSI ETSI EN 305 200-3-1 V1.1.1 (2018-02)6 List of tables Table 1: Implementation of Availability Class .15 Table A.1: DCG bands used by CRIP .31 Table A.2: Weighting values used by CRIP .31 Table A.3: DCCLASS bands used by CRIP .31 Table A.4: DCG bands used by eG4U .32 Table A.5: Weighting values used by eG4U .32 Table A.6: DCCLASS bands used by eG4U .32
SIST EN 305 200-3-1 V1.1.1:2018
ETSI ETSI EN 305 200-3-1 V1.1.1 (2018-02)7 Intellectual Property Rights Essential patents
IPRs essential or potentially essential to normative deliverables may have been declared to ETSI. The information pertaining to these essential IPRs, if any, is publicly available for ETSI members and non-members, and can be found in ETSI SR 000 314: "Intellectual Property Rights (IPRs); Essential, or potentially Essential, IPRs notified to ETSI in respect of ETSI standards", which is available from the ETSI Secretariat. Latest updates are available on the ETSI Web server (https://ipr.etsi.org/). Pursuant to the ETSI IPR Policy, no investigation, including IPR searches, has been carried out by ETSI. No guarantee can be given as to the existence of other IPRs not referenced in ETSI SR 000 314 (or the updates on the ETSI Web server) which are, or may be, or may become, essential to the present document. Trademarks The present document may include trademarks and/or tradenames which are asserted and/or registered by their owners. ETSI claims no ownership of these except for any which are indicated as being the property of ETSI, and conveys no right to use or reproduce any trademark and/or tradename. Mention of those trademarks in the present document does not constitute an endorsement by ETSI of products, services or organizations associated with those trademarks. Foreword This European Standard (EN) has been produced by ETSI Technical Committee Access, Terminals, Transmission and Multiplexing (ATTM). The present document is part 3, sub-part 1 of a multi-part deliverable covering Global Key Performance Indicators for energy management of operational broadband deployment infrastructures as identified below: Part 1: "General requirements"; Part 2: "Specific requirements"; Part 3: "ICT sites; Sub-part 1: DCEM"; Part 4: "Design assessments".
National transposition dates Date of adoption of this EN: 20 February 2018 Date of latest announcement of this EN (doa): 31 May 2018 Date of latest publication of new National Standard or endorsement of this EN (dop/e):
30 November 2018 Date of withdrawal of any conflicting National Standard (dow): 30 November 2018
Modal verbs terminology In the present document "shall", "shall not", "should", "should not", "may", "need not", "will", "will not", "can" and "cannot" are to be interpreted as described in clause 3.2 of the ETSI Drafting Rules (Verbal forms for the expression of provisions). "must" and "must not" are NOT allowed in ETSI deliverables except when used in direct citation. SIST EN 305 200-3-1 V1.1.1:2018
ETSI ETSI EN 305 200-3-1 V1.1.1 (2018-02)8 Introduction Energy costs continue to rise, a trend that will continue in the future, while broadband penetration is introducing new active equipment to the network architecture. In this context, and to reflect other environmental aspects of sustainability, it is vital that the main telecommunication operators implement effective general engineering of fixed and mobile broadband networks and sites provisioning, managing or using those networks (i.e. ICT sites) in order to respond to critical issues of energy consumption while proposing essential solutions to broadband deployment. To guide this process, it is essential that metrics are defined, termed Global Key Performance Indicators (KPIs), that enable energy usage to be managed more effectively.
The Global Key Performance Indicators specified in the ETSI EN 305 200 [i.11] series address operational infrastructures and do not consider design or operation of individual components comprising those infrastructures. ETSI EN 305 200 [i.11] series of standards comprises: • ETSI EN 305 200-1 [i.12] a generic requirements document addressing Global KPIs for operational infrastructures; • a sub-series ETSI EN 305 200-2 that defines the Global KPIs, and drives energy management targets, for specific operational networks and sites and which describes how the Global KPIs are to be applied (which may be used to support future regulatory objectives): - ETSI EN 305 200-2-1 [i.13]: ICT sites; - ETSI EN 305 200-2-2 [i.14]: Fixed broadband access networks; NOTE:
Excluding cable access networks. - ETSI EN 305 200-2-3 [i.15]: Mobile broadband access networks. The standards do not define weightings of Objective KPIs or targets or limits for Global KPIs but may contain information on values that have been used by certain organizations. • a sub-series ETSI EN 305 200-3 including the present document (which replaces ETSI ES 205 200-3) that defines particular implementations of Global KPIs within ICT sites based on the requirements of ETSI EN 305 200-2-1 [i.13], and which may define levels of performance to simplify and provide clearer understanding of Global KPIs allowing the evaluation of performance of energy use management in ICT sites. The standards do not define weightings of Objective KPIs or targets or limits for Global KPIs but may contain information on values that have been used by certain organizations. • a sub-series ETSI EN 305 200-4 including ETSI EN 305 200-4-4 [i.16] that defines design assessments of Global KPIs, and drives energy management targets, for specific operational networks and sites and which describes how the Global KPIs are to be applied (which may be used to support future regulatory objectives). These standards may be considered to be a contribution to the application of ISO 50001 [i.17] in relation to the development of policy for the continuous improvement of energy management and will accelerate: • the availability of operational infrastructure architectures and network implementations that use energy more efficiently; • the definition and attainment objectives for other environmental aspects of sustainability for operational broadband networks. The present document specifies the requirements for a Global KPI for energy management (KPIDCEM) and their underpinning Objective KPIs for the ICT sites of broadband deployment which is a simplified version of the KPIEM of ETSI EN 305 200-2-1 [i.13]. The requirements are mapped to the general requirements of ETSI EN 305 200-1 [i.12]. SIST EN 305 200-3-1 V1.1.1:2018
