13.220.20 - Fire protection
ICS 13.220.20 Details
Fire protection
Brandverhutung
Protection contre l'incendie
Požarna zaščita
General Information
e-Library Subscription
Create subscription and get permanent access to documents within 13.220.20 - Fire protection
Currently subscription includes documents marked with .We are working on making all documents available within the subscription.
This document specifies requirements for earthquake protection of automatic sprinkler systems in accordance with the EN 12845 series of standards. This document applies only to locations in earthquake zones in accordance to EN 1998-1:2004, 3.2.1 and for area subject to peak ground acceleration above 9 % of g. This document does not cover all legislative requirements. In certain countries specific national regulations apply and take precedence over this document. Users of this document are advised to inform themselves of the applicability or non-applicability for this document by their national responsible authorities
- Standard38 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the requirements for flame arresters that prevent flame transmission when explosive gas-air or vapour-air mixtures are present. It establishes uniform principles for the classification, basic construction and information for use, including the marking of flame arresters, and specifies test methods to verify the safety requirements and determine safe limits of use. This document is applicable to pressures ranging from 80 kPa to 160 kPa and temperatures ranging from -20 °C to +200 °C. This document does not apply to the following: - external safety-related measurement and control equipment that might be required to keep the operational conditions within the established safe limits; - flame arresters used for explosive mixtures of vapours and gases, which tend to self-decompose (for example, acetylene) or which are chemically unstable; - flame arresters used for carbon disulfide, due to its special properties; - flame arresters whose intended use is for mixtures other than gas-air or vapour-air mixtures (for example, higher oxygen-nitrogen ratio, chlorine as oxidant); - flame arrester test procedures for reciprocating internal combustion engines; - fast acting valves, extinguishing systems and other explosion isolating systems; - Flame arresters used in gas detectors (those being covered for example, by IEC 60079‑29‑1 and IEC 62990‑1). This edition cancels and replaces ISO 16852:2016, which has been technically revised. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to ISO 16852:2016: a) adaptation of the relevant IEC TC 31 requirements on standards; b) modification of the upper limit of the temperature range from 150 °C to 200 °C under the condition that T0 shall be not larger than 80 % of the auto ignition temperature of the gas-air-mixture; c) change of the term "explosion group" to "equipment group" due to editorial requirements in IEC/TC 31; d) clarification of the conditions and requirements for flame arresters whose intended operating conditions are outside the atmospheric conditions in 7.3.4 and 7.3.5; e) clarification of the requirements on the information for use in Clause 12 f) concerning the burn time; f) addition of a permission to the construction requirements both in 7.1 and 14.1 to substitute visual inspection by performing a flow test; g) addition of a flow chart for the evaluation of test results as Annex D
- Standard61 pagesEnglish languagesale 15% off
This document specifies requirements for earthquake protection of automatic sprinkler systems in accordance with EN 12845:2015+A1:2019.
This document applies only to locations in earthquake zones in accordance with EN 1998-1:2004, 3.2.1 and the Nationally Determined Parameters.
NOTE The requirements in this document are based on the principle that certain peak ground acceleration values are considered as an earthquake which require special means. Attention is drawn to EN 1998-1:2004, where a peak ground acceleration above 0,08 g (0,78 m/s2) is considered an earthquake risk. Additional characteristics, NDP and/or NCI can exist in some countries as well as national annexes.
The principles defined in this document can be applicable to other water based fixed manual or automatic fire fighting systems, according to local requirements.
- Standard38 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the evaluation of the fire performance of water mist systems for lightly loaded non-storage and non-manufacturing occupancies with ordinary combustibles, such as offices, schools, hospitals and hotels.
This document is applicable to ceiling mounted and sidewall automatic nozzles to be used in restricted and/or unlimited areas.
This document is applicable for horizontal, solid, flat ceilings with heights of 2 m and above, up to the maximum tested ceiling height.
