kSIST FprEN 14373:2021
(Main)Explosion suppression systems
Explosion suppression systems
This document describes the basic requirements for the design and application of explosion suppression systems. This document also specifies test methods for evaluating the effectiveness and the scale up of explosion suppression systems against defined explosions. This document covers:
— general requirements for explosion suppression system components;
— evaluating the effectiveness of an explosion suppression system;
— evaluating the scale up of an explosion suppression system;
— development and evaluation of design tools for explosion suppression systems;
— installation, operation and maintenance instructions for an explosion suppression system.
This document is applicable only to explosion suppression systems intended for the protection of closed, or essentially closed, enclosures in which an explosion could result as a consequence of ignition of an explosible mixture, e.g. dust-air, gas(vapour)-air, dust-gas(vapour)-air and mist-air.
This document is not applicable for explosions of materials listed below, or for mixtures containing some of those materials:
— unstable materials that are liable to dissociate;
— explosive materials;
— pyrotechnic materials;
— pyrophoric materials.
Explosions-Unterdrückungssysteme
Dieses Dokument Norm beschreibt die Grundanforderungen für die Konstruktion und Anwendung von Explosions-Unterdrückungssystemen. Dieses Dokument legt außerdem Prüfverfahren zur Beurteilung der Wirksamkeit und Reichweite von Explosions-Unterdrückungssystemen bei bestimmten Explosionen fest. Dieses Dokument behandelt:
— allgemeine Anforderungen an Komponenten für Explosions-Unterdrückungssysteme;
— Bewerten des Leistungsvermögens eines Explosions-Unterdrückungssystems;
— Bewerten der Reichweite eines Explosions-Unterdrückungssystems;
— Entwicklung und Bewertung einer Konstruktionsanleitung für Explosions-Unterdrückungssysteme;
— Einbau-, Betriebs- und Instandhaltungsanweisungen für ein Explosions-Unterdrückungssystem.
Dieses Dokument gilt nur für Explosions-Unterdrückungssysteme, die zum Schutz von geschlossenen oder im Wesentlichen geschlossenen Gehäusen vorgesehen sind, in denen eine Explosion durch die Zündung eines explosionsfähigen Gemisches, z. B. Staub/Luft, Gas(Dampf)/Luft, Staub/Gas(Dampf)/Luft und Ne-bel/Luft, entstehen könnte.
Dieses Dokument ist nicht anwendbar bei Explosionen von nachstehend aufgeführten Stoffen oder Ge-mischen, die diese Stoffe enthalten:
— instabile Stoffe, die möglicherweise zerfallen können;
— Explosivstoffe;
— pyrotechnische Materialien;
— pyrophore Stoffe.
Systèmes de suppression d’explosion
Le présent document décrit les exigences minimales de conception et d’application des systèmes de suppression d’explosion. Il spécifie également des méthodes d’essai pour l’évaluation de l’efficacité et de l’extrapolation des systèmes de suppression d’explosion par rapport { des explosions définies. Le présent document couvre les points suivants :
— les exigences générales concernant les composants des systèmes de suppression d’explosion ;
— l’évaluation de l’efficacité d’un système de suppression d’explosion ;
— l’évaluation de l’extrapolation d’un système de suppression d’explosion ;
— le développement et l’évaluation d’outils de conception pour les systèmes de suppression d’explosion ;
— des instructions relatives à l’installation, au fonctionnement et { la maintenance d’un système de suppression d’explosion.
Le présent document s’applique uniquement aux systèmes de suppression d’explosion destinés { protéger des enveloppes fermées ou en majeure partie fermées, dans lesquelles une explosion peut être la conséquence de l’inflammation de mélanges explosibles de type poussière-air, gaz (vapeur)-air, poussière-gaz (vapeur)-air et brouillard-air, par exemple.
Le présent document ne s’applique pas aux explosions des matières énumérées ci-dessous ni aux mélanges contenant certaines de ces matières :
— matières non stables susceptibles de se dissocier ;
— matières explosives ;
— matières pyrotechniques ;
— matières pyrophoriques.
