IEC 61558-2-15:1999
(Main)Safety of power transformers, power supply units and similar - Part 2-15: Particular requirements for isolating transformers for the supply of medical locations
Safety of power transformers, power supply units and similar - Part 2-15: Particular requirements for isolating transformers for the supply of medical locations
This part 2-15 of IEC 61558 applies to stationary, single-phase or polyphase, air-cooled (natural or forced) isolating transformers for the supply of group II medical locations, designed to be permanently connected to the fixed wiring of IT supply system. This standard also applies to transformers incorporating electronic circuits. This standard does not apply to external circuits and their components intended to be connected to the input and output terminals or socket-outlets of the transformer. It has the status of a group safety publication in accordance with IEC Guide 104. This part 2 is intended to be used in conjunction with IEC 61558-1.
Sécurité des transformateurs, blocs d'alimentation et analogues - Partie 2-15: Règles particulières pour les transformateurs de séparation de circuits pour locaux à usages médicaux
La présente partie 2-15 de la CEI 61558 est applicable aux transformateurs de séparation de circuits fixes, monophasés ou polyphasés, à refroidissement par air (naturel ou forcé), destinés à alimenter des locaux à usages médicaux du groupe II et conçus pour être reliés en permanence au câblage fixe du système d'alimentation IT. Les transformateurs incorporant des circuits électroniques sont également couverts par cette norme. Cette norme ne s'applique pas aux circuits externes et à leurs composants connectés aux bornes ou aux socles de prise de courant du transformateur. Elle a le statut de publication groupée de sécurité conformément au Guide CEI 104. La présente partie 2 est destinée à être utilisée avec la CEI 61558-1.
General Information
Relations
Standards Content (Sample)
NORME
CEI
INTERNATIONALE
IEC
61558-2-15
INTERNATIONAL
Première édition
STANDARD
First edition
1999-02
PUBLICATION GROUPÉE DE SÉCURITÉ
GROUP SAFETY PUBLICATION
Sécurité des transformateurs,
blocs d'alimentation et analogues –
Partie 2-15:
Règles particulières pour les transformateurs
de séparation de circuits pour locaux
à usages médicaux
Safety of power transformers,
power supply units and similar –
Part 2-15:
Particular requirements for isolating transformers
for the supply of medical locations
Numéro de référence
Reference number
CEI/IEC 61558-2-15:1999
Numéros des publications Numbering
Depuis le 1er janvier 1997, les publications de la CEI As from 1 January 1997 all IEC publications are
sont numérotées à partir de 60000. issued with a designation in the 60000 series.
Publications consolidées Consolidated publications
Les versions consolidées de certaines publications de Consolidated versions of some IEC publications
la CEI incorporant les amendements sont disponibles. including amendments are available. For example,
Par exemple, les numéros d’édition 1.0, 1.1 et 1.2 edition numbers 1.0, 1.1 and 1.2 refer, respectively, to
indiquent respectivement la publication de base, la the base publication, the base publication
publication de base incorporant l’amendement 1, et la incorporating amendment 1 and the base publication
publication de base incorporant les amendements 1 incorporating amendments 1 and 2.
et 2.
Validité de la présente publication Validity of this publication
Le contenu technique des publications de la CEI est The technical content of IEC publications is kept under
constamment revu par la CEI afin qu'il reflète l'état constant review by the IEC, thus ensuring that the
actuel de la technique. content reflects current technology.
Des renseignements relatifs à la date de Information relating to the date of the reconfirmation of
reconfirmation de la publication sont disponibles dans the publication is available in the IEC catalogue.
le Catalogue de la CEI.
