This part of IEC 60079 is applicable to equipment protected by enclosure and surface
temperature limitation for use in explosive dust atmospheres. It specifies requirements for
design, construction and testing of Ex Equipment and Ex Components.
This document supplements and modifies the general requirements of IEC 60079-0. Where a
requirement of this document conflicts with a requirement of IEC 60079-0, the requirement of
this document takes precedence.
This document does not apply to dusts of explosives, which do not require atmospheric oxygen
for combustion, or to pyrophoric substances.
This document does not apply to Ex Equipment or Ex Components intended for use in
underground parts of mines as well as those parts of surface installations of such mines
endangered by firedamp and/or combustible dust.
This document does not take account of any hazard due to an emission of flammable or toxic
gas from the dust.
This document does not contain requirements for Ex Equipment used in areas where both
combustible dust and explosive gas atmospheres can occur, whether simultaneously or
separately. Requirements for explosive gas atmospheres can be found in other parts of the
IEC 60079 series. Guidance on Ex Equipment to be used where combustible dust and explosive
gas atmospheres occur simultaneously ("hybrid mixtures") can be found in IEC 60079-14.
Where the Ex Equipment has to meet other environmental conditions, for example, protection
against ingress of water and resistance to corrosion, additional measures which do not
adversely affect the integrity of the enclosure can be necessary.

  • Standard
    25 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Creating an amendment on European level to mirror the IEC interpretation sheet of IEC 60079-28:2015/ISH1:2019 which is still active at IEC.

  • Amendment
    5 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Creating an amendment on European level to mirror the IEC interpretation sheet of IEC 60079-7:2015/ISH1:2016 which is still active at IEC.

  • Amendment
    4 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Creating an amendment on European level to mirror the IEC interpretation sheet of IEC 60079-0:2017/ISH1:2019 and IEC 60079-0:2017/ISH2:2019 which are both active at IEC.

  • Amendment
    6 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Creating an amendment on European level to mirror the IEC interpretation sheet of IEC 60079-1:2014/ISH1:2020 which is still active at IEC.

  • Amendment
    4 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of the IEC 60079 series applies to users and covers only those factors directly related to the inspection and maintenance of electrical installations specifically designed for hazardous areas, where the hazard may be caused by explosive gas or explosive dust atmospheres.
It does not include:
- other fundamental installation and inspection requirements for electrical installations;
- the verification of electrical equipment;
- protection or ventilation of rooms;
- gas detection systems;
- the repair and overhaul of explosion protected equipment (see IEC 60079-19).
While this standard does not include inspection of safety devices such as used in ventilated rooms (see 60079-13), this standard does include the requirements for inspection and maintenance of individual items of equipment that will be part of such systems, for example motors or sensors.
This standard supplements the requirements for inspection and testing in non-hazardous areas in IEC 60364-6.
NOTE 1 Standards applied at the date of installation might not have been IEC standards.
This standard is intended to be applied where there can be a risk due to the presence of explosive gas or dust mixtures with air or combustible dust layers under normal atmospheric conditions. It does not apply to:
- underground mining areas,
- dusts of explosives,
- pyrophoric substances.

  • Standard
    49 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Creating an amendment on European level to mirror the IEC interpretation sheet of IEC 60079-28:2015/ISH1:2019 which is still active at IEC.

  • Amendment
    5 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Creating an amendment on European level to mirror the IEC interpretation sheet of IEC 60079-1:2014/ISH1:2020 which is still active at IEC.

  • Amendment
    4 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Creating an amendment on European level to mirror the IEC interpretation sheet of IEC 60079-7:2015/ISH1:2016 which is still active at IEC.

  • Amendment
    4 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Creating an amendment on European level to mirror the IEC interpretation sheet of IEC 60079-0:2017/ISH1:2019 and IEC 60079-0:2017/ISH2:2019 which are both active at IEC.

  • Amendment
    6 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of the IEC 60079 series applies to users and covers only those factors directly related to the inspection and maintenance of electrical installations specifically designed for hazardous areas, where the hazard may be caused by explosive gas or explosive dust atmospheres. It does not include: - other fundamental installation and inspection requirements for electrical installations; - the verification of electrical equipment; - protection or ventilation of rooms; - gas detection systems; - the repair and overhaul of explosion protected equipment (see IEC 60079-19). While this standard does not include inspection of safety devices such as used in ventilated rooms (see 60079-13), this standard does include the requirements for inspection and maintenance of individual items of equipment that will be part of such systems, for example motors or sensors. This standard supplements the requirements for inspection and testing in non-hazardous areas in IEC 60364-6. NOTE 1 Standards applied at the date of installation might not have been IEC standards. This standard is intended to be applied where there can be a risk due to the presence of explosive gas or dust mixtures with air or combustible dust layers under normal atmospheric conditions. It does not apply to: - underground mining areas, - dusts of explosives, - pyrophoric substances.

