Information technology — Implementation and operation of customer premises cabling — Part 2: Planning and installation

ISO/IEC 14763-2:2012(E) specifies requirements for the planning, installation and operation of cabling and cabling infrastructures (including cabling, pathways, spaces, earthing and bonding) in support of generic cabling standards and associated documents. The following aspects are addressed: - specification of the installation, - quality assurance, - installation planning, - installation practice, - documentation, - administration, - testing, - inspection, - operation, - maintenance and repair. The requirements of Clauses 5 to 14 of this standard are premises-independent and may be amended by the requirements of premises-specific Annexes. This first edition supersedes Clauses 11 and 12 of ISO/IEC 11801, published in 2002, replaces ISO/IEC 14763-1, published in 1999, its Amendment 1 (2004), ISO/IEC TR 14763-2, published in 2000, ISO/IEC 18010, published in 2002, and its Amendment 1 (2005) and constitutes a technical revision. It includes the following significant technical changes with respect to the previous edition: In addition to the supersession of parts of earlier standards and the incorporation of other standards, this standard provides much greater detail in all aspects of planning and installation with respect to ISO/IEC/TR 14763-2 and provides clearly differentiated and directed requirements and recommendations.

Technologies de l'information — Implémentation et fonctionnement du câblage dans les réseaux d'usagers — Partie 2: Planification et installation

General Information

Status
Withdrawn
Publication Date
23-Feb-2012
Withdrawal Date
23-Feb-2012
Current Stage
9599 - Withdrawal of International Standard
Completion Date
20-Dec-2019
Ref Project

Relations

Buy Standard

Standard
ISO/IEC 14763-2:2012 - Information technology -- Implementation and operation of customer premises cabling
English language
128 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

ISO/IEC 14763-2
Edition 1.0 2012-02
INTERNATIONAL
STANDARD

colour
inside


Information technology – Implementation and operation of customer premises
cabling –
Part 2: Planning and installation

ISO/IEC 14763-2:2012(E)

---------------------- Page: 1 ----------------------
THIS PUBLICATION IS COPYRIGHT PROTECTED
Copyright © 2012 ISO/IEC, Geneva, Switzerland

All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester.
If you have any questions about ISO/IEC copyright or have an enquiry about obtaining additional rights to this
publication, please contact the address below or your local IEC member National Committee for further information.


IEC Central Office Tel.: +41 22 919 02 11
3, rue de Varembé Fax: +41 22 919 03 00
CH-1211 Geneva 20 info@iec.ch
Switzerland www.iec.ch

About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.

About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.

Useful links:

IEC publications search - www.iec.ch/searchpub Electropedia - www.electropedia.org
The advanced search enables you to find IEC publications The world's leading online dictionary of electronic and
by a variety of criteria (reference number, text, technical electrical terms containing more than 30 000 terms and
committee,…). definitions in English and French, with equivalent terms in
It also gives information on projects, replaced and additional languages. Also known as the International
withdrawn publications. Electrotechnical Vocabulary (IEV) on-line.

IEC Just Published - webstore.iec.ch/justpublished Customer Service Centre - webstore.iec.ch/csc
Stay up to date on all new IEC publications. Just Published If you wish to give us your feedback on this publication
details all new publications released. Available on-line and or need further assistance, please contact the
also once a month by email. Customer Service Centre: csc@iec.ch.

---------------------- Page: 2 ----------------------
ISO/IEC 14763-2


Edition 1.0 2012-02




INTERNATIONAL



STANDARD








colour

inside










Information technology – Implementation and operation of customer premises

cabling –

Part 2: Planning and installation


























INTERNATIONAL

ELECTROTECHNICAL

COMMISSION

PRICE CODE
XB


ICS 35.200 ISBN 978-2-88912-897-6



  Warning! Make sure that you obtained this publication from an authorized distributor.

---------------------- Page: 3 ----------------------
– 2 – 14763-2 © ISO/IEC:2012(E)
CONTENTS
FOREWORD . 8
INTRODUCTION . 10
1 Scope . 13
2 Normative references . 14
3 Terms, definitions and abbreviations . 15
3.1 Terms and definitions . 15
3.2 Abbreviations . 21
3.3 Conventions . 22
4 Conformance . 22
5 Specification of installations . 23
5.1 General . 23
5.2 Installation specification . 23
5.2.1 Requirements . 23
5.2.2 Recommendations . 25
5.3 Technical specification . 25
5.3.1 General . 25
5.3.2 Safety requirements . 26
5.3.3 Security requirements . 26
5.3.4 Performance and configuration – Requirements. 26
5.3.5 Environmental conditions . 27
5.4 Scope of work . 27
5.4.1 Pre-installation . 27
5.4.2 Installation . 28
5.4.3 Post-installation . 29
5.5 Quality assurance . 29
6 Quality planning . 30
6.1 Quality plan . 30
6.2 Sampling . 31
6.2.1 Balanced cabling . 31
6.2.2 Optical fibre cabling . 33
6.3 Treatment of marginal results . 34
6.3.1 Balanced cabling . 34
6.3.2 Optical fibre cabling . 34
6.4 Treatment of non-compliant results . 35
6.5 Change control . 35
7 Installation planning . 35
7.1 General . 35
7.2 Safety . 35
7.2.1 General . 35
7.2.2 Mains power cabling . 35
7.2.3 Optical fibre cabling . 35
7.3 Environment . 36
7.4 Points of electrical contact. 36
7.5 External service provision . 36
7.5.1 Requirements . 36

