Amendment 1 - Digital addressable lighting interface - Part 303: Particular requirements - Input devices - Occupancy sensor

Digital adressierbare Schnittstelle für die Beleuchtung - Teil 303: Besondere Anforderungen - Eingabegeräte - Präsenzmelder

Amendement 1 - Interface d'éclairage adressable numérique - Partie 303: Exigences particulières - Dispositifs d'entrée - Capteur de présence

Digitalni naslovljivi vmesnik za razsvetljavo - 303. del: Posebne zahteve - Vhodne naprave - Tipalo zasedenosti - Dopolnilo A1

General Information

Status
Not Published
Public Enquiry End Date
31-May-2023
Current Stage
4020 - Public enquire (PE) (Adopted Project)
Start Date
22-Mar-2023
Due Date
09-Aug-2023
Completion Date
01-Jun-2023

Relations

Buy Standard

Draft
EN 62386-303:2018/oprA1:2023 - BARVE
English language
10 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 62386-303:2018/oprA1:2023
01-maj-2023
Digitalni naslovljivi vmesnik za razsvetljavo - 303. del: Posebne zahteve - Vhodne
naprave - Tipalo zasedenosti - Dopolnilo A1
Amendment 1 - Digital addressable lighting interface - Part 303: Particular requirements -
Input devices - Occupancy sensor
Digital adressierbare Schnittstelle für die Beleuchtung - Teil 303: Besondere
Anforderungen - Eingabegeräte - Präsenzmelder
Amendement 1 - Interface d'éclairage adressable numérique - Partie 303: Exigences
particulières - Dispositifs d'entrée - Capteur de présence
Ta slovenski standard je istoveten z: EN 62386-303:2017/prA1:2023
ICS:
29.140.50 Instalacijski sistemi za Lighting installation systems
razsvetljavo
35.200 Vmesniška in povezovalna Interface and interconnection
oprema equipment
SIST EN 62386-303:2018/oprA1:2023 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
SIST EN 62386-303:2018/oprA1:2023

---------------------- Page: 2 ----------------------
SIST EN 62386-303:2018/oprA1:2023
34/1013/CDV

COMMITTEE DRAFT FOR VOTE (CDV)
PROJECT NUMBER:
IEC 62386-303/AMD1 ED1
DATE OF CIRCULATION: CLOSING DATE FOR VOTING:
2023-03-17 2023-06-09
SUPERSEDES DOCUMENTS:
34/780/CD, 34/801A/CC

IEC TC 34 : LIGHTING
SECRETARIAT: SECRETARY:
United Kingdom Mr Petar Luzajic
OF INTEREST TO THE FOLLOWING COMMITTEES: PROPOSED HORIZONTAL STANDARD:


Other TC/SCs are requested to indicate their interest, if
any, in this CDV to the secretary.
FUNCTIONS CONCERNED:
EMC ENVIRONMENT QUALITY ASSURANCE SAFETY
SUBMITTED FOR CENELEC PARALLEL VOTING NOT SUBMITTED FOR CENELEC PARALLEL VOTING
Attention IEC-CENELEC parallel voting
The attention of IEC National Committees, members of
CENELEC, is drawn to the fact that this Committee Draft
for Vote (CDV) is submitted for parallel voting.
The CENELEC members are invited to vote through the
CENELEC online voting system.

This document is still under study and subject to change. It should not be used for reference purposes.
Recipients of this document are invited to submit, with their comments, notification of
• any relevant patent rights of which they are aware and to provide supporting documentation ,
• any relevant “in some countries” clauses to be included should this proposal proceed. Recipients are
reminded that the enquiry stage is the final stage for submitting "in some countries" clauses. See
AC/22/2007.

TITLE:
Amendment 1 - Digital addressable lighting interface - Part 303: Particular requirements - Input
devices - Occupancy sensor

PROPOSED STABILITY DATE: 2026
NOTE FROM TC/SC OFFICERS:


Copyright © 2023 International Electrotechnical Commission, IEC. All rights reserved. It is permitted to
download this electronic file, to make a copy and to print out the content for the sole purpose of preparing National
Committee positions. You may not copy or "mirror" the file or printed version of the document, or any part of it, for
any other purpose without permission in writing from IEC.