  • Standard
    49 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document will refer to UGLD for ultrasonic gas leak detectors.
This standard specifies general requirements for construction, testing and performance, and describes test methods that apply to UGLD.

  • Standard
    31 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 60079-17:2023 is available as IEC 60079-17:2023 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 60079-17:2023 applies to users and covers only those factors directly related to the inspection and maintenance of electrical installations specifically designed for hazardous areas, where the hazard is caused by explosive atmospheres.
It does not include:
- other fundamental installation and inspection requirements for electrical installations;
- the verification of electrical equipment;
- protection or ventilation of rooms;
- gas detection systems;
- the repair, overhaul and reclamation of explosion protected equipment (see IEC 60079-19).
While this document does not include inspection of safety devices such as used in ventilated rooms (see IEC 60079-13), it does include the requirements for inspection and maintenance of individual items of equipment that will be part of such systems, for example motors or sensors. This document supplements the requirements for inspection and testing in non-hazardous areas in IEC 60364-6. This document is intended to be applied where there is a risk due to the potential presence of explosive gas or dust mixtures with air or combustible dust layers under normal atmospheric conditions. It does not apply to:
- underground mining areas,
- dusts of explosives,
- pyrophoric substances.
This sixth edition cancels and replaces the fifth edition published in 2013. This edition constitutes a technical revision.

  • Standard
    144 pages
    English language
    sale 15% off
  • Standard
    95 pages
    English and French language
    sale 15% off

IEC 60079-48:2023, which is a Technical Specification, provides guidance for an owner or operator for the use of portable or personal electronic equipment to be used in hazardous areas requiring Equipment Protection Level (EPL) Gb, Gc, Db, or Dc that are not otherwise commercially available with a certificate.
This document does not apply to:
• equipment that is electrically connected to fixed equipment or fixed wiring during use in the hazardous area, for example a lead light connected to the premises wiring system by a plug and socket,
• portable or personal equipment with a certificate for use in a hazardous area,
• transportable equipment,
• portable or personal equipment used in Group I applications,
• battery powered tools, such as drills and saws,
• portable or personal equipment used in areas requiring EPL Ga or Da equipment, or,
• medical devices.
This document does not address other considerations involving the use of portable or personal electronic equipment for other aspects of safety, for example, creation of a distraction from important work tasks, radio frequency interference with measurement and control equipment, or medical issues.
This document supplements the guidance in IEC 60079-14 regarding the use of personal or portable equipment without a certificate for use in hazardous areas.

  • Technical specification
    15 pages
    English language
    sale 15% off

IEC TS 60079-44:2023, which is a Technical Specification, is to provide guidance to establish recommended minimum criteria to determine roles, establish expectations of the necessary skills and evidence of competence to assess and manage the competence of personnel conducting work in or associated with hazardous areas. The purpose of this document is to provide guidance to establish:
• recommended minimum criteria to determine roles,
• expectations of the necessary skills, and
• evidence of competence
in order to assess and manage the competence of personnel who are conducting work in or associated with hazardous areas.
This document provides examples and recommendations of minimum levels of competence for typical roles associated with hazardous areas by addressing the knowledge, skills, or abilities that is expected of personnel. Additionally, examples of the evidence of competence expected for each role are provided.
The aim of tThis document is to assist in defining, assessing, and managing unique requirements for the competence of individuals working in or associated with installations where an explosive atmosphere could be present. Such a programme could be specific to a facility or used in conjunction with other regulatory requirements where they exist. The competencies for conducting work in a hazardous area are in addition to any competencies which may apply for the general type of work being undertaken (for example, professional credentials, electrical, non-electrical, operations, design).
This document applies to both electrical and non-electrical applications.
This document identifies the minimum level of knowledge and skills required to work in hazardous areas and the specific competence required for work associated with equipment for explosive atmospheres (commonly termed ‘Ex Equipment’) and the standards to which competence is to be assessed and attributed.
The purpose of this document is to provide guidance to establish:
• recommended minimum criteria to determine roles,
• expectations of the necessary skills, and
• evidence of competence
The principal application of this specification document is for personnel dealing with explosion-protected and associated equipment for use in explosive atmospheres, including the following work functions:
• Classification of areas;
• Producing, processing or servicing functions in a hazardous area and not directly involved in installing, maintaining or repairing explosion-protected equipment and systems;
• Designing, commissioning and maintaining explosion-protection strategies and equipment;
• Selecting, installing, testing and maintaining explosion-protected equipment and systems in hazardous areas;
• Inspecting hazardous area equipment, systems and installations;
• Overhauling, repairing and modifying explosion-protected equipment;
• Management of the Ex aspects of the facility.

