Standard Specification for Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Hot- and Cold-Water Distribution Systems

ABSTRACT
This specification covers requirements, test methods, and methods of marking for chlorinated poly(vinyl chloride) plastic hot- and cold-water distribution system components made in one standard dimension ratio and intended for water service up to a certain temperature. These components comprise pipe and tubing, socket-type fittings, street fittings, plastic-to-metal transition fittings, solvent cements, and adhesives. The components are intended for use in residential and commercial, hot and cold, potable water distribution systems. The products covered by this specification are intended for use with the distribution of pressurized liquids only, which are chemically compatible with the piping materials. CPVC 4120 pipe, tubing, and fittings shall be classified by a single standard dimension ratio which shall be SDR 11, by a certain maximum continuous use temperature and by a certain diameter range for nominal pipe or tubing. CPVC plastic-to-metal transition fittings intended for use up a certain temperature are classified on the basis of resistance to failure by thermocycling. The chlorinated poly(vinyl chloride) plastics are categorized by two criteria: basic short-term properties and long-term hydrostatic strength. These short-term properties include mechanical strength, heat resistance, flammability, and chemical resistance which shall be determined after performing different tests. A test shall also be conducted in order to determine the long-term hydrostatic strength of CPVC 41 pipe, tubing, and fittings.
SCOPE
1.1 This specification covers requirements, test methods, assembly, and methods of marking for chlorinated poly(vinyl chloride) plastic hot- and cold-water distribution system components made in one standard dimension ratio and intended for water service up to and including 180°F (82°C). These components comprise pipe and tubing, socket-type fittings, street fittings, plastic-to-metal transition fittings, solvent cements, and adhesives. Requirements and methods of test are included for materials, workmanship, dimensions and tolerances, hydrostatic sustained pressure strength, and thermocycling resistance. The components covered by this specification are intended for use in residential and commercial, hot and cold, potable water distribution systems.  
1.2 The products covered by this specification are intended for use with the distribution of pressurized liquids only, which are chemically compatible with the piping materials. Due to inherent hazards associated with testing components and systems with compressed air or other compressed gases some manufacturers do not allow pneumatic testing of their products. Consult with specific product/component manufacturers for their specific testing procedures prior to pneumatic testing.
Note 1: Pressurized (compressed) air or other compressed gases contain large amounts of stored energy which present serious saftey hazards should a system fail for any reason.  
1.3 The text of this specification references notes, footnotes, and appendixes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the specification.  
1.4 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.
Note 2: Suggested hydrostatic design stresses and hydrostatic pressure ratings for pipe, tubing, and fittings are listed in Appendix X1. Design and installation considerations are discussed in Appendix X2. An optional performance qualification and an in-plant quality control program are recommended in Appendix X3.  
1.5 The following safety hazards caveat pertains only to the test method portion, Sections 9 and 10, of this specificatio...

