ASTM E1289-08(2016)
(Specification)Standard Specification for Reference Specimen for Sound Transmission Loss
Standard Specification for Reference Specimen for Sound Transmission Loss
ABSTRACT
This specification describes the construction and installation of standard reference specimens for quality control of laboratory sound transmission loss measurements. The reference specimen is composed of framed steel panels. The required materials for fabrication and installation are as follows: galvanized sheets, frame, and panels. Four kinds of installation may be done: Installation A using a single layer reference specimen, Installation B using double layer reference specimen with a common plate, Installation C using double layer reference specimen with separate plates-empty cavity, and Installation D using double layer reference specimen with separate plates and added layer of sound-absorbing material in the cavity.
SCOPE
1.1 This specification describes the construction and installation of standard reference specimens for quality control of laboratory sound transmission loss measurements using Test Method E90.
1.2 Laboratories may choose to construct and test all of the reference specimens described here or only a subset. Specific specimens may be required by a test method or an accrediting agency.
1.3 The values stated in SI units are to be regarded as standard. The values given in parentheses are for information only.
General Information
Buy Standard
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:E1289 −08 (Reapproved 2016)
Standard Specification for
Reference Specimen for Sound Transmission Loss
This standard is issued under the fixed designation E1289; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
Blind rivets—diameter, 3.2 mm ( ⁄8 in. ).
Duct tape, 50 mm (2 in.) wide.
1.1 This specification describes the construction and instal-
Drywall screws, Type W—length, 32 mm (1.25 in.).
lation of standard reference specimens for quality control of Bolts #10–24 —25 mm (1 in.) long with appropriate nuts and washers.
Fasteners, to hold wood frame to the perimeter of the test opening.
laboratory sound transmission loss measurements using Test
Non-hardening, caulking,
Method E90.
Nominal 2 by 4 in. wood framing, approximately 40 by 90 mm.
NOTE 1—The quantity and length of each component needed depends
1.2 Laboratories may choose to construct and test all of the
on the size of the laboratory test opening.
reference specimens described here or only a subset. Specific
NOTE 1—To simplify cleaning, the wood framing used to support the
specimens may be required by a test method or an accrediting
steel panels may be painted.
agency.
4.1.2 The weight of each component of the reference
1.3 The values stated in SI units are to be regarded as
specimen and the assembled specimen shall be measured and
standard. The values given in parentheses are for information
kept on record. In addition, the thickness of each of the steel
only.
panels shall be measured in six locations. (See Appendix X1.)
2. Referenced Documents
4.2 Assembly:
2.1 ASTM Standards: 4.2.1 Galvanized Sheets—The length of each galvanized
C634 Terminology Relating to Building and Environmental sheet shall be a few millimetres less than the height of the
Acoustics laboratory test opening. The total width of all the sheets shall
E90 Test Method for Laboratory Measurement of Airborne be a few millimetres less than the width of the laboratory test
Sound Transmission Loss of Building Partitions and opening. This may require that one or more sheets be cut
Elements lengthwise.The intent is that, when installed, the panels fill the
test opening completely.
3. Terminology
4.2.2 Frame—Cut steel right angles to size to form a frame
3.1 Definitions—For definitions of terms used in this for each sheet; the frame shall have the same outside dimen-
specification, see Terminology C634. sions as the sheets. Notch and weld the steel angles to form the
four corners of the frame as shown in Fig. 1. Alternatively,
4. Construction of Reference Specimen
miter the angles and weld similarly. Smooth corners after
4.1 General: welding.
4.1.1 The reference specimen is composed of framed steel 4.2.3 Panels—Construct a panel by riveting steel sheets to
panels. The required materials for fabrication and installation the frames as follows:0
are as follows: 4.2.3.1 Drill holes at 100 mm (4 in.) on-center around the
perimeterofthesheetsfortheinstallationoftheblindrivets.To
Galvanized steel sheets—width, 1220 mm (4 ft); nominal thickness, 0.63 mm
(24 gauge). The weight of the sheets shall be 5.1 ± 0.7 kg/m (1.05 ± 0.15 lb/
ensure proper alignment of the sheets with the frame, it is
ft ).
recommended to drill a few holes and then install rivets to hold
Steel right angles with 25-mm (1-in.) flanges—metal thickness, 3.2 mm ( ⁄8 in.).
the sheet in place. Once this is done, the remaining holes may
be drilled and the rivets installed. Position these holes to avoid
This specification is under the jurisdiction of ASTM Committee E33 on conflict with the clearance holes described in 4.2.3.2.