ETSI ETSI EN 305 200-3-1 V1.1.1 (2018-02)9 1 Scope The present document specifies the requirements for a Global KPI for energy management (KPIDCEM) and their underpinning Objective KPIs addressing the following objectives for the ICT sites of broadband deployment: • energy consumption; • task effectiveness; • energy reuse; • renewable energy. KPIDCEM is a simplified version of the KPIEM of ETSI EN 305 200-2-1 [i.13] and the requirements are mapped to the general requirements of ETSI EN 305 200-1 [i.12]. Energy management of ICT sites comprises a number of independent layers. The present document addresses performance of infrastructures that supports the normal function of hosted ICT equipment (e.g. power distribution, environmental control, security and safety). The present document does not address other layers such as performance of ICT equipment itself, performance of usage of available processing power, and layers related to final service delivered (e.g. processing power required per itemized outcome) or overlay layers (e.g. energy consumption per itemized outcome). The environmental impact and management of different energy sources are outside the scope of the present document. Within the present document: • clause 4 describes the energy parameters for ICT sites together with inclusions/exclusions of different energy contributions; • clause 5 specifies the requirements for measurement, calculation, classification and reporting of KPIDCEM. 2 References 2.1 Normative references References are either specific (identified by date of publication and/or edition number or version number) or non-specific. For specific references, only the cited version applies. For non-specific references, the latest version of the referenced document (including any amendments) applies. Referenced documents which are not found to be publicly available in the expected location might be found at https://docbox.etsi.org/Reference/. NOTE: While any hyperlinks included in this clause were valid at the time of publication, ETSI cannot guarantee their long term validity. The following referenced documents are necessary for the application of the present document. [1] CEN EN 1434 series: "Heat meters". [2] CENELEC EN 50600-2-2: "Information technology - Data centre facilities and infrastructures - Part 2-2: Power distribution". SIST EN 305 200-3-1 V1.1.1:2018
ETSI ETSI EN 305 200-3-1 V1.1.1 (2018-02)10 2.2 Informative references References are either specific (identified by date of publication and/or edition number or version number) or non-specific. For specific references, only the cited version applies. For non-specific references, the latest version of the referenced document (including any amendments) ap
...
ETSI EN 305 200-3-1 V1.1.1 (2018-02)
EUROPEAN STANDARD
Access, Terminals, Transmission and Multiplexing (ATTM);
Energy management;
Operational infrastructures;
Global KPIs;
Part 3: ICT Sites;
Sub-part 1: DCEM
---------------------- Page: 1 ----------------------
2 ETSI EN 305 200-3-1 V1.1.1 (2018-02)
Reference
REN/ATTM-005
Keywords
broadband, energy management, ICT,
sustainability
ETSI
650 Route des Lucioles
F-06921 Sophia Antipolis Cedex - FRANCE
Tel.: +33 4 92 94 42 00 Fax: +33 4 93 65 47 16
Siret N° 348 623 562 00017 - NAF 742 C
Association à but non lucratif enregistrée à la
Sous-Préfecture de Grasse (06) N° 7803/88
Important notice
The present document can be downloaded from:
http://www.etsi.org/standards-search
The present document may be made available in electronic versions and/or in print. The content of any electronic and/or
print versions of the present document shall not be modified without the prior written authorization of ETSI. In case of any
existing or perceived difference in contents between such versions and/or in print, the only prevailing document is the
print of the Portable Document Format (PDF) version kept on a specific network drive within ETSI Secretariat.
Users of the present document should be aware that the document may be subject to revision or change of status.
Information on the current status of this and other ETSI documents is available at
https://portal.etsi.org/TB/ETSIDeliverableStatus.aspx
If you find errors in the present document, please send your comment to one of the following services:
https://portal.etsi.org/People/CommiteeSupportStaff.aspx
Copyright Notification
No part may be reproduced or utilized in any form or by any means, electronic or mechanical, including photocopying
and microfilm except as authorized by written permission of ETSI.
The content of the PDF version shall not be modified without the written authorization of ETSI.
The copyright and the foregoing restriction extend to reproduction in all media.
© ETSI 2018.
All rights reserved.
TM TM TM
DECT , PLUGTESTS , UMTS and the ETSI logo are trademarks of ETSI registered for the benefit of its Members.