General Information

Status
Historical
Publication Date
31-Jul-2017
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM D2846/D2846M-17a - Standard Specification for Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Hot- and Cold-Water Distribution Systems
English language
12 pages
sale 15% off
Preview
sale 15% off
Preview
Technical specification
REDLINE ASTM D2846/D2846M-17a - Standard Specification for Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Hot- and Cold-Water Distribution Systems
English language
12 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:D2846/D2846M −17a An American National Standard
Standard Specification for
Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Hot- and
1
Cold-Water Distribution Systems
This standard is issued under the fixed designation D2846/D2846M; the number immediately following the designation indicates the
year of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last
reapproval. A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
NOTE2—Suggestedhydrostaticdesignstressesandhydrostaticpressure
1. Scope*
ratingsforpipe,tubing,andfittingsarelistedinAppendixX1.Designand
1.1 This specification covers requirements, test methods,
installation considerations are discussed in Appendix X2. An optional
assembly, and methods of marking for chlorinated poly(vinyl performance qualification and an in-plant quality control program are
recommended in Appendix X3.
chloride) plastic hot- and cold-water distribution system com-
ponentsmadeinonestandarddimensionratioandintendedfor 1.5 The following safety hazards caveat pertains only to the
water service up to and including 180°F (82°C). These com-
test method portion, Sections 9 and 10, of this specification:
ponents comprise pipe and tubing, socket-type fittings, street This standard does not purport to address all of the safety
fittings, plastic-to-metal transition fittings, solvent cements,
concerns, if any, associated with its use. It is the responsibility
and adhesives. Requirements and methods of test are included of the user of this standard to establish appropriate safety,
formaterials,workmanship,dimensionsandtolerances,hydro-
health, and environmental, practices and determine the appli-
static sustained pressure strength, and thermocycling resis- cability of regulatory limitations prior to use.
tance. The components covered by this specification are
1.6 This international standard was developed in accor-
intended for use in residential and commercial, hot and cold, dance with internationally recognized principles on standard-
potable water distribution systems.
ization established in the Decision on Principles for the
Development of International Standards, Guides and Recom-
1.2 The products covered by this specification are intended
mendations issued by the World Trade Organization Technical
for use with the distribution of pressurized liquids only, which
Barriers to Trade (TBT) Committee.
are chemically compatible with the piping materials. Due to
inherent hazards associated with testing components and sys-
2. Referenced Documents
tems with compressed air or other compressed gases some
2
2.1 ASTM Standards:
manufacturersdonotallowpneumatictestingoftheirproducts.
D1598Test Method for Time-to-Failure of Plastic Pipe
Consult with specific product/component manufacturers for
Under Constant Internal Pressure
their specific testing procedures prior to pneumatic testing.
NOTE 1—Pressurized (compressed) air or other compressed gases D1599Test Method for Resistance to Short-Time Hydraulic
contain large amounts of stored energy which present serious saftey
Pressure of Plastic Pipe, Tubing, and Fittings
hazards should a system fail for any reason.
D1784Specification for Rigid Poly(Vinyl Chloride) (PVC)
1.3 Thetextofthisspecificationreferencesnotes,footnotes, Compounds and Chlorinated Poly(Vinyl Chloride)
and appendixes which provide explanatory material. These
(CPVC) Compounds
notesandfootnotes(excludingthoseintablesandfigures)shall D2122Test Method for Determining Dimensions of Ther-
not be considered as requirements of the specification.
moplastic Pipe and Fittings
D2855Practice for the Two-Step (Primer and Solvent Ce-
1.4 The values stated in either SI units or inch-pound units
ment) Method of Joining Poly (Vinyl Chloride) (PVC) or
are to be regarded separately as standard. The values stated in
Chlorinated Poly (Vinyl Chloride) (CPVC) Pipe and
each system may not be exact equivalents; therefore, each
Piping Components with Tapered Sockets
system shall be used independently of the other. Combining
D2444Test Method for Determination of the Impact Resis-
values from the two systems may result in non-conformance
tance of Thermoplastic Pipe and Fittings by Means of a
with the standard.
Tup (Falling Weight)
1
This specification is under the jurisdiction ofASTM Committee F17 on Plastic
2
Piping Systems and is the direct responsibility of Subcommittee F17.61 on Water. For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Current edition approved Aug. 1, 2017. Published September 2017. Originally contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
approved in 1969. Last previous edition approved in 2017
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: D2846/D2846M − 17 D2846/D2846M − 17a An American National Standard
Standard Specification for
Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Hot- and
1
Cold-Water Distribution Systems
This standard is issued under the fixed designation D2846/D2846M; the number immediately following the designation indicates the
year of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last
reapproval. A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
1. Scope*
1.1 This specification covers requirements, test methods, assembly, and methods of marking for chlorinated poly(vinyl chloride)
plastic hot- and cold-water distribution system components made in one standard dimension ratio and intended for water service
up to and including 180°F (82°C). These components comprise pipe and tubing, socket-type fittings, street fittings, plastic-to-metal
transition fittings, solvent cements, and adhesives. Requirements and methods of test are included for materials, workmanship,
dimensions and tolerances, hydrostatic sustained pressure strength, and thermocycling resistance. The components covered by this
specification are intended for use in residential and commercial, hot and cold, potable water distribution systems.
1.2 The products covered by this specification are intended for use with the distribution of pressurized liquids only, which are
chemically compatible with the piping materials. Due to inherent hazards associated with testing components and systems with
compressed air or other compressed gases some manufacturers do not allow pneumatic testing of their products. Consult with
specific product/component manufacturers for their specific testing procedures prior to pneumatic testing.
NOTE 1—Pressurized (compressed) air or other compressed gases contain large amounts of stored energy which present serious saftey hazards should
a system fail for any reason.
1.3 The text of this specification references notes, footnotes, and appendixes which provide explanatory material. These notes
and footnotes (excluding those in tables and figures) shall not be considered as requirements of the specification.
1.4 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each
system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the
two systems may result in non-conformance with the standard.
NOTE 2—Suggested hydrostatic design stresses and hydrostatic pressure ratings for pipe, tubing, and fittings are listed in Appendix X1. Design and
installation considerations are discussed in Appendix X2. An optional performance qualification and an in-plant quality control program are recommended
in Appendix X3.
1.5 The following safety hazards caveat pertains only to the test method portion, Sections 9 and 10, of this specification: This
standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user
of this standard to establish appropriate safety safety, health, and healthenvironmental, practices and determine the applicability
of regulatory limitations prior to use.
1.6 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
2. Referenced Documents
2
2.1 ASTM Standards:
D1598 Test Method for Time-to-Failure of Plastic Pipe Under Constant Internal Pressure
D1599 Test Method for Resistance to Short-Time Hydraulic Pressure of Plastic Pipe, Tubing, and Fittings
D1784 Specification for Rigid Poly(Vinyl Chloride) (PVC) Compounds and Chlorinated Poly(Vinyl Chloride) (CPVC)
Compounds
D2122 Test Method for Determining Dimensions of Thermoplastic Pipe and Fittings
1
This specification is under the jurisdiction of ASTM Committee F17 on Plastic Piping Systems and is the direct responsibility of Subcommittee F17.61 on Water.
Current edition approved July 1, 2017Aug. 1, 2017. Published July 2017September 2017. Originally approved in 1969. Last previous edition approved in 20142017 as
ε1
D2846/D2846M – 14– 17. . DOI: 10.1520/D2846_D2846M-17.10.1520/D2846_D2846M-17A.
2
For referenc
...