Building and Environmental Acoustics and is the direct responsibility of Subcom-
4.2.3.2 Drill 4 mm ( ⁄32 inch) diameter holes through the
mittee E33.03 on Sound Transmission.
horizontal members of the frame and sheet as shown in Fig. 2.
Current edition approved May 1, 2016. Published May 2016. Originally
These are clearance holes for the drywall screws used to attach
approved in 1989. Last previous edition approved in 2008 as E1289 – 08. DOI:
10.1520/E1289-08R16.
the panel to the wood plate (see 5.4). Drill similar holes
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
through the vertical members of the panels that will be used to
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
attach the assembled specimen to the vertical wood plates. The
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website. spacing between these holes is not important.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
E1289−08 (2016)
FIG. 3 Construction Details of Steel Panels (not to scale)
5. Installation A: Single Layer Reference Specimen
5.1 Using approximately 40 mm by 90 mm wood studs
(nominal 2 in. by 4 in.), install a wood frame around the
perimeter of the laboratory opening. Use a double bead of
caulking between the wood frame and the surface of the
FIG. 1 Notching and Welding Corners of Steel Angles
laboratory opening. Use suitable fasteners no more than 305
mm (12 in.) on-center.
5.2 Place the reference specimen against the wood frame
with the flanges of the panel frames as shown in Fig. 4.
NOTE 1—The panels are positioned 75 mm from the mid-plane of the
laboratory test opening to minimize changes when laboratories intend to
testotherreferencespecimensdescribedinthisdocumentthatuseseparate
plates.
NOTE 2—The direction of sound transmission for these reference
specimens is not important. It can be left-to-right or right-to-left.
5.3 Insert 25-mm (1-in.) long No. 10-24 bolts or equivalent
through the holes in adjacent vertical flanges drilled according
to 4.2.3.3. Washers may be used if desired. Tighten nut snugly
to close the gap between adjacent panels. (See Fig. 3).
5.4 Fasten the test panels to the vertical and horizontal
sections of the wood frame with Type W drywall screws 32
mm (1.25 in.) long inserted through the holes drilled according
to 4.2.3.2.
5.5 Seal the test panel joints on both sides with a single
layer of 50-mm (2-in.) wide duct tape (centered on the joints).
5.6 Seal the perimeter joint on both sides with a single layer
of 50-mm (2-in.) wide duct tape (centered on the joints) as
shown in Fig. 4.
6. Installation B: Double Layer Reference Specimen
With a Common Plate
6.1 The first layer of this double layer specimen is installed
as for the single layer specimen, installation A.
FIG. 2 Construction Details of Steel Panels (not to scale)
6.2
...
This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: E1289 − 08 E1289 − 08 (Reapproved 2016)
Standard Specification for
Reference Specimen for Sound Transmission Loss
This standard is issued under the fixed designation E1289; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This specification describes the construction and installation of standard reference specimens for quality control of
laboratory sound transmission loss measurements using Test Method E90.
1.2 Laboratories may choose to construct and test all of the reference specimens described here or only a subset. Specific
specimens may be required by a test method or an accrediting agency.
1.3 The values stated in SI units are to be regarded as standard. The values given in parentheses are for information only.
2. Referenced Documents
2.1 ASTM Standards:
C634 Terminology Relating to Building and Environmental Acoustics
E90 Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements
3. Terminology
3.1 Definitions—For definitions of terms used in this specification, see Terminology C634.
4. Construction of Reference Specimen
4.1 General:
4.1.1 The reference specimen is composed of framed steel panels. The required materials for fabrication and installation are as
follows:
Galvanized steel sheets—width, 1220 mm (4 ft); nominal thickness, 0.63 mm
(24 gauge). The weight of the sheets shall be 5.1 ± 0.7 kg/m (1.05 ± 0.15 lb/
ft ).
Steel right angles with 25-mm (1-in.) flanges—metal thickness, 3.2 mm ( ⁄8 in.).
Blind rivets—diameter, 3.2 mm ( ⁄8 in. ).
Duct tape, 50 mm (2 in.) wide.
Drywall screws, Type W—length, 32 mm (1.25 in.).