  • Technical specification
    29 pages
    English language
    sale 15% off

This document specifies general requirements for design, testing and performance, and describes the test methods that apply to portable, transportable and fixed equipment for the measurement of the oxygen concentration in gas mixtures indicating up to 25 % (v/v).

  • Amendment
    5 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 60079-11:2023 specifies the construction and testing of intrinsically safe apparatus intended for use in explosive atmospheres, and for associated apparatus which is intended for connection to intrinsically safe circuits which enter such atmospheres.
This Type of Protection is applicable to electrical equipment in which the electrical circuits themselves are incapable of causing ignition of a surrounding explosive atmosphere. This includes electrical equipment which contains circuits that are intrinsically safe only under certain conditions, for example under battery supply with mains supply removed.
This document is also applicable to electrical equipment or parts of electrical equipment located outside the explosive atmosphere or protected by another Type of Protection listed in IEC 60079 0, where the intrinsic safety of the electrical circuits in the explosive atmosphere may depend upon the design and construction of such electrical equipment or parts of such electrical equipment. The electrical circuits exposed to the explosive atmosphere are assessed for use in such atmospheres by applying this document.
This document applies to sensors connected to intrinsically safe circuits but does not apply to the protection of catalytic elements for Group IIC or Group IIB + H2.
This document does not apply to Ex Equipment cable glands.
The requirements for intrinsically safe systems are provided in IEC 60079-25.
This document supplements and modifies the general requirements of IEC 60079-0, except as indicated in Table 1. Where a requirement of this document conflicts with a requirement of IEC 60079-0, the requirement of this document takes precedence.
Unless otherwise stated, the requirements in this document are applicable to both intrinsically safe apparatus and associated apparatus, and the generic term "apparatus" is used throughout the standard.
As this document applies only to electrical equipment, the term "equipment" used in the standard always means "electrical equipment".
This document applies to apparatus for use under the atmospheric conditions of IEC 60079 0 with additional requirements for use at extended atmospheric pressures in the range from 60 kPa (0,6 bar), up to 110 kPa (1,1 bar).
This seventh edition cancels and replaces the sixth edition published in 2011. This edition constitutes a technical revision.
The identification and significance of the changes between IEC 60079-11, Edition 7 (2022) and IEC 60079-11, Edition 6 (2011 + Corrigendum 1 (2012)) can be found in the table of changes in the foreword of the publication.
The contents of the corrigendum of June 2023 and Interpretation sheet 1 and 2 of May 2024 have been included in this copy.

  • Standard
    209 pages
    English language
    sale 15% off
  • Standard
    433 pages
    English and French language
    sale 15% off

This part of IEC 62990 specifies general requirements for design, function and performance, and describes the test methods that apply to portable, transportable, and fixed equipment for the detection and concentration measurement of toxic gases and vapours in workplace atmospheres and other industrial and commercial applications. This document is applicable to continuously sensing equipment whose primary purpose is to provide an indication, alarm and/or other output function the purpose of which is to indicate the presence of a toxic gas or vapour in the atmosphere and in some cases to initiate automatic or manual protective action(s). It is applicable to equipment in which the sensor generates an electrical signal when gas is present.
This document applies to two types of equipment:
• Type HM (Health Monitoring) ‘occupational exposure’ equipment: For occupational exposure measurement, the performance requirements are focused on uncertainty of measurement of gas concentrations in the region of Occupational Exposure Limit Values (OELV). The upper limit of measurement will be defined by the manufacturer in accordance with 4.2.1.
• Type SM (Safety Monitoring) ‘general gas detection’ equipment: For general gas detection applications (e.g. safety warning, leak detection), the performance requirements are focused on alarm signalling. The upper limit of measurement will be defined by the manufacturer according to the intended use of the equipment. In general, the requirements for accuracy will be higher for Type HM equipment than for Type SM equipment. The same equipment may meet the requirements of both Type HM and Type SM. For equipment used for sensing the presence of multiple gases this document applies only to the detection of toxic gas or vapour.
This document is not applicable to equipment:
- with samplers and concentrators such as sorbents or paper tape having an irreversible indication;
- used for the measurement of gases and vapours related to the risk of explosion;
- used for the measurement of oxygen; – used only in laboratories for analysis or measurement;
- used only for process measurement purposes;
- used in the domestic environment;
- used in environmental air pollution monitoring;
- used for open-path (line of sight) area gas measurement;
- used for ventilation control in car parks or tunnels.