- Standard18 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the evaluation of the fire performance of water mist systems for lightly loaded non-storage and non-manufacturing occupancies with ordinary combustibles, such as offices, schools, hospitals and hotels.
This document is applicable to ceiling mounted and sidewall automatic nozzles to be used in restricted and/or unlimited areas.
This document is applicable for horizontal, solid, flat ceilings with heights of 2 m and above, up to the maximum tested ceiling height.
- Standard18 pagesEnglish languagesale 10% offe-Library read for1 day
This part of EN 45545 specifies the fire resistance requirements and testing methods for fire barriers for railway vehicles.
The objective of the measures and requirements, specified in this part of EN 45545, is to protect passengers and staff in railway vehicles in the event of a developing fire on board.
Use of a Fire Containment and Control System, where permitted as an alternative to a fire barrier, is not in the scope of this part of EN 45545. It is not within the scope of this part of EN 45545 to describe measures that ensure the preservation of the railway vehicles in the event of a fire.
- Standard24 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies fire safety requirements for railway vehicle design to cover the objectives
specified in EN 45545-1:2013.
The measures and requirements specified in this document aim to protect passengers and staff in railway
vehicles in the event of a fire on board by minimizing the risk of a fire starting, delaying the fire
development and controlling the spread of fire products through the railway vehicle, thus aiding
evacuation.
It is not within the scope of this document to describe measures which ensure the preservation of the
railway vehicles in the event of a fire.
- Standard17 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the fire resistance requirements and testing methods for fire barriers for railway vehicles.
The objective of the measures and requirements, specified in this document, is to protect passengers and staff in railway vehicles in the event of a developing fire on board.
Use of a Fire Containment and Control System, where permitted as an alternative to a fire barrier, is not in the scope of this document. It is not within the scope of this document to describe measures that ensure the preservation of the railway vehicles in the event of a fire.
- Standard24 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies fire safety requirements for railway vehicle design to cover the objectives specified in EN 45545-1:2013.
The measures and requirements specified in this document aim to protect passengers and staff in railway vehicles in the event of a fire on board by minimizing the risk of a fire starting, delaying the fire development and controlling the spread of fire products through the railway vehicle, thus aiding evacuation.
It is not within the scope of this document to describe measures which ensure the preservation of the railway vehicles in the event of a fire.
- Standard17 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies requirements, test methods and performance criteria for video fire detectors (VFDs), which operate in the visible spectrum, for use in fire detection and alarm systems installed in and around buildings (see ISO 7240-1). For the testing of other types of VFD working on different principles, this document can be used only for guidance. Detectors developed for the protection of specific risks that incorporate special characteristics (including additional features or enhanced functionality for which this document does not define a test or assessment method) are beyond the scope of this document.
- Standard85 pagesEnglish languagesale 15% off
This part of EN 45545 specifies the reaction to fire performance requirements for materials and products used on railway vehicles as defined in EN 45545-1.
The operation and design categories defined in EN 45545-1 are used to establish hazard levels that are used as the basis of a classification system.
For each hazard level, this part specifies the test methods, test conditions and reaction to fire performance requirements.
It is not within the scope of this European Standard to describe measures that ensure the preservation of the vehicles in the event of a fire.
- Standard50 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies fire testing requirements for water mist systems used for fire protection of commercial low hazard occupancies up to 5 m ceiling height.
EXAMPLE Examples for commercial low hazard occupancies are apartments, churches, concealed spaces, gymnasiums, hospitals, hotels, libraries, museums, offices, restaurant seating areas, schools and university class rooms, unused attics.
- Standard17 pagesEnglish languagesale 10% offe-Library read for1 day
This part of the EN 12259 series specifies requirements for single stage and multi-stage centrifugal pumps with mechanical seal or soft packing for use in automatic sprinkler systems and is for use with EN 12845 and EN 17451.
