ASTM E904-87(2007)
(Practice)Standard Practice for Generating All-Day Thermal Performance Data for Solar Collectors (Withdrawn 2013)
Standard Practice for Generating All-Day Thermal Performance Data for Solar Collectors (Withdrawn 2013)
SIGNIFICANCE AND USE
This practice may be employed for a relative determination of the useful energy collected by different solar collectors tested side-by-side under the same operating and environmental parameters, in the same location, and on the same test day. Variations in inlet temperature and transfer fluid flow rate should be minimized for best results.
Limitations: Caution should be exercised when comparing the all-day thermal performance data for collectors tested by this practice to the performance of other collectors not tested at the same time and the same location, or with the same test conditions. The data collected by this practice represent the behavior of the tested collectors only under the conditions occurring on the day of test and at the specific inlet temperature and fluid flow rate employed during the test.
5.2.1 In the case of low-temperature collectors (operating below 100°C (212°F)), consideration must be given to the relationship of inlet temperature to ambient temperature when analyzing or interpreting the test data.
Data collected in this test have not been shown to provide the overall comparison of collectors or collector concepts that would be required to support a nationally accepted rating or certification program.
SCOPE
1.1 This practice covers a means of generating all-day thermal performance data for flat-plate collectors, concentrating collectors, and tracking collectors.
1.2 The values stated in SI units are to be regarded as the standard. The values given in the parentheses are for information only.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
WITHDRAWN RATIONALE
This practice covers a means of generating all-day thermal performance data for flat-plate collectors, concentrating collectors, and tracking collectors.
Formerly under the jurisdiction of Committee E44 on Solar, Geothermal and Other Alternative Energy Sources, this test method was withdrawn in November 2013. This standard is being withdrawn without replacement because it is believed that this document is no longer used and therefore not needed.
General Information
Relations
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: E904 − 87 (Reapproved 2007)
StandardPractice for
Generating All-Day Thermal Performance Data for Solar
Collectors
This standard is issued under the fixed designation E904; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 3.1.2 For definitions of other terms used in this practice,
refer to Terminology E772.
1.1 This practice covers a means of generating all-day
3.1.3 area, aperture, n— of a solar thermal collector,
thermal performance data for flat-plate collectors, concentrat-
maximum projected area through which the unconcentrated
ing collectors, and tracking collectors.
solar radiant energy is admitted, measured in square metres
1.2 The values stated in SI units are to be regarded as the 2 2
(m ) (square feet (ft )).
standard. The values given in the parentheses are for informa-
NOTE 1—For concentrating collectors, the gross aperature area includes
tion only.
anyareaofthereflectororrefractorshadedbythereceiveranditssupports
1.3 This standard does not purport to address all of the
and including gaps between reflector segments within a collector module.
safety concerns, if any, associated with its use. It is the Net aperture excludes any shaded area or gaps between reflector segments
and is sometimes called effective aperture area.
responsibility of the user of this standard to establish appro-
(E772)
priate safety and health practices and determine the applica-
bility of regulatory limitations prior to use.
3.1.4 heat transfer fluid, n— in solar energy systems, (1)
liquid or gas that passes through the solar collector and carries
2. Referenced Documents
the absorbed thermal energy away from the collector. (2) any
fluid that is used to transfer thermal energy between subsys-
2.1 ASTM Standards:
tems in solar energy systems. (E772)
E772 Terminology of Solar Energy Conversion
3.1.5 non-operational mode exposure, n— condition that
2.2 ASHRAE Standards:
exists when the collector has been filled, then purged of heat
93-86 Methods of Testing to Determine the Thermal Perfor-
transferfluid(ifaliquid)andcapped(butnotsealed)toprevent
mance of Solar Collectors
introduction of foreign substances, mounted on a test rack, and
96-80 Methods of Testing to Determine the Thermal Perfor-
exposed to solar radiation. (E772)
mance of Unglazed Flat-Plate Liquid-Type Solar Collec-
tors
3.1.6 stagnation conditions, n—conditions (that is, tempera-
ture and pressure) existing when an energy system has attained
3. Terminology
a quasi-steady state after the flow of heat transfer fluid has
stopped, but the absorber continues to receive significant solar
3.1 Definitions:
irradiance. (E772)
3.1.1 Terms from Terminology E772 and solar nomencla-
ture documents under ballot, are listed for convenience.
