Chimneys - Thermal and fluid dynamic calculation methods - Part 2: Chimneys serving more than one heating appliance

This European Standard specifies methods for calculation of the thermal and fluid dynamic characteristics of chimneys serving more than one heating appliances. A chimney is serving more than one appliance when either it is connected with more than one flue pipe to the appliances or there is one or more flue pipes connected with more than one appliances. This standard deals with chimneys with negative and positive pressure conditions and is valid for chimneys serving heating appliances for liquid, gazeous and solid fuels.

Abgasanlagen - Wärme- und strömungstechnische Berechnungsverfahren - Teil 2: Abgasanlagen mit mehreren Feuerstätten

Dieser Teil der Normreihe 13384 legt Berechnungsmethoden für die wärme- und strömungstechnischen Eigen-schaften von mehrfach belegten Abgasanlagen fest. Dieser Normteil umfaßt zwei Fälle:
(1) Abgasanlagen in die mehrere Verbindungsstücke von einzelnen oder mehreren Wärmeerzeugern in Mehrfach-anordnung münden.
(2) Abgasanlagen in die ein bestimmtes Verbindungsstück münden, das mehrere Wärmerzeuger in Kaskaden-schaltung verbindet.
Der Fall von Mehrfachanschlüssen von Kaskadenschaltungen ist durch Fall (1) abgedeckt.
Dieser Teil der Normreihe EN 13384 befaßt sich mit Unterdruck-Abgasanlagen und gilt für Abgasanlagen an die Wärmeerzeuger für flüssige, gasförmige und feste Brennstoffe angeschlossen werden.
Dieser Teil der Normreihe EN 13384 gilt nicht für:
¾ Abgasanlagen mit unterschiedlichen Wärmedurchlasswiderständen oder unterschiedlichen Querschnitten in den verschiedenen Abschnittten der Abgasanlage. Energiegewinne werden durch diesenTeil der Normreihe nicht berücksichtigt.
¾ Abgasanlagen für offene Feuerstätten, z.B. offene Kamine oder Abgaseinleitungen in die Abgasanlage, die bestimmungsgemäß offen im Raum betrieben werden.
¾ Abgasanlagen für ein Gemisch aus Abgasen von Ventilator unterstützten-oder Überdruckbrennern oder Naturzugkesseln.
¾ Abgasanlagen mit Mehrfachanschlüssen aus mehr als 5 Geschossen (dies gilt nicht für Luft-Abgasanlagen).
Abgasanlagen an die Wärmerzeuger angeschlossen werden, denen die Zuluft über Zuluftöffnungen oder Zuluftkanäle zugeführt wird, die sich nicht druckmässig im gleichen Luftverbund befinden (z.B. auf der gleichen Seite des Gebäudes).

Conduit de cheminée - Méthode de calcul thermo-aéraulique - Partie 2 : Conduits de fumée desservant plus d'un appareil de chauffage

La présente partie de la norme EN 13384 définit des méthodes de calcul des caractéristiques thermo aérauliques de conduits de fumée desservant plusieurs générateurs de chaleur.
Cette partie de la norme EN 13384 traite des deux cas suivants :
(1)   cas où le conduit de fumée est relié à  plusieurs conduits de raccordement partant d'un ou de plusieurs générateurs de chaleur dans un système multientrées ou
(2)   cas où le conduit de fumée est relié à un seul conduit de raccordement reliant plusieurs générateurs de chaleur dans un système en cascade.
Le cas du système multientrées en cascade est couvert par le cas (1).
La présente partie de la norme EN 13384 traite des conduits de fumée fonctionnant dans des conditions de pression négative et elle s'applique à des conduits desservant des générateurs de chaleur pour combustibles liquides, gazeux et solides.
Cette partie de la norme EN 13384 ne s'applique pas aux conduits de fumée suivants :
   conduits de fumée présentant une résistance thermique différente ou une section différente dans les différents segments du conduit de fumée. Cette partie ne s’applique pas pour le calcul du gain énergétique.
   conduits avec foyer ouvert, par exemple conduits de cheminées d'appartements ou entrées de conduits de fumée normalement conçues pour fonctionner ouvertes sur la pièce ;
   conduits desservant une combinaison d'appareils de chauffage ventilés, d'appareils à tirage forcé ou d'appareils à tirage naturel. Les appareils ventilés possédant un régulateur de tirage entre le ventilateur et le conduit de fumée sont considérés comme des appareils à tirage naturel ;
   conduits multi-entrées desservant plus de 5 étages. (Ceci ne s'applique pas au conduit de fumée collectif «équilibré» pour appareils étanches) ;

Dimniki – Računske metode termodinamike in dinamike fluidov – Dimniki za več kot eno ogrevalno napravo

General Information

Status
Withdrawn
Publication Date
06-May-2003
Withdrawal Date
13-Jan-2009
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
14-Jan-2009
Completion Date
14-Jan-2009

