Standard Test Method for Compressive Strength of Soil-Cement Using Portions of Beams Broken in Flexure (Modified Cube Method)

SIGNIFICANCE AND USE
4.1 This test method is intended for use in the laboratory and as a research tool for determining relative compressive strength values for various soil-cement mixtures. It is not intended as an alternative for Test Method D1633 and the test values obtained by these two test methods are not interchangeable and not necessarily comparable. A comparison of strengths obtained by Test Methods D1633 and D1634 is given by Feld and Abrams.3
Note 1: The quality of the result produced by this standard is dependent on the competence of the personnel performing it, and the suitability of the equipment and facilities used. Agencies that meet the criteria of Practice D3740 are generally considered capable of competent and objective testing/sampling/inspection/etc. Users of this standard are cautioned that compliance with Practice D3740 does not in itself assure reliable results. Reliable results depend on many factors; Practice D3740 provides a means of evaluating some of those factors.
SCOPE
1.1 This test method covers the determination of the compressive strength of soil-cement, using portions of beams broken in flexure in accordance with Test Method D1635, as test specimens.  
1.2 Units—The values stated in inch-pound units are to be regarded as standard, except as noted below. The values given in parentheses are mathematical conversions to SI units, which are provided for information only and are not considered standard.  
1.2.1 The gravitational system of inch-pound units is used when dealing with inch-pound units. In this system, the pound (lbf) represents a unit of force (weight) while the unit for mass is slugs.  
1.2.2 The slug unit of mass is almost never used in commercial practice; that is, density, balances, etc. Therefore, the standard unit for mass in this standard is either kilogram (kg) or gram (g), or both. Also, the equivalent inch-pound unit (slug) is not given/presented in parantheses.  
1.2.3 It is common practice in the engineering/construction profession to concurrently use pounds to represent both a unit of mass (lbm) and of force (lbf). This implicitly combines two separate systems of units; that is, the absolute system and the gravitational system. It is scientifically undesirable to combine the use of two separate sets of inch-pound units within a single standard. As stated, this standard includes the gravitational system of inch-pound units and does not use/present the slug unit for mass. However the use of balances or scales, recording pounds of mass (lbm) or recording density in lbm/ft3 shall not be regarded as nonconformance with this standard.  
1.3 All observed and calculated values shall conform to the guidelines for significant digits and rounding established in Practice D6026 unless superseded by this test method.  
1.3.1 The procedures used to specify how data are collected/recorded and calculated in the standard are regarded as the industry standard. In addition, they are representative of the significant digits that generally should be retained. The procedures used do not consider material variation, purpose for obtaining the data, special purpose studies, or any considerations for the user's objectives; and it is common practice to increase or reduce significant digits of reported data to be commensurate with these considerations. It is beyond the scope of these test methods to consider significant digits used in analysis methods for engineering data.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standar...

General Information

Status
Published
Publication Date
31-Oct-2017
Technical Committee
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM D1634-17 - Standard Test Method for Compressive Strength of Soil-Cement Using Portions of Beams Broken in Flexure (Modified Cube Method)
English language
3 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation:D1634 −17
Standard Test Method for
Compressive Strength of Soil-Cement Using Portions of
1
Beams Broken in Flexure (Modified Cube Method)
This standard is issued under the fixed designation D1634; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope* industry standard. In addition, they are representative of the
significant digits that generally should be retained. The proce-
1.1 This test method covers the determination of the com-
dures used do not consider material variation, purpose for
pressive strength of soil-cement, using portions of beams
obtaining the data, special purpose studies, or any consider-
broken in flexure in accordance with Test Method D1635,as
ations for the user’s objectives; and it is common practice to
test specimens.
increase or reduce significant digits of reported data to be
1.2 Units—The values stated in inch-pound units are to be
commensuratewiththeseconsiderations.Itisbeyondthescope
regarded as standard, except as noted below. The values given
of these test methods to consider significant digits used in
inparenthesesaremathematicalconversionstoSIunits,which
analysis methods for engineering data.
are provided for information only and are not considered
1.4 This standard does not purport to address all of the
standard.
safety concerns, if any, associated with its use. It is the
1.2.1 The gravitational system of inch-pound units is used
responsibility of the user of this standard to establish appro-
when dealing with inch-pound units. In this system, the pound
priate safety, health, and environmental practices and deter-
(lbf) represents a unit of force (weight) while the unit for mass
mine the applicability of regulatory limitations prior to use.
is slugs.
1.5 This international standard was developed in accor-
1.2.2 The slug unit of mass is almost never used in
dance with internationally recognized principles on standard-
commercial practice; that is, density, balances, etc. Therefore,
ization established in the Decision on Principles for the
the standard unit for mass in this standard is either kilogram
Development of International Standards, Guides and Recom-
(kg) or gram (g), or both.Also, the equivalent inch-pound unit
mendations issued by the World Trade Organization Technical
(slug) is not given/presented in parantheses.
Barriers to Trade (TBT) Committee.
1.2.3 It is common practice in the engineering/construction
profession to concurrently use pounds to represent both a unit
2. Referenced Documents
of mass (lbm) and of force (lbf). This implicitly combines two
2
2.1 ASTM Standards:
separate systems of units; that is, the absolute system and the
D653Terminology Relating to Soil, Rock, and Contained
gravitational system. It is scientifically undesirable to combine
Fluids
theuseoftwoseparatesetsofinch-poundunitswithinasingle
D1632Practice for Making and Curing Soil-Cement Com-
standard. As stated, this standard includes the gravitational
pression and Flexure Test Specimens in the Laboratory
system of inch-pound units and does not use/present the slug
D1633Test Methods for Compressive Strength of Molded
unitformass.Howevertheuseofbalancesorscales,recording
3 Soil-Cement Cylinders
pounds of mass (lbm) or recording density in lbm/ft shall not
D1635Test Method for Flexural Strength of Soil-Cement
be regarded as nonconformance with this standard.
Using Simple Beam with Third-Point Loading
1.3 All observed and calculated values shall conform to the
D2216Test Methods for Laboratory Determination ofWater
guidelines for significant digits and rounding established in
(Moisture) Content of Soil and Rock by Mass
Practice D6026 unless superseded by this test method.
D3740Practice for Minimum Requirements for Agencies
1.3.1 Theproceduresusedtospecifyhowdataarecollected/
Engaged in Testing and/or Inspection of Soil and Rock as
recorded and calculated in the standard are regarded as the
Used in Engineering Design and Construction
D6026Practice for Using Significant Digits in Geotechnical
1
ThistestmethodisunderthejurisdictionofASTMCommitteeD18onSoiland
Data
RockandisthedirectresponsibilityofSubcommitteeD18.15onStabilizationWith
Admixtures.
2
Current edition approved Nov. 1, 2017. Published November 2017. Originally For referenced ASTM standards, visit the ASTM website, www.astm.org, or
approved in 1959. Last previous edition approved in 2006 as D1634–00(2006), contact ASTM Customer Service at service@astm.org. For Annual
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.