Standard Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) Pipe and Fittings for Chemical Waste Drainage Systems

SCOPE
1.1 This specification covers the performance requirements of CPVC pipe, fittings and solvent cements used in chemical waste drainage systems.  
1.2 A system is made up of pipe, fittings and solvent cement that meet the requirements of this standard.
Note 1—Consult the manufacturer’s chemical resistance recommendations for chemical waste drainage applications prior to use.
1.3 The text of this specification references notes, footnotes and appendices that provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the specification.
1.4 The pressure tests described in this standard are laboratory hydrostatic tests that are intended to verify joint/system integrity. They are not intended for use as field tests of installed systems.  
1.5 Due to inherent hazards associated with testing components and systems with compressed air or other compressed gases, no such testing shall be done unless the component manufacturer gives approval in writing.
Note 2—Pressurized (compressed) air or other compressed gases contain large amounts of stored energy, which present serious safety hazards should a system fail for any reason.
1.6 Mechanical joints used for joining pipe and fittings of different materials are provided for in this specification. They include common flanges, couplings, and unions.  
1.7 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
Note 3—This specification specifies dimensional, performance, and test requirements for fluid handling applications but does not address venting of combustion gases.

General Information

Status
Historical
Publication Date
31-Mar-2009
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM F2618-09 - Standard Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) Pipe and Fittings for Chemical Waste Drainage Systems
English language
7 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:F2618 −09 AnAmerican National Standard
Standard Specification for
Chlorinated Poly (Vinyl Chloride) (CPVC) Pipe and Fittings
for Chemical Waste Drainage Systems
This standard is issued under the fixed designation F2618; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope priate safety and health practices and determine the applica-
bility of regulatory limitations prior to use.
1.1 This specification covers the performance requirements
of CPVC pipe, fittings and solvent cements used in chemical
NOTE 3—This specification specifies dimensional, performance, and
test requirements for fluid handling applications but does not address
waste drainage systems.
venting of combustion gases.
1.2 Asystem is made up of pipe, fittings and solvent cement
that meet the requirements of this standard.
2. Referenced Documents
NOTE 1—Consult the manufacturer’s chemical resistance recommenda-
2.1 ASTM Standards:
tions for chemical waste drainage applications prior to use.
D543 Practices for Evaluating the Resistance of Plastics to
1.3 The text of this specification references notes, footnotes Chemical Reagents
and appendices that provide explanatory material. These notes
D618 Practice for Conditioning Plastics for Testing
and footnotes (excluding those in tables and figures) shall not D1600 TerminologyforAbbreviatedTermsRelatingtoPlas-
be considered as requirements of the specification.
tics
D1784 Specification for Rigid Poly(Vinyl Chloride) (PVC)
1.4 The pressure tests described in this standard are labora-
Compounds and Chlorinated Poly(Vinyl Chloride)
tory hydrostatic tests that are intended to verify joint/system
(CPVC) Compounds
integrity.Theyarenotintendedforuseasfieldtestsofinstalled
D2122 Test Method for Determining Dimensions of Ther-
systems.
moplastic Pipe and Fittings
1.5 Due to inherent hazards associated with testing compo-
D2321 PracticeforUndergroundInstallationofThermoplas-
nents and systems with compressed air or other compressed
tic Pipe for Sewers and Other Gravity-Flow Applications
gases, no such testing shall be done unless the component
D2412 Test Method for Determination of External Loading
manufacturer gives approval in writing.
Characteristics of Plastic Pipe by Parallel-Plate Loading
D2444 Test Method for Determination of the Impact Resis-
NOTE 2—Pressurized (compressed) air or other compressed gases
contain large amounts of stored energy, which present serious safety
tance of Thermoplastic Pipe and Fittings by Means of a
hazards should a system fail for any reason.