TM TM
3GPP and LTE are trademarks of ETSI registered for the benefit of its Members and
of the 3GPP Organizational Partners.
oneM2M logo is protected for the benefit of its Members.
®
GSM and the GSM logo are trademarks registered and owned by the GSM Association.
ETSI
---------------------- Page: 2 ----------------------
3 ETSI EN 305 200-3-1 V1.1.1 (2018-02)
Contents
Intellectual Property Rights . 7
Foreword . 7
Modal verbs terminology . 7
Introduction . 8
1 Scope . 9
2 References . 9
2.1 Normative references . 9
2.2 Informative references . 10
3 Definitions, symbols and abbreviations . 11
3.1 Definitions . 11
3.2 Symbols . 12
3.3 Abbreviations . 12
4 Energy management of ICT sites . 13
4.1 General . 13
4.1.1 Measured energy . 13
4.1.2 Dedicated ICT sites . 13
4.1.3 Mixed-use ICT sites . 14
4.1.4 Groups of ICT sites . 14
4.2 Related standards . 14
5 Global KPI for ICT sites (KPIDCEM) . 16
5.1 General . 16
5.1.1 Global KPI (KPI ) for ICT sites . 16
DCEM
5.1.2 Objective KPIs . 16
5.1.2.1 Energy consumption (KPI ) . 16
EC
5.1.2.2 Task effectiveness (KPI ) . 17
TE
5.1.2.3 Energy re-use (KPI ) . 17
REUSE
5.1.2.4 Renewable energy (KPI ) . 18
REN
5.2 Scale . 18
5.3 Utilization and evolution . 18
5.4 Definition of boundaries . 19
5.4.1 General . 19
5.4.2 Flows of electrical energy . 19
5.4.3 Flows of thermal energy . 20
5.4.3.1 ICT site cooling (heat discharge systems) . 20
5.4.3.2 Heat distribution networks . 21
5.4.4 Inclusion in Objective KPIs . 21
5.5 Formulae. 22
5.5.1 Global KPI for ICT sites (KPI ) . 22
DCEM
5.5.1.1 General . 22
5.5.1.1.1 KPI . 22
EC
5.5.1.1.2 KPI . 22
EP
5.5.1.2 Definition of terms . 22
5.5.1.3 Clarity . 23
5.5.1.4 Criteria . 23
5.5.1.5 Weighting factors . 23
5.5.1.5.1 General . 23
5.5.1.5.2 Energy re-use (W ) . 23
REUSE
5.5.1.5.3 Renewable energy (W ) . 23
REN
5.5.2 Objective KPIs for ICT sites . 24
5.5.2.1 Energy consumption (KPI ) . 24
EC
5.5.2.1.1 Formula . 24
5.5.2.1.2 Definitions of terms . 24
5.5.2.1.3 Clarity . 24
ETSI
---------------------- Page: 3 ----------------------
4 ETSI EN 305 200-3-1 V1.1.1 (2018-02)
5.5.2.1.4 Criteria . 24
5.5.2.2 Task effectiveness (KPI ) . 25
TE
5.5.2.2.1 Formula . 25
5.5.2.2.2 Definitions of terms . 25
5.5.2.2.3 Clarity . 25
5.5.2.2.4 Criteria . 25
5.5.2.3 Energy re-use (KPI ) . 25
REUSE
5.5.2.3.1 Formula . 25
5.5.2.3.2 Definitions of terms . 26
5.5.2.3.3 Clarity . 26
5.5.2.3.4 Criteria . 26
5.5.2.4 Renewable energy (KPI ) . 26
REN
5.5.2.4.1 Formula . 26
5.5.2.4.2 Definitions of terms . 27
5.5.2.4.3 Clarity . 27
5.5.2.4.4 Criteria . 27
5.6 Measurement points and procedures . 27
5.6.1 Objective KPIs for ICT sites . 27
5.6.1.1 Energy consumption (KPI ) . 27
EC
5.6.1.1.1 Measurement points . 27
5.6.1.1.2 Measurement procedures . 29
5.6.1.2 Task effectiveness (KPI ) . 29
TE
5.6.1.2.1 Measurement points . 29
5.6.1.2.2 Measurement procedures . 30
5.6.1.3 Task effectiveness (KPI ) . 30
TE
5.6.1.3.1 Measurement points . 30
5.6.1.3.2 Measurement procedures . 30
5.6.1.4 Energy re-use (KPI ) . 30
REUSE
5.6.1.4.1 Measurement points . 30
5.6.1.4.2 Measurement procedures . 30
5.6.1.5 Renewable energy (KPI ) . 30
REN
5.6.1.5.1 Measurement points . 30
5.6.1.5.2 Measurement procedures . 30
5.7 Classifications . 31
5.7.1 KPI presented as DC . 31
EC G
5.7.2 KPI presented as DC . 31
EP CLASS
5.7.3 Application to groups of ICT sites . 31
5.8 Reporting . 31
Annex A (informative): Weighting values . 32
A.1 General . 32
A.2 Industry organizations . 32
A.2.1 CRIP . 32
A.2.2 eG4U . 33
History . 34
ETSI
---------------------- Page: 4 ----------------------
5 ETSI EN 305 200-3-1 V1.1.1 (2018-02)
List of figures
Figure 1: Schematic of the functional elements of an ICT site .13
Figure 2: Schematic of energy measurement of a dedicated ICT site .13
Figure 3: Schematic of energy measurement of a mixed-use ICT site .14
Figure 4: Electrical energy flows .19
Figure 5: Energy flows for heat sinks .20
Figure 6: Schematic of Objective and Global KPIs.21
Figure 7: Measurement points for energy consumption .26
ETSI
---------------------- Page: 5 ----------------------
6 ETSI EN 305 200-3-1 V1.1.1 (2018-02)
List of tables
Table 1: Implementation of Availability Class .15
Table A.1: DC bands used by CRIP .31
G
Table A.2: Weighting values used by CRIP .31
Table A.3: DC bands used by CRIP .31
CLASS
Table A.4: DC bands used by eG4U .32
G
