Standard Test Method for Sampling and Testing Grout

SIGNIFICANCE AND USE
3.1 Grout used in masonry is a fluid mixture of cementitious materials and aggregate with a high water content for ease of placement.  
3.1.1 During construction, grout is placed within or between absorptive masonry units. Excess water must be removed from grout specimens in order to provide compressive strength test results more nearly indicative of the grout strength in the wall. In this test method, molds are made from masonry units having the same absorption and moisture content characteristics as those being used in the construction.  
3.2 This test method is used to either help select grout proportions by comparing test values or as a quality control test for uniformity of grout preparation during construction.  
3.3 The physical exposure condition and curing of the grout are not exactly reproduced, but this test method does subject the grout specimens to absorption conditions similar to those experienced by grout in the wall.
Note 2: Test results of grout specimens taken from a wall should not be compared to test results obtained with this test method.
SCOPE
1.1 This test method covers procedures for both field and laboratory sampling and compression testing of grout used in masonry construction. Grout for masonry is specified under Specification C476.
Note 1: The testing agency performing this test method should be evaluated in accordance with Practice C1093.  
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

General Information

Status
Historical
Publication Date
31-Dec-2017
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM C1019-18 - Standard Test Method for Sampling and Testing Grout
English language
6 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM C1019-18 - Standard Test Method for Sampling and Testing Grout
English language
6 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: C1019 −18
Standard Test Method for
1
Sampling and Testing Grout
This standard is issued under the fixed designation C1019; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
1. Scope Testing of Hydraulic Cements and Concretes
C617 Practice for Capping Cylindrical Concrete Specimens
1.1 This test method covers procedures for both field and
C1064/C1064M Test Method for Temperature of Freshly
laboratory sampling and compression testing of grout used in
Mixed Hydraulic-Cement Concrete
masonry construction. Grout for masonry is specified under
C1093 Practice for Accreditation of Testing Agencies for
Specification C476.
Masonry
NOTE 1—The testing agency performing this test method should be
C1611/C1611M Test Method for Slump Flow of Self-
evaluated in accordance with Practice C1093.
Consolidating Concrete
1.2 The values stated in inch-pound units are to be regarded
as standard. The values given in parentheses are mathematical
3. Significance and Use
conversions to SI units that are provided for information only
3.1 Groutusedinmasonryisafluidmixtureofcementitious
and are not considered standard.
materials and aggregate with a high water content for ease of
1.3 This standard does not purport to address all of the
placement.
safety concerns, if any, associated with its use. It is the
3.1.1 Duringconstruction,groutisplacedwithinorbetween
responsibility of the user of this standard to establish appro-
absorptive masonry units. Excess water must be removed from
priate safety, health, and environmental practices and deter-
grout specimens in order to provide compressive strength test
mine the applicability of regulatory limitations prior to use.
results more nearly indicative of the grout strength in the wall.
1.4 This international standard was developed in accor-
In this test method, molds are made from masonry units having
dance with internationally recognized principles on standard-
the same absorption and moisture content characteristics as
ization established in the Decision on Principles for the
those being used in the construction.
Development of International Standards, Guides and Recom-
3.2 This test method is used to either help select grout
mendations issued by the World Trade Organization Technical
proportionsbycomparingtestvaluesorasaqualitycontroltest
Barriers to Trade (TBT) Committee.
for uniformity of grout preparation during construction.
2. Referenced Documents
3.3 The physical exposure condition and curing of the grout
2
2.1 ASTM Standards:
are not exactly reproduced, but this test method does subject
C39/C39M Test Method for Compressive Strength of Cylin-
the grout specimens to absorption conditions similar to those
drical Concrete Specimens
experienced by grout in the wall.
C143/C143M Test Method for Slump of Hydraulic-Cement