---------------------- Page: 4 ----------------------
14763-2 © ISO/IEC:2012(E) – 3 –
7.5.2 Recommendations . 36
7.6 Pathways and pathway systems . 36
7.6.1 General . 36
7.6.2 Inside buildings . 39
7.6.3 Outside buildings . 42
7.7 Spaces . 46
7.7.1 Requirements . 46
7.7.2 Recommendations . 48
7.8 Functional elements . 50
7.8.1 Requirements . 50
7.8.2 Recommendations . 51
7.9 Segregation of information technology cabling and mains power cabling . 52
7.9.1 General . 52
7.9.2 Requirements . 53
7.9.3 Recommendations . 59
7.10 Cabling – Requirements . 59
7.10.1 General . 59
7.10.2 Unscreened cabling . 59
7.10.3 Screened cabling . 60
7.10.4 Optical fibre cabling . 60
8 Installation practices . 60
8.1 General . 60
8.2 Safety . 60
8.2.1 General . 60
8.2.2 Mains power cabling . 60
8.2.3 Functional bonding . 60
8.2.4 Optical fibre cabling . 60
8.2.5 Guards and signs . 61
8.2.6 Enclosed spaces . 61
8.2.7 Maintenance holes . 61
8.2.8 Closures . 61
8.3 Environment . 61
8.3.1 Storage . 61
8.3.2 Installation – Requirements . 61
8.4 Component inspection and testing – Requirements . 61
8.5 Pathways . 62
8.5.1 Requirements . 62
8.5.2 Inside buildings – Requirements . 62
8.5.3 Outside buildings . 62
8.6 Spaces . 63
8.6.1 Requirements . 63
8.6.2 Entrance facilities . 63
8.6.3 Rooms and enclosures intended to contain distributors . 63
8.6.4 Cabinets, frames and racks . 63
8.6.5 Closures . 63
8.6.6 Outlets . 63
8.7 Pathway system installation. 63
8.7.1 General . 63
8.7.2 Inside buildings . 64

---------------------- Page: 5 ----------------------
– 4 – 14763-2 © ISO/IEC:2012(E)
8.7.3 Outside buildings . 64
8.8 Closure installation . 64
8.9 Cable installation . 65
8.9.1 Cable installation within pathway systems . 65
8.9.2 General . 65
8.9.3 Inside buildings . 66
8.9.4 Cable installation in maintenance holes . 66
8.9.5 Cable installation within closures – Requirements . 67
8.10 Jointing and terminating of cables . 67
8.10.1 Requirements . 67
8.10.2 Balanced cabling . 68
8.10.3 Screened balanced cabling . 68
8.10.4 Optical fibre cabling . 68
8.11 Cords and jumpers . 68
8.12 Surge protective devices . 68
8.13 Acceptance . 68
8.13.1 Inspection . 68
8.13.2 Testing . 69
9 Documentation and administration . 69
9.1 Symbols and preparation of documents . 69
9.2 Administration . 69
9.2.1 General . 69
9.2.2 Administration system . 70
9.2.3 Identifiers – Requirements . 72
9.2.4 Component labelling . 72
9.2.5 Records . 75
9.2.6 Cable administration system . 79
9.2.7 Reports . 82
10 Testing . 82
10.1 General . 82
10.1.1 Links and permanent links . 82
10.1.2 Channels . 83
10.1.3 Cabling interface adaptors . 84
10.1.4 Calibration . 84
10.1.5 Equipment protection . 84
10.1.6 Measurement conditions . 84
10.2 Test procedures for balanced cabling . 85
10.2.1 General . 85
10.2.2 Measurement of length-related parameters . 85
10.2.3 Treatment of marginal test results . 85
10.2.4 Treatment of unacceptable test results . 85
10.2.5 Test result format . 85
10.2.6 Test result documentation . 86
10.3 Test procedures for optical fibre cabling . 86
10.3.1 General . 86
10.3.2 Treatment of unacceptable test results . 86
10.3.3 Test result documentation . 87
11 Inspection . 87
11.1 General . 87

