Standard Practice for Specimen Preparation and Mounting of Flexible Fibrous Glass Insulation for Metal Buildings to Assess Surface Burning Characteristics

SIGNIFICANCE AND USE
5.1 Flexible fibrous glass insulation for metal buildings is evaluated in accordance with Test Method E84 to comply with building code requirements. This practice describes, in detail, specimen mounting procedures for Type I and Type II metal building insulation materials.  
5.2 The material to be tested shall be representative of the glass fiber blanket, facing and bonding adhesive used in actual field installations.  
5.3 The limitations for this procedure are those associated with Test Method E84.
SCOPE
1.1 This practice describes a procedure for specimen preparation and mounting when testing Flexible Fibrous Glass Insulation for Metal Buildings to assess flame spread and smoke development as surface burning characteristics using Test Method E84.  
1.2 This practice applies to products described in Specification C991.  
1.3 This practice provides instructions for the testing of both un-faced insulation (Specification C991 Type I) and face insulation (Specification C991 Type II).  
1.4 This practice does not provide pass/fail criteria that can be used as a regulatory tool.  
1.5 Use the values stated in inch-pound units as the standard in referee decisions. The values in the SI system of units are given in parentheses, for information only; see IEEE/ASTM SI-10 for further details.  
1.6 This fire standard cannot be used to provide quantitative measures.  
1.7 Fire testing of products and materials is inherently hazardous and adequate safeguards for personnel and property shall be employed in conducting these tests. Fire testing involves hazardous materials, operations and equipment.  
1.8 This practice gives instructions on specimen preparation and mounting but the fire-test-response method shall be conducted in accordance with Test Method E84. See also Section 8 for information on operator safety.  
1.9 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
31-Jan-2015
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM E2988-15 - Standard Practice for Specimen Preparation and Mounting of Flexible Fibrous Glass Insulation for Metal Buildings to Assess Surface Burning Characteristics
English language
3 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: E2988 − 15
StandardPractice for
Specimen Preparation and Mounting of Flexible Fibrous
Glass Insulation for Metal Buildings to Assess Surface
1
Burning Characteristics
This standard is issued under the fixed designation E2988; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 2. Referenced Documents
2
1.1 This practice describes a procedure for specimen prepa- 2.1 ASTM Standards:
ration and mounting when testing Flexible Fibrous Glass C168 Terminology Relating to Thermal Insulation
Insulation for Metal Buildings to assess flame spread and C991 Specification for Flexible Fibrous Glass Insulation for
smoke development as surface burning characteristics using Metal Buildings
Test Method E84. E84 Test Method for Surface Burning Characteristics of
Building Materials
1.2 This practice applies to products described in Specifi-
E176 Terminology of Fire Standards
cation C991.
IEEE/ASTM SI-10 American National Standard for Use of
1.3 Thispracticeprovidesinstructionsforthetestingofboth
theInternationalSystemofUnits(SI):TheModernMetric
un-faced insulation (Specification C991 Type I) and face
System
insulation (Specification C991 Type II).
3. Terminology
1.4 This practice does not provide pass/fail criteria that can
be used as a regulatory tool.
3.1 Definitions—For definitions of terms used in this prac-
tice and associated with insulation issues, refer to terminology
1.5 Use the values stated in inch-pound units as the standard
contained in Terminology C168 or Specification C991. For
in referee decisions. The values in the SI system of units are
definitions of terms used in this practice and associated with
given in parentheses, for information only; see IEEE/ASTM
fire issues, refer to Terminology E176.
SI-10 for further details.
3.2 Definitions of Terms Specific to This Standard:
1.6 This fire standard cannot be used to provide quantitative
1
3.2.1 metal rods, n—as related to fire testing, steel rods, ⁄4
measures.
in.(6.3mm)diameterandbetween23and24in.(0.58and0.61
1.7 Fire testing of products and materials is inherently
m) long.
hazardous and adequate safeguards for personnel and property
shall be employed in conducting these tests. Fire testing
4. Summary of Practice
involves hazardous materials, operations and equipment.
4.1 This practice describes a procedure for specimen prepa-
1.8 This practice gives instructions on specimen preparation
ration and mounting when testing flexible fibrous glass insu-
and mounting but the fire-test-response method shall be con-
lation for metal buildings to assess flame spread and smoke
ducted in accordance with Test Method E84. See also Section
development as surface burning characteristics using Test
8 for information on operator safety.
Method E84.
1.9 This standard does not purport to address all of the
4.2 Flexible fibrous glass insulation for metal buildings is a
safety concerns, if any, associated with its use. It is the
fibrous glass insulation, furnished in two types as described in
responsibility of the user of this standard to establish appro-
Specification C991. Type I is an un-faced insulation blanket.
priate safety and health practices and determine the applica-
Type II is a Type I blanket that is post-processed by a
bility of regulatory limitations prior to use.
laminating process that applies an adhesive bonded facing to
one surface.
1
This practice is under the jurisdiction of ASTM Committee E05 on Fire
2
Standards and is the direct responsibility of Subcommittee E05.22 on Surface For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Burning. contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Current edition approved Feb. 1, 2015. Published February 2015. DOI: 10.1520/ Standards volume information, refer to the standard’s Document Summary page on
E2988-15 the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
E2988 − 15
4.3 Flexible fibrous glass insulation for metal buildings 6.4.1 For Type II material, a minimum of two specimens
shallbetestedinaccordancewiththespecimenpreparationand shall be tested. One specimen shall be tested with a longitudi-
mounting procedures described in this practice, using Test nal slit down the length of the sample oriented between the
Method E84. burners.Theslitistobeofsuchdepthastoexposethebonding
adhesiveandglassfiberinsulation.Theotherspecimenshallbe
5. Significance and Use
tested with the facing without a slit.
5.1 Flexible fibrous glass insulation for
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.