3.1.7 tilt angle, n—in solar energy applications, angle
between the horizontal and the plane of the detector (collector,
photovoltaic array, instrument) surface. (E772)
This practice is under the jurisdiction of ASTM Committee E44 on Solar,
3.1.8 time constant, n—time required for the temperature
Geothermal and OtherAlternative Energy Sources and is the direct responsibility of
change in the fluid leaving a solar collector to attain 63.2 % of
Subcommittee E44.05 on Solar Heating and Cooling Systems and Materials.
Current edition approved March 1, 2007. Published April 2007. Originally its equilibrium value following a step change in the solar
approvedin1982.Lastpreviouseditionapprovedin2001asE904 – 87(2001).DOI:
irradiance or inlet fluid temperature.
10.1520/E0904-87R07.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
NOTE 2—The step change involved should be thoroughly described in
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
the procedure.
Standards volume information, refer to the standard’s Document Summary page on
3.2 Definitions of Terms Specific to This Standard:
the ASTM website.
.Available from the American Society of Heating, Refrigeration, and Air-
3.2.1 useful energy (removed), n—time integral of the prod-
conditioning Engineers, Inc. (ASHRAE), Publications Sales Department, 1791
uct of mass flow rate, specific heat, and temperature difference
Tullie Circle, N.E.Atlanta, GA30329, http://www.ashrae.org; orAmerican National
across the collector when the outlet temperature is greater than
Standards Institute, (ANSI), 25 W. 43rd St., 4th Floor, New York, NY 10036,
http://www.ansi.org, for the ANSI standard. the inlet temperature.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
E904 − 87 (Reapproved 2007)
4. Summary of Practice applications,thentestacollectorassemblyconsistingoftwoor
more collectors of each type, together with any required
4.1 The solar collector is mounted in accordance with the
external manifolding. Include a description of the manifolding
manufacturer’s instructions. A constant flow rate and inlet
in the report, giving the pipe length, diameter, and material and
temperature, and the transfer fluid, is preselected and specified.
the insulation type and thickness used. It shall be stated
The temperature, fluid flow rate, irradiance, and wind param-
whether collectors were joined in series or parallel.
eters are recorded throughout the daylight hours. Data are
7.1.2 Time constant—Determine the collector time constant
collectedat1-minintervalsormorefrequently,andtheaverage
at the mass flow rate utilized in this test method and in
values are reported for each 5-min interval of the test day.
accordance with ASHRAE 93-86.
All-day thermal performance is determined from the summa-
tion of energy outputs for all intervals of the test day. 7.2 Test Conditions:
7.2.1 Exposure Conditions—Precondition the solar collec-
5. Significance and Use
tors in accordance with Section 6.
5.1 This practice may be employed for a relative determi-
7.2.2 Operating Conditions—Pump the specified transfer
nation of the useful energy collected by different solar collec- fluid through the collectors at a constant preselected mass flow
tors tested side-by-side under the same operating and environ-
rate and inlet temperature specified by the manufacturer. The
mental parameters, in the same location, and on the same test
selected flow rate should be the projected flow rate for the
day. Variations in inlet temperature and transfer fluid flow rate
anticipated end-use application, and the inlet temperature
should be minimized for best results.
should be selected to provide the anticipated end-use tempera-
ture. Maintain the inlet temperatures within6 0.5°C (6 1°F)
5.2 Limitations: Caution should be exercised when com-
during each 5-min measurement interval and within 6 2.5°C
paring the all-day the
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.