  • Amendment
    6 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 60079-19:2019 gives instructions, principally of a technical nature, on the repair, overhaul, reclamation and modification of equipment designed for use in explosive atmospheres; it is not applicable to maintenance, other than when repair and overhaul cannot be disassociated from maintenance, neither does it give advice on cable entry systems which may require a renewal when the equipment is re-installed. This fourth edition cancels and replaces the third edition published in 2010 together with Amendment 1:2015. This edition constitutes a technical revision. The significance of the changes between IEC 60079-19, Edition 3 (2010), including Amendment 1 (2015), and IEC 60079-19, Edition 4 (2019) are defined in the foreword and cover minor and editorial changes, extension, and major technical changes.

  • Standard
    85 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of IEC 62990 specifies general requirements for design, function and performance, and describes the test methods that apply to portable, transportable, and fixed equipment for the detection and concentration measurement of toxic gases and vapours in workplace atmospheres and other industrial and commercial applications. This document is applicable to continuously sensing equipment whose primary purpose is to provide an indication, alarm and/or other output function the purpose of which is to indicate the presence of a toxic gas or vapour in the atmosphere and in some cases to initiate automatic or manual protective action(s). It is applicable to equipment in which the sensor generates an electrical signal when gas is present. This document applies to two types of equipment: - Type HM (Health Monitoring) ‘occupational exposure’ equipment: For occupational exposure measurement, the performance requirements are focused on uncertainty of measurement of gas concentrations in the region of Occupational Exposure Limit Values (OELV). The upper limit of measurement will be defined by the manufacturer in accordance with 4.2.1. - Type SM (Safety Monitoring) ‘general gas detection’ equipment: For general gas detection applications (e.g. safety warning, leak detection), the performance requirements are focused on alarm signalling. The upper limit of measurement will be defined by the manufacturer according to the intended use of the equipment. In general, the requirements for accuracy will be higher for Type HM equipment than for Type SM equipment. The same equipment may meet the requirements of both Type HM and Type SM. For equipment used for sensing the presence of multiple gases this document applies only to the detection of toxic gas or vapour. This document is not applicable to equipment: - with samplers and concentrators such as sorbents or paper tape having an irreversible indication; - used for the measurement of gases and vapours related to the risk of explosion; - used for the measurement of oxygen; – used only in laboratories for analysis or measurement; - used only for process measurement purposes; - used in the domestic environment; - used in environmental air pollution monitoring; - used for open-path (line of sight) area gas measurement; - used for ventilation control in car parks or tunnels.

  • Standard
    64 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of IEC 62990 specifies general requirements for design, function and performance, and describes the test methods that apply to portable, transportable, and fixed equipment for the detection and concentration measurement of toxic gases and vapours in workplace atmospheres and other industrial and commercial applications. This document is applicable to continuously sensing equipment whose primary purpose is to provide an indication, alarm and/or other output function the purpose of which is to indicate the presence of a toxic gas or vapour in the atmosphere and in some cases to initiate automatic or manual protective action(s). It is applicable to equipment in which the sensor generates an electrical signal when gas is present. This document applies to two types of equipment: • Type HM (Health Monitoring) ‘occupational exposure’ equipment: For occupational exposure measurement, the performance requirements are focused on uncertainty of measurement of gas concentrations in the region of Occupational Exposure Limit Values (OELV). The upper limit of measurement will be defined by the manufacturer in accordance with 4.2.1. • Type SM (Safety Monitoring) ‘general gas detection’ equipment: For general gas detection applications (e.g. safety warning, leak detection), the performance requirements are focused on alarm signalling. The upper limit of measurement will be defined by the manufacturer according to the intended use of the equipment. In general, the requirements for accuracy will be higher for Type HM equipment than for Type SM equipment. The same equipment may meet the requirements of both Type HM and Type SM. For equipment used for sensing the presence of multiple gases this document applies only to the detection of toxic gas or vapour. This document is not applicable to equipment: - with samplers and concentrators such as sorbents or paper tape having an irreversible indication; - used for the measurement of gases and vapours related to the risk of explosion; - used for the measurement of oxygen; – used only in laboratories for analysis or measurement; - used only for process measurement purposes; - used in the domestic environment; - used in environmental air pollution monitoring; - used for open-path (line of sight) area gas measurement; - used for ventilation control in car parks or tunnels.

