ASTM C1629/C1629M-14
(Classification)Standard Classification for Abuse-Resistant Nondecorated Interior Gypsum Panel Products and Fiber-Reinforced Cement Panels
Standard Classification for Abuse-Resistant Nondecorated Interior Gypsum Panel Products and Fiber-Reinforced Cement Panels
SIGNIFICANCE AND USE
4.1 Each abuse/impact property of abuse resistant wall panels is divided into three classification levels. The three levels of classification are: Level I, Level II, and Level III, with Level I representing the lowest rating for any given property. The test methods specified are utilized to establish the abuse-resistance classification of an abuse resistant wall panel. Each classification level requires a minimum overall specified performance. Any classified abuse resistant wall panel can be used at a classification level which is rated lower than the highest level qualified.
SCOPE
1.1 This standard establishes classifications of abuse resistance based on minimum abuse-resistance performance of nondecorated interior gypsum panel products and fiber-reinforced cement panels (abuse resistant wall panels).
1.1.1 This standard is a method of classifying gypsum panel product performance and is not intended to classify systems for abuse resistance.
1.2 The values stated in inch-pound and SI (metric) units are to be regarded separately as standard. Within the text, the SI units are shown in brackets. The values stated in each system shall be used independent of the other. Values from the two systems shall not be combined.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
General Information
Relations
Buy Standard
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:C1629/C1629M −14
StandardClassification for
Abuse-Resistant Nondecorated Interior Gypsum Panel
1
Products and Fiber-Reinforced Cement Panels
This standard is issued under the fixed designation C1629/C1629M; the number immediately following the designation indicates the
year of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last
reapproval. A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope* 2.2 ISO Documents:
ISO 6707-1 Building and Civil Engineering -- Vocabulary --
1.1 This standard establishes classifications of abuse resis-
Part 1: General Terms
tance based on minimum abuse-resistance performance of
nondecorated interior gypsum panel products and fiber-
3. Terminology
reinforced cement panels (abuse resistant wall panels).
1.1.1 This standard is a method of classifying gypsum panel
3.1 Definitions of terms shall be in accordance with Termi-
productperformanceandisnotintendedtoclassifysystemsfor
nologies C11 and C1154.
abuse resistance.
3.2 Definitions of Terms Specific to This Standard:
1.2 Thevaluesstatedininch-poundandSI(metric)unitsare
3.2.1 failure (hard body impact), n—test result constituted
to be regarded separately as standard. Within the text, the SI
either by the penetration of the wall cavity by the impacting
units are shown in brackets. The values stated in each system
head of the impacting arm or the denting of the panel resulting
shall be used independent of the other. Values from the two
in an indentation of a depth that exceeds the thickness of the
systems shall not be combined.
test panel.
1.3 This standard does not purport to address all of the 3.2.1.1 Discussion—Depth of the indentation on the test
safety concerns, if any, associated with its use. It is the panel is measured from the face side.
responsibility of the user of this standard to establish appro-
3.2.2 failure (soft body impact), n—a test result constituted
priate safety and health practices and determine the applica-
either by the breaking of the wall cavity by the soft body
bility of regulatory limitations prior to use.
impactor or the residual deflection of any area on the test panel
that exceeds the thickness of the test panel.
2. Referenced Documents
3.2.2.1 Discussion—Deformation of the test panel in the
2
2.1 ASTM Standards:
form of residual deflection is measured from the face side.
C11 Terminology Relating to Gypsum and Related Building
3.2.2.1 deformation, n—change of shape or dimension or
Materials and Systems
both. ISO 6707-1
C1154 Terminology for Non-Asbestos Fiber-Reinforced Ce-
3.2.2.2 surface damage, n—pulverization of the core of the
ment Products
test panel at the point of impact, which is evidenced by
D4977 Test Method for Granule Adhesion to Mineral Sur-
cracking, creasing, or other visible damage short of failure as
faced Roofing by Abrasion
defined in 3.2.2.
D5420 Test Method for Impact Resistance of Flat, Rigid
Plastic Specimen by Means of a Striker Impacted by a
3.2.3 residual deflection, n—permanent deformation of a
Falling Weight (Gardner Impact)
building element, component, or structure after removal of
E695 Test Method of Measuring Relative Resistance of
applied force.
Wall, Floor, and Roof Construction to Impact Loading
3.2.3.1 Discussion—Also called permanent set or residual
deformation.