This document is only applicable for the following pumps, independent of installed orientation (vertical, horizontal or sloped):
- end suction pumps (close coupled or long coupled) of the back pull-out type pump;
- axial horizontal split case pumps;
- ring section pumps;
- inline pumps (vertical line shaft pump with inlet and outlet in line);
- vertical turbine pumps;
- multistage inline pumps;
- multi stage-multi outlet pumps;
- submersible motor borehole pumps.
- Standard15 pagesEnglish languagesale 10% offe-Library read for1 day
This part of EN 45545 specifies the reaction to fire performance requirements for materials and products used on railway vehicles as defined in EN 45545-1.
The operation and design categories defined in EN 45545-1 are used to establish hazard levels that are used as the basis of a classification system.
For each hazard level, this part specifies the test methods, test conditions and reaction to fire performance requirements.
It is not within the scope of this European Standard to describe measures that ensure the preservation of the vehicles in the event of a fire.
- Standard50 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies requirements for single stage and multi-stage centrifugal pumps with mechanical seal or soft packing for use in automatic sprinkler systems and is for use with EN 12845 and EN 17451 .
This document is applicable for the following pumps, independent of installed orientation (vertical, horizontal or sloped according to the manufacturer indications):
- end suction pumps (close coupled or long coupled) of the back pull-out type pump;
- axial horizontal split case pumps;
- ring section pumps including multistage single or multi outlet;
- single or multistage inline pumps (pump with inlet and outlet in line);
- submersible motor borehole pumps.
This document is also applicable to vertical turbine pumps.
- Standard15 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the evaluation of the firefighting performance of water mist systems for false ceilings and false floors with heights between 300 mm and 800 mm.
This fire test protocol is applicable to pendent or upright automatic nozzles to be used in unlimited volume.
This document is applicable for horizontal, solid, flat ceilings.
It is not possible to apply these tests to other applications than the ones specified within this fire test protocol.
In case of a positive result of the tests, the water mist system can be applied for the protection of the following risks:
False ceilings and false floors between 300 mm and 800 mm.
- Standard15 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies fire testing requirements for water mist systems used for fire protection of cable tunnels. The test protocol covers deluge water mist systems with open nozzles which are either activated with an automatic release system, e.g. fire detection system, or manually released.
- Standard12 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies fire testing requirements for water mist systems used for fire protection of commercial low hazard occupancies up to 5 m ceiling height.
- Standard17 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies requirements, test methods and performance criteria for point-type smoke detectors that operate using scattered light, transmitted light or ionization, for use in fire detection and alarm systems installed in buildings (see ISO 7240-1). This document also covers point-type smoke detectors that incorporate more than one smoke sensor operating on these principles. Additional requirements and test methods for such detectors are given in Annex N. For the testing of other types of smoke detectors, or smoke detectors working on different principles, this document is only intended to be used for guidance. This document is not applicable to smoke detectors with special characteristics, developed for specific risks. NOTE Certain types of detectors contain radioactive materials.
- Standard59 pagesEnglish languagesale 15% off
This document specifies the evaluation of the firefighting performance of water mist systems for false ceilings and false floors with heights between 300 mm and 800 mm.
This fire test protocol is applicable to pendent or upright automatic nozzles to be used in unlimited volume.
This document is applicable for horizontal, solid, flat ceilings.
It is not possible to apply these tests to other applications than the ones specified within this fire test protocol.
- Standard15 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies fire testing requirements for water mist systems used for fire protection of cable tunnels. The test protocol covers deluge water mist systems with open nozzles which are either activated with an automatic release system, e.g. fire detection system, or manually released.
- Standard12 pagesEnglish languagesale 10% offe-Library read for1 day
This document defines a practical degree of fire prevention and protection intended to provide enough time for occupants to escape a fire on board small craft.
It applies to small craft having a length of the hull (LH) of up to 24 m except for personal watercraft.
This document does not cover:
— the design and installation of permanently installed galley stoves and heating appliances (including components used to distribute the heat) using fuels that are liquid at atmospheric pressure on small craft, which are covered by ISO 14895:2016;
— carbon monoxide detecting systems, which are covered by ISO 12133.