Les renseignements relatifs à des questions à l’étude et Information on the subjects under consideration and
des travaux en cours entrepris par le comité technique work in progress undertaken by the technical
qui a établi cette publication, ainsi que la liste des committee which has prepared this publication, as well
publications établies, se trouvent dans les documents ci- as the list of publications issued, is to be found at the
dessous: following IEC sources:
• «Site web» de la CEI* • IEC web site*
• Catalogue des publications de la CEI • Catalogue of IEC publications
Publié annuellement et mis à jour régulièrement Published yearly with regular updates
(Catalogue en ligne)* (On-line catalogue)*
• Bulletin de la CEI • IEC Bulletin
Disponible à la fois au «site web» de la CEI* et Available both at the IEC web site* and as a
comme périodique imprimé printed periodical
Terminologie, symboles graphiques Terminology, graphical and letter
et littéraux symbols
En ce qui concerne la terminologie générale, le lecteur For general terminology, readers are referred to
se reportera à la CEI 60050: Vocabulaire Electro- IEC 60050: International Electrotechnical Vocabulary
technique International (VEI). (IEV).
Pour les symboles graphiques, les symboles littéraux For graphical symbols, and letter symbols and signs
et les signes d'usage général approuvés par la CEI, le approved by the IEC for general use, readers are
lecteur consultera la CEI 60027: Symboles littéraux à referred to publications IEC 60027: Letter symbols to
utiliser en électrotechnique, la CEI 60417: Symboles be used in electrical technology, IEC 60417: Graphical
graphiques utilisables sur le matériel. Index, relevé et symbols for use on equipment. Index, survey and
compilation des feuilles individuelles, et la CEI 60617: compilation of the single sheets and IEC 60617:
Symboles graphiques pour schémas. Graphical symbols for diagrams.
* Voir adresse «site web» sur la page de titre. * See web site address on title page.
NORME
CEI
INTERNATIONALE
IEC
61558-2-15
INTERNATIONAL
Première édition
STANDARD
First edition
1999-02
PUBLICATION GROUPÉE DE SÉCURITÉ
GROUP SAFETY PUBLICATION
Sécurité des transformateurs,
blocs d'alimentation et analogues –
Partie 2-15:
Règles particulières pour les transformateurs
de séparation de circuits pour locaux
à usages médicaux
Safety of power transformers,
power supply units and similar –
Part 2-15:
Particular requirements for isolating transformers
for the supply of medical locations
IEC 1999 Droits de reproduction réservés Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni No part of this publication may be reproduced or utilized in
utilisée sous quelque forme que ce soit et par aucun any form or by any means, electronic or mechanical,
procédé, électronique ou mécanique, y compris la photo- including photocopying and microfilm, without permission in
copie et les microfilms, sans l'accord écrit de l'éditeur. writing from the publisher.
International Electrotechnical Commission 3, rue de Varembé Geneva, Switzerland
Telefax: +41 22 919 0300 e-mail: inmail@iec.ch IEC web site http: //www.iec.ch
CODE PRIX
Commission Electrotechnique Internationale
PRICE CODE P
International Electrotechnical Commission
Pour prix, voir catalogue en vigueur
For price, see current catalogue
– 2 – 61558-2-15 © CEI:1999
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
__________
SÉCURITÉ DES TRANSFORMATEURS,
BLOCS D'ALIMENTATION ET ANALOGUES –
Partie 2-15: Règles particulières pour les transformateurs de séparation
de circuits pour locaux à usages médicaux
AVANT-PROPOS
1) La CEI (Commission Electrotechnique Internationale) est une organisation mondiale de normalisation composée
de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI à pour objet de
favoriser la coopération internationale pour toutes les questions de normalisation dans les domaines de
l'électricité et de l'électronique. A cet effet, la CEI, entre autres activités, publie des Normes Internationales.
Leur élaboration est confiée à des comités d'études, aux travaux desquels tout Comité national intéressé par le
sujet traité peut participer. Les organisation internationales, gouvernementales et non gouvernementales, en
liaison avec la CEI, participent également aux travaux. La CEI collabore étroitement avec l'Organisation
Internationale de Normalisation (ISO), selon des conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques, représentent dans la mesures
du possible un accord international sur les sujets étudiés, étant donné que les comités nationaux intéressés
sont représentés dans chaque comité d’études.