  • Amendment
    6 pages
    English language
    sale 10% off
    e-Library read for
    1 day

NEXT ACTION: TB ACTION BY 2020-01-31 (prep doc for BT meeting - Feb2021)
BT CONSULTATION FAILED (addition of Annex ZZ) ON 2020-11-10
HAS CONSULTANT ASSESSMENT BY 2020-09-24 (PUB assessment) - Compliant assessment on 2020-09-22
2020-04-8 mah: Consultant assessment at FV missing, Annex ZZ did not go to FV.

  • Amendment
    8 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of IEC 60079 contains the specific requirements for design, construction and
assessment of intrinsically safe systems, Type of Protection “i”, intended for use, as a whole or
in part, in locations in which the use of Group I, II or III Ex Equipment is required.
NOTE 1 This standard is intended for use by the designer of the system e.g. a person who could be a manufacturer,
a specialist consultant or a member of the end-user’s staff.
This document supplements and modifies the general requirements of IEC 60079-0 and the
intrinsic safety standard IEC 60079-11. Where a requirement of this standard conflicts with a
requirement of IEC 60079-0 or IEC 60079-11, the requirement of this standard takes
precedence.
The installation requirements of Group II or Group III systems designed in accordance with this
standard are specified in IEC 60079-14.
NOTE 2 Group I installation requirements are presently not provided in IEC 60079-14. Installation requirements for
Group I are being considered.

  • Standard
    64 pages
    English language
    sale 10% off
    e-Library read for
    1 day

EN 60079-29-1 specifies general requirements for construction, testing and performance, and describes the test methods that apply to portable, transportable and fixed equipment for the detection and measurement of flammable gas or vapour concentrations with air. The equipment, or parts thereof, is intended for use in explosive atmospheres and in mines susceptible to firedamp.
EN 60079-29-1 is applicable to flammable gas detection equipment with a measuring range up to any volume fraction as declared by the manufacturer, and which is intended to provide an indication, alarm or other output function; the purpose of which is to indicate a potential explosion hazard and in some cases, to initiate automatic or manual protective action(s).

  • Amendment
    5 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 60079-25:2020 contains the specific requirements for design, construction and assessment of intrinsically safe systems, Type of Protection “i”, intended for use, as a whole or in part, in locations in which the use of Group I, II or III Ex Equipment is required. This document supplements and modifies the general requirements of IEC 60079-0 and the intrinsic safety standard IEC 60079-11. Where a requirement of this standard conflicts with a requirement of IEC 60079-0 or IEC 60079-11, the requirement of this standard takes precedence. The installation requirements of Group II or Group III systems designed in accordance with this standard are specified in IEC 60079-14. This third edition cancels and replaces the second edition published in 2010 and constitutes a technical revision.