- Standard39 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies requirements and test methods for early suppression and fast response (ESFR) sprinklers with a nominal discharge coefficient of 200 (pendent and upright), 240 (pendent and upright), 320 (pendent), 360 (pendent), 400 (pendent) and 480 (pendent) l/min/(bar)1/2.
- Standard64 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies requirements for the construction and performance of residential sprinklers as well as test methods for their type approval, which are operated by a change of state of an element or bursting of a glass bulb under the influence of heat, for use only in automatic sprinkler systems for domestic and residential applications as defined in EN 16925:− .
This standard does not cover representative fire and other tests for special sprinklers that are intended to provide for specific fire hazards, nor does it cover fire and other tests for sprinklers for commercial and industrial sprinkler systems as in EN 12845. Those test requirements are covered by EN 12259-1.
NOTE 1 All pressure data in this European Standard are given as gauge pressures in bar.
NOTE 2 Sprinklers according to EN12259-1 can also be used in residential and domestic applications if the system is designed according to EN 12845.
- Standard61 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the evaluation of the fire performance of water mist systems for fire protection of interior atriums, with low or medium fire load where the fire load or any obstructions do not extend above 1,5 m height.
- Standard19 pagesEnglish languagesale 10% offe-Library read for1 day
This document applies to resettable line-type heat detectors consisting of a sensing element distributed either continuously or discretely at close intervals along its length and connected to a sensor control unit, either directly or through an interface module, intended for use in fire detection and fire alarm systems installed in and around buildings and other civil engineering works. Examples of such technology are an optical fibre, a pneumatic tube, or an electrical sensor cable This document specifies the requirements and performance criteria, the corresponding test methods, and provides for the assessment. This document also covers resettable line-type heat detectors intended for use in the local protection of plants and equipment. This document does not cover non-resettable line-type heat detectors that can only respond once and are based on fixed temperature electrical cables.
- Standard60 pagesEnglish languagesale 15% off
This draft European Standard specifies requirements, test methods and performance criteria for point smoke detectors that operate using scattered light, transmitted light or ionization, intended for use in fire detection and fire alarm systems installed in and around buildings (see EN 54 1:2011).
This European standard provides for the assessment of verification of consistency of performance (AVCP) of point smoke detectors to this EN.
For other types of smoke detector, or smoke detectors working on different principles, this standard should only be used for guidance. Smoke detectors with special characteristics and developed for specific risks are not covered by this standard.
NOTE Certain types of detector contain radioactive materials. The national requirements for radiation protection differ from country to country and they are not specified in this standard.
- Standard79 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard specifies the requirements, test methods and performance criteria for point heat detectors intended for use in fire detection and fire alarm systems installed in and around buildings (see EN 54-1:2011).
This European Standard provides for the assessment of verification of constancy of performance (AVCP) of point heat detectors to this EN.
For other types of heat detector, or for detectors intended for use in other environments, this standard should only be used for guidance.
Heat detectors with special characteristics and developed for specific risks are not covered by this standard.
- Standard62 pagesEnglish languagesale 10% offe-Library read for1 day
(1) This technical specification gives minimum design, installation and commissioning requirements for powered smoke and heat control systems for enclosed car parks using horizontal flow powered ventilation, with or without sprinkler protection, on one or more levels, for cars and light commercial vehicles (max 3,5 t), to reach the design objectives outlined in this technical specification.
see design objectives in CEN TC191 SC1 doc. N721, 5.1 (1):
For any fire location, the system shall keep at least one access route sufficiently clear of smoke for fire-fighters from the exterior or from a protected access route (e.g. stairwell) to a distance of 15 m from the front of the fire. Criteria should be verified when the conditions within the car park have reached a steady-state regime.
NOTE: The limit of 15 m is necessary to reach the fire with the jet from the hose nozzle.