Relations

Buy Standard

Standard
EN 13384-2:2003
English language
63 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-september-2003
'LPQLNL±5DþXQVNHPHWRGHWHUPRGLQDPLNHLQGLQDPLNHIOXLGRY±'LPQLNL]DYHþ
NRWHQRRJUHYDOQRQDSUDYR
Chimneys - Thermal and fluid dynamic calculation methods - Part 2: Chimneys serving
more than one heating appliance
Abgasanlagen - Wärme- und strömungstechnische Berechnungsverfahren - Teil 2:
Abgasanlagen mit mehreren Feuerstätten
Conduits de fumée - Méthodes de calcul thermo-aéraulique - Partie 2: Conduits de
fumée desservant plus d'un appareil de chauffage
Ta slovenski standard je istoveten z: EN 13384-2:2003
ICS:
91.060.40 Dimniki, jaški, kanali Chimneys, shafts, ducts
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD
EN 13384-2
NORME EUROPÉENNE
EUROPÄISCHE NORM
May 2003
ICS 91.060.40
English version
Chimneys - Thermal and fluid dynamic calculation methods -
Part 2: Chimneys serving more than one heating appliance
Conduits de fumée - Méthodes de calcul thermo-aéraulique Abgasanlagen - Wärme- und strömungstechnische
- Partie 2: Conduits de fumée desservant plus d'un appareil Berechnungsverfahren - Teil 2: Abgasanlagen mit
de chauffage mehreren Feuerstätten
This European Standard was approved by CEN on 11 March 2003.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the official
versions.
CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,
Hungary, Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal, Slovak Republic, Spain, Sweden, Switzerland and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36  B-1050 Brussels
© 2003 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 13384-2:2003 E
worldwide for CEN national Members.

Contents
page
Foreword .4
1 Scope .5
2 Normative references.5
3 Terms and definitions .6
3.1 chimney segment .6
3.2 collector segment.6
3.3 air-flue gas system .6
3.4 flue gas mass flow ( m) .6
3.4.1 declared flue gas mass flow ( m).6
W, j
3.4.2 calculated flue gas mass flow ( m) .6
Wc,j
3.5 calculated flue gas temperature (T ).6
Wc, j
3.6 calculated draught of the flue gas of the heating appliance (P ) .6
Wc,j
3.7 flue damper .6
3.8 balanced flue chimney .7
3.9 cascade arrangement.7
3.10 uulti inlet arrangement.7
3.11 air duct.7
3.12 pressure equalising opening.7
4 Symbols, terminology, units .7
5 Calculation method .9
5.1 General principles .9
5.2 Pressure equilibrium condition.10
5.3 Mass flow requirement.12
5.4 Pressure requirement.12
5.5 Temperature requirement .12
5.6 Calculation procedure.13
6 Flue gas data characterising the heating appliance.14
7 Data for chimney and connecting flue pipes.16
8 Basic data for the calculation.16
8.1 Air temperatures.16
8.1.1 External air temperature (T ).16
L
8.1.2 Ambient air temperature (T ) .16
u
8.2 External air pressure (p ) .16
L
8.3 Gas constant .16
8.3.1 Gas constant of the air (R ).16
L
8.3.2 Gas constant of flue gas (R) .16
8.4 Density of air () .16
L
8.5 Specific heat capacity of the flue gas (c ) .16
p
8.6 Water vapour content ((H O) ) and condensing temperature (T ) .16
2 ,j sp
8.7 Correction factor for temperature instability (S ).17
H
8.8 Flow safety coefficient (S ) .17
E
8.9 External coefficient of heat transfer .17
9 Determination of temperatures .17
10 Mixing calculations.19
( m)
10.1 Flue gas mass flow .19
, j
10.2 Flue gas temperature at the inlet of the chimney segment (T ).19
e,j
10.3 CO -content of the flue gas in the chimney segment ((CO ) ) .19
2 ,j
10.4 H O-content of the flue gas ((H O) ) .19
2 2 ,j
10.5 Gas constant of the flue gas (R ) .20
,j
10.6 Flue gas data.20
10.6.1 Specific heat capacity (c ), (c ) .20
pV,j p,j
10.6.2 Thermal conductivity of the flue gas (), () .20
AV,j A,j
10.6.3 Dynamic viscosity (), () .21
AV,j A,j
11 Density and velocity of the flue gas .21
12 Draught at the outlet of the connecting flue pipe and draught at the inlet of the chimney
segment .22
12.1 Draught at the inlet of the chimney segment.22
12.1.1 Draught due to chimney effect in the chimney segment (P ) .23
H,j
(P )
12.1.2 Pressure resistance in the chimney segment .23
R,j
12.2 Draught required at the outlet of the connecting flue pipe (P ) .25
Ze,j
12.2.1 Calculated pressure resistance of the connecting flue pipe (P ).26
V,j
12.2.2 Pressure resistance of the air supply (P ) .28
B,j
13 Inner wall temperature .29
14 Cascade installations.30
14.1 Principle of the calculation method.30
14.2 Pressure equilibrium condition.30
14.3 Mass flow requirement.32
14.4 Pressure requirement.32
14.5 Temperature requirement .32
14.6 Calculation procedure.32
14.7 Draught at the outlet of the connecting flue pipe and draught at the inlet of the collector
segment .33
14.7.1 Draught at the flue gas inlet into the collector segment (P ).33
ZC,j,l
14.7.2 Draught at the outlet of the connecting flue pipe (P ).35
ZeC,j,l
14.8 Inner wall temperature (T ) .37
iobC,j,l
15 Balanced flue chimney.37
15.1 Principle of the calculation method.37
15.2 Pressure equilibrium condition.37
15.3 Mass flow requirement.38
15.4 Pressure requirements.38
15.5 Temperature requirements .40
15.6 Calculation procedure for balanced flue chimneys .40
15.7 Mass flow of the supply air.41
15.8 Determination of the temperatures in balanced flue chimneys.42
15.8.1 Separate ducts .42
15.8.2 Concentric ducts .42
...