  • Standard
    64 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 60079-31:2022 is available as IEC 60079-31:2022 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 60079-31:2022 is applicable to equipment protected by enclosure and surface temperature limitation for use in explosive dust atmospheres. It specifies requirements for design, construction and testing of Ex Equipment and Ex Components. This document supplements and modifies the general requirements of IEC 60079-0. Where a requirement of this document conflicts with a requirement of IEC 60079-0, the requirement of this document takes precedence. This document does not apply to dusts of explosives, which do not require atmospheric oxygen for combustion, or to pyrophoric substances. This document does not apply to Ex Equipment or Ex Components intended for use in underground parts of mines as well as those parts of surface installations of such mines endangered by firedamp and/or combustible dust. This document does not take account of any risk due to an emission of flammable or toxic gas from the dust. This third edition cancels and replaces the second edition published in 2013. This edition constitutes a technical revision. Main significant changes from the previous edition are: 1) Document has been restructured from edition 2 2) Fault current rating of interrupting contacts in clauses 4.3.1 and 4.4.1, major change type C1 3) Cells and batteries in clauses 4.3.5.1 and 4.4.5.1, major change type C2 4) Overload or malfunction condition for the determination of temperature class for "tb" converter fed rotating electric machines, major change type C3 5) Additional requirements for entry devices with dust ignition protection by enclosure "t", major change type C4 Information about the background of ‘Major Technical Changes’ C1 – Ex Equipment having Level of Protection "ta" shall be rated for connection to a circuit with a prospective short circuit current of not greater than 1.5 kA. For Ex Equipment having Level of Protection "tb" or "tc" which is intended for mains connection and intended to interrupt fault current above 10kA, the equipment shall have a rated maximum short circuit withstand current, be tested according to 6.1.1.1, and be marked according to Clause 7. C2 – For Ex Equipment having Level of Protection "ta" which contains a cell or battery, only a sealed cell or battery shall be used. For Ex Equipment having Level of Protection "tb" and "tc" where there are sparking contacts or hot surfaces, and which contains a cell or battery, only a sealed cell or battery shall be used. C3 – Table 2 now includes malfunction conditions for temperature class determination of Level of Protection "tb" converter-fed electric machines. C4 – Annex A added for entry devices with Type of Protection "t" including cable transit devices.

  • Standard
    25 pages
    English language
    sale 10% off
    e-Library read for
    1 day

NEXT ACTION: TB ACTION BY 2020-01-31 (prep doc for BT meeting - Feb2021)
BT CONSULTATION FAILED (addition of Annex ZZ) ON 2020-11-10
HAS CONSULTANT ASSESSMENT BY 2020-09-24 (PUB assessment) - Compliant assessment on 2020-09-22
2020-04-8 mah: Consultant assessment at FV missing, Annex ZZ did not go to FV.

  • Amendment
    8 pages
    English language
    sale 10% off
    e-Library read for
    1 day

EN 60079-29-1 specifies general requirements for construction, testing and performance, and describes the test methods that apply to portable, transportable and fixed equipment for the detection and measurement of flammable gas or vapour concentrations with air. The equipment, or parts thereof, is intended for use in explosive atmospheres and in mines susceptible to firedamp. EN 60079-29-1 is applicable to flammable gas detection equipment with a measuring range up to any volume fraction as declared by the manufacturer, and which is intended to provide an indication, alarm or other output function; the purpose of which is to indicate a potential explosion hazard and in some cases, to initiate automatic or manual protective action(s).

  • Amendment
    5 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Standard
    3 pages
    English language
    sale 15% off
  • Standard
    5 pages
    English and French language
    sale 15% off

ISO/IEC 80079-20-1:2017 is published as a dual log standard and provides guidance on classification of gases and vapours. It describes a test method intended for the measurement of the maximum experimental safe gaps (MESG) for gas-air mixtures or vapour-air mixtures under normal conditions of temperature and pressure (20 °C, 101,3 kPa) so as to permit the selection of an appropriate group of equipment. This document also describes a test method intended for use in the determination of the auto-ignition temperature (AIT) of a vapour-air mixture or gas-air mixture at atmospheric pressure, so as to permit the selection of an appropriate temperature class of equipment. Values of chemical properties of materials are provided to assist in the selection of equipment to be used in hazardous areas. Further data may be added as the results of validated tests become available. The materials and the characteristics included in a table (see Annex B) have been selected with particular reference to the use of equipment in hazardous areas. The data in this document have been taken from a number of references which are given in the bibliography. These methods for determining the MESG or the AIT may also be used for gas-air-inert mixtures or vapour-air-inert mixtures. However, data on air-inert mixtures are not tabulated.
Keywords: classification of gases and vapours, measurement of the maximum experimental safe gaps (MESG)

  • Standard
    93 pages
    English language
    sale 10% off
    e-Library read for
    1 day