(2) This technical specification is applicable for fires of cars powered by petrol or diesel or other fuels which will have a fire performance similar to vehicles powered by petrol or by electricity. It is not applicable for other fires within the car park (e.g. storage).
NOTE: It is assumed that cars powered by fuels other than petrol or diesel will have a fire performance similar to vehicles powered by petrol or diesel.
(3) This technical specification only covers traditional car parks that are with cars parked alongside each other with common access roadways/lanes for cars to be driven in and out. It does not cover other forms of car parking systems, such as stacking systems. Smoke and heat control systems for vehicles more than 3,5 t (lorry parks, coach parks, etc.) are not covered by this technical specification.
(4) This technical specification does not cover requirements for day‐to‐day ventilation.
(5) Any other risks than fire from cars are not covered by this technical specification.
- Technical specification51 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the fire resistance requirements for lift landing doors which can be exposed to a fire from the landing side. This document applies to all types of lift landing doors used as a means of access to lifts in buildings and which are intended to provide a fire barrier to the spread of fire via the lift well.
It also specifies the method of testing and classification of fire resistance of lift landing doors. The test method is only valid for furnaces where the door is mounted in a vertical position. The test method allows for the measurement of integrity and if required the measurement of radiation and thermal insulation.
This document covers the hazard of fire spreading to the lift well during a defined period of time. The fire resistance requirements are expressed in terms of integrity (E), insulation (EI) and radiation (EW).
This document do not cover other technical requirements in addition to fire resistance requirements. The other technical requirements are specified in relevant product standards referring to this document.
This document refers to CO2 as means of tracing the propagation of fire. The document does not cover hazards due to emission of gasses.
This document is not applicable to lift landing doors installed in lifts before the date of its publication.
- Standard34 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the design, installation, commissioning and service requirements for video fire detector systems (VFDS; see ISO/TS 7240-29), which are primarily intended to provide early detection of fire within one or more specified indoor areas for the protection of lives and equipment. The VFDS can also serve to protect from specific defined risks. The VFDS can be an independent fire detection system or can be used in conjunction with a fire detection and alarm system (FDAS; see ISO 7240‑1:2014, Figure 1).
- Technical specification18 pagesEnglish languagesale 15% off
This document specifies requirements for the construction and performance of residential sprinklers as well as test methods for their type approval, which are operated by a change of state of an element or bursting of a glass bulb under the influence of heat, for use only in automatic sprinkler systems for domestic and residential applications as defined in EN 16925:− .
This standard does not cover representative fire and other tests for special sprinklers that are intended to provide for specific fire hazards, nor does it cover fire and other tests for sprinklers for commercial and industrial sprinkler systems as in EN 12845. Those test requirements are covered by EN 12259-1.
NOTE 1 All pressure data in this European Standard are given as gauge pressures in bar.
NOTE 2 Sprinklers according to EN12259-1 can also be used in residential and domestic applications if the system is designed according to EN 12845.
- Standard61 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies requirements, test methods and performance criteria for line-type smoke detectors for use in fire detection systems installed in buildings. The detectors consist of at least a transmitter and a receiver and can include reflector(s) for the detection of smoke by the attenuation and/or changes in attenuation of an optical beam. This document is not applicable to: — line-type smoke detectors designed to operate with separations between opposed components of less than 1 m; — line-type smoke detectors whose optical path length is defined or adjusted by an integral mechanical connection; — line-type smoke detectors with special characteristics, which cannot be assessed by the test methods in this document. NOTE The term “optical” is used to describe that part of the electromagnetic spectrum produced by the transmitter to which the receiver is responsive; this is not restricted to visible wavelengths.
- Standard53 pagesEnglish languagesale 15% off
This document specifies the fire resistance requirements for lift landing doors which are intended to provide a barrier to the spread of fire from the landing side and via the lift well in buildings during a defined period of time. The fire resistance requirements are expressed in terms of integrity (E), insulation (EI) and radiation (EW).