Tup (Falling Weight)
1.6 Mechanical joints used for joining pipe and fittings of D3311 Specification for Drain, Waste, and Vent (DWV)
different materials are provided for in this specification. They Plastic Fittings Patterns
include common flanges, couplings, and unions. F402 Practice for Safe Handling of Solvent Cements,
Primers, and Cleaners Used for Joining Thermoplastic
1.7 The values stated in inch-pound units are to be regarded
Pipe and Fittings
as standard. The values given in parentheses are mathematical
F412 Terminology Relating to Plastic Piping Systems
conversions to SI units that are provided for information only
F493 Specification for Solvent Cements for Chlorinated
and are not considered standard.
Poly(Vinyl Chloride) (CPVC) Plastic Pipe and Fittings
1.8 This standard does not purport to address all of the
F1498 Specification forTaper PipeThreads 60° forThermo-
safety concerns, if any, associated with its use. It is the
plastic Pipe and Fittings
responsibility of the user of this standard to establish appro-
1 2
This specification is under the jurisdiction ofASTM Committee F17 on Plastic For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Piping Systems and is the direct responsibility of Subcommittee F17.63 on DWV. contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Current edition approved April 1, 2009. Published June 2009. DOI: 10.1520/ Standards volume information, refer to the standard’s Document Summary page on
F2618-09. the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
F2618−09
F2135 Specification for Molded Drain, Waste, and Vent 4.2.2 CPVC materials shall be permitted to contain stabiliz-
(DWV) Short-Pattern Plastic Fittings ers, lubricants, and pigments not detrimental to pipe and
2.2 Other Documents: fittings provided that the final compound, and the pipe and
International Plumbing Code fittings produced, meet the requirements of this specification.
Uniform Plumbing Code 4.2.3 Rework Material—Clean rework material generated
Federal Standard 123 Marking for Shipment (CivilianAgen- from the manufacturer’s own pipe or fittings may be used
cies) providedthepipeorfittingsproducedmeettherequirementsof
Federal Standard 129 Military Marking for Shipment and this specification.
Storage 4.2.4 All thread sealants, gaskets, and seal rings shall be of
a material that meets the chemical resistance for the end use
3. Terminology
application.
3.1 Definitions:
5. General Requirements for Solvent Cement
3.1.1 Definitions used in this specification are in accordance
with the definitions given in Terminology F412, and abbrevia-
5.1 The solvent cement shall meet the general requirements
tions are in accordance with Terminology D1600, unless
of standard F493 and be classified as heavy-bodied, having a
otherwise indicated.
minimum viscosity of 1600 cP (1600 MPa-s).
3.1.2 The plumbing terminology used in this specification is
5.2 The cement shall not contain any inorganic fillers.
in accordance with the definitions given in the International
5.3 CPVC solvent cement meeting the requirements of this
Plumbing Code and the Uniform Plumbing Code, unless
standard shall be mustard in color to facilitate identification
otherwise indicated.
and minimize unintentional use of other cements that may fail
4. Requirements
at elevated service temperatures.
4.1 The requirements in this section are intended only for
NOTE 5—Safe handling of solvent cements: Solvent cements for plastic
use as quality control tests, not as simulated service tests.
pipe are made from flammable liquids. Keep them away from all sources
of ignition. Maintain proper ventilation to reduce fire hazard and to
4.1.1 All pipe and fittings shall be homogeneous throughout
minimize breathing of solvent vapors. Avoid contact of cement with skin
and be free of visible cracks, holes, foreign inclusions, or other
and eyes. Refer to Practice F402 for information on safe handling of
injurious defects. The pipe and fittings shall be as uniform as
solvent cements.
commercially practicable in color, opacity, density and other
physical properties.
6. Dimensions and Tolerances
4.1.2 Pipe and fittings shall be joined by the use of solvent
6.1 The patterns, dimensions, and laying lengths of molded
cement, threading, or mechanical joints meeting the require-
fittings, including adaptors, shall meet the requirements of
ments of this standard and as recommended by the manufac-
Specifications D3311 or F2135 or shall be of a proven design
turer.
and shall allow a smooth transition of flow from one direction
4.1.3 All dimensions shall be determined in accordance
to another. Specialty fittings or fittings with laying lengths not
with Test Method D2122.
meeting the requirements of Specification D3311 or Specifica-
4.1.4 All components within a system shall meet the speci-
tion F2135 shall not be excluded. For these fittings, laying
fications of this standard.
lengths shall be provided by the manufacturer.