Table A.5: Weighting values used by eG4U .32
Table A.6: DC bands used by eG4U .32
CLASS
ETSI
---------------------- Page: 6 ----------------------
7 ETSI EN 305 200-3-1 V1.1.1 (2018-02)
Intellectual Property Rights
Essential patents
IPRs essential or potentially essential to normative deliverables may have been declared to ETSI. The information
pertaining to these essential IPRs, if any, is publicly available for ETSI members and non-members, and can be found
in ETSI SR 000 314: "Intellectual Property Rights (IPRs); Essential, or potentially Essential, IPRs notified to ETSI in
respect of ETSI standards", which is available from the ETSI Secretariat. Latest updates are available on the ETSI Web
server (https://ipr.etsi.org/).
Pursuant to the ETSI IPR Policy, no investigation, including IPR searches, has been carried out by ETSI. No guarantee
can be given as to the existence of other IPRs not referenced in ETSI SR 000 314 (or the updates on the ETSI Web
server) which are, or may be, or may become, essential to the present document.
Trademarks
The present document may include trademarks and/or tradenames which are asserted and/or registered by their owners.
ETSI claims no ownership of these except for any which are indicated as being the property of ETSI, and conveys no
right to use or reproduce any trademark and/or tradename. Mention of those trademarks in the present document does
not constitute an endorsement by ETSI of products, services or organizations associated with those trademarks.
Foreword
This European Standard (EN) has been produced by ETSI Technical Committee Access, Terminals, Transmission and
Multiplexing (ATTM).
The present document is part 3, sub-part 1 of a multi-part deliverable covering Global Key Performance Indicators for
energy management of operational broadband deployment infrastructures as identified below:
Part 1: "General requirements";
Part 2: "Specific requirements";
Part 3: "ICT sites;
Sub-part 1: DCEM";
Part 4: "Design assessments".
National transposition dates
Date of adoption of this EN: 20 February 2018
Date of latest announcement of this EN (doa): 31 May 2018
Date of latest publication of new National Standard
or endorsement of this EN (dop/e): 30 November 2018
Date of withdrawal of any conflicting National Standard (dow): 30 November 2018
Modal verbs terminology
In the present document "shall", "shall not", "should", "should not", "may", "need not", "will", "will not", "can" and
"cannot" are to be interpreted as described in clause 3.2 of the ETSI Drafting Rules (Verbal forms for the expression of
provisions).
"must" and "must not" are NOT allowed in ETSI deliverables except when used in direct citation.
ETSI
---------------------- Page: 7 ----------------------
8 ETSI EN 305 200-3-1 V1.1.1 (2018-02)
Introduction
Energy costs continue to rise, a trend that will continue in the future, while broadband penetration is introducing new
active equipment to the network architecture. In this context, and to reflect other environmental aspects of
sustainability, it is vital that the main telecommunication operators implement effective general engineering of fixed
and mobile broadband networks and sites provisioning, managing or using those networks (i.e. ICT sites) in order to
respond to critical issues of energy consumption while proposing essential solutions to broadband deployment. To guide
this process, it is essential that metrics are defined, termed Global Key Performance Indicators (KPIs), that enable
energy usage to be managed more effectively.
The Global Key Performance Indicators specified in the ETSI EN 305 200 [i.11] series address operational
infrastructures and do not consider design or operation of individual components comprising those infrastructures.
ETSI EN 305 200 [i.11] series of standards comprises:
• ETSI EN 305 200-1 [i.12] a generic requirements document addressing Global KPIs for operational
infrastructures;
• a sub-series ETSI EN 305 200-2 that defines the Global KPIs, and drives energy management targets, for
specific operational networks and sites and which describes how the Global KPIs are to be applied (which may
be used to support future regulatory objectives):
- ETSI EN 305 200-2-1 [i.13]: ICT sites;
- ETSI EN 305 200-2-2 [i.14]: Fixed broadband access networks;
NOTE: Excluding cable access networks.