It is applicable to lift landing doors installed in the lift well openings at landings and used as means of access to lift car.
It also specifies the method of testing and classification of fire resistance of lift landing doors. The test method is only valid for furnaces where the door is mounted in a vertical position. The test method specifies the measurement of integrity and if required the measurement of radiation and thermal insulation.
This document does not cover other technical requirements in addition to fire resistance requirements.
This document refers to CO2 as means of tracing the propagation of fire. The document does not cover hazards due to emission of gases.
This document is not applicable to lifts which are installed before the date of its publication.
- Standard34 pagesEnglish languagesale 10% offe-Library read for1 day
This document applies to pressure differential system kits, positioned on the market and intended to operate as part of a pressure differential system. The purpose of a pressure differential system is to prevent protected spaces from smoke spread by using pressure difference and airflow. This document specifies characteristics and test methods for components and kits for pressure differential systems to produce and control the required pressure differential and airflow between protected and unprotected space.
- Standard65 pagesEnglish languagesale 10% offe-Library read for1 day
This document gives guidance and requirements for the design and calculation methods, installation, acceptance testing, routine testing and maintenance for pressure differential systems (PDS).
PDSs are designed to hold back smoke at a leaky physical barrier in a building, such as a door (either open or closed) or other similarly restricted openings and to keep tenable conditions in escape and access routes depending on the application.
It covers systems intended to protect means of escape e.g. staircases, corridors, lobbies, as well as systems intended to provide a protected firefighting bridgehead for the fire services.
It provides details on the critical features and relevant procedures for the installation.
It describes the commissioning procedures and acceptance testing criteria required to confirm that the calculated design is achieved in the building.
This document gives complete rules, requirements and procedures to design PDS for buildings up to 60 m.
For buildings taller than 60 m the same requirements are given (e.g. Table 1), but additional calculations and verification methods are necessary. Requirements for such methods and verification are given in Annex D, but the methods fall outside the scope of this document [e.g. Computational Fluid Dynamics (CFD)].
Routine testing and maintenance requirements are also defined in the document.
In the absence of national requirements and under expected ambient and outside conditions, the requirements in Table 1 are fulfilled by the PDS.
- Standard118 pagesEnglish languagesale 10% offe-Library read for1 day
This document provides a catalogue of test fires and is intended to enhance comprehensive understanding of fire detection test methods. It describes a series of test fires to which fire detectors, such as smoke, heat and flame detectors, are subjected, as specified in other Parts of the ISO 7240 series. This document does not specify normative requirements regarding the test methods for the test fires.
- Technical report53 pagesEnglish languagesale 15% off
This document establishes the detailed test procedures for conducting the test on the plenum and air extract ducts.
- Technical specification6 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies fire testing requirements for water mist systems used for fire protection of combustion turbines in enclosures with volumes not exceeding 260 m³.
- Standard20 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the evaluation of the fire performance for water mist systems used for fire protection of combustion turbines in enclosures with volumes exceeding 260 m³.
- Standard21 pagesEnglish languagesale 10% offe-Library read for1 day
This document establishes the detailed test procedures for conducting the test on the plenum and air extract ducts.
- Technical specification6 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies, as far as the pressure risk is concerned, the rules of design, type testing, fabrication and inspection control of portable fire extinguishers with a metallic body which comply with the requirements of EN 3-7:2004+A1:2007.
This part of EN 3 applies to portable fire extinguishers of which the maximum allowable pressure PS is lower than or equal to 30 bar and containing non-explosive, non-flammable, non-toxic and non-oxidising fluids.
This document also applies to the marking of metallic propellant gas cartridges (see Annex E).
This document does not apply to carbon dioxide fire extinguishers.