4.1.5 CPVC Solvent Cement—The CPVC solvent cement
used to join the pipe and fittings covered under this specifica- NOTE 6—ASTM International takes no position respecting the validity
ofanypatentrightsassertedinconnectionwithanyitemmentionedinthis
tion shall comply with Section 5 and 9.4. Consult the pipe and
standard. Users of this standard are expressly advised that determination
fitting manufacturer to determine whether or not a primer is
of the validity of any such patent rights, and the risk of infringement of
required.
such rights, are entirely their own responsibility.
NOTE 4—At lower temperatures (< 40°F, or < 4°C) and for larger
6.1.1 The outside diameter and wall thickness of pipe shall
diameters of pipe and fittings (>6 in. in diameter), a primer may be
meet the requirements of Table 1 and Table 2.
recommended by the manufacturer.
6.1.2 Fitting sockets shall conform to the dimensional
4.1.6 Mechanical fittings shall meet the requirements of
requirements as specified in Table 3.
7.4.
6.1.3 The spigot dimensions of fittings shall meet the
requirements of Table 1 and Table 2.
4.2 Materials:
4.2.1 CPVC Material—All pipe and fittings shall be made
6.2 Cleanouts—Cleanout plugs, and caps, as commonly
CPVC compounds meeting or exceeding the requirements of
used in the manufacturer’s laboratory drainage system, shall
cell classification 23447 as defined in Specification D1784.
have a thread size and depth sufficient to ensure that the
Available from International Code Council (ICC), 500 New Jersey Ave., NW,
6th Floor, Washington, DC 20001-2070, http://www.iccsafe.org. Molded fittings meeting the requirements of Specification D3311 made from
Available from International Association of Plumbing and Mechanical Offi- CPVC and used for piping that handles corrosive waste are covered by a patent.
cials, 5001 E. Philadelphia St., Ontario, CA 91761, http://www.iapmo.org. Interested parties are invited to submit information regarding the identification of an
Available from Standardization Documents Order Desk, DODSSP, Bldg. 4, alternative(s) to this patented item to the ASTM International Headquarters. Your
Section D, 700 Robbins Ave., Philadelphia, PA 19111-5098, http:// comments will receive careful consideration at a meeting of the responsible
www.dodssp.daps.mil. technical committee, which you may attend.
F2618−09
TABLE 1 Outside Diameters and Tolerances for Pipe and Spigot
7.6 CPVC Compound Chemical Resistance—CPVC com-
Ends, in. (mm)
pounds used to produce pipe or fittings to this standard shall
Nominal Average Tolerance Out-of-Roundness
meet the requirements of 8.2.
Pipe Size Outside [maximum minus minimum]
Diameter
NOTE 7—Before installing a CPVC chemical waste piping system,
1 ⁄4 1.660 ± 0.005 0.024
chemical resistance data for the piping in question should be evaluated.
(42.2) (±0.13) (0.61)
Cautionshouldbetakenwhenmixingchemicalsaspropertiescanchange.
1 ⁄2 1.900 ± 0.006 0.024
If there is a chemical resistance question, consult the manufacturer(s).
(48.3) (±0.15) (0.61)
2 2.375 ± 0.006 0.024
(60.3) (±0.15) (0.61)
8. Test Methods
3 3.500 ± 0.008 0.030
(88.9) (±0.20) (0.76)
8.1 Conditioning:
4 4.500 ± 0.009 0.100
(114.3) (±0.23) (2.54) 8.1.1 Forroutinequalitycontroltesting,conditionthespeci-
6 6.625 ±0.011 0.100
mens at the room temperature and humidity of the manufac-
(168.3) (±0.28) (2.54)
turers testing facilities for not less than one hour or until the
8 8.625 ± 0.015 0.150
specimens reach room temperature.