- ETSI EN 305 200-2-3 [i.15]: Mobile broadband access networks.
The standards do not define weightings of Objective KPIs or targets or limits for Global KPIs but may contain
information on values that have been used by certain organizations.
• a sub-series ETSI EN 305 200-3 including the present document (which replaces ETSI ES 205 200-3) that
defines particular implementations of Global KPIs within ICT sites based on the requirements of ETSI
EN 305 200-2-1 [i.13], and which may define levels of performance to simplify and provide clearer
understanding of Global KPIs allowing the evaluation of performance of energy use management in ICT sites.
The standards do not define weightings of Objective KPIs or targets or limits for Global KPIs but may contain
information on values that have been used by certain organizations.
• a sub-series ETSI EN 305 200-4 including ETSI EN 305 200-4-4 [i.16] that defines design assessments of
Global KPIs, and drives energy management targets, for specific operational networks and sites and which
describes how the Global KPIs are to be applied (which may be used to support future regulatory objectives).
These standards may be considered to be a contribution to the application of ISO 50001 [i.17] in relation to the
development of policy for the continuous improvement of energy management and will accelerate:
• the availability of operational infrastructure architectures and network implementations that use energy more
efficiently;
• the definition and attainment objectives for other environmental aspects of sustainability for operational
broadband networks.
The present document specifies the requirements for a Global KPI for energy management (KPI ) and their
DCEM
of
underpinning Objective KPIs for the ICT sites of broadband deployment which is a simplified version of the KPI
EM
ETSI EN 305 200-2-1 [i.13]. The requirements are mapped to the general requirements of ETSI EN 305 200-1 [i.12].
ETSI
---------------------- Page: 8 ----------------------
9 ETSI EN 305 200-3-1 V1.1.1 (2018-02)
1 Scope
The present document specifies the requirements for a Global KPI for energy management (KPI ) and their
DCEM
underpinning Objective KPIs addressing the following objectives for the ICT sites of broadband deployment:
• energy consumption;
• task effectiveness;
• energy reuse;
• renewable energy.
KPI is a simplified version of the KPI of ETSI EN 305 200-2-1 [i.13] and the requirements are mapped to the
DCEM EM
general requirements of ETSI EN 305 200-1 [i.12].
Energy management of ICT sites comprises a number of independent layers. The present document addresses
performance of infrastructures that supports the normal function of hosted ICT equipment (e.g. power distribution,
environmental control, security and safety). The present document does not address other layers such as performance of
ICT equipment itself, performance of usage of available processing power, and layers related to final service delivered
(e.g. processing power required per itemized outcome) or overlay layers (e.g. energy consumption per itemized
outcome).
The environmental impact and management of different energy sources are outside the scope of the present document.
Within the present document:
• clause 4 describes the energy parameters for ICT sites together with inclusions/exclusions of different energy
contributions;
• clause 5 specifies the requirements for measurement, calculation, classification and reporting of KPI .
DCEM
2 References
2.1 Normative references
References are either specific (identified by date of publication and/or edition number or version number) or
non-specific. For specific references, only the cited version applies. For non-specific references, the latest version of the
referenced document (including any amendments) applies.
Referenced documents which are not found to be publicly available in the expected location might be found at
https://docbox.etsi.org/Reference/.
NOTE: While any hyperlinks included in this clause were valid at the time of publication, ETSI cannot guarantee
their long term validity.
The following referenced documents are necessary for the application of the present document.
[1] CEN EN 1434 series: "Heat meters".
[2] CENELEC EN 50600-2-2: "Information technology - Data centre facilities and infrastructures -
Part 2-2: Power distribution".
ETSI
---------------------- Page: 9 ----------------------
10 ETSI EN 305 200-3-1 V1.1.1 (2018-02)
2.2 Informative references
References are either specific (identified by date of publication and/or edition number or version number) or
non-specific. For specific references, only the cited version applies. For non-specific references, the latest version of the
referenced document (including any amendments) applies.
NOTE: While any hyperli
...
Draft ETSI EN 305 200-3-1 V1.1.0 (2017-11)
EUROPEAN STANDARD
Access, Terminals, Transmission and Multiplexing (ATTM);
Energy management;
Operational infrastructures;
Global KPIs;
Part 3: ICT Sites;
Sub-part 1: DCEM
---------------------- Page: 1 ----------------------
2 Draft ETSI EN 305 200-3-1 V1.1.0 (2017-11)
Reference
REN/ATTM-005
Keywords
broadband, energy management, ICT,
sustainability
ETSI
650 Route des Lucioles
F-06921 Sophia Antipolis Cedex - FRANCE
Tel.: +33 4 92 94 42 00 Fax: +33 4 93 65 47 16
Siret N° 348 623 562 00017 - NAF 742 C
Association à but non lucratif enregistrée à la
Sous-Préfecture de Grasse (06) N° 7803/88
Important notice
The present document can be downloaded from:
http://www.etsi.org/standards-search
The present document may be made available in electronic versions and/or in print. The content of any electronic and/or
print versions of the present document shall not be modified without the prior written authorization of ETSI. In case of any
existing or perceived difference in contents between such versions and/or in print, the only prevailing document is the
print of the Portable Document Format (PDF) version kept on a specific network drive within ETSI Secretariat.