3) Les documents produits se présentent sous la forme de recommandations internationales. Ils sont publiés
comme normes, rapports techniques ou guides et agréés comme tels par les Comités nationaux.
4) Dans le but d'encourager l'unification internationale, les Comités nationaux de la CEI s’engagent à appliquer de
façon transparente, dans toute la mesure possible, les Normes internationales de la CEI dans leurs normes
nationales et régionales. Toute divergence entre la norme CEI et la norme nationale ou régionale
correspondante doit être indiquée en termes clairs dans cette dernière.
5) La CEI n’a fixé aucune procédure concernant le marquage comme indication d’approbation et sa responsabilité
n’est pas engagée quand un matériel est déclaré conforme à l’une de ses normes.
6) L’attention est attirée sur le fait que certains des éléments de la présente Norme internationale peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La Norme internationale CEI 61558-2-15 a été établie par le comité d'études 96 de la CEI:
Petits transformateurs, bobines d’inductance et blocs d'alimentation, transformateurs,
bobines d’inductance et blocs d'alimentation spéciaux: Prescriptions de sécurité.
Elle a le statut de publication groupée de sécurité conformément au Guide CEI 104:
Elaboration des publications de sécurité et utilisation des publications fondamentales de
sécurité et publications groupées de sécurité (1997).
Le texte de cette norme est issu des documents suivants:
FDIS Rapport de vote
96/119/FDIS 96/124/RVD
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l’approbation de cette norme.
La présente partie 2 est destinée à être utilisée avec la CEI 61558-1. Elle a été établie sur les
bases de la première édition (1997) de cette norme.
La présente partie 2 complète ou modifie les articles correspondants de la CEI 61558-1, de
façon à la transformer en norme CEI: Règles particulières pour les transformateurs de
séparation de circuits pour locaux à usages médicaux.
61558-2-15 © IEC:1999 – 3 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
__________
SAFETY OF POWER TRANSFORMERS,
POWER SUPPLY UNITS AND SIMILAR –
Part 2-15: Particular requirements for isolating transformers for
the supply of medical locations
FOREWORD
1) The IEC (International Electrotechnical Commission) is a world-wide organisation for standardisation comprising all
national electrotechnical committees (IEC National Committees). The object of the IEC is to promote international co-
operation on all questions concerning standardization in the electrical and electronic fields. To this end and in addition
to other activities, the IEC publishes International Standards. Their preparation is entrusted to technical committees;
any IEC National Committee interested in the subject dealt with may participate in this preparatory work. International,
governmental and non-governmental organizations liaising with the IEC also participate in this preparation. The IEC
collaborates closely with the International Organisation for Standardisation (ISO) in accordance with conditions
determined by agreement between the two organisations.
2) The formal decisions or agreements of the IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all interested
National Committees.
3) The documents produced have the form of recommendations for international use and are published in the form of
standards, technical reports or guides and they are accepted by the National Committees in that sense.
4) In order to promote international unification, IEC National Committees undertake to apply IEC International Standards
transparently to the maximum extent possible in their national and regional standards. Any divergence between the
IEC Standard and the corresponding national or regional standard shall be clearly indicated in the latter.
5) The IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with one of its standards.
6) Attention is drawn to the possibility that some of the elements of this International Standard may be the subject of
patents rights. The IEC shall not be held responsible for identifying any or all such patents rights.
International standard IEC 61558-2-15 has been prepared by technical committee 96: Small
power transformers, reactors and power supply units and special transformers, reactors and
power supply units: Safety requirements.
It has the status of a group safety publication in accordance with IEC Guide 104: The preparation
of safety publications and the use of basic safety publications and group safety publications
(1997).
The text of this standard is based on the following documents:
FDIS Report on Voting
96/119/FDIS 96/124/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This part 2 is intended to be used in conjunction with IEC 61558-1. It was established on the
basis of the first edition (1997) of that standard.
This part 2 supplements or modifies the corresponding clauses in IEC 61558-1, so as to
convert that publication into the IEC standard: Particular requirements for isolating
transformers for the supply of medical locations.