(219.1) (±0.38) (3.81)
10 10.750 ± 0.015 0.150
8.1.2 Forrefereepurposes,conditionandtestthespecimens
(273.1) (±0.38) (3.81)
before testing, in a standard laboratory atmosphere of 73.4 6
12 12.750 ± 0.015 0.150
(323.9) (±0.38) (3.81)
3.6°F (23 6 2°C) and 50 6 5% relative humidity for not less
than 40 hours prior to testing in accordance with Procedure A
of Practice D618.
TABLE 2 Wall Thickness and Tolerances for Pipe and Fitting
Spigot Ends, in. (mm)
8.2 CPVC Compound Chemical Resistance—Pipe and fit-
ting materials shall be evaluated in accordance with Test
Nominal Pipe Size Minimum Tolerance
1 ⁄4 0.140 (3.56) +0.020 (+0.51) – 0.000
Method D543 practice A, procedures I and II, using the
1 ⁄2 0.145 (3.68) +0.020 (+0.51) –0.000
chemicalslistedinTable4.Weightchangeshallnotexceed2%
2 0.154 (3.91) +0.020 (+0.51) –0.000
3 0.216 (5.49) +0.026 (+0.66) –0.000 nor shall apparent tensile strength change by more than 10 %.
4 0.237 (6.02) +0.028 (+0.71) –0.000
Incaseswherethereisachangeintheapparenttensilestrength
6 0.280 (7.11) +0.034 (+0.86) – 0.000
greater than 10%, a further evaluation shall be made after the
8 0.322 (8.18) +0.039 (+0.99) – 0.000
10 0.365 (9.27) +0.044 (+1.12) –0.000 test specimen is removed from the chemical and conditioned
12 0.406 (10.31) +0.049 ( +1.24) –0.000
for 72 h. If after 72 h, there is a minimum of 50% recovery of
tensile strength as compared to the unexposed specimen, and
thatfigureiswithin 610%oftheoriginaltensilestrengthofthe
minimum waterway dimensions are maintained. All CPVC
unexposed specimen, the test shall be considered acceptable.
cleanouts having female threads shall be supplied with CPVC
plugs. 8.3 Solvent Cement Joint Chemical Resistance Integrity
Test—Prepare ten pipe test specimens, each having two sec-
6.3 Traps—All traps shall have a minimum water seal of 2
tions of pipe connected by a coupling using the manufacturer’s
in. (50 mm).
specified solvent cement that is used to join the CPVC
6.4 Threaded fittings—for all fittings having taper pipe
chemical waste drainage systems. The ten pipe test specimens
threads, threads shall conform to standard F1498.
shall be fitted with test caps on both ends with drain and vent
connectionstoenablethespecimenstobefilledwithchemicals
7. System Integrity
and to subsequently be internally pressurized. Allow the
7.1 Solvent Cemented Joint Hydrostatic Pressure Test—
materials to be conditioned at 73.4 6 3.6°F (23 6 2°C) for 24
Solvent cement joints shall not leak when tested in accordance
h after the joints are completed. After the 24 h conditioning
with 8.4.
period, completely fill each of the ten specimens with the
7.2 Solvent Cement Joint Chemical Resistance Integrity chemicals listed in Table 4. One chemical at the specified
Test: Solvent cemented joints shall not leak when tested in
concentrations within Table 4 shall be used per test specimen,
accordance with 8.3. making sure that the chemical media completely fills the
specimen prior to being capped off. The specimens shall be
7.3 CPVC Pipe Flattening Test: There shall be no evidence
pre-labeled to identify with which of the chemicals it is filled.
of splitting, cracking, or breaking when the pipe is tested in
Expose each of the ten specimens to the chemicals for one
accordance with 8.8.
week at 73.4 6 3.6°F (23 6 2°C) under an internal test
7.4 Impact Resistance—The impact resistance testing shall
pressure of 5 psig (34.5 kPa).After the holding period, remo
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.