Users of the present document should be aware that the document may be subject to revision or change of status.
Information on the current status of this and other ETSI documents is available at
https://portal.etsi.org/TB/ETSIDeliverableStatus.aspx
If you find errors in the present document, please send your comment to one of the following services:
https://portal.etsi.org/People/CommiteeSupportStaff.aspx
Copyright Notification
No part may be reproduced or utilized in any form or by any means, electronic or mechanical, including photocopying
and microfilm except as authorized by written permission of ETSI.
The content of the PDF version shall not be modified without the written authorization of ETSI.
The copyright and the foregoing restriction extend to reproduction in all media.
© ETSI 2017.
All rights reserved.
TM TM TM
DECT , PLUGTESTS , UMTS and the ETSI logo are trademarks of ETSI registered for the benefit of its Members.
TM
3GPP and LTE™ are trademarks of ETSI registered for the benefit of its Members and
of the 3GPP Organizational Partners.
oneM2M logo is protected for the benefit of its Members.
GSM® and the GSM logo are trademarks registered and owned by the GSM Association.
ETSI
---------------------- Page: 2 ----------------------
3 Draft ETSI EN 305 200-3-1 V1.1.0 (2017-11)
Contents
Intellectual Property Rights . 7
Foreword . 7
Modal verbs terminology . 7
Introduction . 8
1 Scope . 9
2 References . 9
2.1 Normative references . 9
2.2 Informative references . 10
3 Definitions, symbols and abbreviations . 11
3.1 Definitions . 11
3.2 Symbols . 12
3.3 Abbreviations . 12
4 Energy management of ICT sites . 13
4.1 General . 13
4.1.1 Measured energy . 13
4.1.2 Dedicated ICT sites . 13
4.1.3 Mixed-use ICT sites . 14
4.1.4 Groups of ICT sites . 14
4.2 Related standards . 14
5 Global KPI for ICT sites (KPIDCEM) . 16
5.1 General . 16
5.1.1 Global KPI (KPI ) for ICT sites . 16
DCEM
5.1.2 Objective KPIs . 16
5.1.2.1 Energy consumption (KPI ) . 16
EC
5.1.2.2 Task effectiveness (KPI ) . 17
TE
5.1.2.3 Energy re-use (KPI ) . 17
REUSE
5.1.2.4 Renewable energy (KPI ) . 18
REN
5.2 Scale . 18
5.3 Utilization and evolution . 18
5.4 Definition of boundaries . 19
5.4.1 General . 19
5.4.2 Flows of electrical energy . 19
5.4.3 Flows of thermal energy . 20
5.4.3.1 ICT site cooling (heat discharge systems) . 20
5.4.3.2 Heat distribution networks . 21
5.4.4 Inclusion in Objective KPIs . 21
5.5 Formulae. 22
5.5.1 Global KPI for ICT sites (KPI ) . 22
DCEM
5.5.1.1 General . 22
5.5.1.1.1 KPI . 22
EC
5.5.1.1.2 KPI . 22
EP
5.5.1.2 Definition of terms . 22
5.5.1.3 Clarity . 23
5.5.1.4 Criteria . 23
5.5.1.5 Weighting factors . 23
5.5.1.5.1 General . 23
5.5.1.5.2 Energy re-use (W ) . 23
REUSE
5.5.1.5.3 Renewable energy (W ) . 23
REN
5.5.2 Objective KPIs for ICT sites . 24
5.5.2.1 Energy consumption (KPI ) . 24
EC
ETSI
---------------------- Page: 3 ----------------------
4 Draft ETSI EN 305 200-3-1 V1.1.0 (2017-11)
5.5.2.1.1 Formula . 24
5.5.2.1.2 Definitions of terms . 24
5.5.2.1.3 Clarity . 24
5.5.2.1.4 Criteria . 24
5.5.2.2 Task effectiveness (KPI ) . 25
TE
5.5.2.2.1 Formula . 25
5.5.2.2.2 Definitions of terms . 25
5.5.2.2.3 Clarity . 25
5.5.2.2.4 Criteria . 25
5.5.2.3 Energy re-use (KPI ) . 25
REUSE
5.5.2.3.1 Formula . 25
5.5.2.3.2 Definitions of terms . 26
5.5.2.3.3 Clarity . 26
5.5.2.3.4 Criteria . 26
5.5.2.4 Renewable energy (KPI ) . 26
REN
5.5.2.4.1 Formula . 26
5.5.2.4.2 Definitions of terms . 27
5.5.2.4.3 Clarity . 27
5.5.2.4.4 Criteria . 27
5.6 Measurement points and procedures . 27
5.6.1 Objective KPIs for ICT sites . 27
5.6.1.1 Energy consumption (KPI ) . 27
EC
5.6.1.1.1 Measurement points . 27
5.6.1.1.2 Measurement procedures . 29
5.6.1.2 Task effectiveness (KPI ) . 29
TE
5.6.1.2.1 Measurement points . 29
5.6.1.2.2 Measurement procedures . 30
5.6.1.3 Task effectiveness (KPI ) . 30
TE
5.6.1.3.1 Measurement points . 30
5.6.1.3.2 Measurement procedures . 30
5.6.1.4 Energy re-use (KPI ) . 30
REUSE
5.6.1.4.1 Measurement points . 30
5.6.1.4.2 Measurement procedures . 30
5.6.1.5 Renewable energy (KPI ) . 30