NEW!IEC 60079-15:2017 is available as IEC 60079-15:2017 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 60079-15:2017 specifies requirements for the construction, testing and marking for Group II electrical equipment with type of protection “n” which includes; sealed devices “nC”, hermetically sealed devices “nC”, non-incendive components “nC” and restricted breathing enclosures “nR” intended for use in explosive gas atmospheres. This part of IEC 60079 applies to electrical equipment where the rated input voltage does not exceed 15 kV r.m.s. AC or DC including where the internal working voltages of the Ex product exceeds 15 kV, for example starters for HID luminaires. This part of IEC 60079 supplements and modifies the general requirements of IEC 60079-0, except as indicated in Table 1 (Clause 1). Where a requirement of this part of IEC 60079 conflicts with a requirement of IEC 60079-0, the requirement of this part of IEC 60079 takes precedence. This fifth edition cancels and replaces the fourth edition, published in 2010, and constitutes a technical revision. Refer to the Forward of the document for a complete listing of the technical changes between edition 5.0 and the previous edition of the document. Keywords: Group II electrical equipment with type of protection “n”

  • Standard
    36 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 60050-426:2020 gives terms specifically relevant to explosive atmospheres. This new edition reviews and complements the previous one. This terminology is consistent with the terminology developed in the other specialized parts of the IEV.
It has the status of a horizontal standard in accordance with IEC Guide 108.

  • Standard
    443 pages
    English and French language
    sale 10% off
    e-Library read for
    1 day
  • Standard
    430 pages
    English and French language
    sale 15% off

IEC 60079-31:2022 is available as IEC 60079-31:2022 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.
IEC 60079-31:2022 is applicable to equipment protected by enclosure and surface temperature limitation for use in explosive dust atmospheres. It specifies requirements for design, construction and testing of Ex Equipment and Ex Components. This document supplements and modifies the general requirements of IEC 60079-0. Where a requirement of this document conflicts with a requirement of IEC 60079-0, the requirement of this document takes precedence. This document does not apply to dusts of explosives, which do not require atmospheric oxygen for combustion, or to pyrophoric substances. This document does not apply to Ex Equipment or Ex Components intended for use in underground parts of mines as well as those parts of surface installations of such mines endangered by firedamp and/or combustible dust. This document does not take account of any risk due to an emission of flammable or toxic gas from the dust. This third edition cancels and replaces the second edition published in 2013. This edition constitutes a technical revision. Main significant changes from the previous edition are:
1) Document has been restructured from edition 2
2) Fault current rating of interrupting contacts in clauses 4.3.1 and 4.4.1, major change type C1
3) Cells and batteries in clauses 4.3.5.1 and 4.4.5.1, major change type C2
4) Overload or malfunction condition for the determination of temperature class for "tb" converter fed rotating electric machines, major change type C3
5) Additional requirements for entry devices with dust ignition protection by enclosure "t", major change type C4
Information about the background of ‘Major Technical Changes’
C1 – Ex Equipment having Level of Protection "ta" shall be rated for connection to a circuit with a prospective short circuit current of not greater than 1.5 kA. For Ex Equipment having Level of Protection "tb" or "tc" which is intended for mains connection and intended to interrupt fault current above 10kA, the equipment shall have a rated maximum short circuit withstand current, be tested according to 6.1.1.1, and be marked according to Clause 7.
C2 – For Ex Equipment having Level of Protection "ta" which contains a cell or battery, only a sealed cell or battery shall be used. For Ex Equipment having Level of Protection "tb" and "tc" where there are sparking contacts or hot surfaces, and which contains a cell or battery, only a sealed cell or battery shall be used.
C3 – Table 2 now includes malfunction conditions for temperature class determination of Level of Protection "tb" converter-fed electric machines.
C4 – Annex A added for entry devices with Type of Protection "t" including cable transit devices.
The contents of the corrigendum of October 2023 have been included in this copy.

  • Standard
    61 pages
    English language
    sale 15% off
  • Standard
    39 pages
    English and French language
    sale 15% off

This part of IEC 60079, which is a technical specification, specifies requirements for the construction, marking, and documenting of apparatus, systems and installations for use with the 2-Wire Intrinsically Safe Ethernet concept (2-WISE). The physical layer specification for 2-wire Ethernet 10BASE-T1L is defined in IEEE 802.3cg
2-WISE is the 2-Wire Intrinsically Safe Ethernet concept for advance physical layer (APL), designed to simplify the examination process for components and cable Entity Parameters within APL segments. This is achieved by defining universal Entity Parameter limits for APL ports, according to location and type of hazardous atmosphere, and listing a concise set of rules for the segment setup.
The requirements for construction and installation of 2-WISE apparatus and systems are included in IEC 60079-11, IEC 60079-14, and IEC 60079-25, except as modified by this technical specification. Parts of a 2-WISE apparatus may be protected by any Type of Protection listed in IEC 60079-0 appropriate to the EPL for the intended use. In these circumstances, the requirements of this technical specification apply only to intrinsically safe circuits of the apparatus.