---------------------- Page: 3 ----------------------
SIST EN 62386-303:2018/oprA1:2023
IEC CDV 62386-303 AMD 1 © IEC 2023 2 34/1013/CDV

1 FOREWORD
2 This amendment has been prepared by committee TC34 Lighting / WG11 Control Interface.
3 The text of this amendment is based on the following documents:
FDIS Report on voting
34C/XX/FDIS 34C/XX/RVD
4
5 Full information on the voting for the approval of this amendment can be found in the report on
6 voting indicated in the above table.
7 The committee has decided that the contents of this amendment and the base publication will
)
1
8 remain unchanged until the maintenance result date indicated on the IEC web site under
9 "http://webstore.iec.ch" in the data related to the specific publication. At this date, the publication
10 will be
11 • reconfirmed,
12 • withdrawn,
13 • replaced by a revised edition, or
14 • amended.
15 _____________
16 The following proposals serve to amend
17 IEC 62386-303:2017 according to the decisions of IEC TC34 WG 11 at their meeting in October
18 2021.
19
20 Proposal
21
22 All pages
23
24 Delete all references to IEC 62386-101:2014/AMD1.
25 Delete all references to IEC 62386-103:2014/AMD1.
26 Replace all dated references to IEC 62386-101 with IEC 62386-101:2022.
27 Replace all dated references to IEC 62386-103 with IEC 62386-103:2022.
28 Renumber tables 2 to table 5 and their references, to accommodate the new table 2 inserted in
29 clause 9.3.3.
30 Renumber tables 6 to 10 and their references, to accommodate the new table 2 inserted in clause
31 9.3.3 and the new table 7 in clause 9.5.6.
32
33 Page 6
34
35 INTRODUCTION
36
37 Replace the existing Figure 1 by the following new figure 1.
38

)
1
The National Committees are requested to note that for this publication the maintenance result date is .

---------------------- Page: 4 ----------------------
SIST EN 62386-303:2018/oprA1:2023
IEC CDV 62386-303 AMD 1 © IEC 2023 3 34/1013/CDV

39
40 Figure 1 – IEC 62386 graphical overview
41
42 Page 8
43
44 1 Scope
45
46 Replace the existing Scope by the following new Scope:
47
48 This part of IEC 62386 specifies a bus system for control by digital signals of electronic lighting
49 equipment.
50 This document is only applicable to IEC 62386-103:2022 input devices that deliver occupancy
51 information to the lighting control system through movement or presence sensing.
52
53 Page 8
54
55 2 Normative references
56
57 Replace the existing reference to IEC 62386-333 with the following reference:
58 IEC 62386-333:2018, Digital addressable lighting interface – Part 333: Particular requirements
59 for control devices – Manual configuration (feature type 33)
60
61 Page 10
62
63 9.3.2 Input signal mapping for movement sensors
64
65 Replace the first and the second paragraph by the following new paragraphs, and add a note:
66
67 For movement sensors, the input signal shall directly map onto movement (only). Depending on
68 the type of sensor used, it is possible that a very short pulse may be produced only when
69 movement is first detected, or a longer signal may be produced whilst movement continues to be
70 detected. In any case, the instance shall change “inputValue” to 0xFF immediately if movement
71 is detected, remaining in this state for at least 1 s, thus reporting an occupied area state as well.
72 See Figure 2.
73 NOTE This means that an instance receiving a rapid succession of movement signals which are less than 1 s apart,
74 will remain in the occupied and movement state, and will create a movement event only at the time it entered this state.
75 A movement sensor shall support a hold timer, with timeout value T , which shall be (re)started
hold
76 each time movement is detected. A transition of “inputValue” to 0x00 shall only take place at the
77 moment the hold timer expires or is cancelled. In such a case the ‘vacant’ trigger shall be
78 generated. (Re)starting the hold timer means: “discard any remaining hold time and start timing
79 a new hold time period”.
80 Update figure 2 as follows:

---------------------- Page: 5 ----------------------
SIST EN 62386-303:2018/oprA1:2023
IEC CDV 62386-303 AMD 1 © IEC 2023 4 34/1013/CDV