REN
5.6.1.5.1 Measurement points . 30
5.6.1.5.2 Measurement procedures . 30
5.7 Classifications . 31
5.7.1 KPI presented as DC . 31
EC G
5.7.2 KPI presented as DC . 31
EP CLASS
5.7.3 Application to groups of ICT sites . 31
5.8 Reporting . 31
Annex A (informative): Weighting values . 32
A.1 General . 32
A.2 Industry organizations . 32
A.2.1 CRIP . 32
A.2.2 eG4U . 33
History . 34
ETSI
---------------------- Page: 4 ----------------------
5 Draft ETSI EN 305 200-3-1 V1.1.0 (2017-11)
List of figures
Figure 1: Schematic of the functional elements of an ICT site .13
Figure 2: Schematic of energy measurement of a dedicated ICT site .13
Figure 3: Schematic of energy measurement of a mixed-use ICT site .14
Figure 4: Electrical energy flows .19
Figure 5: Energy flows for heat sinks .20
Figure 6: Schematic of Objective and Global KPIs.21
Figure 7: Measurement points for energy consumption .26
ETSI
---------------------- Page: 5 ----------------------
6 Draft ETSI EN 305 200-3-1 V1.1.0 (2017-11)
List of tables
Table 1: Implementation of Availability Class .15
Table A.1: DC bands used by CRIP .31
G
Table A.2: Weighting values used by CRIP .31
Table A.3: DC bands used by CRIP .31
CLASS
Table A.4: DC bands used by eG4U .32
G
Table A.5: Weighting values used by eG4U .32
Table A.6: DC bands used by eG4U .32
CLASS
ETSI
---------------------- Page: 6 ----------------------
7 Draft ETSI EN 305 200-3-1 V1.1.0 (2017-11)
Intellectual Property Rights
Essential patents
IPRs essential or potentially essential to the present document may have been declared to ETSI. The information
pertaining to these essential IPRs, if any, is publicly available for ETSI members and non-members, and can be found
in ETSI SR 000 314: "Intellectual Property Rights (IPRs); Essential, or potentially Essential, IPRs notified to ETSI in
respect of ETSI standards", which is available from the ETSI Secretariat. Latest updates are available on the ETSI Web
server (https://ipr.etsi.org/).
Pursuant to the ETSI IPR Policy, no investigation, including IPR searches, has been carried out by ETSI. No guarantee
can be given as to the existence of other IPRs not referenced in ETSI SR 000 314 (or the updates on the ETSI Web
server) which are, or may be, or may become, essential to the present document.
Trademarks
The present document may include trademarks and/or tradenames which are asserted and/or registered by their owners.
ETSI claims no ownership of these except for any which are indicated as being the property of ETSI, and conveys no
right to use or reproduce any trademark and/or tradename. Mention of those trademarks in the present document does
not constitute an endorsement by ETSI of products, services or organizations associated with those trademarks.
Foreword
This draft European Standard (EN) has been produced by ETSI Technical Committee Access, Terminals, Transmission
and Multiplexing (ATTM), and is now submitted for the combined Public Enquiry and Vote phase of the ETSI
standards EN Approval Procedure.
The present document is part 3, sub-part 1 of a multi-part deliverable covering Global Key Performance Indicators for
energy management of operational broadband deployment infrastructures as identified below:
Part 1: "General requirements";
Part 2: "Specific requirements";
Part 3-1: "ICT sites; Sub-part 1: DCEM";
Part 4-4: "Design assessments; Sub-part 4: Cable Access Networks".
Proposed national transposition dates
Date of latest announcement of this EN (doa): 3 months after ETSI publication
Date of latest publication of new National Standard
or endorsement of this EN (dop/e): 6 months after doa
Date of withdrawal of any conflicting National Standard (dow): 6 months after doa
Modal verbs terminology
In the present document "shall", "shall not", "should", "should not", "may", "need not", "will", "will not", "can" and
"cannot" are to be interpreted as described in clause 3.2 of the ETSI Drafting Rules (Verbal forms for the expression of
provisions).
"must" and "must not" are NOT allowed in ETSI deliverables except when used in direct citation.