– 4 – 61558-2-15 © CEI:1999
Lorsqu'un paragraphe particulier de la partie 1 n'est pas mentionné dans cette partie 2, ce
paragraphe s'applique pour autant qu'il est raisonnable. Lorsque la présente norme spécifie
«addition», «modification» ou «remplacement», le texte correspondant de la partie 1 doit être
adapté en conséquence.
Dans la présente norme, les caractères d'imprimerie suivants sont employés:
– prescriptions proprement dites: caractères romains;
– modalités d'essais: caractères italiques;
– commentaires: petits caractères romains.
Dans le texte de la norme les mots en gras sont définis à l'article 3.
Les paragraphes ou figures complémentaires à ceux de la partie 1 sont numérotés à partir de
101; les annexes complémentaires sont appelées AA, BB, etc.
61558-2-15 © IEC:1999 – 5 –
When a particular subclause of part 1 is not mentioned in this part 2, that subclause applies as
far as is reasonable. Where this standard states "addition", "modification" or "replacement", the
relevant text of part 1 is to be adapted accordingly.
In this standard, the following print types are used :
– requirements proper: in roman type;
– test specifications: in italic type;
– explanatory matter: in smaller roman type.
In the text of the standard, the words in bold are defined in clause 3.
Subclauses which are additional to those in part 1 are numbered starting from 101;
supplementary annexes are entitled AA, BB, etc.
– 6 – 61558-2-15 © CEI:1999
SÉCURITÉ DES TRANSFORMATEURS,
BLOCS D'ALIMENTATION ET ANALOGUES –
Partie 2-15: Règles particulières pour les transformateurs de séparation
de circuits pour locaux à usages médicaux
1 Domaine d’application
Remplacement:
Cette norme internationale traite de tous les aspects de la sécurité tels qu'électriques,
thermiques et mécaniques.
La présente partie 2-15 de la CEI 61558 est applicable aux transformateurs de séparation de
circuits fixes, monophasés ou polyphasés, à refroidissement par air (naturel ou forcé),
destinés à alimenter des locaux à usages médicaux du groupe II et conçus pour être reliés en
permanence au câblage fixe du système d'alimentation IT, ayant une tension primaire
assignée ne dépassant pas 1 000 V courant alternatif et une fréquence assignée ne
dépassant pas 500 Hz. La puissance assignée ne doit pas être inférieure à 3 kVA et ne doit
pas dépasser 10 kVA.
NOTE 1 – Des détails sur le système d'alimentation IT figurent dans la CEI 60364-3.
*
NOTE 2 – Les règles d'installation pour les locaux médicaux du groupe II sont à l'étude [1] .
La tension secondaire à vide et la tension secondaire assignée ne doivent pas dépasser
250 V courant alternatif monophasé ou polyphasé (tension entre phases).
Les transformateurs de séparation des circuits sont utilisés lorsque la double isolation ou
l’isolation renforcée sont requises entre les circuits par les règles d’installation ou par la
spécification de l’appareil d’utilisation.
La présente norme est applicable aux transformateurs secs. Les enroulements peuvent être
enrobés ou non enrobés.
NOTE 3 – Pour les transformateurs à remplissage par diélectrique liquide ou par des matières pulvérulentes telles
que le sable, les règles sont à l’étude.
NOTE 4 – L'attention est attirée sur le fait que:
– pour les transformateurs prévus pour être utilisés dans des régions tropicales, des prescriptions particulières
peuvent être nécessaires;
– des règles spéciales peuvent être exigées pour l'emploi dans des emplacements présentant des conditions
particulières d'environnement.
Les transformateurs incorporant des circuits électroniques sont également couverts par cette
norme. Cette norme ne s'applique pas aux circuits externes et à leurs composants connectés
aux bornes ou aux socles de prise de courant du transformateur.
________
*
Les chiffres entre crochets renvoient à la bibliographie.