81 • In state 0xFF, replace the text “(Re-)trigger hold timer” with “Stop hold timer”.
82 • Delete all three instances of the text, “ / (Re-)trigger report timer”
83 • In the arrow exiting from state 0xFF into state 0xAA, append the text “(Re-)start hold
84 timer” after “No movement detected /'No movement' trigger”.
85
86 Page 12
87
88 9.3.3 Input signal mapping for presence sensors
89
90 Change the second sentence of the first paragraph to:
91
92 If a presence sensor is not able to detect motion, it shall report no movement and shall not enter
93 states 0x55 or 0xFF.
94
95 After the note, insert the following paragraph and example:
96 If a presence sensor is not able to detect motion without this also causing occupancy, the n the
97 presence sensor shall not enter state 0x55.
98 EXAMPLE For a presence sensor that is not able to detect motion without this also causing occupancy, example
99 state transitions are as follows: Starting in state 0x00, a person moving into the area is detect ed, causing simultaneous
100 movement and occupancy triggers and entry to state 0xFF. Without the movement stopping, the person exits the area
101 causing movement and presence to simultaneously end, causing a return to state 0x00. If instead the person entering
102 the area then pauses (ceases movement) for a while, this would cause a state change to 0xAA. From this state, a
103 return to 0x00 or 0xFF are both possible.
104
105 Replace figure 3 with the following:
Presence sensor
Report
Report
0x55: 0xFF:
timer
timer
expired /
expired /
Occupied and
Vacant and
'Repeat'
'Repeat'
trigger movement movement
trigger
Report Report
0x00: 0xAA:
timer timer
expired / expired /
Vacant and Occupied and
'Repeat' 'Repeat'
no movement no movement
trigger trigger
106
107
108
109 Insert the following paragraph and table after figure 3:
110 Table 2 shows the state transitions with the conditions for exiting each state, and the action upon
111 exit.

---------------------- Page: 6 ----------------------
SIST EN 62386-303:2018/oprA1:2023
IEC CDV 62386-303 AMD 1 © IEC 2023 5 34/1013/CDV

112 Table 1 - Presence sensor state transitions
Initial state Exit condition Action on exit New state
0x00: Vacant & no Movement detected 'Movement' trigger 0x55: Vacant & movement
movement
0x00: Vacant & no Occupancy detected 'Occupied' trigger 0xAA: Occupied & no
movement movement
0x00: Vacant & no Occupancy & movement 'Occupied' and 'movement' 0xFF: Occupied & movement
movement detected triggers
0x55: Vacant & No movement detected 'No movement' trigger 0x00: Vacant & no movement
movement
0x55: Vacant & Occupancy detected 'Occupied' trigger 0xFF: Occupied & movement
movement
0x55: Vacant & Occupancy & no movement 'Occupied' and 'no 0xAA: Occupied & no
movement detected movement' triggers movement
0xAA: Occupied & no Movement detected 'Movement' trigger 0xFF: Occupied & movement
movement
0xAA: Occupied & no Vacancy detected 'Vacant' trigger 0x00: Vacant & no movement
movement
0xAA: Occupied & no Vacancy & movement 'Vacant' and 'movement' 0x55: Vacant & movement
movement detected triggers
0xFF: Occupied & No movement detected 'No movement' trigger 0xAA: Occupied & no
movement movement
0xFF: Occupied & Vacancy detected 'Vacant' trigger 0x55: Vacant & movement
movement
0xFF: Occupied & Vacancy & no movement 'Vacant' and 'no movement' 0x00: Vacant & no movement
movement detected triggers
113
114
115
116
117 Page 13
118 9.4.4 Event configuration
119
120 Replace the first paragraph with the following:
121 Events shall be enabled or disabled according to the value of “eventFilter”. For this document,
122 “eventFilter” shall be reduced to one byte.
123 Correct the second paragraph after table 3 to:
124 If the ‘repeat’ event is enabled, on expiration of the report timer the ‘still vacant’ event shall be
125 sent if the ‘vacant’ event is enabled, and the ‘still occupied’ event shall be sent if the ‘occupied’
126 event is enabled.
127
128 Add at the end of the clause the following new paragraph:
129
130 Disabling an event shall not cancel transmission of an event that has already occurred and is
131 waiting to be sent due to the deadtime timer or bus unavailability.
132
133 Page 14
134 9.4.5 Event generation
135 Cancel in the seco
...