Sistemi za dušenje eksplozij
General Information
RELATIONS
Standards Content (sample)
SLOVENSKI STANDARD
oSIST prEN 14373:2019
01-april-2019
Sistemi za dušenje eksplozij
Explosion suppression systems
Explosions-Unterdrückungssysteme
Systèmes de suppression d’explosion
Ta slovenski standard je istoveten z: prEN 14373
ICS:
13.230 Varstvo pred eksplozijo Explosion protection
oSIST prEN 14373:2019 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------oSIST prEN 14373:2019
---------------------- Page: 2 ----------------------
oSIST prEN 14373:2019
DRAFT
EUROPEAN STANDARD
prEN 14373
NORME EUROPÉENNE
EUROPÄISCHE NORM
January 2019
ICS 13.230 Will supersede EN 14373:2005
English Version
Explosion suppression systems
Systèmes de suppression d'explosion Explosions-Unterdrückungssysteme
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee
CEN/TC 305.If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and United Kingdom.Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2019 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 14373:2019 E
worldwide for CEN national Members.---------------------- Page: 3 ----------------------
oSIST prEN 14373:2019
prEN 14373:2019 (E)
Contents Page
European foreword ....................................................................................................................................................... 4
1 Scope .................................................................................................................................................................... 5
2 Normative references .................................................................................................................................... 5
3 Terms and definitions ................................................................................................................................... 6
4 Explosion suppression .................................................................................................................................. 9
4.1 Objectives ........................................................................................................................................................... 9
4.2 General function .............................................................................................................................................. 9
4.3 Essential requirements ................................................................................................................................. 9
5 Environmental aspects ............................................................................................................................... 12
5.1 General ............................................................................................................................................................. 12
5.2 Suppressant .................................................................................................................................................... 13
5.3 Actuators and other components ........................................................................................................... 13
6 Experimental testing of the efficacy of an explosion suppression system .............................. 13
6.1 Required information ................................................................................................................................. 13
6.1.1 General ............................................................................................................................................................. 13
6.1.2 Intended use .................................................................................................................................................. 13
6.1.3 Information on the components of the suppression system ........................................................ 13
6.1.4 Calculation model ........................................................................................................................................ 14
6.2 Testing .............................................................................................................................................................. 14
6.2.1 General requirements for test setup ..................................................................................................... 14
6.2.2 Test program for non metallic dusts ..................................................................................................... 15
6.3 Test program for metal dust .................................................................................................................... 17
6.4 Test program for gas ................................................................................................................................... 17
6.5 Test program for hybrid mixtures ......................................................................................................... 18
6.6 Measuring techniques ................................................................................................................................ 18
6.7 Test Report ..................................................................................................................................................... 18
7 Instructions .................................................................................................................................................... 20
7.1 General ............................................................................................................................................................. 20
7.2 User manual ................................................................................................................................................... 20
7.3 Installation of cables ................................................................................................................................... 20
7.4 Assembling ..................................................................................................................................................... 20
7.4.1 General ............................................................................................................................................................. 20
7.4.2 Assembly ......................................................................................................................................................... 20
7.5 Commissioning .............................................................................................................................................. 21
7.5.1 General ............................................................................................................................................................. 21
7.5.2 Instructions for hand-over ....................................................................................................................... 21
7.5.3 Commissioning report ................................................................................................................................ 21
7.6 Safety ................................................................................................................................................................ 21
7.7 Maintenance ................................................................................................................................................... 22
8 Marking and packaging .............................................................................................................................. 22
8.1 General ............................................................................................................................................................. 22
8.2 Explosion suppression system components....................................................................................... 22
8.3 Explosion suppression system ................................................................................................................ 23
8.4 Omission of markings ................................................................................................................................. 23
---------------------- Page: 4 ----------------------oSIST prEN 14373:2019
prEN 14373:2019 (E)
Annex A (informative) Development of an explosion suppression calculation model .................... 24
Annex B (informative) Applications ................................................................................................................... 27
Annex C (informative) Extrapolation to larger volumes ............................................................................. 33
Annex D (informative) Significant changes between this European Standard andEN 14373:2005 .............................................................................................................................................. 37
ANNEX ZA (informative) Relationship between this European Standard and the essential
requirements of EU Directive 2014/34/EU aimed to be covered ............................................... 39
Bibliography ................................................................................................................................................................. 41
---------------------- Page: 5 ----------------------oSIST prEN 14373:2019
prEN 14373:2019 (E)
European foreword
This document (prEN 14373:2019) has been prepared by Technical Committee CEN/TC 305
“Potentially explosive atmospheres — Explosion prevention and protection”, the secretariat of which is
held by DIN.This document is currently submitted to the CEN Enquiry.
