Standard Guide for Application of Asphalt Based Protection Board

SIGNIFICANCE AND USE
4.1 This guide outlines general procedures for the storage and application of semi-rigid protection board to below grade and below wearing surface waterproofing. The proper application is necessary to prevent damage to the waterproofing membrane during backfilling, paving, or other construction operations, as well as to minimize the effects of soil stresses.  
4.2 This guide is intended to supplement instructions from designers and manufacturers.
SCOPE
1.1 This guide lists minimum application and installation requirements for semi-rigid protection board when used as protection for below grade or below wearing surface (like plaza decks) waterproofing.  
1.2 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this guide to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statement, see Section 8.

General Information

Status
Historical
Publication Date
30-Apr-2014
Current Stage
Ref Project

Buy Standard

Guide
ASTM D6451/D6451M-99(2014)e1 - Standard Guide for Application of Asphalt Based Protection Board
English language
2 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
´1
Designation: D6451/D6451M − 99 (Reapproved 2014)
Standard Guide for
Application of Asphalt Based Protection Board
This standard is issued under the fixed designation D6451/D6451M; the number immediately following the designation indicates the
year of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last
reapproval. A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
ε NOTE—Units information was editorially corrected in May 2014.
1. Scope tion is necessary to prevent damage to the waterproofing
membrane during backfilling, paving, or other construction
1.1 This guide lists minimum application and installation
operations, as well as to minimize the effects of soil stresses.
requirements for semi-rigid protection board when used as
protectionforbelowgradeorbelowwearingsurface(likeplaza 4.2 This guide is intended to supplement instructions from
decks) waterproofing. designers and manufacturers.
1.2 The values stated in either SI units or inch-pound units
5. Delivery of Materials
are to be regarded separately as standard. The values stated in
each system may not be exact equivalents; therefore, each 5.1 Deliver materials in supplier’s original containers and
packaging.
system shall be used independently of the other. Combining
values from the two systems may result in non-conformance
6. Storage and Handling
with the standard.
1.3 This standard does not purport to address all of the 6.1 Store adhesive and mastic in tightly closed original
safety concerns, if any, associated with its use. It is the containers under conditions as recommended by the manufac-
responsibility of the user of this guide to establish appropriate turer.
safety and health practices and determine the applicability of
6.2 Store the protection board in supplier’s original pack-
regulatory limitations prior to use. For specific precautionary
aging in a horizontal position to prevent deformation. Protect
statement, see Section 8.
against exposure to direct sunlight, precipitation, dust, and
other such contaminants.
2. Referenced Documents
2.1 ASTM Standards:
7. Materials
D1079 Terminology Relating to Roofing and Waterproofing
7.1 Adhesive, when used, must be acceptable to or have
D5957 Guide for Flood Testing Horizontal Waterproofing
been recommended by the waterproofing membrane manufac-
Installations
turer or supplier and further must be fully compatible with the
membrane and the asphalt protection board.
3. Terminology
7.2 Mastic or tape, or both, (if used on the joints) must be
3.1 Definitions—For definitions of terms relating to
acceptable to or have been recommended by the waterproofing
waterproofing, see Terminology D1079.
membrane manufacturer or supplier and further be fully
4. Significance and Use
compatible with the membrane and the asphalt protection
board.
4.1 This guide outlines general procedures for the storage
and application of semi-rigid protection board to below grade
8. Safety Precautions
and below wearing surface waterproofing. The proper applica-
8.1 Store flammable materials in a manner that will not pose
a fire hazard. Solvent bearing adhesives may be flammable. Do
This guide is under the jurisdiction of ASTM Committee D08 on Roofing and
Waterproofing and is the direct responsibility of Subcommittee D08.22 on Water- not use flammable materials near an open flame or equipment
proofing and Dampproofing Systems.
that may produce sparks.
Current edition approved May 1, 2014. Published May 2014. Originally
approved in 1999. Last previous edition approved in 2006 as D6451 – 99 (2006).
9. Environmental Conditions at Time of Application
DOI: 10.1520/D6451_D6451M-99R14E01.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
9.1 Environmental conditions under which installation may
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
proceed shall be as recommended by the suppliers of the
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website. adhesive and the protection board.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
´1
D6451/D6451M − 99 (2014)
10. Substrate Preparation 11.3.1 The protection board is to be applied with the long
axis of the board going up the slope. The joints in the
10.1 The waterproofing membrane must be clean and suf-
cross-the-slope direction shall be aligned while the up-slope
ficiently dry so as not to interfere with adhesion of the
joints shall be in a stacked brick pattern, with joints centered
protection board.
over previously applied boards.
10.2 If a flood test of the membrane is desired, this test
11.3.2 Using adhesive as described in 7.2, coat the outside
should be made before placing the protection co
...