ETSI
---------------------- Page: 7 ----------------------
8 Draft ETSI EN 305 200-3-1 V1.1.0 (2017-11)
Introduction
Energy costs continue to rise, a trend that will continue in the future, while broadband penetration is introducing new
active equipment to the network architecture. In this context, and to reflect other environmental aspects of
sustainability, it is vital that the main telecommunication operators implement effective general engineering of fixed
and mobile broadband networks and sites provisioning, managing or using those networks (i.e. ICT sites) in order to
respond to critical issues of energy consumption while proposing essential solutions to broadband deployment. To guide
this process, it is essential that metrics are defined, termed Global Key Performance Indicators (KPIs), that enable
energy usage to be managed more effectively.
The Global Key Performance Indicators specified in the ETSI EN 305 200 [i.11] series address operational
infrastructures and do not consider design or operation of individual components comprising those infrastructures.
ETSI EN 305 200 [i.11] series of standards comprises:
• ETSI EN 305 200-1 [i.12] a generic requirements document addressing Global KPIs for operational
infrastructures;
• a sub-series ETSI EN 305 200-2 that defines the Global KPIs, and drives energy management targets, for
specific operational networks and sites and which describes how the Global KPIs are to be applied (which may
be used to support future regulatory objectives):
- ETSI EN 305 200-2-1 [i.13]: ICT sites;
- ETSI EN 305 200-2-2 [i.14]: Fixed broadband access networks;
NOTE: Excluding cable access networks.
- ETSI EN 305 200-2-3 [i.15]: Mobile broadband access networks.
The standards do not define weightings of Objective KPIs or targets or limits for Global KPIs but may contain
information on values that have been used by certain organizations.
• a sub-series ETSI EN 305 200-3 including the present document (which replaces ETSI ES 205 200-3) that
defines particular implementations of Global KPIs within ICT sites based on the requirements of ETSI
EN 305 200-2-1 [i.13], and which may define levels of performance to simplify and provide clearer
understanding of Global KPIs allowing the evaluation of performance of energy use management in ICT sites.
The standards do not define weightings of Objective KPIs or targets or limits for Global KPIs but may contain
information on values that have been used by certain organizations.
• a sub-series ETSI EN 305 200-4 including ETSI EN 305 200-4-4 [i.16] that defines design assessments of
Global KPIs, and drives energy management targets, for specific operational networks and sites and which
describes how the Global KPIs are to be applied (which may be used to support future regulatory objectives).
These standards may be considered to be a contribution to the application of ISO 50001 [i.17] in relation to the
development of policy for the continuous improvement of energy management and will accelerate:
• the availability of operational infrastructure architectures and network implementations that use energy more
efficiently;
• the definition and attainment objectives for other environmental aspects of sustainability for operational
broadband networks.
The present document specifies the requirements for a Global KPI for energy management (KPI ) and their
DCEM
of
underpinning Objective KPIs for the ICT sites of broadband deployment which is a simplified version of the KPI
EM
ETSI EN 305 200-2-1 [i.13]. The requirements are mapped to the general requirements of ETSI EN 305 200-1 [i.12].
ETSI
---------------------- Page: 8 ----------------------
9 Draft ETSI EN 305 200-3-1 V1.1.0 (2017-11)
1 Scope
The present document specifies the requirements for a Global KPI for energy management (KPI ) and their
DCEM
underpinning Objective KPIs addressing the following objectives for the ICT sites of broadband deployment:
• energy consumption;
• task effectiveness;
• energy reuse;
• renewable energy.
KPI is a simplified version of the KPI of ETSI EN 305 200-2-1 [i.13] and the requirements are mapped to the
DCEM EM
general requirements of ETSI EN 305 200-1 [i.12].
Energy management of ICT sites comprises a number of independent layers. The present document addresses
performance of infrastructures that supports the normal function of hosted ICT equipment (e.g. power distribution,
environmental control, security and safety). The present document does not address other layers such as performance of
ICT equipment itself, performance of usage of available processing power, and layers related to final service delivered
(e.g. processing power required per itemized outcome) or overlay layers (e.g. energy consumption per itemized
outcome).
The environmental impact and management of different energy sources are outside the scope of the present document.
Within the present document:
• clause 4 describes the energy parameters for ICT sites together with inclusions/exclusions of different energy
contributions;
• clause 5 specifies the requirements for measurement, calculation, classification and reporting of KPI .
DCEM
2 References
2.1 Normative references
References are either specific (identified by date of publication and/or edition number or version number) or
non-specific. For specific references, only the cited version applies. For non-specific references, the latest version of the
referenced document (including any amendments) applies.
Referenced documents which are not found to be publicly available in the expected location might be found at
https://docbox.etsi.org/Reference/.
NOTE: While any hyperlinks included in this clause were valid at the time of publication, ETSI cannot guarantee
their long term validity.
The following referenced documents are necessary for the application of the present document.
[1] CEN EN 1434 series: "Heat meters".
[2] CENELEC EN 50600-2-2: "Information technology - Data centre facilities and infrastructures -
Part 2-2: Power distribution".
ETSI
---------------------- Page: 9 ----------------------
10 Draft ETSI EN 305 200-3-1 V1.1.0 (2017-11)
2.2 Informative references
References are either specific (identified by date of publication and/or edition number or version number) or
non-specific. For specific references, only the
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.