Standard Specification for Poly(Vinyl Chloride) (PVC) Schedule 40 Drain, Waste, and Vent Pipe with a Cellular Core

SCOPE
1.1 This specification covers coextruded poly(vinyl chloride) (PVC) plastic drain, waste and vent pipe made to Schedule 40 iron pipe sizes (IPS) and produced by the coextrusion process with concentric inner and outer solid PVC layers and the core consisting of closed-cell cellular PVC. Plastic which does not meet the material requirements specified in Section 5 is excluded from single layer and all coextruded layers.  
1.2 Fittings meeting the requirements of Specification D2665 and D3311 are suitable for use with pipe meeting the requirements of this specification.  
1.3 Poly(vinyl chloride) plastic which does not meet the definitions of virgin PVC plastic as given in 5.1 is excluded, as performance of plastic other than those defined as virgin was not determined. PVC rework plastic which meets the requirements of rework plastic as given in 5.2 is acceptable.  
1.4 Reprocessed plastic or recycled plastic as defined in Terminology D883 is excluded.  
1.5 Recommendations for storage, joining and installation are provided in Appendix X1, Appendix X2, and Appendix X3 respectively.  
1.6 The text of this specification references notes, footnotes and appendices which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the specification.  
1.7 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
31-Mar-2015
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM F3128-15 - Standard Specification for Poly(Vinyl Chloride) (PVC) Schedule 40 Drain, Waste, and Vent Pipe with a Cellular Core
English language
8 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:F3128 −15 An American National Standard
Standard Specification for
Poly(Vinyl Chloride) (PVC) Schedule 40 Drain, Waste, and
1
Vent Pipe with a Cellular Core
This standard is issued under the fixed designation F3128; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 2. Referenced Documents
2
1.1 This specification covers coextruded poly(vinyl chlo- 2.1 ASTM Standards:
ride) (PVC) plastic drain, waste and vent pipe made to D618 Practice for Conditioning Plastics for Testing
Schedule 40 iron pipe sizes (IPS) and produced by the D883 Terminology Relating to Plastics
coextrusion process with concentric inner and outer solid PVC D1600 Terminology forAbbreviatedTerms Relating to Plas-
layers and the core consisting of closed-cell cellular PVC. tics
Plasticwhichdoesnotmeetthematerialrequirementsspecified D1784 Specification for Rigid Poly(Vinyl Chloride) (PVC)
in Section 5 is excluded from single layer and all coextruded Compounds and Chlorinated Poly(Vinyl Chloride)
layers. (CPVC) Compounds
D2122 Test Method for Determining Dimensions of Ther-
1.2 Fittings meeting the requirements of Specification
moplastic Pipe and Fittings
D2665 and D3311 are suitable for use with pipe meeting the
D2152 Test Method for Adequacy of Fusion of Extruded
requirements of this specification.
Poly(Vinyl Chloride) (PVC) Pipe and Molded Fittings by
1.3 Poly(vinyl chloride) plastic which does not meet the
Acetone Immersion
definitions of virgin PVC plastic as given in 5.1 is excluded, as
D2321 PracticeforUndergroundInstallationofThermoplas-
performance of plastic other than those defined as virgin was
tic Pipe for Sewers and Other Gravity-Flow Applications
not determined. PVC rework plastic which meets the require-
D2412 Test Method for Determination of External Loading
ments of rework plastic as given in 5.2 is acceptable.
Characteristics of Plastic Pipe by Parallel-Plate Loading
1.4 Reprocessed plastic or recycled plastic as defined in D2444 Test Method for Determination of the Impact Resis-
tance of Thermoplastic Pipe and Fittings by Means of a
Terminology D883 is excluded.
Tup (Falling Weight)
1.5 Recommendations for storage, joining and installation
D2564 Specification for Solvent Cements for Poly(Vinyl
are provided in Appendix X1, Appendix X2, and Appendix X3
Chloride) (PVC) Plastic Piping Systems
respectively.
D2665 Specification for Poly(Vinyl Chloride) (PVC) Plastic
1.6 The text of this specification references notes, footnotes
Drain, Waste, and Vent Pipe and Fittings
and appendices which provide explanatory material. These
D2855 Practice for the Two-Step (Primer and Solvent Ce-
notesandfootnotes(excludingthoseintablesandfigures)shall
ment) Method of Joining Poly (Vinyl Chloride) (PVC) or
not be considered as requirements of the specification.
Chlorinated Poly (Vinyl Chloride) (CPVC) Pipe and
Piping Components with Tapered Sockets
1.7 The values stated in inch-pound units are to be regarded
D3311 Specification for Drain, Waste, and Vent (DWV)
as standard. The values given in parentheses are mathematical
Plastic Fittings Patterns
conversions to SI units that are provided for information only
D4396 Specification for Rigid Poly(Vinyl Chloride) (PVC)
and are not considered standard.
and Chlorinated Poly(Vinyl Chloride) (CPVC) Com-
1.8 This standard does not purport to address all of the
pounds for Plastic Pipe and Fittings Used in Nonpressure
safety concerns, if any, associated with its use. It is the
Applications
responsibility of the user of this standard to establish appro-
F402 Practice for Safe Handling of Solvent Cements,
priate safety and health practices and determine the applica-
Primers, and Cleaners Used for Joining Thermoplastic
bility of regulatory limitations prior to use.
Pipe and Fittings
1 2
This specification is under the jurisdiction ofASTM Committee F17 on Plastic For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Piping Systems and is the direct responsibility of Subcommittee F17.63 on DWV. contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Current edition approved April 1, 2015. Published June 2015. DOI: 10.1520/ Standards volume information, refer to the standard’s Document Summary page on
F3128–15 the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
F3128−15
thecognizantbuildingcodeauthorityshouldbeobtainedasconditionsnot
F412 Terminology Relating to Plastic Piping Systems
commonly found in normal use may be encounter
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.