This document will supersede EN 14373:2005.
This document has been prepared under a standardization request given to CEN by the European
Commission and the European Free Trade Association, and supports essential requirements of
EU Directive(s).For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this
document.---------------------- Page: 6 ----------------------
oSIST prEN 14373:2019
prEN 14373:2019 (E)
1 Scope
This document describes the basic requirements for the design and application of explosion
suppression systems. This document also specifies test methods for evaluating the effectiveness and the
scale up of explosion suppression systems against defined explosions. This document covers:
— general requirements for explosion suppression system components;— evaluating the effectiveness of an explosion suppression system;
— evaluating the scale up of an explosion suppression system;
— development and evaluation of design tools for explosion suppression systems;
— installation, operation and maintenance instructions for an explosion suppression system.
This document is applicable only to explosion suppression systems intended for the protection of
closed, or essentially closed, enclosures in which an explosion could result as a consequence of ignition
of an explosible mixture, e.g. dust-air, gas(vapour)-air, dust-gas(vapour)-air and mist-air.
This document is not applicable for explosions of materials listed below, or for mixtures containing
some of those materials:— unstable materials that are liable to dissociate;
— explosive materials;
— pyrotechnic materials;
— pyrophoric materials.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
prEN 1127-1:2018, Explosive atmospheres — Explosion prevention and protection — Part 1: Basic
concepts and methodologyEN 13237:2012, Potentially explosive atmospheres — Terms and definitions for equipment and protective
systems intended for use in potentially explosive atmospheresEN 15233:2007, Methodology for functional safety assessment of protective systems for potentially
explosive atmospheresEN 15967:2011, Determination of the maximum explosion pressure and the maximum rate of pressure
rise of gases and vapoursEN 14034-1:2004+A1:2011, Determination of explosion characteristics of dust clouds — Part 1:
Determination of the maximum explosion pressure pmax of dust cloudsEN 14034-2:2006+A1:2011, Determination of explosion characteristics of dust clouds — Part 2:
Determination of the maximum rate of explosion pressure rise (dp/dt)max of dust clouds
---------------------- Page: 7 ----------------------oSIST prEN 14373:2019
prEN 14373:2019 (E)
EN 61508-1:2010, Functional safety of electrical/electronic/programmable electronic safety-related
systems — Part 1: General requirementsEN 61508-2:2010, Functional safety of electrical/electronic/programmable electronic safety-related
systems — Part 2: Requirements for electrical/electronic/programmable electronic safety-related systems
EN 61508-3:2010, Functional safety of electrical/electronic/programmable electronic safety-related
systems — Part 3: Software requirementsEN 61508-4:2010, Functional safety of electrical/electronic/programmable electronic safety-related
systems — Part 4: Definitions and abbreviationsEN 61508-5:2010, Functional safety of electrical/electronic/programmable electronic safety-related
systems — Part 5: Examples of methods for the determination of safety integrity levels
EN 61508-6:2010, Functional safety of electrical/electronic/programmable electronic safety-related
systems — Part 6: Guidelines on the application of IEC 61508-2 and IEC 61508-3EN 61508-7:2010, Functional safety of electrical/electronic/programmable electronic safety-related
systems — Part 7: Overview of techniques and measures3 Terms and definitions
For the purposes of this document, the terms and definitions given in prEN 1127-1:2018,
EN 13237:2012 and the following apply.ISO and IEC maintain terminological databases for use in standardization at the following addresses:
• IEC Electropedia: available at http://www.electropedia.org/• ISO Online browsing platform: available at http://www.iso.org/obp
3.1
HRD-suppressor
vessel with opening mechanism, which upon activation discharges an explosion suppressant at a high
rateNote 1 to entry: HRD is the abbreviation of High Rate Discharge.