61558-2-15 © IEC:1999 – 7 –
SAFETY OF POWER TRANSFORMERS,
POWER SUPPLY UNITS AND SIMILAR –
Part 2-15: Particular requirements for isolating transformers for
the supply of medical locations
1 Scope
Replacement:
This international standard deals with all aspects of safety such as electrical, thermal and
mechanical.
This part 2-15 of IEC 61558 applies to stationary, single-phase or polyphase, air-cooled
(natural or forced) isolating transformers for the supply of group II medical locations,
designed to be permanently connected to the fixed wiring of IT supply system, having a rated
supply voltage not exceeding 1 000 V a.c. and rated frequency not exceeding 500 Hz. The
rated output shall not be less than 3 kVA and shall not exceed 10 kVA.
NOTE 1 – Details of IT supply systems are to be found in IEC 60364-3.
*
NOTE 2 – The wiring rules for group II medical locations are under consideration [1] .
The no-load output voltage and the rated output voltage shall not exceed 250 V a.c. single-
phase or polyphase (phase-to-phase voltage).
Isolating transformers are used where double or reinforced insulation between circuits is
required by the installation rules or by the appliance specification.
This standard is applicable to dry-type transformers. The winding may be encapsulated or
non-encapsulated.
NOTE 3 – For transformers filled with liquid dielectric or pulverised material such as sand, requirements are under
consideration.
NOTE 4 – Attention is drawn to the fact that:
– for transformers intended to be used in tropical countries, special requirements may be necessary;
– in locations where special environmental conditions prevail, particular requirements may be necessary.
This standard also applies to transformers incorporating electronic circuits. This standard does
not apply to external circuits and their components intended to be connected to the input and
output terminals or socket-outlets of the transformer.
________
*
The figures in square brackets refer to the bibliography.
– 8 – 61558-2-15 © CEI:1999
2 Références normatives
L’article de la partie 1 est applicable à l’exception de ce qui suit:
Addition:
CEI 60252:1993, Condensateurs des moteurs à courant alternatif
CEI 60364-3:1993, Installations électriques des bâtiments – Troisième partie: Détermination
des caractéristiques générales
3 Définitions
L’article de la partie 1 est applicable à l’exception de ce qui suit:
Addition:
3.1.101
transformateur de séparation de circuits pour locaux à usages médicaux
transformateur de séparation de circuits utilisé pour l'alimentation des locaux à usages
médicaux, avec une double isolation ou isolation renforcée entre chaque partie du
transformateur (masse, écran, circuits, dispositif de protection thermique) excepté entre le
noyau et la masse
3.3.101
courant d’appel
valeur maximale instantanée du courant primaire à vide du transformateur (valeur de crête)
quand il est mis sous la tension primaire assignée
3.4.101
écran fonctionnel
séparation entre deux enroulements ou entre un enroulement et le noyau ou protection d’une
partie ou de l’ensemble du transformateur, par le moyen d’un matériau conducteur pour des
raisons fonctionnelles
3.5.101
courant primaire assigné
courant primaire, quand le transformateur est chargé à la puissance assignée
4 Prescriptions générales
L’article de la partie 1 est applicable.
5 Généralités sur les essais
L’article de la partie 1 est applicable.
61558-2-15 © IEC:1999 – 9 –
2 Normative references
This clause of part 1 is applicable except as follows:
Addition:
IEC 60252:1993, A.C. motor capacitors
IEC 60364-3:1993, Electrical installations of buildings – Part 3: Assessment of general
characteristics
3 Definitions
This clause of part 1 is applicable except as follows:
Addition:
3.1.101
isolating transformer for the supply of medical locations
an isolating transformer used for the supply of medical locations with double or reinforced
insulation between each part of the transformer (body, screen, circuits, thermal device)
except between the core and the body
3.3.101
inrush current
the maximum instantaneous value of the no-load input current of the transformer (peak value)
when switching on the transformer at rated supply voltage
3.4.101
functional screening
separation between two windings or between a winding and the core or shielding of a part or of
the whole transformer, by means of a conductive material for functional reasons
3.5.101
rated input current
the input current, when the transformer is loaded with rated output
4 General requirements
This clause of part 1 is applicable.