NOTE 2—Test results of grout specimens taken from a wall should not
Concrete
be compared to test results obtained with this test method.
C476 Specification for Grout for Masonry
C511 Specification for Mixing Rooms, Moist Cabinets,
4. Apparatus
Moist Rooms, and Water Storage Tanks Used in the
4.1 Maximum-Minimum Thermometer.
4.2 Straightedge, a steel straightedge not less than 6 in.
1
This test method is under the jurisdiction ofASTM Committee C12 on Mortars
1
(152.4 mm) long and not less than ⁄16 in. (1.6 mm) in
and Grouts for Unit Masonry and is the direct responsibility of Subcommittee
C12.02 on Research and Methods of Test.
thickness.
Current edition approved Jan. 1, 2018. Published February 2018. Originally
4.3 TampingRod,around,straight,steelrodwithadiameter
approved in 1984. Last previous edition approved in 2016 as C1019 – 16. DOI:
3 1
10.1520/C1019-18.
of ⁄8 6 ⁄16 in. (10 6 2 mm) and a length of 12 6 4 inches.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
(300 6 100 millimetres). The rod shall have the tamping end
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
or both ends rounded to a hemispherical tip of the same
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website. diameter as the rod.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
C1019 − 18
4.4 Nonabsorbent Blocks and Spacers, nonabsorbent, rigid
squares and rectangles with side dimensions so as to achieve
the desired grout spec
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: C1019 − 16 C1019 − 18
Standard Test Method for
1
Sampling and Testing Grout
This standard is issued under the fixed designation C1019; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
1. Scope*Scope
1.1 This test method covers procedures for both field and laboratory sampling and compression testing of grout used in masonry
construction. Grout for masonry is specified under Specification C476.
NOTE 1—The testing agency performing this test method should be evaluated in accordance with Practice C1093.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety safety, health, and healthenvironmental practices and determine the
applicability of regulatory limitations prior to use.
1.4 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
2. Referenced Documents
2
2.1 ASTM Standards:
C39/C39M Test Method for Compressive Strength of Cylindrical Concrete Specimens
C143/C143M Test Method for Slump of Hydraulic-Cement Concrete
C476 Specification for Grout for Masonry
C511 Specification for Mixing Rooms, Moist Cabinets, Moist Rooms, and Water Storage Tanks Used in the Testing of Hydraulic
Cements and Concretes
C617 Practice for Capping Cylindrical Concrete Specimens
C1064/C1064M Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
C1093 Practice for Accreditation of Testing Agencies for Masonry
C1611/C1611M Test Method for Slump Flow of Self-Consolidating Concrete
3. Significance and Use
3.1 Grout used in masonry is a fluid mixture of cementitious materials and aggregate with a high water content for ease of
placement.
3.1.1 During construction, grout is placed within or between absorptive masonry units. Excess water must be removed from
grout specimens in order to provide compressive strength test results more nearly indicative of the grout strength in the wall. In
this test method, molds are made from masonry units having the same absorption and moisture content characteristics as those
being used in the construction.
3.2 This test method is used to either help select grout proportions by comparing test values or as a quality control test for
uniformity of grout preparation during construction.
1
This test method is under the jurisdiction of ASTM Committee C12 on Mortars and Grouts for Unit Masonry and is the direct responsibility of Subcommittee C12.02
on Research and Methods of Test.
Current edition approved Jan. 1, 2016Jan. 1, 2018. Published January 2016February 2018. Originally approved in 1984. Last previous edition approved in 20142016 as
C1019 – 14.C1019 – 16. DOI: 10.1520/C1019-16.10.1520/C1019-18.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
C1019 − 18
3.3 The physical exposure condition and curing of the grout are not exactly reproduced, but this test method does subject the
grout specimens to absorption conditions similar to those experienced by grout in the wall.
NOTE 2—Test results of grout specimens taken from a wall should not be compared to test results obtained with this test method.
4. Apparatus
4.1 Maximum-Minimum Thermometer.
1
4.2 Straightedge, a steel straightedge not less than 6 in. (152.4 mm) long and not less than ⁄16 in. (1.6 mm) in thickness.
3 1
4.3 Tampi
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.