Bolts #10–24 —25 mm (1 in.) long with appropriate nuts and washers.
Fasteners, to hold wood frame to the perimeter of the test opening.
Non-hardening, caulking,
Nominal 2 by 4 in. wood framing, approximately 40 by 90 mm.
NOTE 1—The quantity and length of each component needed depends
on the size of the laboratory test opening.
NOTE 1—To simplify cleaning, the wood framing used to support the
steel panels may be painted.
4.1.2 The weight of each component of the reference specimen and the assembled specimen shall be measured and kept on
record. In addition, the thickness of each of the steel panels shall be measured in six locations. (See Appendix X1.)
4.2 Assembly:
4.2.1 Galvanized Sheets—The length of each galvanized sheet shall be a few millimetres less than the height of the laboratory
test opening. The total width of all the sheets shall be a few millimetres less than the width of the laboratory test opening. This
may require that one or more sheets be cut lengthwise. The intent is that, when installed, the panels fill the test opening completely.
This specification is under the jurisdiction of ASTM Committee E33 on Building and Environmental Acoustics and is the direct responsibility of Subcommittee E33.03
on Sound Transmission.
Current edition approved Jan. 15, 2008May 1, 2016. Published February 2008May 2016. Originally approved in 1989. Last previous edition approved in 19972008 as
E1289 – 97E1289 – 08.(2003). DOI: 10.1520/E1289-08.10.1520/E1289-08R16.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
E1289 − 08 (2016)
FIG. 1 Notching and Welding Corners of Steel Angles
4.2.2 Frame—Cut steel right angles to size to form a frame for each sheet; the frame shall have the same outside dimensions
as the sheets. Notch and weld the steel angles to form the four corners of the frame as shown in Fig. 1. Alternatively, miter the
angles and weld similarly. Smooth corners after welding.
4.2.3 Panels—Construct a panel by riveting steel sheets to the frames as follows:0
4.2.3.1 Drill holes at 100 mm (4 in.) on-center around the perimeter of the sheets for the installation of the blind rivets. To ensure
proper alignment of the sheets with the frame, it is recommended to drill a few holes and then install rivets to hold the sheet in
place. Once this is done, the remaining holes may be drilled and the rivets installed. Position these holes to avoid conflict with the
clearance holes described in 4.2.3.2.
4.2.3.2 Drill 4 mm ( ⁄32 inch) diameter holes through the horizontal members of the frame and sheet as shown in Fig. 2. These
are clearance holes for the drywall screws used to attach the panel to the wood plate (see 5.4). Drill similar holes through the
vertical members of the panels that will be used to attach the assembled specimen to the vertical wood plates. The spacing between
these holes is not important.
4.2.3.3 Drill 6.4 mm ( ⁄4 in.) diameter holes at 406 mm (16 in.) on-center through the vertical flanges of the steel frame. These
are clearance holes for the bolts used to connect the panels together (see 5.3 and Fig. 3). The holes in adjacent vertical members
should be carefully aligned with each other to ease installation of the panels.
5. Installation A: Single Layer Reference Specimen
5.1 Using approximately 40 mm by 90 mm wood studs (nominal 2 in. by 4 in.), install a wood frame around the perimeter of
the laboratory opening. Use a double bead of caulking between the wood frame and the surface of the laboratory opening. Use
suitable fasteners no more than 305 mm (12 in.) on-center.
5.2 Place the reference specimen against the wood frame with the flanges of the panel frames as shown in Fig. 4.
NOTE 1—The panels are positioned 75 mm from the mid-plane of the laboratory test opening to minimize changes when laboratories intend to test other
reference specimens described in this document that use separate plates.
NOTE 2—The direction of sound transmission for these reference specimens is not important. It can be left-to-right or right-to-left.
5.3 Insert 25-mm (1-in.) long No. 10-24 bolts or equivalent through the holes in adjacent vertical flanges drilled according to
4.2.3.3. Washers may be used if desired. Tighten nut snugly to close the gap between adjacent panels. (See Fig. 3).
5.4 Fasten the test panels to the vertical and horizontal sections of the wood frame with Type W drywall screws 32 mm (1.25
in.) long inserted through the holes drilled according to 4.2.3.2.
5.5 Seal the test panel joints on both sides with a single layer of 50-mm (2-in.) wide duct tape (centered on the joints).
5.6 Seal the perimeter joint on b
...