3.2
suppressant
substance contained in the HRD-suppressor which, when dispersed into an enclosure to be protected,
can arrest and mitigate a developing explosion in that enclosureNote 1 to entry: Two categories of suppressants are in general use, separately or in combination:
— powder suppressant;— liquid suppressant.
---------------------- Page: 8 ----------------------
oSIST prEN 14373:2019
prEN 14373:2019 (E)
3.2.1
powder suppressant
powder with recognised flame extinguishing properties such as products based on monoammonium
phosphate, potassium bicarbonate or sodium bicarbonateNote 1 to entry: Such suppressants can contain additives to improve their flow properties and their
effectiveness3.2.2
liquid suppressant
substance stored as a liquid with recognised flame extinguishing properties such as water and
halogenated alkanes, cold or hotNote 1 to entry: Additives can be included to provide frost protection, and/or to improve the suppressant
effectiveness.3.3
dispersion pressure
pressure in HRD-suppressor to disperse the suppressant, which is provided by gas, chemical reaction or
the application of heat3.4
suppressant charge
mass of the suppressant contained within the suppressor
3.5
explosion detector
device that responds to an explosion (e.g. developing pressure and/or radiation) and provides a signal
to the control and indicating equipmentNote 1 to entry: See 3.10.
3.6
activation pressure
pressure at which the CIE activates the HRD-suppressor(s)
3.7
maximum reduced (suppressed) explosion pressure
red,max
maximum explosion overpressure generated by an explosion of an explosive atmosphere in an
enclosure at optimum fuel concentration, after effective explosion venting or explosion suppression
3.8explosion suppression
technique limiting and/or avoiding the destructive effect of an explosion by the deployment of
suppressant---------------------- Page: 9 ----------------------
oSIST prEN 14373:2019
prEN 14373:2019 (E)
3.9
explosion suppression system
arrangement comprising one or more explosion detectors, CIE and one or more HRD-suppressors
aiming at achieving explosion suppression3.10
control and indicating equipment
CIE
electronic system which controls, records and monitors the status of the explosion protection system
and initiates the explosion protection devices upon detectionNote 1 to entry: On detection of an incipient explosion, the CIE activates the explosion protection devices and
initiates alarm systems and process shutdown.3.11
dispersion nozzle
device fitted on a HRD-suppressor and designed to distribute the suppressant throughout the enclosure
to be protected3.12
compact enclosure/cubic enclosure
enclosures having a length (height) to diameter ratio of less than 2
3.13
elongated enclosures
enclosures with a length (height) to diameter ratio of 2 to 10
3.14
pipe
construction with a length (height) to diameter ratio greater than 10
3.15
hazard sector
three-dimensional space for which the explosion suppression system is designed to be active
3.16LOAEL
lowest concentration of the suppressant at which an adverse toxicological or physiological effect has
been observedNote 1 to entry: LOAEL is the abbreviation of Lowest Observable Adverse Effect Level.