5 General notes on tests
This clause of part 1 is applicable.
– 10 – 61558-2-15 © CEI:1999
6 Caractéristiques assignées
L’article de la partie 1 est applicable à l’exception de ce qui suit:
Addition:
6.101 La tension secondaire assignée ne doit pas dépasser 250 V courant alternatif
monophasé ou polyphasé (tension entre phases).
6.102 La puissance assignée ne doit pas être inférieure à 3 kVA et ne doit pas dépasser 10 kVA.
6.103 La fréquence assignée ne doit pas dépasser 500 Hz.
6.104 La tension primaire assignée ne doit pas dépasser 1 000 V courant alternatif.
La conformité aux prescriptions de 6.101, 6.102, 6.103 et 6.104 est vérifiée par examen du marquage.
7 Classification
L’article de la partie 1 est applicable à l’exception de ce qui suit:
Remplacement:
7.2 D’après la protection contre les courts-circuits ou la protection contre une utilisation
anormale en:
– transformateur nonrésistant aux courts-circuits.
8 Marquage et indications
L’article de la partie 1 est applicable à l’exception de ce qui suit:
8.1 h) Les transformateurs de séparation de circuits pour locaux à usages médicaux
doivent être marqués du symbole graphique figurant en 8.11:
Addition:
8.11
Symbole Explication Numéro du symbole
dans la CEI 60417
transformateur de séparation des circuits
non résistant aux courts-circuits pour locaux à
usages médicaux
9 Protection contre l’accessibilité aux parties actives dangereuses
L’article de la partie 1 est applicable.
61558-2-15 © IEC:1999 – 11 –
6 Ratings
This clause of part 1 is applicable except as follows:
Addition:
6.101 The rated output voltage shall not exceed 250 V a.c. single-phase or polyphase
(phase-to-phase voltage).
6.102 The rated output shall not be less than 3 kVA and shall not exceed 10 kVA.
6.103 The rated frequency shall not exceed 500 Hz.
6.104 The rated supply voltage shall not exceed 1 000 V a.c.
Compliance with the requirements of 6.101, 6.102, 6.103 and 6.104 is checked by inspection of
the marking.
7 Classification
This clause of part 1 is applicable except as follows:
Replacement:
7.2 According to short-circuit protection or protection against abnormal use:
– non-short-circuit proof transformer.
8 Marking and other information
This clause of part 1 is applicable except as follows:
8.1 h) Isolating transformers for the supply of medical location shall be marked with the
graphical symbol shown in 8.11:
Addition:
8.11
Symbol Explanation Number of symbol
in IEC 60417
non-short-circuit proof isolating transformer
for the supply of medical locations
9 Protection against accessibility to hazardous live parts
This clause of part 1 is applicable.
– 12 – 61558-2-15 © CEI:1999
10 Changement de la tension primaire d’alimentation
L’article de la partie 1 est applicable.
11 Tension secondaire et courant secondaire en charge
L’article de la partie 1 est applicable.
12 Tension secondaire à vide
L’article de la partie 1 est applicable, à l’exception de ce qui suit:
Addition:
12.101 La tension secondaire à vide ne doit pas dépasser 250 V courant alternatif.
12.102 La différence entre la tension secondaire à vide et la tension secondaire en charge
ne doit pas être excessive.
La conformité aux prescriptions de 12.101 et 12.102 est vérifiée en mesurant la tension
secondaire à vide lorsque le transformateur est raccordé à la tension primaire assignée, à
la fréquence assignée, à la température ambiante.
L'écart entre la tension secondaire à vide mesurée dans cet article et la tension secondaire
en charge mesurée pendant l'essai de l'article 11, exprimée en pourcentage de cette dernière
tension, ne doit pas dépasser 5 %.
UU−
à vide charge
NOTE – Le rapport est défini comme suit: × 100
U
charge
13 Tension de court-circuit
Cet article est remplacé
...