---------------------- Page: 6 ----------------------
14763-2 © ISO/IEC:2012(E) – 5 –
11.2 Inspection Level 1 . 87
11.3 Inspection Level 2 . 88
11.4 Inspection Level 3 . 88
11.5 Inspection documentation – Requirements . 88
12 Operation . 89
12.1 Standard operating procedure . 89
12.1.1 Requirements . 89
12.1.2 Recommendations . 89
12.2 Cords and jumpers . 89
12.3 Optical fibre adaptors . 89
13 Maintenance . 89
13.1 Approaches to maintenance . 89
13.1.1 General . 89
13.1.2 Requirements . 90
13.2 Maintenance procedures . 90
13.2.1 Requirements . 90
13.2.2 Recommendations . 90
14 Repair . 91
Annex A (normative) Optical fibre polarity maintenance: connecting hardware for
multiple optical fibres . 92
Annex B (normative) Common infrastructures within multi-tenant premises . 101
Annex C (normative) Cabling in accordance with ISO/IEC 11801 . 109
Annex D (normative) Cabling in accordance with ISO/IEC 15018 . 116
Annex E (normative) Cabling in accordance with ISO/IEC 24764 . 122
Annex F (normative) Cabling in accordance with ISO/IEC 24702 . 135
Annex G (normative) Cabling in accordance with ISO/IEC TR 24704 . 138
Bibliography . 139

Figure 1 – Schematic relationship between ISO/IEC 14763-2 and other relevant
standards . 12
Figure 2 – Quality assurance schematic . 23
Figure 3 – Example of conformant and non-conformant bend radius management . 40
Figure 4 – Example of use of curved corners in pathway systems . 42
Figure 5 – Example of cabling installations outside buildings . 43
Figure 6 – Dimensions of rooms intended to contain distributors . 50
Figure 7 – Process of determining cable separation . 54
Figure 8 – Flowchart for cable separation calculation . 57
Figure 9 – Separation of mains power and information technology cables without
dividers . 58
Figure 10 – Separation of mains power and information technology cables with dividers . 58
Figure 11 – Examples of cord and jumper labelling . 74
Figure 12 – Cable administration database and possible linkages . 80
Figure 13 – Basic cabling administration . 80
Figure 14 – Examples of cabling permanent links . 83
Figure 15 – Reference planes for link and channels (point-to-point) . 83
Figure 16 – Example of a cabling channel . 84

---------------------- Page: 7 ----------------------
– 6 – 14763-2 © ISO/IEC:2012(E)
Figure A.1 – Duplex connecting hardware plug . 93
Figure A.2 – Duplex connecting adapter . 93
Figure A.3 – Duplex patch cord . 93
Figure A.4 – Views of crossover patch cords . 94
Figure A.5 – Optical fibre sequences and adapter orientation in patch panel for the
symmetrical position method . 95
Figure A.6 – Optical fibre sequences and adapter orientation in patch panel for the
reverse-pair position method . 95
Figure A.7 – Array connector cable or patch cord (key-up to key-up) . 97
Figure A.8 – Array adapter with aligned keyways . 97
Figure A.9 – Transition assembly . 98
Figure A.10 – Connectivity method for duplex signals . 99
Figure A.11 – Connectivity method for parallel optics channels . 100
Figure B.1 – Example of common pathways and spaces in a multi-tenant building . 102
Figure B.2 – Example of a campus entrance facility . 104
Figure B.3 – Example 1: Common equipment room . 106
Figure B.4 – Example 1: Common telecommunications room . 107
Figure B.5 – Example 2: Common telecommunications room . 107
Figure C.1 – Connection of functional elements providing redundancy . 110
Figure E.1 – Connection of functional elements providing redundancy . 123
Figure E.2 – Example of layered cable trays with smaller width upper trays . 126
Figure E.3 – Example of uncovered (accessible) row of floor tiles to provide access to
lower tray . 127
Figure E.4 – Dimensions of rooms intended to contain distributors . 129
Figure E.5 – Example of "hot" aisles, "cold" aisles and cable pathway locations . 131

Table 1 – Installed balanced cabling test parameters . 31
Table 2 – Minimum sample sizes for alien (exogenous) crosstalk testing . 33
Table 3 – Installed optical fibre cabling test parameters . 33
Table 4 – Examples of pathway systems . 37
Table 5 – Stacking height for non-continuous and interval support pathway systems . 41
Table 6 – Design and planning of pathways outside buildings . 43
Table 7 – Separation recommendations between metallic information technology
cabling and specific EMI sources . 53
Table 8 – Classification of information technology cables . 55
Table 9 – Minimum separation S . 55
Table 10 – Power cabling factor P . 56
Table 11 – Level of installation complexity . 70
Table 12 – Level of operational complexity .
...