3.17suppression model
mathematical calculation which predicts the course of an explosion, the action of the suppression
system and its interaction with the explosion, in order to enable an accurate design of explosion
suppression systems3.18
maximum throw
maximum distance from a suppressor at which the concentration of the expelled suppressant is still
sufficiently high to extinguish an explosion flame---------------------- Page: 10 ----------------------
oSIST prEN 14373:2019
prEN 14373:2019 (E)
4 Explosion suppression
4.1 Objectives
Explosion suppression systems shall be designed to extinguish propagating flames and to reduce the
maximum explosion pressure, P to a reduced explosion pressure (P ), following an ignition in
max, redthe protected enclosure. In general, successful explosion suppression implies that the P will not
redexceed the strength of the protected equipment. Explosion suppression systems can be applied to
flammable gases, mists, dusts or hybrid mixtures.4.2 General function
Explosion suppression is a protective measure for enclosures, where a gas, mist, dust or hybrid mixture
explosion is detected and arrested during incipient stages (see Figure 1).Key
1 supressor
a The explosive atmosphere in an enclosure is ignited. The enclosure is provided with one (or more)
explosion detectors (D) and one (or more) suppressors (1).b The explosion is detected by the explosion detector(s).
c The control and indicating equipment CIE (not shown) has received the signal from the explosion
detector(s) and activated the suppressor(s). The suppressor(s) have started to inject suppressant into
the enclosure.d The suppressant cloud reaches the explosion flame.
e The flame is extinguished: the explosion is suppressed.
Figure 1 — Stages in explosion suppression of an enclosure
The performance of an explosion suppression system depends on:
— the response time of the system: time until explosion is detected + response time of the various
components + time required to inject sufficient suppressant into the enclosure;— the suppressant dispersion: spatial distribution, as a function of time;
— the effectiveness of the suppressant.
4.3 Essential requirements
An explosion suppression system consists of at least one: explosion detector, HRD suppressor, complete
with suppressant / dispersion nozzle and connected to control and indicating equipment (CIE).
---------------------- Page: 11 ----------------------oSIST prEN 14373:2019
prEN 14373:2019 (E)
Essential requirements are:
— the overall requirement of the explosion suppression system is to detect an explosion in the
incipient stage and to have a fast response to allow for the dispersion of suppressant and
extinguishment of the flame in order to limit the maximum reduced explosion pressure below the
admissible pressure of the protected equipment - Experimental validation shall be performed as
described in Clause 6;— the system as installed or any of its components shall not introduce ignition hazards, such as
electrostatic discharge, mechanical friction, electrical sparks, hot surfaces;— the activation of the suppression system shall not result in dangerous ejected parts;
— the explosion suppression system shall have a defined reliability for safety-functions according to
the intended use (see 4.3 d);— if discharging the suppressant during maintenance or inspection can result in injury, the explosion
suppression system shall have provisions in place to prevent an unintended suppressor discharge
prior to performing such operations;— the suppression system shall be configured to prevent unintended arming;
— the supplier shall provide instructions which ensure safe operation of the explosion suppression
system and the system is always activated when explosible atmospheres are present and is
disarmed before access to be inside protected equipment is granted (see 7.6);— the explosion suppression system shall avoid operation of the protected process by provision of a
safe signal interface through the CIE so that operation cannot be resumed until the suppression
system is armed and fault free.Other essential requirements are:
a) Explosion Detector
An explosion detector shall detect the onset of the explosion in time to allow for achieving
successful suppression.b) Control and Indication Equipment (CIE)
The components and software used in the Control and Indication Equipment (CIE) shall ensure
explosion suppression system functionality by undertaking the following:— process detection signals;
— initiate the suppressors;
— initiate interlocks/alarms;
— enable safe isolation;
— enable an automatic and orderly safe-mode of the protected process upon activation,
fault/trouble condition.c) Emergency power
---------------------- Page: 12 ----------------------
oSIST prEN 14373:2019
prEN 14373:2019 (E)
Emergency power shall be specified and facilitated such that full uninterrupted unchanged
explosion protection functionality is ensured at least 4 h after a mains power failure.
d) Explosion SuppressorsExplosion suppressors shall inject sufficient suppressant into the protected enclosure in the
required time. Either monitored mechanical blocking or other monitored provisions to prevent
unintended activation shall be present.NOTE 1 The performance of suppressors depends upon at least:
— volume, shape and outlet diameter of the suppressor;
— filling ratio and pressure inside the suppressor;
— opening time of the suppressor;
— characteristics of the dispersion nozzle and the suppressant.
e) Dispersion nozzle
The dispersion nozzle shall spread the suppressant into the protected enclosure to achieve both
required throw and spatial distribution / concentration.NOTE 2 The performance of a dispersion nozzle depends upon at least:
— design of the nozzle;
— characteristics of the suppressor and the suppressant.