1
This classification is under the jurisdiction of ASTM Committee C11 on
4. Significance and Use
Gypsum and Related Building Materials and Systems and is the direct responsibility
of Subcommittee C11.01 on Specifications and Test Methods for Gypsum Products.
4.1 Each abuse/impact property of abuse resistant wall
Current edition approved April 1, 2014. Published May 2014. Originally
panels is divided into three classification levels. The three
approved in 2005. Last previous edition approved in 2011 as C1629/C1629M – 06
(2011). DOI: 10.1520/C1629_C1629M-14.
levelsofclassificationare:LevelI,LevelII,andLevelIII,with
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Level I representing the lowest rating for any given property.
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
The test methods specified are utilized to establish the abuse-
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website. resistance classification of an abuse resistant wall panel. Each
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1
---------------------- Page: 1 ----------------------
C1629/C1629M−14
TABLE 2 Performance Requirements
classification level requires a minimum overall specified per-
Indentation Resistance
formance.Any classified a
...
This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: C1629/C1629M − 06 (Reapproved 2011) C1629/C1629M − 14
Standard Classification for
Abuse-Resistant Nondecorated Interior Gypsum Panel
1
Products and Fiber-Reinforced Cement Panels
This standard is issued under the fixed designation C1629/C1629M; the number immediately following the designation indicates the
year of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last
reapproval. A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope*
1.1 This standard establishes classifications of abuse resistance based on minimum abuse-resistance performance of
nondecorated interior gypsum panel products and fiber-reinforced cement panels (abuse resistant wall panels).
1.1.1 This standard is a method of classifying gypsum panel product performance and is not intended to classify systems for
abuse resistance.
1.2 The values stated in inch-pound and SI (metric) units are to be regarded separately as standard. Within the text, the SI units
are shown in brackets. The values stated in each system shall be used independent of the other. Values from the two systems shall
not be combined.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
2. Referenced Documents
2
2.1 ASTM Standards:
C11 Terminology Relating to Gypsum and Related Building Materials and Systems
C1154 Terminology for Non-Asbestos Fiber-Reinforced Cement Products
D4977 Test Method for Granule Adhesion to Mineral Surfaced Roofing by Abrasion
D5420 Test Method for Impact Resistance of Flat, Rigid Plastic Specimen by Means of a Striker Impacted by a Falling Weight
(Gardner Impact)
E695 Test Method of Measuring Relative Resistance of Wall, Floor, and Roof Construction to Impact Loading
2.2 ISO Documents:
ISO 6707-1 Building and Civil Engineering -- Vocabulary -- Part 1: General Terms
3. Terminology
3.1 Definitions of terms shall be in accordance with Terminologies C11 and C1154.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 failure (hard body impact), n—test result constituted either by the penetration of the wall cavity by the impacting head
of the impacting arm or the denting of the panel resulting in an indentation of a depth that exceeds the thickness of the test panel.
1
This classification is under the jurisdiction of ASTM Committee C11 on Gypsum and Related Building Materials and Systems and is the direct responsibility of
Subcommittee C11.01 on Specifications and Test Methods for Gypsum Products.
Current edition approved June 15, 2011April 1, 2014. Published July 2011May 2014. Originally approved in 2005. Last previous edition approved in 20062011 as
C1629/C1629M – 06.C1629/C1629M – 06 (2011). DOI: 10.1520/C1629_C1629M-06R11.10.1520/C1629_C1629M-14.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
3.2.1.1 Discussion—
Depth of the indentation on the test panel is measured from the face side.
3.2.2 failure (soft body impact), n—a test result constituted either by the breaking of the wall cavity by the soft body impactor
or the residual deflection of any area on the test panel that exceeds the thickness of the test panel.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1
---------------------- Page: 1 ----------------------
C1629/C1629M − 14
3.2.2.1 Discussion—
Deformation of the test panel in the form of residual deflection is measured from the face side.
3.2.2.1 deformation, n—change of shape or dimension or both. ISO 6707-1
3.2.2.2 surface damage, n—pulverization of the core of the test panel at the point of impact, which is evidenced by cracking,
creasing, or other visible damage short of failure as defined in 3.2.2.
3.2.3 residual deflection, n—permanent deformation of a building element, component, or structure after removal of applied
force.
3.2.3.1 Discussion—
Also called permanent set or residual deformation.
4. Significance and Use
4.1 Each abuse/impact property of abuse resistant wall panels is divided into three classification levels.
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.