  • Technical specification
    17 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 62990-2:2021 gives guidance on the selection, installation, use and maintenance of electrical equipment used for the measurement of toxic gases and vapours in workplace atmospheres. The primary purpose of such equipment is to ensure safety of personnel and property by providing an indication of the concentration of a toxic gas or vapour and warning of its presence. This document is applicable to equipment whose purpose is to provide an indication, alarm or other output function to give a warning of the presence of a toxic gas or vapour in the atmosphere and in some cases to initiate automatic or manual protective actions. It is applicable to equipment in which the sensor automatically generates an electrical signal when gas is present. For the purposes of this document, equipment includes: a) fixed equipment; b) transportable equipment, and c) portable equipment. This document is intended to cover equipment defined within IEC 62990-1, but can provide useful information for equipment not covered by that document.

  • Standard
    65 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of IEC 60079, which is a technical specification, specifies requirements for the construction, marking, and documenting of apparatus, systems and installations for use with the 2-Wire Intrinsically Safe Ethernet concept (2-WISE). The physical layer specification for 2-wire Ethernet 10BASE-T1L is defined in IEEE 802.3cg 2-WISE is the 2-Wire Intrinsically Safe Ethernet concept for advance physical layer (APL), designed to simplify the examination process for components and cable Entity Parameters within APL segments. This is achieved by defining universal Entity Parameter limits for APL ports, according to location and type of hazardous atmosphere, and listing a concise set of rules for the segment setup. The requirements for construction and installation of 2-WISE apparatus and systems are included in IEC 60079-11, IEC 60079-14, and IEC 60079-25, except as modified by this technical specification. Parts of a 2-WISE apparatus may be protected by any Type of Protection listed in IEC 60079-0 appropriate to the EPL for the intended use. In these circumstances, the requirements of this technical specification apply only to intrinsically safe circuits of the apparatus.

  • Technical specification
    17 pages
    English language
    sale 10% off
    e-Library read for
    1 day

NEW!IEC 60079-0:2017 is available as IEC 60079-0:2017 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 60079-0:2017 specifies the general requirements for construction, testing and marking of Ex Equipment and Ex Components intended for use in explosive atmospheres. The standard atmospheric conditions (relating to the explosion characteristics of the atmosphere) under which it may be assumed that Ex Equipment can be operated are: -temperature –20 °C to +60 °C; -pressure 80 kPa (0,8 bar) to 110 kPa (1,1 bar); and -air with normal oxygen content, typically 21 % v/v. This part of IEC 60079 and other standards supplementing this standard specify additional test requirements for Ex Equipment operating outside the standard temperature range, but further additional consideration and additional testing may be required for Ex Equipment operating outside the standard atmospheric pressure range and standard oxygen content. Such additional testing may be particularly relevant with respect to Types of Protection that depend on quenching of a flame such as ‘flameproof enclosures “d”’ (IEC 60079-1) or limitation of energy, ‘intrinsic safety “i”’ (IEC 60079-11). This seventh edition cancels and replaces the sixth edition, published in 2011. This edition constitutes a technical revision. Refer to the Forward of the document for a complete listing of the technical changes between edition 7.0 and the previous edition of the document. Keywords: Ex Equipment and Ex Components intended for use in explosive atmospheres

  • Standard
    148 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Standard
    148 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 62990-2:2021 gives guidance on the selection, installation, use and maintenance of electrical equipment used for the measurement of toxic gases and vapours in workplace atmospheres. The primary purpose of such equipment is to ensure safety of personnel and property by providing an indication of the concentration of a toxic gas or vapour and warning of its presence.
This document is applicable to equipment whose purpose is to provide an indication, alarm or other output function to give a warning of the presence of a toxic gas or vapour in the atmosphere and in some cases to initiate automatic or manual protective actions. It is applicable to equipment in which the sensor automatically generates an electrical signal when gas is present.
For the purposes of this document, equipment includes:
a) fixed equipment;
b) transportable equipment, and
c) portable equipment.
This document is intended to cover equipment defined within IEC 62990-1, but can provide useful information for equipment not covered by that document.