- Standard36 pagesEnglish languagesale 10% offe-Library read for1 day
This document establishes the minimum requirements applicable to the design, installation, functioning, test and maintenance of fixed automatic fire extinguishing systems for kitchen protection that covers the cooking appliances, the hood, the plenum and the air extract ducts. This document also provides requirements for the construction and components performance as applicable to specific types, designs, sizes and arrangements of pre-engineered kitchen fire-extinguishing systems.
This document does not cover household kitchens or industrial food production equipment.
The detailed test procedures for the plenum and air extract ducts are contained in CEN/TS 17749.
Closed plenum type ventilated ceilings designed similar to standard hoods are included in this document. Open plenum type ventilated ceilings are excluded and require an engineered solution for the plenum protection. Protection for appliances below open or closed plenum ventilated ceilings are included.
- Standard36 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the evaluation of the fire performance of water mist systems for offices, school classrooms and hotels. This fire test protocol is applicable to ceiling mounted automatic nozzles to be used in unlimited volume. This document is applicable for horizontal, solid, flat ceilings with heights of 2 m and above, up to the maximum tested ceiling height.
- Standard25 pagesEnglish languagesale 10% offe-Library read for1 day
This document defines the terms and definitions that are used throughout the EN 54 series of standards. It gives the principles on which each part of the series has been based and describes the functions carried out by the components of a fire detection and fire alarm system.
This document applies to fire detection and fire alarm systems for buildings and civil engineering works.
This document does not apply to smoke alarm devices which are covered by EN 14604.
- Standard22 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the minimum requirements for secure remote services (e. g. via IP connections) to the following systems:
a) fire safety systems including, but not limited to, fire detection and fire alarm systems, fixed firefighting systems, smoke and heat control
systems,
b) security systems including, but not limited to, intruder and hold-up alarm systems, electronic access control systems, external perimeter security systems and video surveillance systems,
c) social alarm systems,
d) a combination of such systems
The scope doesn´t cover:
a) the alarm transmission infrastructure,
b) the use of remote access performed by end-users
- Standard20 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies fire testing requirements for water mist systems used for fire protection of combustion turbines in enclosures with volumes exceeding 260 m³.
- Standard21 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies fire testing requirements for water mist systems used for fire protection of combustion turbines in enclosures with volumes not exceeding 260 m³.
- Standard20 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies requirements, test methods, performance criteria and manufacturers' instructions for smoke alarms that operate using scattered light, transmitted light or ionization, and are intended for household or similar residential applications. For the testing of other types of smoke alarms, or smoke alarms working on different principles, this document is recommended only as guidance. Smoke alarms with special characteristics and developed for specific risks are not covered by this document. This document allows, although it does not require, the inclusion within the smoke alarm of facilities for the following: — visual fault condition indication; — extended temperature-range operation; — interconnection with other similar smoke alarms or accessories; — temporary disablement; — alarm silencing; — signal frequency characteristics; — standby power source low condition silence; — smoke alarms with voice; — smoke alarms using radio frequency links; — response to slowly developing fires (drift compensation). Where such facilities are included, this document specifies applicable requirements. This document does not cover devices intended for incorporation in systems using separate control and indicating equipment. Such systems are specified in the ISO 7240 series.
- Standard80 pagesEnglish languagesale 15% off
- Standard80 pagesEnglish languagesale 15% off
This document specifies the minimum requirements for the provision of secure remote services via a remote access infrastructure (RAI) carried out either at site or off-site (e.g. via IP connections) to the following systems:
a) fire safety systems including, but not limited to, fire detection and fire alarm systems, fixed firefighting systems, smoke and heat control systems;
b) security systems including, but not limited to, intruder and hold-up alarm systems, electronic access control systems, external perimeter security systems and video surveillance systems;
c) social alarm systems;
d) emergency sound systems;
e) a combination of such systems;
f) management systems connected to systems a) – e).
This document does not cover:
a) at site services without using remote connection;
b) the monitoring and alarm receiving services by the MARC, which are described in the EN 50518.
- Standard20 pagesEnglish languagesale 10% offe-Library read for1 day