Depending on the intended use specific dispersion nozzles can be applied, with special
performances, for example to obtain strong directional effects.f) Suppressant
The suppressant shall have dispersion characteristics and extinguishing properties allowing for
extinguishing an explosion flame for a given fuel type.NOTE 3 The properties influencing these characteristics include:
— the particle/droplet size distribution;
— chemical and thermal properties.
Apart from the effectiveness in explosion suppression of the suppressant applied, also the
compatibility of the suppressant with the process shall be considered:— temperature stability;
— any adverse reaction with the process products;
— toxicity levels of the suppressant.
g) Installation, commissioning, service and maintenance
---------------------- Page: 13 ----------------------
oSIST prEN 14373:2019
prEN 14373:2019 (E)
Installation instructions, service and maintenance requirements and intervals shall be specified in
the system documentation (see Clause 7).h) Reliability and functional safety
The functional safety of the suppression system shall be quantified by the manufacturer according
to EN 61508-1:2010, EN 61508-2:2010, EN 61508-3:2010, EN 61508-4:2010, EN 61508-5:2010,
EN 61508-6:2010, EN 61508-7:2010 and EN 15233:2007.The reliability of the system shall be ensured by monitoring of as a minimum the following:
1) wiring circuits for continuity, earth faults and open circuits;2) mains power supply;
3) emergency power supply;
4) system safety interlock circuitry;
5) system-disabling interlock circuitry;
6) electrically operated actuating devices;
7) detection devices;
8) health monitoring of HRD Suppressors (e.g. pressure).
In addition one shall assess the functional safety. As a minimum the following aspects shall be
addressed:a) design faults in the hardware;
b) adverse environmental conditions, including electromagnetic disturbance;
c) design faults in the software.
In case of an identifiable fault such that the safety function of the system cannot be guaranteed to
the agreed level of safety integrity, the suppression system shall provide a fail-safe means to place
the installation into a safe condition.5 Environmental aspects
5.1 General
Dispositions shall be taken to limit the impact of the explosion suppression devices on the environment.
Materials shall be selected to optimize product durability and lifetime and consideration shall be made
to avoiding the selection of rare or hazardous materials. Consideration shall be made to using recycled
or reused materials, and to the selection of materials which can then be subsequently recycled.
Packaging design shall consider using recycled materials, and materials that need little energy for their
manufacture, and shall minimize waste.It shall be taken into account that each combustion process can generate toxic decomposition products.
---------------------- Page: 14 ----------------------oSIST prEN 14373:2019
prEN 14373:2019 (E)
After activation of a suppression system the installation shall be cleaned up properly with duly
precautions regarding toxicity of the suppressant. Also the combustible material may have been
affected by the suppressant and by the combustion and may exhibit toxic properties. Waste and
cleaning materials shall be disposed according to the manufacturer instructions and to the enforced law
in respect of environmental protection to limit any risk of water and soil pollution.
5.2 SuppressantDuring explosion suppression a large quantity of the suppressant is released into the process. The
manufacturer’s instructions shall address the following items:— food compatibility;
— toxicity of the suppressant;
— corrosion of equipment.
Depending on the application, non-toxic, non-corrosive and food compatible suppressants should be
preferred.5.3 Actuators and other components
Other components including actuators (after activation) can affect the environment and shall be
handled accordingly.6 Experimental testing of the efficacy of an explosion suppression system
6.1 Required information
6.1.1 General
Before testing the manufacturer shall describe the intended use and shall provide detailed information
on the suppression system.As a minimum, the following information shall be provided prior to testing.
6.1.2 Intended use
The manufacturer shall provide limits of applications. The minimum requirements are listed below:
a) explosive atmosphere type including fuel type (K , p ,...